Zone HVAC Air Loop Terminal Units

18 object types from idfpy.models.zone_terminals · EnergyPlus 26.2

Object Summary
AirTerminal:DualDuct:ConstantVolume Central air system terminal unit, dual duct, constant volume.
AirTerminal:DualDuct:VAV Central air system terminal unit, dual duct, variable volume.
AirTerminal:DualDuct:VAV:OutdoorAir Central air system terminal unit, dual duct, variable volume with special controls.
AirTerminal:SingleDuct:ConstantVolume:CooledBeam Central air system terminal unit, single duct, constant volume, with cooled beam (active or passive).
AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam Central air system terminal unit, single duct, constant volume, with heating and/or cooling.
AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction Central air system terminal unit, single duct, variable volume, induction unit with hot water reheat coil and …
AirTerminal:SingleDuct:ConstantVolume:NoReheat Central air system terminal unit, single duct, constant volume, without reheat coil
AirTerminal:SingleDuct:ConstantVolume:Reheat Central air system terminal unit, single duct, constant volume, with reheat coil (hot water, electric, gas, …
AirTerminal:SingleDuct:Mixer The mixer air terminal unit provides a means of supplying central system air to the air inlet or outlet side …
AirTerminal:SingleDuct:ParallelPIU:Reheat Central air system terminal unit, single duct, variable volume, parallel powered induction unit (PIU), with …
AirTerminal:SingleDuct:SeriesPIU:Reheat Central air system terminal unit, single duct, variable volume, series powered induction unit (PIU), with …
AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat Central air system terminal unit, single duct, variable volume for both cooling and heating, with no reheat …
AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat Central air system terminal unit, single duct, variable volume for both cooling and heating, with reheat coil …
AirTerminal:SingleDuct:VAV:NoReheat Central air system terminal unit, single duct, variable volume, with no reheat coil.
AirTerminal:SingleDuct:VAV:Reheat Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, …
AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, …
ZoneHVAC:AirDistributionUnit Central air system air distribution unit, serves as a wrapper for a specific type of air terminal unit.
ZoneHVAC:ExhaustControl Defines a controlled exhaust flow from a zone which finally feeds into one of AirLoopHVAC:ZoneMixer's inlets, …

AirTerminal:DualDuct:ConstantVolume

from idfpy.models import AirTerminalDualDuctConstantVolume

Central air system terminal unit, dual duct, constant volume.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit. This is also the zone inlet node.
hot_air_inlet_node_name
Hot Air Inlet Node Name required
string
cold_air_inlet_node_name
Cold Air Inlet Node Name required
string
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:DualDuct:VAV

from idfpy.models import AirTerminalDualDuctVAV

Central air system terminal unit, dual duct, variable volume.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit. This is also the zone inlet node.
hot_air_inlet_node_name
Hot Air Inlet Node Name required
string
cold_air_inlet_node_name
Cold Air Inlet Node Name required
string
maximum_damper_air_flow_rate
Maximum Damper Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_fraction
Zone Minimum Air Flow Fraction
number 0.2 fraction of maximum air flow
Range: ≥ 0, ≤ 1
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the design minimum flow rate by multiplying it using this schedule of fraction values. This field is used with "Zone Minimum Air Flow Fraction". Schedule values are fractions 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1 and the VAV air terminal uses fixed fraction specified in the field "Zone Minimum Air Flow Fraction".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:DualDuct:VAV:OutdoorAir

from idfpy.models import AirTerminalDualDuctVAVOutdoorAir

Central air system terminal unit, dual duct, variable volume with special controls. One VAV duct is controlled to supply ventilation air and the other VAV duct is controlled to meet the zone cooling load.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit. This is also the zone inlet node.
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name required
string
recirculated_air_inlet_node_name
Recirculated Air Inlet Node Name
string
maximum_terminal_air_flow_rate
Maximum Terminal Air Flow Rate required
number or Autosize
m3/s
If autosized this is the sum of flow needed for cooling and maximum required outdoor air
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name required
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based mode selected in the next field. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
per_person_ventilation_rate_mode
Per Person Ventilation Rate Mode
choice CurrentOccupancy models demand controlled ventilation using the current number of people DesignOccupancy uses the total Number of People in the zone and is constant
One of CurrentOccupancy, DesignOccupancy
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ConstantVolume:CooledBeam

from idfpy.models import AirTerminalSingleDuctConstantVolumeCooledBeam

Central air system terminal unit, single duct, constant volume, with cooled beam (active or passive).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooled_beam_type
Cooled Beam Type required
choice One of Active, Passive
supply_air_inlet_node_name
Supply Air Inlet Node Name required
string
supply_air_outlet_node_name
Supply Air Outlet Node Name required
string
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
supply_air_volumetric_flow_rate
Supply Air Volumetric Flow Rate
number or Autosize
m3/s
Autosize
maximum_total_chilled_water_volumetric_flow_rate
Maximum Total Chilled Water Volumetric Flow Rate
number or Autosize
m3/s
Autosize
number_of_beams
Number of Beams
integer or Autosize Autosize Number of individual beam units in the zone
beam_length
Beam Length
number or Autosize
m
Autosize Length of an individual beam unit
design_inlet_water_temperature
Design Inlet Water Temperature
number
C
15.0 Range: ≥ 0
design_outlet_water_temperature
Design Outlet Water Temperature
number
C
17.0 Range: ≥ 0
coil_surface_area_per_coil_length
Coil Surface Area per Coil Length
number
m2/m
5.422 Range: ≥ 0
model_parameter_a
Model Parameter a
number 15.3 Range: ≥ 0
model_parameter_n1
Model Parameter n1
number 0.0 Range: ≥ 0
model_parameter_n2
Model Parameter n2
number 0.84 Range: ≥ 0
model_parameter_n3
Model Parameter n3
number 0.12 Range: ≥ 0
model_parameter_a0
Model Parameter a0
number
m2/m
0.171 Free area of the coil in plan view per unit beam length
Range: ≥ 0
model_parameter_k1
Model Parameter K1
number 0.0057 Range: ≥ 0
model_parameter_n
Model Parameter n
number 0.4 Range: ≥ 0
coefficient_of_induction_kin
Coefficient of Induction Kin
number or Autocalculate Autocalculate
leaving_pipe_inside_diameter
Leaving Pipe Inside Diameter
number
m
0.0145 Range: > 0
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam

from idfpy.models import AirTerminalSingleDuctConstantVolumeFourPipeBeam

Central air system terminal unit, single duct, constant volume, with heating and/or cooling. Operates as two-pipe unit if heating or cooling water is omitted. Heating and/or cooling can be scheduled off for dedicated ventilation.

Field Type Default Details
name
Name required
string
primary_air_availability_schedule_name
Primary Air Availability Schedule Name
reference Primary air is supplied by central air handling unit and must be on for heating or cooling. Schedule value > 0 means the primary air supply is available. If this field is blank, the primary air supply is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_availability_schedule_name
Cooling Availability Schedule Name
reference Cooling operation can be controlled separately using this availability schedule. Schedule value > 0 means beam cooling is available. If this field is blank, the beam cooling is always available (as long as primary air is also available).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_availability_schedule_name
Heating Availability Schedule Name
reference Heating operation can be controlled separately using this availability schedule. Schedule value > 0 means beam heating is available. If this field is blank, the beam heating is always available (as long as primary air is also available).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
primary_air_inlet_node_name
Primary Air Inlet Node Name required
string Name of the air system node for primary supply air entering the air distribution unit.
primary_air_outlet_node_name
Primary Air Outlet Node Name required
string Name of the air system node for primary supply air leaving the air distribution unit and entering the zone.
chilled_water_inlet_node_name
Chilled Water Inlet Node Name
string Name of the plant system node for chilled water entering the beam. The two chilled water nodes can (only) be omitted to model a two-pipe heating only beam.
chilled_water_outlet_node_name
Chilled Water Outlet Node Name
string Name of the plant system node for chilled water leaving the beam.
hot_water_inlet_node_name
Hot Water Inlet Node Name
string Name of the plant system node for hot water entering the beam. The two hot water nodes can (only) be omitted to model a two-pipe cooling-only beam.
hot_water_outlet_node_name
Hot Water Outlet Node Name
string Name of the plant system node for hot water leaving the beam.
design_primary_air_volume_flow_rate
Design Primary Air Volume Flow Rate
number or Autosize
m3/s
Autosize
design_chilled_water_volume_flow_rate
Design Chilled Water Volume Flow Rate
number or Autosize
m3/s
Autosize
design_hot_water_volume_flow_rate
Design Hot Water Volume Flow Rate
number or Autosize
m3/s
Autosize
zone_total_beam_length
Zone Total Beam Length
number or Autosize
m
Autosize Sum of the length of all the beam units in the zone represented by this terminal unit.
rated_primary_air_flow_rate_per_beam_length
Rated Primary Air Flow Rate per Beam Length
number
m3/s-m
0.035 Primary air supply flow rate normalized by beam length.
Range: > 0
beam_rated_cooling_capacity_per_beam_length
Beam Rated Cooling Capacity per Beam Length
number
W/m
600.0 Sensible cooling capacity per meter of beam length at the rating point.
Range: > 0
beam_rated_cooling_room_air_chilled_water_temperature_difference
Beam Rated Cooling Room Air Chilled Water Temperature Difference
number
deltaC
10.0 Difference in temperature between the zone air and the entering chilled water at the rating point.
Range: > 0
beam_rated_chilled_water_volume_flow_rate_per_beam_length
Beam Rated Chilled Water Volume Flow Rate per Beam Length
number
m3/s-m
5e-05 The volume flow rate of chilled water per meter of beam length at the rating point.
Range: > 0
beam_cooling_capacity_temperature_difference_modification_factor_curve_name
Beam Cooling Capacity Temperature Difference Modification Factor Curve Name
reference Adjusts beam cooling capacity when the temperature difference between entering water and zone air is different than at the rating point. Single independent variable is the ratio of the current temperature difference divided by the rating point temperature difference. This field is required when beam is connected to a chilled water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
beam_cooling_capacity_air_flow_modification_factor_curve_name
Beam Cooling Capacity Air Flow Modification Factor Curve Name
reference Adjusts beam cooling capacity when the primary air supply flow rate is different than at the rating point. The single independent variable is the current normalized air flow rate divided by the normalized air flow rate at the rating point. This field is required when beam is connected to a chilled water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
beam_cooling_capacity_chilled_water_flow_modification_factor_curve_name
Beam Cooling Capacity Chilled Water Flow Modification Factor Curve Name
reference Adjusts beam cooling capacity when the normalized chilled water flow rate is different than at the rating point. The single independent variable is the current normalized chilled water flow rate divided by the normalized chilled water flow rate at the rating point. This field is required when beam is connected to a chilled water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
beam_rated_heating_capacity_per_beam_length
Beam Rated Heating Capacity per Beam Length
number
W/m
1500.0 Sensible heating capacity per meter of beam length at the rating point.
Range: > 0
beam_rated_heating_room_air_hot_water_temperature_difference
Beam Rated Heating Room Air Hot Water Temperature Difference
number
deltaC
27.8 Difference in temperature between the zone air and the entering hot water at the rating point.
Range: > 0
beam_rated_hot_water_volume_flow_rate_per_beam_length
Beam Rated Hot Water Volume Flow Rate per Beam Length
number
m3/s-m
5e-05 The volume flow rate of hot water per meter of beam length at the rating point.
Range: > 0
beam_heating_capacity_temperature_difference_modification_factor_curve_name
Beam Heating Capacity Temperature Difference Modification Factor Curve Name
reference Adjusts beam heating capacity when the temperature difference between entering water and zone air is different than at the rating point. Single independent variable is the ratio of the current temperature difference divided by the rating point temperature difference. This field is required when beam is connected to a hot water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
beam_heating_capacity_air_flow_modification_factor_curve_name
Beam Heating Capacity Air Flow Modification Factor Curve Name
reference Adjusts beam heating capacity when the primary air supply flow rate is different than at the rating point. The single independent variable is the current normalized air flow rate divided by the normalized air flow rate at the rating point. This field is required when beam is connected to a hot water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
beam_heating_capacity_hot_water_flow_modification_factor_curve_name
Beam Heating Capacity Hot Water Flow Modification Factor Curve Name
reference Adjusts beam heating capacity when the normalized hot water flow rate is different than at the rating point. The single independent variable is the current normalized hot water flow rate divided by the normalized hot water flow rate at the rating point. This field is required when beam is connected to a hot water plant.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction

from idfpy.models import AirTerminalSingleDuctConstantVolumeFourPipeInduction

Central air system terminal unit, single duct, variable volume, induction unit with hot water reheat coil and chilled water recool coil.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_total_air_flow_rate
Maximum Total Air Flow Rate required
number or Autosize
m3/s
induction_ratio
Induction Ratio
number 2.5 ratio of induced air flow rate to primary air flow rate
Range: ≥ 0
supply_air_inlet_node_name
Supply Air Inlet Node Name required
string
induced_air_inlet_node_name
Induced Air Inlet Node Name required
string should be a zone exhaust node, also the heating coil inlet node
air_outlet_node_name
Air Outlet Node Name required
string should be a zone inlet node
heating_coil_object_type
Heating Coil Object Type required
choice One of Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_flow_rate
Maximum Hot Water Flow Rate
number or Autosize
m3/s
Not used when heating coil type is gas or electric
minimum_hot_water_flow_rate
Minimum Hot Water Flow Rate
number
m3/s
0.0 Not used when heating coil type is gas or electric
Range: ≥ 0
heating_convergence_tolerance
Heating Convergence Tolerance
number 0.001 Range: > 0
cooling_coil_object_type
Cooling Coil Object Type
choice One of Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry
cooling_coil_name
Cooling Coil Name
reference Names a Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry
maximum_cold_water_flow_rate
Maximum Cold Water Flow Rate
number or Autosize
m3/s
minimum_cold_water_flow_rate
Minimum Cold Water Flow Rate
number
m3/s
0.0 Range: ≥ 0
cooling_convergence_tolerance
Cooling Convergence Tolerance
number 0.001 Range: > 0
zone_mixer_name
Zone Mixer Name required
reference Names a AirLoopHVAC:ZoneMixer
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ConstantVolume:NoReheat

from idfpy.models import AirTerminalSingleDuctConstantVolumeNoReheat

Central air system terminal unit, single duct, constant volume, without reheat coil

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string The air-inlet node name that connects the air splitter to the individual zone air distribution unit. This node should also be one of the outlet air node of an AirLoopHVAC:ZoneSplitter or AirLoopHVAC:SupplyPlenum component.
air_outlet_node_name
Air Outlet Node Name required
string This is an air outlet node from the air distribution unit. This node name should be one of the supply air inlet node names of a zone served by this component.
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used to modulate the terminal unit flow rate based on the specified outdoor air requirement. When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will adjust flow to meet this outdoor air requirement and no more. There is no control for zone load. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on either the current or design occupancy as specified in the Per Person Ventilation Rate Mode field. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. The requested flow rate may not be fully met if the system is operating with cycling fan. If this field is blank, then the terminal unit will not be controlled for outdoor air flow. This field is optional.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
per_person_ventilation_rate_mode
Per Person Ventilation Rate Mode
choice CurrentOccupancy CurrentOccupancy uses current number of people in the zone which may vary DesignOccupancy uses the total number of people in the zone and is constant
One of CurrentOccupancy, DesignOccupancy
Referenced by 3 object types

AirflowNetwork:Distribution:Component:TerminalUnit, AirflowNetwork:Distribution:Linkage, ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ConstantVolume:Reheat

from idfpy.models import AirTerminalSingleDuctConstantVolumeReheat

Central air system terminal unit, single duct, constant volume, with reheat coil (hot water, electric, gas, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
reheat_coil_object_type
Reheat Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when reheat coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when reheat coil type is gas or electric
Range: ≥ 0
convergence_tolerance
Convergence Tolerance
number 0.001 Range: > 0
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:Component:TerminalUnit, AirflowNetwork:Distribution:Linkage, ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:Mixer

from idfpy.models import AirTerminalSingleDuctMixer

The mixer air terminal unit provides a means of supplying central system air to the air inlet or outlet side of a zoneHVAC equipment such as a four pipe fan coil unit. Normally the central air would be ventilation air from a dedicated outdoor air system (DOAS).

Field Type Default Details
name
Name required
string
zonehvac_unit_object_type
ZoneHVAC Unit Object Type required
choice The type of ZoneHVAC equipment to which this terminal mixer will be connected.
One of AirLoopHVAC:UnitarySystem, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitVentilator, ZoneHVAC:WaterToAirHeatPump
zonehvac_unit_object_name
ZoneHVAC Unit Object Name required
reference The name of ZoneHVAC equipment to which this terminal mixer will be connected.
Names a AirLoopHVAC:UnitarySystem, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitVentilator, ZoneHVAC:WaterToAirHeatPump
mixer_outlet_node_name
Mixer Outlet Node Name required
string This is the outlet air node name of the mixer. This will be the inlet air node name of the ZoneHVAC equipment if the connection type in the input field Mixer Connection Type below is InletSide, else this will be an inlet air node name of the conditioned zone if the connection type in the input field Mixer Connection Type below is SupplySide.
mixer_primary_air_inlet_node_name
Mixer Primary Air Inlet Node Name required
string The primary air (treated outdoor air) inlet node name of the mixer. This will be an outlet air node name of an AirLoopHVAC:ZoneSplitter or AirLoopHVAC:SupplyPlenum providing the connection to the DOA system.
mixer_secondary_air_inlet_node_name
Mixer Secondary Air Inlet Node Name required
string The secondary air (recirculating air) inlet node name of the mixer. This will be the outlet air node name of the ZoneHVAC equipment if the connection type in the input field mixer Connection Type below is SupplySide, or else this will be an exhaust air node name of the conditioned zone if the connection type in the input field Mixer Connection Type below is InletSide.
mixer_connection_type
Mixer Connection Type required
choice This input field allows user to specify the mixer connection type. Valid choices are InletSide or SupplySide. This is a required input field. If the mixer connection type selected is InletSide, then the mixer is connected on the inlet side of the ZoneHVAC equipment, or else if the mixer connection type selected is SupplySide, then the mixer is connected at the outlet side of the ZoneHVAC equipment.
One of InletSide, SupplySide
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will adjust flow to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone, as for demand controlled ventilation. If this field is blank, then the terminal unit will be controlled using the DesignSpecification:OutdoorAir object referenced in the Sizing:Zone object.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
per_person_ventilation_rate_mode
Per Person Ventilation Rate Mode
choice CurrentOccupancy CurrentOccupancy models demand controlled ventilation using the current number of people DesignOccupancy uses the total Number of People in the zone and is constant
One of CurrentOccupancy, DesignOccupancy
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:ParallelPIU:Reheat

from idfpy.models import AirTerminalSingleDuctParallelPIUReheat

Central air system terminal unit, single duct, variable volume, parallel powered induction unit (PIU), with reheat coil (hot water, electric, gas, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_primary_air_flow_rate
Maximum Primary Air Flow Rate required
number or Autosize
m3/s
maximum_secondary_air_flow_rate
Maximum Secondary Air Flow Rate required
number or Autosize
m3/s
minimum_primary_air_flow_fraction
Minimum Primary Air Flow Fraction required
number or Autosize When set to autosize, the calculated air flow is determined based on the System Outdoor Air Method used in the air loop's Sizing:System object.
fan_on_flow_fraction
Fan On Flow Fraction required
number or Autosize the fraction of the primary air flow at which fan turns on
supply_air_inlet_node_name
Supply Air Inlet Node Name
string
secondary_air_inlet_node_name
Secondary Air Inlet Node Name
string
outlet_node_name
Outlet Node Name
string
zone_mixer_name
Zone Mixer Name
reference Names a AirLoopHVAC:ZoneMixer
fan_name
Fan Name
reference Fan type must be Fan:SystemModel or Fan:ConstantVolume
Names a Fan:ConstantVolume, Fan:SystemModel
reheat_coil_object_type
Reheat Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when reheat coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when reheat coil type is gas or electric
Range: ≥ 0
convergence_tolerance
Convergence Tolerance
number 0.001 Range: > 0
fan_control_type
Fan Control Type
choice ConstantSpeed If VariableSpeed, then the fan object type must be Fan:SystemModel
One of ConstantSpeed, VariableSpeed
minimum_fan_turn_down_ratio
Minimum Fan Turn Down Ratio
number
dimensionless
0.3 flow through terminal at minimum fan speed is this ratio multiplied by Maximum Air Flow Rate
Range: ≥ 0, ≤ 1
heating_control_type
Heating Control Type
choice Only used if Fan Control Type is VariableSpeed
One of Modulated, Staged
design_heating_discharge_air_temperature
Design Heating Discharge Air Temperature
number
C
32.1 Only used if Heating Control Type is Modulated Used to control second stage heating, typically zone heat setpoint plus 20F
high_limit_heating_discharge_air_temperature
High Limit Heating Discharge Air Temperature
number
C
37.7 Only used if Heating Control Type is Modulated Used to determine end of third stage heating
backdraft_damper_leakage_fraction_curve_name
Backdraft Damper Leakage Fraction Curve Name
reference Backdraft damper leakage fraction is the ratio of mass leakage flow rate to primary air flow rate at a constant static pressure setpoint. This curve should describe the ratio as a function primary air flow fraction (ratio of primary flow fraction to maximum nominal primary air flow rate).
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
backdraft_damper_leakage_zone_name
Backdraft Damper Leakage Zone Name
reference Name of a zone that will be impacted by the backdraft damper leakage.
Names a Zone
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:SeriesPIU:Reheat

from idfpy.models import AirTerminalSingleDuctSeriesPIUReheat

Central air system terminal unit, single duct, variable volume, series powered induction unit (PIU), with reheat coil (hot water, electric, gas, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
maximum_primary_air_flow_rate
Maximum Primary Air Flow Rate required
number or Autosize
m3/s
minimum_primary_air_flow_fraction
Minimum Primary Air Flow Fraction required
number or Autosize When set to autosize, the calculated air flow is determined based on the System Outdoor Air Method used in the air loop's Sizing:System object.
supply_air_inlet_node_name
Supply Air Inlet Node Name
string
secondary_air_inlet_node_name
Secondary Air Inlet Node Name
string
outlet_node_name
Outlet Node Name
string
zone_mixer_name
Zone Mixer Name
reference Names a AirLoopHVAC:ZoneMixer
fan_name
Fan Name
reference Fan type must be Fan:SystemModel or Fan:ConstantVolume
Names a Fan:ConstantVolume, Fan:SystemModel
reheat_coil_object_type
Reheat Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when reheat coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when reheat coil type is gas or electric
Range: ≥ 0
convergence_tolerance
Convergence Tolerance
number 0.001 Range: > 0
fan_control_type
Fan Control Type
choice ConstantSpeed If VariableSpeed, then the fan object type must be Fan:SystemModel
One of ConstantSpeed, VariableSpeed
minimum_fan_turn_down_ratio
Minimum Fan Turn Down Ratio
number
dimensionless
0.3 flow through terminal at minimum fan speed is this ratio multiplied by Maximum Air Flow Rate
Range: ≥ 0, ≤ 1
heating_control_type
Heating Control Type
choice Only used if Fan Control Type is VariableSpeed
One of Modulated, Staged
design_heating_discharge_air_temperature
Design Heating Discharge Air Temperature
number
C
32.1 Only used if Heating Control Type is Modulated Used to control second stage heating, typically zone heat setpoint plus 20F
high_limit_heating_discharge_air_temperature
High Limit Heating Discharge Air Temperature
number
C
37.7 Only used if Heating Control Type is Modulated Used to determine end of third stage heating
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat

from idfpy.models import AirTerminalSingleDuctVAVHeatAndCoolNoReheat

Central air system terminal unit, single duct, variable volume for both cooling and heating, with no reheat coil.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit. This is also the zone inlet node.
air_inlet_node_name
Air Inlet Node Name required
string
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_fraction
Zone Minimum Air Flow Fraction required
number fraction of maximum air flow
Range: ≥ 0, ≤ 1
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the design minimum flow rate by multiplying it using this schedule of fraction values. This field is used with "Zone Minimum Air Flow Fraction". Schedule values are fractions 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1 and the model uses the fixed fraction specified in in the field "Zone Minimum Air Flow Fraction".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat

from idfpy.models import AirTerminalSingleDuctVAVHeatAndCoolReheat

Central air system terminal unit, single duct, variable volume for both cooling and heating, with reheat coil (hot water, electric, gas, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
damper_air_outlet_node_name
Damper Air Outlet Node Name required
string the outlet node of the damper and the inlet node of the reheat coil this is an internal node to the terminal unit and connects the damper and reheat coil
air_inlet_node_name
Air Inlet Node Name required
string the inlet node to the terminal unit and the damper
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_fraction
Zone Minimum Air Flow Fraction required
number fraction of maximum air flow
Range: ≥ 0, ≤ 1
reheat_coil_object_type
Reheat Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when reheat coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when reheat coil type is gas or electric
Range: ≥ 0
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit and the reheat coil. This is also the zone inlet node.
convergence_tolerance
Convergence Tolerance
number 0.001 Range: > 0
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the design minimum flow rate by multiplying it using this schedule of fraction values. This field is used with "Zone Minimum Air Flow Fraction". Schedule values are fractions 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1 and the model uses the fixed fraction specified in in the field "Zone Minimum Air Flow Fraction".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:VAV:NoReheat

from idfpy.models import AirTerminalSingleDuctVAVNoReheat

Central air system terminal unit, single duct, variable volume, with no reheat coil.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_node_name
Air Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_input_method
Zone Minimum Air Flow Input Method
choice Constant Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate) FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate) Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air Flow
One of Constant, FixedFlowRate, Scheduled
constant_minimum_air_flow_fraction
Constant Minimum Air Flow Fraction
number or Autosize Autosize This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional; if a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used. The values for autosizing are picked up from the Sizing:Zone input fields "Cooling Minimum Air Flow per Zone Floor Area", "Cooling Minimum Air Flow", and "Cooling Minimum Air Flow Fraction". If there is no sizing calculation a default of 0.000762 m3/s-m2 (0.15 cfm/ft2) is used.
fixed_minimum_air_flow_rate
Fixed Minimum Air Flow Rate
number or Autosize
m3/s
Autosize This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate. If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional; if a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the previous field are entered, the larger result is used. The values for autosizing are picked up from the Sizing:Zone input fields "Cooling Minimum Air Flow per Zone Floor Area", "Cooling Minimum Air Flow", and "Cooling Minimum Air Flow Fraction". If there is no sizing calculation a default of 0.000762 m3/s-m2 (0.15 cfm/ft2) is used.
minimum_air_flow_fraction_schedule_name
Minimum Air Flow Fraction Schedule Name
reference This field is used if the field Zone Minimum Air Flow Input Method is Scheduled Schedule values are fractions, 0.0 to 1.0. If the field Constant Minimum Air Flow Fraction is blank, then the average of the minimum and maximum schedule values is used for sizing normal-action reheat coils.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the design minimum flow rate by multiplying it using this schedule of fraction values. This field can be used with any of the three "Zone Minimum Air Flow Input Method". Schedule values are fractions, 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:VAV:Reheat

from idfpy.models import AirTerminalSingleDuctVAVReheat

Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
damper_air_outlet_node_name
Damper Air Outlet Node Name required
string the outlet node of the damper and the inlet node of the reheat coil this is an internal node to the terminal unit and connects the damper and reheat coil
air_inlet_node_name
Air Inlet Node Name required
string the inlet node to the terminal unit and the damper
maximum_air_flow_rate
Maximum Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_input_method
Zone Minimum Air Flow Input Method
choice Constant Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate) FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate) Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air Flow
One of Constant, FixedFlowRate, Scheduled
constant_minimum_air_flow_fraction
Constant Minimum Air Flow Fraction
number or Autosize Autosize This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional; if a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used. The values for autosizing are picked up from the Sizing:Zone input fields "Cooling Minimum Air Flow per Zone Floor Area", "Cooling Minimum Air Flow", and "Cooling Minimum Air Flow Fraction". If there is no sizing calculation a default of 0.000762 m3/s-m2 (0.15 cfm/ft2) is used.
fixed_minimum_air_flow_rate
Fixed Minimum Air Flow Rate
number or Autosize
m3/s
Autosize This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate. If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional; if a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the previous field are entered, the larger result is used. The values for autosizing are picked up from the Sizing:Zone input fields "Cooling Minimum Air Flow per Zone Floor Area", "Cooling Minimum Air Flow", and "Cooling Minimum Air Flow Fraction". If there is no sizing calculation a default of 0.000762 m3/s-m2 (0.15 cfm/ft2) is used.
minimum_air_flow_fraction_schedule_name
Minimum Air Flow Fraction Schedule Name
reference This field is used if the field Zone Minimum Air Flow Input Method is Scheduled Schedule values are fractions, 0.0 to 1.0. If the field Constant Minimum Air Flow Fraction is blank, then the average of the minimum and maximum schedule values is used for sizing normal-action reheat coils.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
reheat_coil_object_type
Reheat Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when reheat coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when reheat coil type is gas or electric
Range: ≥ 0
air_outlet_node_name
Air Outlet Node Name required
string The outlet node of the terminal unit and the reheat coil. This is also the zone inlet node.
convergence_tolerance
Convergence Tolerance
number 0.001 Range: > 0
damper_heating_action
Damper Heating Action
choice ReverseWithLimits Normal means the damper is fixed at the minimum position in heating mode Reverse means the damper can open fully during reheat ReverseWithLimits means the damper will open partially during reheat as specified in the following 2 fields
One of Normal, Reverse, ReverseWithLimits
maximum_flow_per_zone_floor_area_during_reheat
Maximum Flow per Zone Floor Area During Reheat
number or Autosize
m3/s-m2
Autosize Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = ReverseWithLimits When autocalculating, the maximum flow per zone is set to 0.002032 m3/s-m2 (0.4 cfm/sqft) This optional field limits the maximum flow allowed in reheat mode. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate.
maximum_flow_fraction_during_reheat
Maximum Flow Fraction During Reheat
number or Autosize Autosize Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = ReverseWithLimits When autocalculating, the maximum flow fraction is set to the ratio of 0.002032 m3/s-m2 (0.4 cfm/sqft) multiplied by the zone floor area and the Maximum Air Flow Rate. This optional field limits the maximum flow allowed in reheat mode. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate.
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the design minimum flow rate by multiplying it using this schedule of fraction values. This field can be used with any of the three "Zone Minimum Air Flow Input Method". Schedule values are fractions, 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 3 object types

AirflowNetwork:Distribution:Component:TerminalUnit, AirflowNetwork:Distribution:Linkage, ZoneHVAC:AirDistributionUnit

AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan

from idfpy.models import AirTerminalSingleDuctVAVReheatVariableSpeedFan

Central air system terminal unit, single duct, variable volume, with reheat coil (hot water, electric, gas, or steam) and variable-speed fan. These units are usually employed in underfloor air distribution (UFAD) systems where the air is supplied at low static pressure through an underfloor plenum. The fan is used to control the flow of conditioned air that enters the space.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_cooling_air_flow_rate
Maximum Cooling Air Flow Rate required
number or Autosize
m3/s
maximum_heating_air_flow_rate
Maximum Heating Air Flow Rate required
number or Autosize
m3/s
zone_minimum_air_flow_fraction
Zone Minimum Air Flow Fraction required
number fraction of cooling air flow rate
Range: ≥ 0, ≤ 1
air_inlet_node_name
Air Inlet Node Name
string The name of the HVAC system node that is the air inlet node for the terminal unit. This is also the air inlet node for the unit's fan.
air_outlet_node_name
Air Outlet Node Name
string The name of the HVAC system node that is the air outlet node for the terminal unit. This is also the air outlet node for the unit's heating coil's air outlet node. This node is also a zone inlet node.
fan_object_type
Fan Object Type required
choice One of Fan:SystemModel, Fan:VariableVolume
fan_name
Fan Name required
reference Names a Fan:SystemModel, Fan:VariableVolume
heating_coil_object_type
Heating Coil Object Type required
choice One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_hot_water_or_steam_flow_rate
Maximum Hot Water or Steam Flow Rate
number or Autosize
m3/s
Not used when heating coil type is gas or electric
minimum_hot_water_or_steam_flow_rate
Minimum Hot Water or Steam Flow Rate
number
m3/s
0.0 Not used when heating coil type is gas or electric
Range: ≥ 0
heating_convergence_tolerance
Heating Convergence Tolerance
number 0.001 Range: > 0
minimum_air_flow_turndown_schedule_name
Minimum Air Flow Turndown Schedule Name
reference This field adjusts the fan-off minimum flow rate by multiplying it using this scheduled fraction values. This field is used with "Zone Minimum Air Flow Fraction". Schedule values are fractions 0.0 to 1.0. This field adjusts the minimum airflow turndown below the design minimum air flow and is intended for use with ASHRAE Standard 170. If this field is left blank, then the turndown minimum air flow fraction value is set to 1 and the model uses the fixed fraction specified in in the field "Zone Minimum Air Flow Fraction".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

ZoneHVAC:AirDistributionUnit

from idfpy.models import ZoneHVACAirDistributionUnit

Central air system air distribution unit, serves as a wrapper for a specific type of air terminal unit. This object is referenced in a ZoneHVAC:EquipmentList.

Field Type Default Details
name
Name required
string
air_distribution_unit_outlet_node_name
Air Distribution Unit Outlet Node Name required
string
air_terminal_object_type
Air Terminal Object Type required
choice One of AirTerminal:DualDuct:ConstantVolume, AirTerminal:DualDuct:VAV, AirTerminal:DualDuct:VAV:OutdoorAir, AirTerminal:SingleDuct:ConstantVolume:CooledBeam, AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:Mixer, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:UserDefined, AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat, AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat, AirTerminal:SingleDuct:VAV:NoReheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan
air_terminal_name
Air Terminal Name required
reference Names a AirTerminal:DualDuct:ConstantVolume, AirTerminal:DualDuct:VAV, AirTerminal:DualDuct:VAV:OutdoorAir, AirTerminal:SingleDuct:ConstantVolume:CooledBeam, AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:Mixer, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:UserDefined and 5 more
nominal_upstream_leakage_fraction
Nominal Upstream Leakage Fraction
number 0.0 fraction at system design Flow; leakage Flow constant, leakage fraction varies with variable system Flow Rate.
Range: ≥ 0, ≤ 0.3
constant_downstream_leakage_fraction
Constant Downstream Leakage Fraction
number 0.0 Range: ≥ 0, ≤ 0.3
design_specification_air_terminal_sizing_object_name
Design Specification Air Terminal Sizing Object Name
reference This optional field is the name of a DesignSpecification:AirTerminal:Sizing object which specifies sizing adjustments to be made for this terminal unit.
Names a DesignSpecification:AirTerminal:Sizing
Referenced by 2 object types

SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList

ZoneHVAC:ExhaustControl

from idfpy.models import ZoneHVACExhaustControl

Defines a controlled exhaust flow from a zone which finally feeds into one of AirLoopHVAC:ZoneMixer's inlets, which are part of an AirLoopHVAC:ExhaustSystem.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this exhaust system. Schedule value > 0 means it is available. If this field is blank, the exhaust system is always available. If the attached AirLoopHVAC:ExhaustSystem is off, then the flow will be zero.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_name
Zone Name required
reference Zone the exhaust inlet node is part of
Names a Zone
inlet_node_name
Inlet Node Name required
string Inlet node name for the exhaust. Must be a zone exhaust node.
outlet_node_name
Outlet Node Name required
string Outlet node name for the exhaust
design_exhaust_flow_rate
Design Exhaust Flow Rate
number or Autosize
m3/s
Autosize
flow_control_type
Flow Control Type
choice Scheduled Control type of the zone exhaust flow
One of FollowSupply, Scheduled
exhaust_flow_fraction_schedule_name
Exhaust Flow Fraction Schedule Name
reference Schedule name of the exhaust flow fraction. Used only with Scheduled control type. If this field is blank, the flow fraction is always 1.0.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_node_or_nodelist_name
Supply Node or NodeList Name
string Used only with FollowSupply control type.
minimum_zone_temperature_limit_schedule_name
Minimum Zone Temperature Limit Schedule Name
reference Schedule name of the Minimum Zone Temperature Limit in degree Celsius If this field is blank, there is no limit.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
minimum_exhaust_flow_fraction_schedule_name
Minimum Exhaust Flow Fraction Schedule Name
reference Schedule name of the minimum exhaust flow fraction. Applied when the zone temperature falls below the Minimum Zone Temperature Limit.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
balanced_exhaust_fraction_schedule_name
Balanced Exhaust Fraction Schedule Name
reference Schedule name of the Balanced Exhaust Fraction.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules