Zone HVAC Equipment Connections

6 object types from idfpy.models.zone_equipment · EnergyPlus 26.2

Object Summary
SpaceHVAC:EquipmentConnections Specifies the HVAC equipment connections for a space.
SpaceHVAC:ZoneEquipmentMixer Mixes the airflow from one or more Spaces into a piece of zone equipment.
SpaceHVAC:ZoneEquipmentSplitter Distributes the output from a piece of zone equipment to one or more Spaces in the Zone.
SpaceHVAC:ZoneReturnMixer Mixes the return airflow from one or more Spaces into a zone return node.
ZoneHVAC:EquipmentConnections Specifies the HVAC equipment connections for a zone.
ZoneHVAC:EquipmentList List equipment in simulation order.

SpaceHVAC:EquipmentConnections

from idfpy.models import SpaceHVACEquipmentConnections

Specifies the HVAC equipment connections for a space. Node names are specified for the space air node, air inlet nodes, air exhaust nodes, and the air return node. If any space in a zone has a SpaceHVAC:EquipmentConnections object, then all spaces in the zone must have one. Used only when ZoneAirHeatBalanceAlgorithm "Do Space Heat Balance for Simulation" is Yes.

Field Type Default Details
space_name
Space Name required
reference Names a Space
space_air_inlet_node_or_nodelist_name
Space Air Inlet Node or NodeList Name
string
space_air_exhaust_node_or_nodelist_name
Space Air Exhaust Node or NodeList Name
string
space_air_node_name
Space Air Node Name required
string
space_return_air_node_or_nodelist_name
Space Return Air Node or NodeList Name
string
space_return_air_node_1_flow_rate_fraction_schedule_name
Space Return Air Node 1 Flow Rate Fraction Schedule Name
reference This schedule is multiplied times the base return air flow rate. If this field is left blank, the schedule defaults to 1.0 at all times.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
space_return_air_node_1_flow_rate_basis_node_or_nodelist_name
Space Return Air Node 1 Flow Rate Basis Node or NodeList Name
string The optional basis node(s) used to calculate the base return air flow rate for the first return air node in this space. The return air flow rate is the sum of the flow rates at the basis node(s) multiplied by the Space Return Air Flow Rate Fraction Schedule. If this field is blank, then the base return air flow rate is the total supply inlet flow rate to the zone less the total exhaust node flow rate from the space.

SpaceHVAC:ZoneEquipmentMixer

from idfpy.models import SpaceHVACZoneEquipmentMixer extensible

Mixes the airflow from one or more Spaces into a piece of zone equipment. All spaces in the zone must also have a SpaceHVAC:EquipmentConnections object. Used only when ZoneAirHeatBalanceAlgorithm "Do Space Heat Balance for Simulation" is Yes.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Must be a controlled zone which has a ZoneHVAC:EquipmentConnections object.
Names a Zone
zone_equipment_inlet_node_name
Zone Equipment Inlet Node Name required
string The inlet node from the zone equipment that will be mixed from the spaces. Must match a Zone Exhaust Node for this zone.
space_fraction_method
Space Fraction Method
choice DesignCoolingLoad The basis used to autosize the space output fractions.
One of DesignCoolingLoad, DesignHeatingLoad, FloorArea, PerimeterLength, Volume
spaces list Each item: space_name, space_fraction (dimensionless), space_node_name

SpaceHVAC:ZoneEquipmentSplitter

from idfpy.models import SpaceHVACZoneEquipmentSplitter extensible

Distributes the output from a piece of zone equipment to one or more Spaces in the Zone. If any equipment in a zone has a SpaceHVAC:ZoneEquipmentSplitter, then all equipment in the zone must have one. except Fan:ZoneExhaust. All spaces in the zone must also have a SpaceHVAC:EquipmentConnections object. Used only when ZoneAirHeatBalanceAlgorithm "Do Space Heat Balance for Simulation" is Yes.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Must be a controlled zone which has a ZoneHVAC:EquipmentConnections object.
Names a Zone
zone_equipment_object_type
Zone Equipment Object Type required
choice One of AirLoopHVAC:UnitarySystem, HeatExchanger:AirToAir:FlatPlate, WaterHeater:HeatPump:PumpedCondenser, WaterHeater:HeatPump:WrappedCondenser, ZoneHVAC:AirDistributionUnit, ZoneHVAC:Baseboard:Convective:Electric, ZoneHVAC:Baseboard:Convective:Water, ZoneHVAC:Baseboard:RadiantConvective:Electric, ZoneHVAC:Baseboard:RadiantConvective:Steam, ZoneHVAC:Baseboard:RadiantConvective:Water, ZoneHVAC:CoolingPanel:RadiantConvective:Water, ZoneHVAC:Dehumidifier:DX, ZoneHVAC:EnergyRecoveryVentilator, ZoneHVAC:EvaporativeCoolerUnit, ZoneHVAC:ForcedAir:UserDefined, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:HighTemperatureRadiant, ZoneHVAC:HybridUnitaryHVAC, ZoneHVAC:IdealLoadsAirSystem, ZoneHVAC:LowTemperatureRadiant:ConstantFlow, ZoneHVAC:LowTemperatureRadiant:Electric, ZoneHVAC:LowTemperatureRadiant:VariableFlow, ZoneHVAC:OutdoorAirUnit, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:RefrigerationChillerSet, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump, ZoneHVAC:WindowAirConditioner
zone_equipment_name
Zone Equipment Name required
reference Names a AirLoopHVAC:UnitarySystem, Fan:ZoneExhaust, HeatExchanger:AirToAir:FlatPlate, WaterHeater:HeatPump:PumpedCondenser, WaterHeater:HeatPump:WrappedCondenser, ZoneHVAC:AirDistributionUnit, ZoneHVAC:Baseboard:Convective:Electric, ZoneHVAC:Baseboard:Convective:Water, ZoneHVAC:Baseboard:RadiantConvective:Electric, ZoneHVAC:Baseboard:RadiantConvective:Steam, ZoneHVAC:Baseboard:RadiantConvective:Steam:Design, ZoneHVAC:Baseboard:RadiantConvective:Water and 22 more
zone_equipment_outlet_node_name
Zone Equipment Outlet Node Name
string Only used for airflow equipment. The outlet node from the zone equipment that will be split to the spaces.
thermostat_control_method
Thermostat Control Method
choice SingleSpace SingleSpace satisfies the thermostat in the Control Space Name Maximum satisfies the thermostat in the connected spaces with the highest deviation from setpoint Ideal ignores the Space Output Fractions and distributes the output to match the current space sensible loads.
One of Ideal, Maximum, SingleSpace
control_space_name
Control Space Name
reference This field is only used when Thermostat Control Method = SingleSpace.
Names a Space
space_fraction_method
Space Fraction Method
choice DesignCoolingLoad The basis used to autosize the space output fractions.
One of DesignCoolingLoad, DesignHeatingLoad, FloorArea, PerimeterLength, Volume
spaces list Each item: space_name, space_fraction (dimensionless), space_supply_node_name

SpaceHVAC:ZoneReturnMixer

from idfpy.models import SpaceHVACZoneReturnMixer extensible

Mixes the return airflow from one or more Spaces into a zone return node. All spaces in the zone must also have a SpaceHVAC:EquipmentConnections object. Used only when ZoneAirHeatBalanceAlgorithm "Do Space Heat Balance for Simulation" is Yes.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Must be a controlled zone which has a ZoneHVAC:EquipmentConnections object.
Names a Zone
zone_return_air_node_name
Zone Return Air Node Name required
string The zone return air node will be mixed from the spaces. Must match a Zone Return Air Node for this zone.
spaces list Each item: space_name, space_return_air_node_name

ZoneHVAC:EquipmentConnections

from idfpy.models import ZoneHVACEquipmentConnections

Specifies the HVAC equipment connections for a zone. Node names are specified for the zone air node, air inlet nodes, air exhaust nodes, and the air return node. A zone equipment list is referenced which lists all HVAC equipment connected to the zone.

Field Type Default Details
zone_name
Zone Name required
reference Names a Zone
zone_conditioning_equipment_list_name
Zone Conditioning Equipment List Name required
reference Enter the name of a ZoneHVAC:EquipmentList object.
Names a ZoneHVAC:EquipmentList
zone_air_inlet_node_or_nodelist_name
Zone Air Inlet Node or NodeList Name
string
zone_air_exhaust_node_or_nodelist_name
Zone Air Exhaust Node or NodeList Name
string
zone_air_node_name
Zone Air Node Name required
string
zone_return_air_node_or_nodelist_name
Zone Return Air Node or NodeList Name
string
zone_return_air_node_1_flow_rate_fraction_schedule_name
Zone Return Air Node 1 Flow Rate Fraction Schedule Name
reference This schedule is multiplied times the base return air flow rate. If this field is left blank, the schedule defaults to 1.0 at all times.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_return_air_node_1_flow_rate_basis_node_or_nodelist_name
Zone Return Air Node 1 Flow Rate Basis Node or NodeList Name
string The optional basis node(s) used to calculate the base return air flow rate for the first return air node in this zone. The return air flow rate is the sum of the flow rates at the basis node(s) multiplied by the Zone Return Air Flow Rate Fraction Schedule. If this field is blank, then the base return air flow rate is the total supply inlet flow rate to the zone less the total exhaust node flow rate from the zone.

ZoneHVAC:EquipmentList

from idfpy.models import ZoneHVACEquipmentList extensible

List equipment in simulation order. Note that an ZoneHVAC:AirDistributionUnit object must be listed in this statement if there is a forced air system serving the zone from the air loop. Equipment is simulated in the order specified by Zone Equipment Cooling Sequence and Zone Equipment Heating or No-Load Sequence, depending on the thermostat request. For equipment of similar type, assign sequence 1 to the first system intended to serve that type of load. For situations where one or more equipment types has limited capacity or limited control, order the sequence so that the most controllable piece of equipment runs last. For example, with a dedicated outdoor air system (DOAS), the air terminal for the DOAS should be assigned Heating Sequence = 1 and Cooling Sequence = 1. Any other equipment should be assigned sequence 2 or higher so that it will see the net load after the DOAS air is added to the zone.

Field Type Default Details
name
Name required
string
load_distribution_scheme
Load Distribution Scheme
choice SequentialLoad One of SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR
equipment list Each item: zone_equipment_object_type, zone_equipment_name, zone_equipment_cooling_sequence, zone_equipment_heating_or_no_load_sequence, zone_equipment_sequential_cooling_fraction_schedule_name, zone_equipment_sequential_heating_fraction_schedule_name
Referenced by 1 object types

ZoneHVAC:EquipmentConnections