HVAC Templates¶
32 object types from idfpy.models.hvac_templates · EnergyPlus 26.2
| Object | Summary |
|---|---|
| HVACTemplate:Plant:Boiler | This object adds a boiler to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop. |
| HVACTemplate:Plant:Boiler:ObjectReference | This object references a detailed boiler object and adds it to an HVACTemplate:Plant:HotWaterLoop or … |
| HVACTemplate:Plant:ChilledWaterLoop | Plant and condenser loops to serve all HVACTemplate chilled water coils, chillers, and towers. |
| HVACTemplate:Plant:Chiller | This object adds a chiller to an HVACTemplate:Plant:ChilledWaterLoop. |
| HVACTemplate:Plant:Chiller:ObjectReference | This object references a detailed chiller object and adds it to an HVACTemplate:Plant:ChilledWaterLoop. |
| HVACTemplate:Plant:HotWaterLoop | Plant loop to serve all HVACTemplate hot water coils and boilers. |
| HVACTemplate:Plant:MixedWaterLoop | Central plant loop portion of a water source heat pump system. |
| HVACTemplate:Plant:Tower | This object adds a cooling tower to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop. |
| HVACTemplate:Plant:Tower:ObjectReference | This object references a detailed cooling tower object and adds it to an HVACTemplate:Plant:ChilledWaterLoop … |
| HVACTemplate:System:ConstantVolume | Constant Air Volume air loop with optional chilled water cooling coil, optional heating coil and optional … |
| HVACTemplate:System:DedicatedOutdoorAir | This object creates a dedicated outdoor air system that must be used with HVACTemplate:Zone:* objects for … |
| HVACTemplate:System:DualDuct | Dual-duct constant volume or variable volume air loop |
| HVACTemplate:System:PackagedVAV | Packaged Variable Air Volume (PVAV) air loop with optional heating coil and optional preheat. |
| HVACTemplate:System:Unitary | Unitary furnace with air conditioner |
| HVACTemplate:System:UnitaryHeatPump:AirToAir | Unitary furnace with electric air-to-air heat pump |
| HVACTemplate:System:UnitarySystem | Unitary HVAC system with optional cooling and heating. |
| HVACTemplate:System:VAV | Variable Air Volume (VAV) air loop with optional heating coil and optional preheat. |
| HVACTemplate:System:VRF | Variable refrigerant flow (VRF) heat pump condensing unit. |
| HVACTemplate:Thermostat | Zone thermostat control. |
| HVACTemplate:Zone:BaseboardHeat | Zone baseboard heating system. |
| HVACTemplate:Zone:ConstantVolume | Zone terminal unit, constant volume, reheat optional. |
| HVACTemplate:Zone:DualDuct | Zone terminal unit, dual-duct, constant or variable volume. |
| HVACTemplate:Zone:FanCoil | 4 pipe fan coil unit with optional outdoor air. |
| HVACTemplate:Zone:IdealLoadsAirSystem | Zone with ideal air system that meets heating or cooling loads |
| HVACTemplate:Zone:PTAC | Packaged Terminal Air Conditioner |
| HVACTemplate:Zone:PTHP | Packaged Terminal Heat Pump |
| HVACTemplate:Zone:Unitary | Zone terminal unit, constant volume, no controls. |
| HVACTemplate:Zone:VAV | Zone terminal unit, variable volume, reheat optional. |
| HVACTemplate:Zone:VAV:FanPowered | Zone terminal unit, fan powered variable volume, reheat optional. |
| HVACTemplate:Zone:VAV:HeatAndCool | VAV system with VAV for both heating and cooling and optional reheat coil. |
| HVACTemplate:Zone:VRF | Zone terminal unit with variable refrigerant flow (VRF) DX cooling and heating coils (air-to-air or … |
| HVACTemplate:Zone:WaterToAirHeatPump | Water to Air Heat Pump to be used with HVACTemplate:Plant:MixedWaterLoop |
HVACTemplate:Plant:Boiler¶
from idfpy.models import HVACTemplatePlantBoiler
This object adds a boiler to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
boiler_Boiler Type required |
choice | One of CondensingHotWaterBoiler, DistrictHotWater, HotWaterBoiler |
|
capacityCapacity |
number or AutosizeW |
Autosize |
|
efficiencyEfficiency |
number | 0.8 |
Not applicable if Boiler Type is DistrictHotWater Range: ≥ 0, ≤ 1 |
fuel_Fuel Type |
choice | Not applicable if Boiler Type is DistrictHotWater One of Coal, Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane |
|
priorityPriority |
string | If Hot Water Plant Operation Scheme Type=Default in HVACTemplate:Plant:HotWaterLoop, then equipment operates in priority order, 1, 2, 3, etc. | |
sizing_Sizing Factor |
number | 1.0 |
Multiplies the autosized capacity and flow rates Range: > 0 |
minimum_Minimum Part Load Ratio |
number | 0.0 |
Range: ≥ 0 |
maximum_Maximum Part Load Ratio |
number | 1.1 |
Range: ≥ 0 |
optimum_Optimum Part Load Ratio |
number | 1.0 |
Range: ≥ 0 |
water_Water Outlet Upper Temperature Limit |
number C |
100.0 |
|
template_Template Plant Loop Type |
choice | Specifies if this boiler serves a template hot water loop or mixed water loop If left blank, will serve a hot water loop if present, or a mixed water loop (if no hot water loop is present). One of HotWater, MixedWater |
HVACTemplate:Plant:Boiler:ObjectReference¶
from idfpy.models import HVACTemplatePlantBoilerObjectReference
This object references a detailed boiler object and adds it to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop. The user must create a complete detailed boiler object with all required curve or performance objects.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | The name of this object. | |
boiler_Boiler Object Type |
choice | Boiler:HotWater |
One of Boiler:HotWater |
boiler_Boiler Name required |
reference | The name of the detailed boiler object. Names a Boiler:HotWater |
|
priorityPriority |
number | If Hot Water Plant Operation Scheme Type=Default in HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc. | |
template_Template Plant Loop Type |
choice | Specifies if this boiler serves a template hot water loop or mixed water loop If left blank, will serve a hot water loop if present, or a mixed water loop (if no hot water loop is present). One of HotWater, MixedWater |
HVACTemplate:Plant:ChilledWaterLoop¶
from idfpy.models import HVACTemplatePlantChilledWaterLoop unique
Plant and condenser loops to serve all HVACTemplate chilled water coils, chillers, and towers.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
pump_Pump Schedule Name |
reference | If blank, always available Applies to both chilled water and condenser loop pumps Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
pump_Pump Control Type |
choice | Intermittent |
Applies to both chilled water and condenser loop pumps One of Continuous, Intermittent |
chiller_Chiller Plant Operation Scheme Type |
choice | Default |
Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Chiller objects. One of Default, UserDefined |
chiller_Chiller Plant Equipment Operation Schemes Name |
reference | Name of a PlantEquipmentOperationSchemes object Ignored if Chiller Plant Operation Scheme Type = Default Names a PlantEquipmentOperationSchemes |
|
chilled_Chilled Water Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
chilled_Chilled Water Design Setpoint |
number C |
7.22 |
Used for sizing and as constant setpoint if no Chilled Water Setpoint Schedule Name is specified. |
chilled_Chilled Water Pump Configuration |
choice | ConstantPrimaryNoSecondary |
VariablePrimaryNoSecondary - variable flow to chillers and coils ConstantPrimaryNoSecondary - constant flow to chillers and coils, excess bypassed ConstantPrimaryVariableSecondary - constant flow to chillers, variable flow to coils VariablePrimaryConstantSecondary - currently unsupported - variable flow to chillers, constant flow to coils One of ConstantPrimaryNoSecondary, ConstantPrimaryVariableSecondary, VariablePrimaryNoSecondary |
primary_Primary Chilled Water Pump Rated Head |
number Pa |
179352.0 |
default head is 60 feet H2O Range: ≥ 0 |
secondary_Secondary Chilled Water Pump Rated Head |
number Pa |
179352.0 |
default head is 60 feet H2O Range: ≥ 0 |
condenser_Condenser Plant Operation Scheme Type |
choice | Default |
Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Tower objects. May be left blank if not serving any water cooled chillers One of Default, UserDefined |
condenser_Condenser Equipment Operation Schemes Name |
reference | Name of a CondenserEquipmentOperationSchemes object Ignored if Condenser Plant Operation Scheme Type = Default May be left blank if not serving any water cooled chillers Names a CondenserEquipmentOperationSchemes |
|
condenser_Condenser Water Temperature Control Type |
choice | May be left blank if not serving any water cooled chillers One of OutdoorWetBulbTemperature, SpecifiedSetpoint |
|
condenser_Condenser Water Setpoint Schedule Name |
reference | Leave blank if constant setpoint May be left blank if not serving any water cooled chillers Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
condenser_Condenser Water Design Setpoint |
number C |
29.4 |
Used for sizing and as constant setpoint if no Condenser Water Setpoint Schedule Name is specified. May be left blank if not serving any water cooled chillers |
condenser_Condenser Water Pump Rated Head |
number Pa |
179352.0 |
May be left blank if not serving any water cooled chillers default head is 60 feet H2O Range: ≥ 0 |
chilled_Chilled Water Setpoint Reset Type |
choice | None |
Overrides Chilled Water Setpoint Schedule Name One of None, OutdoorAirTemperatureReset |
chilled_Chilled Water Setpoint at Outdoor Dry-Bulb Low |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
chilled_Chilled Water Reset Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. |
chilled_Chilled Water Setpoint at Outdoor Dry-Bulb High |
number C |
6.7 |
Applicable only for OutdoorAirTemperatureReset control. |
chilled_Chilled Water Reset Outdoor Dry-Bulb High |
number C |
26.7 |
Applicable only for OutdoorAirTemperatureReset control. |
chilled_Chilled Water Primary Pump Type |
choice | SinglePump |
Describes the type of pump configuration used for the primary portion of the chilled water loop. One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerChiller, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps |
chilled_Chilled Water Secondary Pump Type |
choice | SinglePump |
Describes the type of pump configuration used for the secondary portion of the chilled water loop. One of FiveHeaderedPumps, FourHeaderedPumps, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps |
condenser_Condenser Water Pump Type |
choice | SinglePump |
Describes the type of pump configuration used for the condenser water loop. One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerTower, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps |
chilled_Chilled Water Supply Side Bypass Pipe |
choice | Yes |
Determines if a supply side bypass pipe is present in the chilled water loop. One of No, Yes |
chilled_Chilled Water Demand Side Bypass Pipe |
choice | Yes |
Determines if a demand side bypass pipe is present in the chilled water loop. One of No, Yes |
condenser_Condenser Water Supply Side Bypass Pipe |
choice | Yes |
Determines if a supply side bypass pipe is present in the condenser water loop. One of No, Yes |
condenser_Condenser Water Demand Side Bypass Pipe |
choice | Yes |
Determines if a demand side bypass pipe is present in the condenser water loop. One of No, Yes |
fluid_Fluid Type |
choice | Water |
One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water |
loop_Loop Design Delta Temperature |
number deltaC |
6.67 |
The temperature difference used in sizing the loop flow rate. |
minimum_Minimum Outdoor Dry Bulb Temperature |
number C |
The minimum outdoor dry-bulb temperature that the chilled water loops operate. Leave blank for no limit. | |
chilled_Chilled Water Load Distribution Scheme |
choice | SequentialLoad |
One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR |
condenser_Condenser Water Load Distribution Scheme |
choice | SequentialLoad |
One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR |
HVACTemplate:Plant:Chiller¶
from idfpy.models import HVACTemplatePlantChiller
This object adds a chiller to an HVACTemplate:Plant:ChilledWaterLoop.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
chiller_Chiller Type required |
choice | One of DistrictChilledWater, ElectricCentrifugalChiller, ElectricReciprocatingChiller, ElectricScrewChiller |
|
capacityCapacity |
number or AutosizeW |
Autosize |
|
nominal_Nominal COP required |
number W/W |
Not applicable if Chiller Type is DistrictChilledWater Electric Reciprocating Chiller Range: > 0 |
|
condenser_Condenser Type |
choice | WaterCooled |
Not applicable if Chiller Type is DistrictChilledWater One of AirCooled, EvaporativelyCooled, WaterCooled |
priorityPriority |
string | If Chiller Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc. | |
sizing_Sizing Factor |
number | 1.0 |
Multiplies the autosized capacity and flow rates Range: > 0 |
minimum_Minimum Part Load Ratio |
number | 0.0 |
Part load ratio below which the chiller starts cycling on/off to meet the load. Must be less than or equal to Maximum Part Load Ratio. Range: ≥ 0 |
maximum_Maximum Part Load Ratio |
number | 1.0 |
Maximum allowable part load ratio. Must be greater than or equal to Minimum Part Load Ratio. Range: > 0 |
optimum_Optimum Part Load Ratio |
number | 1.0 |
Optimum part load ratio where the chiller is most efficient. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio. Range: > 0 |
minimum_Minimum Unloading Ratio |
number | 0.25 |
Part load ratio where the chiller can no longer unload and false loading begins. Minimum unloading ratio must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio. Range: ≥ 0 |
leaving_Leaving Chilled Water Lower Temperature Limit |
number C |
5.0 |
HVACTemplate:Plant:Chiller:ObjectReference¶
from idfpy.models import HVACTemplatePlantChillerObjectReference
This object references a detailed chiller object and adds it to an HVACTemplate:Plant:ChilledWaterLoop. The user must create a complete detailed chiller object with all required curve or performance objects.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | The name of this object. | |
chiller_Chiller Object Type |
choice | Chiller:Electric:EIR |
One of Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR |
chiller_Chiller Name required |
reference | The name of the detailed chiller object. Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
priorityPriority |
number | If Chiller Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc. |
HVACTemplate:Plant:HotWaterLoop¶
from idfpy.models import HVACTemplatePlantHotWaterLoop unique
Plant loop to serve all HVACTemplate hot water coils and boilers.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
pump_Pump Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
pump_Pump Control Type |
choice | Intermittent |
One of Continuous, Intermittent |
hot_Hot Water Plant Operation Scheme Type |
choice | Default |
Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Boiler objects. One of Default, UserDefined |
hot_Hot Water Plant Equipment Operation Schemes Name |
reference | Name of a PlantEquipmentOperationSchemes object Ignored if Plant Operation Scheme Type = Default Names a PlantEquipmentOperationSchemes |
|
hot_Hot Water Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
hot_Hot Water Design Setpoint |
number C |
82.0 |
Used for sizing and as constant setpoint if no Setpoint Schedule Name is specified. |
hot_Hot Water Pump Configuration |
choice | ConstantFlow |
VariableFlow - variable flow to boilers and coils, excess bypassed ConstantFlow - constant flow to boilers and coils, excess bypassed One of ConstantFlow, VariableFlow |
hot_Hot Water Pump Rated Head |
number Pa |
179352.0 |
Default head is 60 feet H2O Range: ≥ 0 |
hot_Hot Water Setpoint Reset Type |
choice | None |
Overrides Hot Water Setpoint Schedule Name One of None, OutdoorAirTemperatureReset |
hot_Hot Water Setpoint at Outdoor Dry-Bulb Low |
number C |
82.2 |
Applicable only for OutdoorAirTemperatureReset control. |
hot_Hot Water Reset Outdoor Dry-Bulb Low |
number C |
-6.7 |
Applicable only for OutdoorAirTemperatureReset control. |
hot_Hot Water Setpoint at Outdoor Dry-Bulb High |
number C |
65.6 |
Applicable only for OutdoorAirTemperatureReset control. |
hot_Hot Water Reset Outdoor Dry-Bulb High |
number C |
10.0 |
Applicable only for OutdoorAirTemperatureReset control. |
hot_Hot Water Pump Type |
choice | SinglePump |
Describes the type of pump configuration used for the hot water loop. One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerBoiler, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps |
supply_Supply Side Bypass Pipe |
choice | Yes |
Determines if a supply side bypass pipe is present in the hot water loop. One of No, Yes |
demand_Demand Side Bypass Pipe |
choice | Yes |
Determines if a demand side bypass pipe is present in the hot water loop. One of No, Yes |
fluid_Fluid Type |
choice | Water |
One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water |
loop_Loop Design Delta Temperature |
number deltaC |
11.0 |
The temperature difference used in sizing the loop flow rate. |
maximum_Maximum Outdoor Dry Bulb Temperature |
number C |
The maximum outdoor dry-bulb temperature that the hot water loops operate. Leave blank for no limit. | |
load_Load Distribution Scheme |
choice | SequentialLoad |
One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR |
HVACTemplate:Plant:MixedWaterLoop¶
from idfpy.models import HVACTemplatePlantMixedWaterLoop unique
Central plant loop portion of a water source heat pump system.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
pump_Pump Schedule Name |
reference | If blank, always available Applies to both chilled water and condenser loop pumps Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
pump_Pump Control Type |
choice | Intermittent |
Applies to both chilled water and condenser loop pumps One of Continuous, Intermittent |
operation_Operation Scheme Type |
choice | Default |
Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Boiler and HVACTemplate:Plant:Tower objects. One of Default, UserDefined |
equipment_Equipment Operation Schemes Name |
reference | Name of a PlantEquipmentOperationSchemes object Ignored if Plant Operation Scheme Type = Default Names a PlantEquipmentOperationSchemes |
|
high_High Temperature Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
high_High Temperature Design Setpoint |
number C |
33.0 |
Used for sizing and as constant setpoint if no Setpoint Schedule Name is specified. |
low_Low Temperature Setpoint Schedule Name |
reference | Leave blank if constant setpoint May be left blank if not serving any water cooled chillers Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
low_Low Temperature Design Setpoint |
number C |
20.0 |
Used for sizing and as constant setpoint if no Condenser Water Setpoint Schedule Name is specified. May be left blank if not serving any water cooled chillers |
water_Water Pump Configuration |
choice | ConstantFlow |
VariableFlow - variable flow to boilers and coils, excess bypassed ConstantFlow - constant flow to boilers and coils, excess bypassed One of ConstantFlow, VariableFlow |
water_Water Pump Rated Head |
number Pa |
179352.0 |
May be left blank if not serving any water cooled chillers default head is 60 feet H2O Range: ≥ 0 |
water_Water Pump Type |
choice | SinglePump |
Describes the type of pump configuration used for the mixed water loop. One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerTowerOrBoiler, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps |
supply_Supply Side Bypass Pipe |
choice | Yes |
Determines if a supply side bypass pipe is present in the hot water loop. One of No, Yes |
demand_Demand Side Bypass Pipe |
choice | Yes |
Determines if a demand side bypass pipe is present in the hot water loop. One of No, Yes |
fluid_Fluid Type |
choice | Water |
One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water |
loop_Loop Design Delta Temperature |
number deltaC |
5.6 |
The temperature difference used in sizing the loop flow rate. |
load_Load Distribution Scheme |
choice | SequentialLoad |
One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR |
HVACTemplate:Plant:Tower¶
from idfpy.models import HVACTemplatePlantTower
This object adds a cooling tower to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
tower_Tower Type required |
choice | One of SingleSpeed, TwoSpeed |
|
high_High Speed Nominal Capacity |
number or AutosizeW |
Autosize |
Applicable for tower type SingleSpeed and TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at high speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt(3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions. |
high_High Speed Fan Power |
number or AutosizeW |
Autosize |
Applicable for tower type SingleSpeed and TwoSpeed |
low_Low Speed Nominal Capacity |
number or AutosizeW |
Autosize |
Applicable only for Tower Type TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at low speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions. |
low_Low Speed Fan Power |
number or AutosizeW |
Autosize |
Applicable only for Tower Type TwoSpeed |
free_Free Convection Capacity |
number or AutosizeW |
Autosize |
Applicable for Tower Type SingleSpeed and TwoSpeed Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Tower free convection capacity times (1.25) gives the actual tower heat rejection at these operating conditions. |
priorityPriority |
string | Applicable for all Tower Types If Condenser Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc. | |
sizing_Sizing Factor |
number | 1.0 |
Multiplies the autosized capacity and flow rates Range: > 0 |
template_Template Plant Loop Type |
choice | Specifies if this tower serves a template chilled water loop or mixed water loop If left blank, will serve a chilled water loop if present, or a mixed water loop (if no chilled water loop is present). One of ChilledWater, MixedWater |
HVACTemplate:Plant:Tower:ObjectReference¶
from idfpy.models import HVACTemplatePlantTowerObjectReference
This object references a detailed cooling tower object and adds it to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop. The user must create a complete detailed cooling tower object with all required curve or performance objects.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | The name of this object. | |
cooling_Cooling Tower Object Type |
choice | CoolingTower:SingleSpeed |
One of CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed |
cooling_Cooling Tower Name required |
reference | The name of the detailed cooling tower object. Names a CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed, CoolingTower:VariableSpeed:Merkel |
|
priorityPriority |
number | If Condenser Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc. | |
template_Template Plant Loop Type |
choice | Specifies if this tower serves a template chilled water loop or mixed water loop If left blank, will serve a chilled water loop if present, or a mixed water loop (if no chilled water loop is present). One of ChilledWater, MixedWater |
HVACTemplate:System:ConstantVolume¶
from idfpy.models import HVACTemplateSystemConstantVolume
Constant Air Volume air loop with optional chilled water cooling coil, optional heating coil and optional preheat.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
600.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
cooling_Cooling Coil Type |
choice | ChilledWater |
One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, None |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint Control Type |
choice | FixedSetpoint |
One of ControlZone, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled, Warmest |
cooling_Cooling Coil Control Zone name |
reference | name of the HVACTemplate:ZoneConstantVolume object that contains the cooling thermostat when Cooling Coil Setpoint Control Type = ControlZone Names a HVACTemplate:Zone:ConstantVolume |
|
cooling_Cooling Coil Design Setpoint Temperature |
number C |
12.8 |
Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified. |
cooling_Cooling Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F) |
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb High |
number C |
12.8 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb High |
number C |
23.3 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Type |
choice | HotWater |
One of Electric, Gas, HotWater, None |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint Control Type |
choice | FixedSetpoint |
One of ControlZone, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled |
heating_Heating Coil Control Zone name |
reference | name of the HVACTemplate:ZoneConstantVolume object that contains the heating thermostat Names a HVACTemplate:Zone:ConstantVolume |
|
heating_Heating Coil Design Setpoint |
number C |
10.0 |
Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified. |
heating_Heating Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
15.0 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Reset Outdoor Dry-Bulb Low |
number C |
7.8 |
Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F) |
heating_Heating Coil Setpoint at Outdoor Dry-Bulb High |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Reset Outdoor Dry-Bulb High |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
preheat_Preheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
preheat_Preheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
preheat_Preheat Coil Design Setpoint |
number C |
7.2 |
Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified. |
preheat_Preheat Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
gas_Gas Preheat Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Preheat Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Upper Temperature Limit |
number C |
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Lower Temperature Limit |
number C |
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Upper Enthalpy Limit |
number J/kg |
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Range: ≥ 0, ≤ 1 |
heat_Heat Recovery Heat Exchanger Type |
choice | Plate |
One of Plate, Rotary |
heat_Heat Recovery Frost Control Type |
choice | None |
One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint. One of CoolReheat, None |
dehumidification_Dehumidification Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
dehumidification_Dehumidification Relative Humidity Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
dehumidification_Dehumidification Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Relative Humidity Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
300.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:ConstantVolume
HVACTemplate:System:DedicatedOutdoorAir¶
from idfpy.models import HVACTemplateSystemDedicatedOutdoorAir
This object creates a dedicated outdoor air system that must be used with HVACTemplate:Zone:* objects for BaseboardHeat FanCoil PTAC PTHP WaterToAirHeatPump and VRF. Does not support HVACTemplate:Zone:VAV or other central multizone systems
| Field | Type | Default | Details |
|---|---|---|---|
nameName |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; DOAS System always on. Schedule is used in availability manager and fan scheduling. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
air_Air Outlet Type |
choice | DirectIntoZone |
One of DirectIntoZone |
supply_Supply Fan Flow Rate |
number or Autosizem3/s |
Autosize |
|
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
cooling_Cooling Coil Type |
choice | ChilledWater |
One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, HeatExchangerAssistedDX, None, TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint Control Type |
choice | FixedSetpoint |
One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled |
cooling_Cooling Coil Design Setpoint |
number C |
12.8 |
Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified. |
cooling_Cooling Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F) |
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb High |
number C |
12.8 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb High |
number C |
23.3 |
Applicable only for OutdoorAirTemperatureReset control. |
dx_DX Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat |
dx_DX Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Gross SHR |
dx_DX Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input Range: > 0 |
heating_Heating Coil Type |
choice | HotWater |
One of Electric, Gas, HotWater, None |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint Control Type |
choice | FixedSetpoint |
When selecting OutdoorAirTemperatureReset, the Heating Coil Design Setpoint may need to be changed One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled |
heating_Heating Coil Design Setpoint |
number C |
12.2 |
Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified. |
heating_Heating Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
15.0 |
Applicable only for OutdoorAirTemperatureReset control. Defaults 15.0C (59F) at 7.8C (46F) to 12.2C (54F) at 12.2C (54F) |
heating_Heating Coil Reset Outdoor Dry-Bulb Low |
number C |
7.8 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Setpoint at Outdoor Dry-Bulb High |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Reset Outdoor Dry-Bulb High |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
heat_Heat Recovery Sensible Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
heat_Heat Recovery Latent Effectiveness |
number | 0.65 |
Range: ≥ 0, ≤ 1 |
heat_Heat Recovery Heat Exchanger Type |
choice | Plate |
One of Plate, Rotary |
heat_Heat Recovery Frost Control Type |
choice | None |
One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheatHeatingCoil = cool beyond the dry-bulb setpoint, reheat with heating coil Valid for all cooling coil types. If no heating coil specified, cold supply temps may occur. CoolReheatDesuperheater = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with desuperheater coil. Valid only for Cooling Coil Type = TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX, or HeatExchangerAssistedDX. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only for Cooling Coil Type = TwoStageHumidityControlDX or HeatExchangerAssistedDX One of CoolReheatDesuperheater, CoolReheatHeatingCoil, Multimode, None |
dehumidification_Dehumidification Setpoint |
number kgWater/kgDryAir |
0.00924 |
The supply air humidity ratio for dehumidification control. Default of 0.00924 kgWater/kgDryAir is equivalent to 12.8C (55F) dewpoint. Ignored if Dehumidification Setpoint Schedule specified below Range: ≥ 0, ≤ 1 |
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Constant Setpoint |
number kgWater/kgDryAir |
0.003 |
The supply air humidity ratio for humidification control. Ignored if Humidifier Setpoint Schedule specified below Range: ≥ 0, ≤ 1 |
dehumidification_Dehumidification Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Dehumidification Setpoint above. Schedule values must be in units of humidity ratio (kgWater/kgDryAir or lbWater/lbDryAir) Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Humidifier Constant Setpoint above. Schedule values must be in units of humidity ratio (kgWater/kgDryAir or lbWater/lbDryAir) Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
Referenced by 7 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump
HVACTemplate:System:DualDuct¶
from idfpy.models import HVACTemplateSystemDualDuct
Dual-duct constant volume or variable volume air loop
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
system_System Configuration Type |
choice | SingleFanConstantVolume |
SingleFan - a single supply fan before the split to dual ducts DualFan - two supply fans, one each for the cold and hot ducts ConstantVolume - constant volume VariableVolume - variable volume One of DualFanConstantVolume, DualFanVariableVolume, SingleFanConstantVolume, SingleFanVariableVolume |
main_Main Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
main_Main Supply Fan Minimum Flow Fraction |
number | 0.2 |
Range: ≥ 0, ≤ 1 |
main_Main Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
main_Main Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
main_Main Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
main_Main Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
main_Main Supply Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
cold_Cold Duct Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
cold_Cold Duct Supply Fan Minimum Flow Fraction |
number | 0.2 |
Range: ≥ 0, ≤ 1 |
cold_Cold Duct Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
cold_Cold Duct Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
cold_Cold Duct Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
cold_Cold Duct Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cold_Cold Duct Supply Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
cold_Cold Duct Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
hot_Hot Duct Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
hot_Hot Duct Supply Fan Minimum Flow Fraction |
number | 0.2 |
Range: ≥ 0, ≤ 1 |
hot_Hot Duct Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
hot_Hot Duct Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
hot_Hot Duct Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
hot_Hot Duct Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
hot_Hot Duct Supply Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
hot_Hot Duct Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
cooling_Cooling Coil Type |
choice | ChilledWater |
One of ChilledWater, ChilledWaterDetailedFlatModel, None |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint Control Type |
choice | FixedSetpoint |
One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled, Warmest |
cooling_Cooling Coil Design Setpoint Temperature |
number C |
12.8 |
Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified. |
cooling_Cooling Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb Low |
number C |
15.6 |
Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F) |
cooling_Cooling Coil Setpoint at Outdoor Dry-Bulb High |
number C |
12.8 |
Applicable only for OutdoorAirTemperatureReset control. |
cooling_Cooling Coil Reset Outdoor Dry-Bulb High |
number C |
23.3 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Type |
choice | HotWater |
One of Electric, Gas, HotWater, None |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint Control Type |
choice | FixedSetpoint |
One of Coldest, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled |
heating_Heating Coil Design Setpoint |
number C |
50.0 |
Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified. |
heating_Heating Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint at Outdoor Dry-Bulb Low |
number C |
50.0 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Reset Outdoor Dry-Bulb Low |
number C |
7.8 |
Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F) |
heating_Heating Coil Setpoint at Outdoor Dry-Bulb High |
number C |
20.0 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Reset Outdoor Dry-Bulb High |
number C |
12.2 |
Applicable only for OutdoorAirTemperatureReset control. |
heating_Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
preheat_Preheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
preheat_Preheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
preheat_Preheat Coil Design Setpoint |
number C |
7.2 |
Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified. |
preheat_Preheat Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
gas_Gas Preheat Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Preheat Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Control Type |
choice | ProportionalMinimum |
One of FixedMinimum, ProportionalMinimum |
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of NoLockout |
economizer_Economizer Upper Temperature Limit |
number C |
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Lower Temperature Limit |
number C |
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Upper Enthalpy Limit |
number J/kg |
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
cold_Cold Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves the cold inlets of all zones on this system. Blank if none. Names a Zone |
|
hot_Hot Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves the hot inlets of all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Range: ≥ 0, ≤ 1 |
heat_Heat Recovery Heat Exchanger Type |
choice | Plate |
One of Plate, Rotary |
heat_Heat Recovery Frost Control Type |
choice | None |
One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint. One of CoolReheat, None |
dehumidification_Dehumidification Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
dehumidification_Dehumidification Relative Humidity Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
dehumidification_Dehumidification Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Relative Humidity Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
sizing_Sizing Option |
choice | NonCoincident |
Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates. One of Coincident, NonCoincident |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
500.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
return_Return Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:DualDuct
HVACTemplate:System:PackagedVAV¶
from idfpy.models import HVACTemplateSystemPackagedVAV
Packaged Variable Air Volume (PVAV) air loop with optional heating coil and optional preheat.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; PVAV System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Minimum Flow Rate |
number or Autosizem3/s |
Autosize |
This field is only used to set a minimum part load on the VAV fan power curve. Autosize or zero is recommended. |
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | TwoSpeedDX |
One of TwoSpeedDX, TwoSpeedHumidControlDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Design Setpoint |
number C |
12.8 |
Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified. |
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Gross SHR |
cooling_Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input Range: > 0 |
heating_Heating Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Design Setpoint |
number C |
10.0 |
Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified. |
heating_Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Control Type |
choice | ProportionalMinimum |
One of FixedMinimum, ProportionalMinimum |
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of LockoutWithCompressor, LockoutWithHeating, NoLockout |
economizer_Economizer Maximum Limit Dry-Bulb Temperature |
number C |
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Enthalpy |
number J/kg |
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Minimum Limit Dry-Bulb Temperature |
number C |
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
supply_Supply Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Setpoint Reset Type |
choice | None |
Overrides Cooling Coil Setpoint Schedule Name None = no reset, control to Cooling Coil Design Setpoint Temperature or Schedule Warmest = reset as warm as possible yet meet all zone cooling loads at max supply air flow rate OutdoorAirTemperatureReset = reset based on outdoor air temperature (18.0C at 15.6C ODB, to the Cooling Design Setpoint at 26.7C) WarmestTemperatureFirst = reset as warm as possible yet meet all zone cooling loads at min supply air flow rate One of None, OutdoorAirTemperatureReset, Warmest, WarmestTemperatureFirst |
heating_Heating Coil Setpoint Reset Type |
choice | None |
Overrides Heating Coil Setpoint Schedule Name None = no reset, control to Heating Coil Design Setpoint Temperature or Schedule OutdoorAirTemperatureReset = reset based on outdoor air temperature (Heating Design Setpoint at -6.7C ODB to Heating Design Setpoint minus 5.2C at 10C ODB) min supply air flow rate One of None, OutdoorAirTemperatureReset |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint. One of CoolReheat, None |
dehumidification_Dehumidification Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
dehumidification_Dehumidification Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
sizing_Sizing Option |
choice | NonCoincident |
Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates. One of Coincident, NonCoincident |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
500.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
return_Return Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
Referenced by 4 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool
HVACTemplate:System:Unitary¶
from idfpy.models import HVACTemplateSystemUnitary
Unitary furnace with air conditioner
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; Unitary System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
control_Control Zone or Thermostat Location Name required |
reference | Names a Zone | |
supply_Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
600.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | SingleSpeedDX |
One of None, SingleSpeedDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Design Supply Air Temperature |
number C |
12.8 |
Used for sizing. |
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Gross SHR |
cooling_Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electric power Range: > 0 |
heating_Heating Coil Type required |
choice | One of Electric, Gas, HotWater |
|
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Design Supply Air Temperature |
number C |
50.0 |
Used for sizing. |
heating_Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the minimum outdoor air flow rate If blank, always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of LockoutWithCompressor, LockoutWithHeating, NoLockout |
economizer_Economizer Upper Temperature Limit |
number C |
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Lower Temperature Limit |
number C |
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Upper Enthalpy Limit |
number J/kg |
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum serves all zones on this system. Blank if none. Names a Zone |
|
supply_Supply Fan Placement |
choice | BlowThrough |
One of BlowThrough, DrawThrough |
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Applicable only if Heat Recovery Type is Enthalpy. Range: ≥ 0, ≤ 1 |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible cooling load only CoolReheatHeatingCoil = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with main heating coil. CoolReheatDesuperheater = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with desuperheater coil. One of CoolReheatDesuperheater, CoolReheatHeatingCoil, None |
dehumidification_Dehumidification Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
500.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary
HVACTemplate:System:UnitaryHeatPump:AirToAir¶
from idfpy.models import HVACTemplateSystemUnitaryHeatPumpAirToAir
Unitary furnace with electric air-to-air heat pump
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; Unitary System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
control_Control Zone or Thermostat Location Name required |
reference | Names a Zone | |
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
no_No Load Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is Continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Placement |
choice | BlowThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
600.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | SingleSpeedDX |
One of SingleSpeedDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Design Supply Air Temperature |
number C |
12.8 |
Used for sizing. |
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
cooling_Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input Range: > 0 |
heat_Heat Pump Heating Coil Type |
choice | SingleSpeedDXHeatPump |
One of SingleSpeedDXHeatPump |
heat_Heat Pump Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Design Supply Air Temperature |
number C |
50.0 |
Used for sizing. |
heat_Heat Pump Heating Coil Gross Rated Capacity |
number or AutosizeW |
Autosize |
Rated heating capacity excluding the effect of supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C |
heat_Heat Pump Heating Coil Rated COP |
number W/W |
2.75 |
Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy. Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C Range: > 0 |
heat_Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature |
number C |
-8.0 |
Range: ≥ -20 |
heat_Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature |
number C |
5.0 |
Range: ≥ 0, ≤ 7.22 |
heat_Heat Pump Defrost Strategy |
choice | ReverseCycle |
One of Resistive, ReverseCycle |
heat_Heat Pump Defrost Control |
choice | Timed |
One of OnDemand, Timed |
heat_Heat Pump Defrost Time Period Fraction |
number | 0.058333 |
Fraction of time in defrost mode only applicable if Timed defrost control is specified Range: ≥ 0 |
supplemental_Supplemental Heating Coil Type |
choice | Electric |
One of Electric, Gas, HotWater |
supplemental_Supplemental Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supplemental_Supplemental Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
supplemental_Supplemental Heating Coil Maximum Outdoor Dry-Bulb Temperature |
number C |
21.0 |
Supplemental heater will not operate when outdoor temperature exceeds this value. Range: ≤ 21 |
supplemental_Supplemental Gas Heating Coil Efficiency |
number | 0.8 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0, ≤ 1 |
supplemental_Supplemental Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the minimum outdoor air flow rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of LockoutWithCompressor, LockoutWithHeating, NoLockout |
economizer_Economizer Maximum Limit Dry-Bulb Temperature |
number C |
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Enthalpy |
number J/kg |
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Minimum Limit Dry-Bulb Temperature |
number C |
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum serves all zones on this system. Blank if none. Names a Zone |
|
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Applicable only if Heat Recovery Type is Enthalpy. Range: ≥ 0, ≤ 1 |
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
500.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary
HVACTemplate:System:UnitarySystem¶
from idfpy.models import HVACTemplateSystemUnitarySystem
Unitary HVAC system with optional cooling and heating. Supports DX and chilled water, cooling, gas, electric, and hot water heating, air-to-air and water-to-air heat pumps.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always available. Also see Supply Fan Operating Mode Schedule Name field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
control_Control Type |
choice | Load |
Load control requires a Controlling Zone name. SetPoint control requires set points at coil outlet nodes. The user must add appropriate SetpointManager objects to the idf file. One of Load, SetPoint |
control_Control Zone or Thermostat Location Name |
reference | This field is required if Control Type is Load. Names a Zone |
|
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
no_No Load Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is Continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Placement |
choice | BlowThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
600.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | SingleSpeedDX |
One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, HeatExchangerAssistedDX, MultiSpeedDX, None, SingleSpeedDX, SingleSpeedDXWaterCooled, TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX |
number_Number of Speeds for Cooling |
integer | 1 |
Used only for Cooling Coil Type = MultiSpeedDX. Range: ≥ 0, ≤ 4 |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Design Supply Air Temperature |
number C |
12.8 |
Used for sizing. |
dx_DX Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb |
dx_DX Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
dx_DX Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input Range: > 0 |
heating_Heating Coil Type |
choice | Gas |
One of Electric, Gas, HotWater, MultiSpeedDXHeatPumpAirSource, MultiStageElectric, MultiStageGas, None, SingleSpeedDXHeatPumpAirSource, SingleSpeedDXHeatPumpWaterSource |
number_Number of Speeds or Stages for Heating |
integer | 1 |
Used only for Heating Coil Type = MultiSpeedDXHeatPumpAirSource), MultiStageElectric, or MultiStageGas. Range: ≥ 0, ≤ 4 |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Design Supply Air Temperature |
number C |
50.0 |
Used for sizing. |
heating_Heating Coil Gross Rated Capacity |
number or AutosizeW |
Autosize |
Rated heating capacity excluding the effect of supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C |
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
heat_Heat Pump Heating Coil Gross Rated COP |
number W/W |
2.75 |
Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy. Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C Applies only to DX coils Range: > 0 |
heat_Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature |
number C |
-8.0 |
Range: ≥ -20 |
heat_Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature |
number C |
5.0 |
Range: ≥ 0, ≤ 7.22 |
heat_Heat Pump Defrost Strategy |
choice | ReverseCycle |
One of Resistive, ReverseCycle |
heat_Heat Pump Defrost Control |
choice | Timed |
One of OnDemand, Timed |
heat_Heat Pump Defrost Time Period Fraction |
number | 0.058333 |
Fraction of time in defrost mode only applicable if Timed defrost control is specified Range: ≥ 0 |
supplemental_Supplemental Heating or Reheat Coil Type |
choice | None |
One of DesuperHeater, Electric, Gas, HotWater, None |
supplemental_Supplemental Heating or Reheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supplemental_Supplemental Heating or Reheat Coil Capacity |
number or AutosizeW |
Autosize |
|
supplemental_Supplemental Heating or Reheat Coil Maximum Outdoor Dry-Bulb Temperature |
number C |
21.0 |
Supplemental heater will not operate when outdoor temperature exceeds this value. Range: ≤ 21 |
supplemental_Supplemental Gas Heating or Reheat Coil Efficiency |
number | 0.8 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0, ≤ 1 |
supplemental_Supplemental Gas Heating or Reheat Coil Parasitic Electric Load |
number W |
0.0 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the minimum outdoor air flow rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of LockoutWithCompressor, LockoutWithHeating, NoLockout |
economizer_Economizer Maximum Limit Dry-Bulb Temperature |
number C |
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Enthalpy |
number J/kg |
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
economizer_Economizer Minimum Limit Dry-Bulb Temperature |
number C |
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum serves all zones on this system. Blank if none. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Applicable only if Heat Recovery Type is Enthalpy. Range: ≥ 0, ≤ 1 |
heat_Heat Recovery Heat Exchanger Type |
choice | Plate |
One of Plate, Rotary |
heat_Heat Recovery Frost Control Type |
choice | None |
One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint, reheat with reheat coil If no reheat coil specified, cold supply temps may occur. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only for Cooling Coil Type = TwoStageHumidityControlDX or HeatExchangerAssistedDX One of CoolReheat, Multimode, None |
dehumidification_Dehumidification Relative Humidity Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
dehumidification_Dehumidification Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Relative Humidity Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Relative Humidity Setpoint Schedule Name |
reference | Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100). Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
sizing_Sizing Option |
choice | NonCoincident |
Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates. One of Coincident, NonCoincident |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
300.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary
HVACTemplate:System:VAV¶
from idfpy.models import HVACTemplateSystemVAV
Variable Air Volume (VAV) air loop with optional heating coil and optional preheat.
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | If blank, always on; VAV System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones. |
supply_Supply Fan Minimum Flow Rate |
number or Autosizem3/s |
Autosize |
This field is only used to set a minimum part load on the VAV fan power curve. Autosize or zero is recommended. |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | ChilledWater |
One of ChilledWater, ChilledWaterDetailedFlatModel |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Design Setpoint |
number C |
12.8 |
Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified. |
heating_Heating Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Design Setpoint |
number C |
10.0 |
Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified. |
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
preheat_Preheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
preheat_Preheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
preheat_Preheat Coil Setpoint Schedule Name |
reference | Leave blank if constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
preheat_Preheat Coil Design Setpoint |
number C |
7.2 |
Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified. |
gas_Gas Preheat Coil Efficiency |
number | 0.8 |
Range: ≥ 0, ≤ 1 |
gas_Gas Preheat Coil Parasitic Electric Load |
number W |
0.0 |
Range: ≥ 0 |
maximum_Maximum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
|
minimum_Minimum Outdoor Air Control Type |
choice | ProportionalMinimum |
One of FixedMinimum, ProportionalMinimum |
minimum_Minimum Outdoor Air Schedule Name |
reference | Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
economizer_Economizer Type |
choice | NoEconomizer |
One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer |
economizer_Economizer Lockout |
choice | NoLockout |
One of NoLockout |
economizer_Economizer Upper Temperature Limit |
number C |
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Lower Temperature Limit |
number C |
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Upper Enthalpy Limit |
number J/kg |
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit. | |
economizer_Economizer Maximum Limit Dewpoint Temperature |
number C |
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type. | |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Supply plenum serves all zones on this system. Blank if none. Names a Zone |
|
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
night_Night Cycle Control |
choice | StayOff |
One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff |
night_Night Cycle Control Zone Name |
reference | Applicable only if Night Cycle Control is Cycle On Control Zone. Names a Zone |
|
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number | 0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number | 0.65 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Setpoint Reset Type |
choice | None |
Overrides Cooling Coil Setpoint Schedule Name None = no reset, control to Cooling Coil Design Setpoint Temperature or Schedule Warmest = reset as warm as possible yet meet all zone cooling loads at max supply air flow rate OutdoorAirTemperatureReset = reset based on outdoor air temperature (18.0C at 15.6C ODB, to the Cooling Design Setpoint at 26.7C) WarmestTemperatureFirst = reset as warm as possible yet meet all zone cooling loads at min supply air flow rate One of None, OutdoorAirTemperatureReset, Warmest, WarmestTemperatureFirst |
heating_Heating Coil Setpoint Reset Type |
choice | None |
Overrides Heating Coil Setpoint Schedule Name None = no reset, control to Heating Coil Design Setpoint Temperature or Schedule OutdoorAirTemperatureReset = reset based on outdoor air temperature (Heating Design Setpoint at -6.7C ODB to Heating Design Setpoint minus 5.2C at 10C ODB) min supply air flow rate One of None, OutdoorAirTemperatureReset |
dehumidification_Dehumidification Control Type |
choice | None |
None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint. One of CoolReheat, None |
dehumidification_Dehumidification Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
dehumidification_Dehumidification Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
humidifier_Humidifier Type |
choice | None |
One of ElectricSteam, None |
humidifier_Humidifier Availability Schedule Name |
reference | If blank, always available Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
humidifier_Humidifier Rated Capacity |
number m3/s |
1e-06 |
Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity. Range: ≥ 0 |
humidifier_Humidifier Rated Electric Power |
number or AutosizeW |
Autosize |
Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty. |
humidifier_Humidifier Control Zone Name |
reference | Zone name where humidistat is located Names a Zone |
|
humidifier_Humidifier Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
sizing_Sizing Option |
choice | NonCoincident |
Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates. One of Coincident, NonCoincident |
return_Return Fan |
choice | No |
Specifies if the system has a return fan. One of No, Yes |
return_Return Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
return_Return Fan Delta Pressure |
number Pa |
500.0 |
Range: ≥ 0 |
return_Return Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
return_Return Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
return_Return Fan Part-Load Power Coefficients |
choice | InletVaneDampers |
This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table. One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset |
Referenced by 4 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool
HVACTemplate:System:VRF¶
from idfpy.models import HVACTemplateSystemVRF
Variable refrigerant flow (VRF) heat pump condensing unit. Serves one or more VRF zone terminal units (HVACTemplate:Zone:VRF).
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
system_System Availability Schedule Name |
reference | Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
gross_Gross Rated Total Cooling Capacity |
number or AutosizeW |
Autosize |
Enter the total cooling capacity in watts at rated conditions or set to autosize. Total cooling capacity not accounting for the effect of supply air fan heat |
gross_Gross Rated Cooling COP |
number W/W |
3.3 |
Enter the coefficient of performance at rated conditions or leave blank to use default. COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electric power input Range: > 0 |
minimum_Minimum Outdoor Temperature in Cooling Mode |
number C |
-6.0 |
Enter the minimum outdoor temperature allowed for cooling operation. Cooling is disabled below this temperature. |
maximum_Maximum Outdoor Temperature in Cooling Mode |
number C |
43.0 |
Enter the maximum outdoor temperature allowed for cooling operation. Cooling is disabled above this temperature. |
gross_Gross Rated Heating Capacity |
number or AutosizeW |
Autosize |
Enter the heating capacity in watts at rated conditions or set to autosize. Heating capacity not accounting for the effect of supply air fan heat |
rated_Rated Heating Capacity Sizing Ratio |
number W/W |
1.0 |
If the Gross Rated Heating Capacity is autosized, the heating capacity is sized to be equal to the cooling capacity multiplied by this sizing ratio. The zone terminal unit heating coils are also sized using this ratio unless the sizing ratio input in the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object is entered. Range: ≥ 1 |
gross_Gross Rated Heating COP |
number W/W |
3.4 |
COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electrical energy input Range: > 0 |
minimum_Minimum Outdoor Temperature in Heating Mode |
number C |
-20.0 |
Enter the minimum outdoor temperature allowed for heating operation. |
maximum_Maximum Outdoor Temperature in Heating Mode |
number C |
16.0 |
Enter the maximum outdoor temperature allowed for heating operation. |
minimum_Minimum Heat Pump Part-Load Ratio |
number dimensionless |
0.15 |
Enter the minimum heat pump part-load ratio (PLR). When the cooling or heating PLR is below this value, the heat pump compressor will cycle to meet the cooling or heating demand. |
zone_Zone Name for Master Thermostat Location |
reference | Enter the name of the zone where the master thermostat is located. Names a Zone |
|
master_Master Thermostat Priority Control Type |
choice | MasterThermostatPriority |
Choose a thermostat control logic scheme. If these control types fail to control zone temperature within a reasonable limit, consider using multiple VRF systems One of LoadPriority, MasterThermostatPriority, Scheduled, ThermostatOffsetPriority, ZonePriority |
thermostat_Thermostat Priority Schedule Name |
reference | this field is required if Master Thermostat Priority Control Type is Scheduled. Schedule values of 0 denote cooling, 1 for heating, and all other values disable the system. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heat_Heat Pump Waste Heat Recovery |
choice | No |
This field is reserved for future use. The only valid choice is No. One of No, Yes |
equivalent_Equivalent Piping Length used for Piping Correction Factor in Cooling Mode |
number m |
30.0 |
Enter the equivalent length of the farthest terminal unit from the condenser |
vertical_Vertical Height used for Piping Correction Factor |
number m |
10.0 |
Enter the height difference between the highest and lowest terminal unit |
equivalent_Equivalent Piping Length used for Piping Correction Factor in Heating Mode |
number m |
30.0 |
Enter the equivalent length of the farthest terminal unit from the condenser |
crankcase_Crankcase Heater Power per Compressor |
number W |
33.0 |
Enter the value of the resistive heater located in the compressor(s). This heater is used to warm the refrigerant and oil when the compressor is off. |
number_Number of Compressors |
integer dimensionless |
2 |
Enter the total number of compressor. This input is used only for crankcase heater calculations. |
ratio_Ratio of Compressor Size to Total Compressor Capacity |
number W/W |
0.5 |
Enter the ratio of the first stage compressor to total compressor capacity. All other compressors are assumed to be equally sized. This inputs is used only for crankcase heater calculations. |
maximum_Maximum Outdoor Dry-bulb Temperature for Crankcase Heater |
number C |
5.0 |
Enter the maximum outdoor temperature above which the crankcase heaters are disabled. |
defrost_Defrost Strategy |
choice | Resistive |
Select a defrost strategy. Reverse cycle reverses the operating mode from heating to cooling to melt frost formation on the condenser coil. The resistive strategy uses a resistive heater to melt the frost. One of Resistive, ReverseCycle |
defrost_Defrost Control |
choice | Timed |
Choose a defrost control type. Either use a fixed Timed defrost period or select OnDemand to defrost only when necessary. One of OnDemand, Timed |
defrost_Defrost Time Period Fraction |
number dimensionless |
0.058333 |
Fraction of time in defrost mode. Only applicable if timed defrost control is specified. Range: ≥ 0 |
resistive_Resistive Defrost Heater Capacity |
number or AutosizeW |
Autosize |
Enter the size of the resistive defrost heating element. Only applicable if resistive defrost strategy is specified |
maximum_Maximum Outdoor Dry-bulb Temperature for Defrost Operation |
number C |
5.0 |
Enter the maximum outdoor temperature above which defrost operation is disabled. |
condenser_Condenser Type |
choice | AirCooled |
Select either an air cooled or evaporatively cooled condenser. One of AirCooled, EvaporativelyCooled, WaterCooled |
water_Water Condenser Volume Flow Rate |
number or Autosizem3/s |
Autosize |
Only used when Condenser Type = WaterCooled. |
evaporative_Evaporative Condenser Effectiveness |
number dimensionless |
0.9 |
Enter the effectiveness of the evaporatively cooled condenser. This field is only used when the Condenser Type = EvaporativelyCooled. Range: ≥ 0, ≤ 1 |
evaporative_Evaporative Condenser Air Flow Rate |
number or Autosizem3/s |
Autosize |
Used to calculate evaporative condenser water use. This field is only used when the Condenser Type = EvaporativelyCooled. |
evaporative_Evaporative Condenser Pump Rated Power Consumption |
number or AutosizeW |
0.0 |
Rated power consumed by the evaporative condenser's water pump. This field is only used when the Condenser Type = EvaporativelyCooled. |
basin_Basin Heater Capacity |
number W/K |
0.0 |
This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off. Range: ≥ 0 |
basin_Basin Heater Setpoint Temperature |
number C |
2.0 |
This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on. Range: ≥ 2 |
basin_Basin Heater Operating Schedule Name |
reference | This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
fuel_Fuel Type |
choice | Electricity |
One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane |
minimum_Minimum Outdoor Temperature in Heat Recovery Mode |
number C |
-15.0 |
The minimum outdoor temperature below which heat recovery mode will not operate. |
maximum_Maximum Outdoor Temperature in Heat Recovery Mode |
number C |
45.0 |
The maximum outdoor temperature above which heat recovery mode will not operate. |
Referenced by 2 object types
AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VRF
HVACTemplate:Thermostat¶
from idfpy.models import HVACTemplateThermostat
Zone thermostat control. Referenced schedules must be defined elsewhere in the idf. Thermostat control type is dual setpoint with deadband. It is not necessary to create a thermostat object for every zone, only for each unique set of setpoint schedules. For example, an office building may have two thermostat objects, one for "Office" and one for "Storage".
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | This name is referenced by HVACTemplate:Zone:* objects | |
heating_Heating Setpoint Schedule Name |
reference | Leave blank if constant setpoint specified below, must enter schedule or constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
constant_Constant Heating Setpoint |
number C |
Ignored if schedule specified above, must enter schedule or constant setpoint | |
cooling_Cooling Setpoint Schedule Name |
reference | Leave blank if constant setpoint specified below, must enter schedule or constant setpoint Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
constant_Constant Cooling Setpoint |
number C |
Ignored if schedule specified above, must enter schedule or constant setpoint |
Referenced by 13 object types
HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:ConstantVolume, HVACTemplate:Zone:DualDuct, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:IdealLoadsAirSystem, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:Unitary, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump
HVACTemplate:Zone:BaseboardHeat¶
from idfpy.models import HVACTemplateZoneBaseboardHeat
Zone baseboard heating system.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
baseboard_Baseboard Heating Type |
choice | HotWater |
One of Electric, HotWater |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
HVACTemplate:Zone:ConstantVolume¶
from idfpy.models import HVACTemplateZoneConstantVolume
Zone terminal unit, constant volume, reheat optional. Referenced schedules must be defined elsewhere in the idf.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Constant Volume System Name required |
reference | Name of a HVACTemplate:System:ConstantVolume object serving this zone Names a HVACTemplate:System:ConstantVolume |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
reheat_Reheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
reheat_Reheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
maximum_Maximum Reheat Air Temperature |
number C |
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended. Range: > 0 |
|
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum runs through only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum runs through only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature |
Referenced by 1 object types
HVACTemplate:Zone:DualDuct¶
from idfpy.models import HVACTemplateZoneDualDuct
Zone terminal unit, dual-duct, constant or variable volume.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Dual Duct System Name required |
reference | Name of a HVACTemplate:System:DualDuct object serving this zone Names a HVACTemplate:System:DualDuct |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Minimum Air Flow Fraction |
number | 0.2 |
This field is the Zone Minimum Air Flow Fraction specified as a fraction of the maximum air flow rate. This field is ignored if the system serving this zone is constant volume. Range: ≥ 0, ≤ 1 |
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object Name for Sizing |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
design_Design Specification Outdoor Air Object Name for Control |
reference | When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow. Note that this field is used only for specifying the design outdoor air flow rate used for control. The field Design Specification Outdoor Air Object Name for Sizing (see below) is used to specify the design outdoor air flow rate. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
cold_Cold Supply Plenum Name |
reference | Plenum zone name. Cold supply plenum that serves only this zone. Blank if none. Names a Zone |
|
hot_Hot Supply Plenum Name |
reference | Plenum zone name. Hot supply plenum that serves only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum that serves only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:DualDuct Cooling Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:DualDuct Heating Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
HVACTemplate:Zone:FanCoil¶
from idfpy.models import HVACTemplateZoneFanCoil
4 pipe fan coil unit with optional outdoor air.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
75.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Fan Motor in Air Stream Fraction |
number | 1.0 |
Range: ≥ 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | ChilledWater |
One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Design Setpoint |
number C |
14.0 |
Used for sizing when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
heating_Heating Coil Type |
choice | HotWater |
One of Electric, HotWater |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Design Setpoint |
number C |
50.0 |
Used for sizing when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Cooling Coil Design Setpoint (above) TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Heating Coil Design Setpoint (above) TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
capacity_Capacity Control Method |
choice | If this field is left blank, it will default to CyclingFan if a Dedicated Outdoor Air System is specified (see above), otherwise it will default to ConstantFanVariableFlow. One of ASHRAE90VariableFan, ConstantFanVariableFlow, CyclingFan, MultiSpeedFan, VariableFanConstantFlow, VariableFanVariableFlow |
|
low_Low Speed Supply Air Flow Ratio |
number | 0.33 |
Range: > 0 |
medium_Medium Speed Supply Air Flow Ratio |
number | 0.66 |
Medium Speed Supply Air Flow Ratio should be greater than Low Speed Supply Air Flow Ratio Range: > 0 |
outdoor_Outdoor Air Schedule Name |
reference | Value of schedule multiplies maximum outdoor air flow rate This schedule is ignored if this zone is served by an HVACTemplate dedicated outdoor air system. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
HVACTemplate:Zone:IdealLoadsAirSystem¶
from idfpy.models import HVACTemplateZoneIdealLoadsAirSystem
Zone with ideal air system that meets heating or cooling loads
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
maximum_Maximum Heating Supply Air Temperature |
number C |
50.0 |
Range: > 0, < 100 |
minimum_Minimum Cooling Supply Air Temperature |
number C |
13.0 |
Range: > -100, < 50 |
maximum_Maximum Heating Supply Air Humidity Ratio |
number kgWater/kgDryAir |
0.0156 |
Range: > 0 |
minimum_Minimum Cooling Supply Air Humidity Ratio |
number kgWater/kgDryAir |
0.0077 |
Range: > 0 |
heating_Heating Limit |
choice | NoLimit |
One of LimitCapacity, LimitFlowRate, LimitFlowRateAndCapacity, NoLimit |
maximum_Maximum Heating Air Flow Rate |
number or Autosizem3/s |
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit. | |
maximum_Maximum Sensible Heating Capacity |
number or AutosizeW |
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit. | |
cooling_Cooling Limit |
choice | NoLimit |
One of LimitCapacity, LimitFlowRate, LimitFlowRateAndCapacity, NoLimit |
maximum_Maximum Cooling Air Flow Rate |
number or Autosizem3/s |
This field is ignored if Cooling Limit = NoLimit This field is required if Outdoor Air Economizer Type is anything other than NoEconomizer. | |
maximum_Maximum Total Cooling Capacity |
number or AutosizeW |
This field is ignored if Cooling Limit = NoLimit | |
heating_Heating Availability Schedule Name |
reference | If blank, heating is always available. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Availability Schedule Name |
reference | If blank, cooling is always available. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
dehumidification_Dehumidification Control Type |
choice | ConstantSensibleHeatRatio |
ConstantSensibleHeatRatio means that the ideal loads system will be controlled to meet the sensible cooling load, and the latent cooling rate will be computed using a constant sensible heat ratio (SHR) Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. None means that there is no dehumidification. ConstantSupplyHumidityRatio means that during cooling the supply air will always be at the Minimum Cooling Supply Humidity Ratio. One of ConstantSensibleHeatRatio, ConstantSupplyHumidityRatio, Humidistat, None |
cooling_Cooling Sensible Heat Ratio |
number dimensionless |
0.7 |
This field is applicable only when Dehumidification Control Type is ConstantSensibleHeatRatio Range: > 0, ≤ 1 |
dehumidification_Dehumidification Setpoint |
number percent |
60.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
humidification_Humidification Control Type |
choice | None |
None means that there is no humidification. Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. ConstantSupplyHumidityRatio means that during heating the supply air will always be at the Maximum Heating Supply Humidity Ratio. One of ConstantSupplyHumidityRatio, Humidistat, None |
humidification_Humidification Setpoint |
number percent |
30.0 |
Zone relative humidity setpoint in percent (0 to 100) Range: ≥ 0, ≤ 100 |
outdoor_Outdoor Air Method |
choice | None |
None means there is no outdoor air and all related fields will be ignored Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, None, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object Name |
reference | When the name of a DesignSpecification:OutdoorAir object is entered, the minimum outdoor air flow rate will be computed using these specifications. The outdoor air flow rate will also be affected by the next two fields. If this field is blank, there will be no outdoor air and the remaining fields will be ignored. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
demand_Demand Controlled Ventilation Type |
choice | None |
This field controls how the minimum outdoor air flow rate is calculated. None means that design occupancy will be used to compute the minimum outdoor air flow rate OccupancySchedule means that current occupancy level will be used. CO2Setpoint means that the design occupancy will be used to compute the minimum outdoor air flow rate and the outdoor air flow rate may be increased if necessary to maintain the indoor air carbon dioxide setpoint defined in a ZoneControl:ContaminantController object. One of CO2Setpoint, None, OccupancySchedule |
outdoor_Outdoor Air Economizer Type |
choice | NoEconomizer |
DifferentialDryBulb and DifferentialEnthalpy will increase the outdoor air flow rate when there is a cooling load and the outdoor air temperature or enthalpy is below the zone exhaust air temperature or enthalpy. One of DifferentialDryBulb, DifferentialEnthalpy, NoEconomizer |
heat_Heat Recovery Type |
choice | None |
One of Enthalpy, None, Sensible |
sensible_Sensible Heat Recovery Effectiveness |
number dimensionless |
0.7 |
Range: ≥ 0, ≤ 1 |
latent_Latent Heat Recovery Effectiveness |
number dimensionless |
0.65 |
Applicable only if Heat Recovery Type is Enthalpy. Range: ≥ 0, ≤ 1 |
HVACTemplate:Zone:PTAC¶
from idfpy.models import HVACTemplateZonePTAC
Packaged Terminal Air Conditioner
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
no_No Load Supply Air Flow Rate |
number or Autosizem3/s |
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers. | |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule Name values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
75.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | SingleSpeedDX |
One of SingleSpeedDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
cooling_Cooling Coil Gross Rated Cooling COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input Range: > 0 |
heating_Heating Coil Type |
choice | Electric |
One of Electric, Gas, HotWater |
heating_Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heating_Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
gas_Gas Heating Coil Efficiency |
number | 0.8 |
Applies only if Heating Coil Type is Gas Range: ≥ 0, ≤ 1 |
gas_Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Applies only if Heating Coil Type is Gas Range: ≥ 0 |
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
14.0 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
capacity_Capacity Control Method |
choice | None |
One of None, SingleZoneVAV |
HVACTemplate:Zone:PTHP¶
from idfpy.models import HVACTemplateZonePTHP
Packaged Terminal Heat Pump
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
no_No Load Supply Air Flow Rate |
number or Autosizem3/s |
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers. | |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
75.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | SingleSpeedDX |
One of SingleSpeedDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
cooling_Cooling Coil Gross Rated COP |
number W/W |
3.0 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input Range: > 0 |
heat_Heat Pump Heating Coil Type |
choice | SingleSpeedDXHeatPump |
One of SingleSpeedDXHeatPump |
heat_Heat Pump Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heat_Heat Pump Heating Coil Gross Rated Capacity |
number or AutosizeW |
Autosize |
Capacity excluding supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C |
heat_Heat Pump Heating Coil Gross Rated COP |
number W/W |
2.75 |
Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, Does not include supply air fan heat or supply air fan electrical energy Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C Range: > 0 |
heat_Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature |
number C |
-8.0 |
Range: ≥ -20 |
heat_Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature |
number C |
5.0 |
Range: ≥ 0, ≤ 7.22 |
heat_Heat Pump Defrost Strategy |
choice | ReverseCycle |
One of Resistive, ReverseCycle |
heat_Heat Pump Defrost Control |
choice | Timed |
One of OnDemand, Timed |
heat_Heat Pump Defrost Time Period Fraction |
number | 0.058333 |
Fraction of time in defrost mode only applicable if Timed defrost control is specified Range: ≥ 0 |
supplemental_Supplemental Heating Coil Type |
choice | Electric |
One of Electric, Gas, HotWater |
supplemental_Supplemental Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supplemental_Supplemental Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
supplemental_Supplemental Heating Coil Maximum Outdoor Dry-Bulb Temperature |
number C |
21.0 |
Supplemental heater will not operate when outdoor temperature exceeds this value. Range: ≤ 21 |
supplemental_Supplemental Gas Heating Coil Efficiency |
number | 0.8 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0, ≤ 1 |
supplemental_Supplemental Gas Heating Coil Parasitic Electric Load |
number W |
0.0 |
Applies only if Supplemental Heating Coil Type is Gas Range: ≥ 0 |
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
14.0 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
capacity_Capacity Control Method |
choice | None |
One of None, SingleZoneVAV |
HVACTemplate:Zone:Unitary¶
from idfpy.models import HVACTemplateZoneUnitary
Zone terminal unit, constant volume, no controls.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Unitary System Name required |
reference | Enter the name of an HVACTemplate:System:Unitary, HVACTemplate:System:UnitaryHeatPump:AirToAir, or HVACTemplate:System:UnitarySystem object serving this zone. Names a HVACTemplate:System:Unitary, HVACTemplate:System:UnitaryHeatPump:AirToAir, HVACTemplate:System:UnitarySystem |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum runs through only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum runs through only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:Unitary or HVACTemplate:System:UnitaryHeatPump:AirToAir Cooling Design Supply Air Temperature One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:Unitary or HVACTemplate:System:UnitaryHeatPump:AirToAir Heating Design Supply Air Temperature One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
HVACTemplate:Zone:VAV¶
from idfpy.models import HVACTemplateZoneVAV
Zone terminal unit, variable volume, reheat optional. For heating, this unit activates reheat coil first, then increases airflow (if reverse action specified).
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template VAV System Name required |
reference | Name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Minimum Air Flow Input Method |
choice | Constant |
Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate) FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate) Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air Flow One of Constant, FixedFlowRate, Scheduled |
constant_Constant Minimum Air Flow Fraction |
number | 0.2 |
This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used. Range: ≥ 0, ≤ 1 |
fixed_Fixed Minimum Air Flow Rate |
number m3/s |
This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate. If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the previous field are entered, the larger result is used. | |
minimum_Minimum Air Flow Fraction Schedule Name |
reference | This field is used if the field Zone Minimum Air Flow Input Method is Scheduled Schedule values are fractions, 0.0 to 1.0. If the field Constant Minimum Air Flow Fraction is blank, then the average of the minimum and maximum schedule values is used for sizing normal-action reheat coils. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
reheat_Reheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
reheat_Reheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
damper_Damper Heating Action |
choice | Reverse |
One of Normal, Reverse |
maximum_Maximum Flow per Zone Floor Area During Reheat |
number or Autocalculatem3/s-m2 |
Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = Reverse When autocalculating, the maximum flow per zone is set to 0.002032 m3/s-m2 (0.4 cfm/sqft) This optional field limits the maximum flow allowed in reheat mode. If this field and the following field are left blank, the maximum flow will not be limited. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate. | |
maximum_Maximum Flow Fraction During Reheat |
number or Autocalculate |
Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = Reverse When autocalculating, the maximum flow fraction is set to the ratio of 0.002032 m3/s-m2 (0.4 cfm/sqft) multiplied by the zone floor area and the Maximum Air Flow Rate. This optional field limits the maximum flow allowed in reheat mode. If this field and the previous field are left blank, the maximum flow will not be limited. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate. | |
maximum_Maximum Reheat Air Temperature |
number C |
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended. Range: > 0 |
|
design_Design Specification Outdoor Air Object Name for Control |
reference | When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow. Note that this field is used only for specifying the design outdoor air flow rate used for control. The field Design Specification Outdoor Air Object Name for Sizing (see below) is used to specify the design outdoor air flow rate. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum runs through only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum runs through only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
design_Design Specification Outdoor Air Object Name for Sizing |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
HVACTemplate:Zone:VAV:FanPowered¶
from idfpy.models import HVACTemplateZoneVAVFanPowered
Zone terminal unit, fan powered variable volume, reheat optional. Referenced schedules must be defined elsewhere in the idf.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone Name must match a building zone name Names a Zone |
|
template_Template VAV System Name required |
reference | Enter the name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone. Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
primary_Primary Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
primary_Primary Supply Air Minimum Flow Fraction |
number or Autosize |
Autosize |
|
secondary_Secondary Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
flow_Flow Type |
choice | Parallel |
One of Parallel, ParallelFromPlenum, Series, SeriesFromPlenum |
parallel_Parallel Fan On Flow Fraction |
number or Autosize |
Autosize |
The fraction of the primary air flow at which fan turns on Applicable only to Parallel Flow Type |
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
reheat_Reheat Coil Type |
choice | Electric |
One of Electric, Gas, HotWater |
reheat_Reheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
fan_Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
fan_Fan Delta Pressure |
number Pa |
1000.0 |
Range: ≥ 0 |
fan_Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum runs through only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum runs through only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
zone_Zone PIU Fan Schedule Name |
reference | This is the operating schedule for the zone PIU fan. For a parallel PIU, the fan operates only when the primary air flow is below the Parallel Fan On Flow Fraction and the Zone PIU Fan Schedule is on, or it is activated by an availability manager. For a series PIU, the zone fan operates whenever the Zone PIU Fan Schedule is on, or it is activated by an availability manager. If this field is left blank, the System Availability Schedule for the HVACTemplate:System serving this zone will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
design_Design Specification Outdoor Air Object Name |
reference | Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList | |
design_Design Specification Zone Air Distribution Object Name |
reference | Names a DesignSpecification:ZoneAirDistribution |
HVACTemplate:Zone:VAV:HeatAndCool¶
from idfpy.models import HVACTemplateZoneVAVHeatAndCool
VAV system with VAV for both heating and cooling and optional reheat coil. For heating, this unit increases airflow first, then activates reheat coil.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template VAV System Name required |
reference | Name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
supply_Supply Air Maximum Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
constant_Constant Minimum Air Flow Fraction |
number | 0.2 |
This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used. Range: ≥ 0, ≤ 1 |
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object Name for Sizing |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
reheat_Reheat Coil Type |
choice | None |
One of Electric, Gas, HotWater, None |
reheat_Reheat Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
maximum_Maximum Reheat Air Temperature |
number C |
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended. Range: > 0 |
|
supply_Supply Plenum Name |
reference | Plenum zone name. Supply plenum runs through only this zone. Blank if none. Names a Zone |
|
return_Return Plenum Name |
reference | Plenum zone name. Return plenum runs through only this zone. Blank if none. Names a Zone |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SystemSupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
12.8 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Heating Coil Design Setpoint TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
HVACTemplate:Zone:VRF¶
from idfpy.models import HVACTemplateZoneVRF
Zone terminal unit with variable refrigerant flow (VRF) DX cooling and heating coils (air-to-air or water-to-air heat pump). The VRF terminal units are served by an HVACTemplate:System:VRF system.
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template VRF System Name required |
reference | Name of a HVACTemplate:System:VRF object serving this zone Names a HVACTemplate:System:VRF |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
rated_Rated Total Heating Capacity Sizing Ratio |
number W/W |
1.0 |
If this terminal unit's heating coil is autosized, the heating capacity is sized to be equal to the cooling capacity multiplied by this sizing ratio. This input applies to the terminal unit heating coil and overrides the sizing ratio entered in the HVACTemplate:System:VRF object. Range: ≥ 1 |
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
no_No Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
This flow rate is used when the terminal is not cooling and the previous mode was cooling. This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
no_No Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
This flow rate is used when the terminal is not heating and the previous mode was heating. This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
cooling_Cooling Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero. |
heating_Heating Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero. |
no_No Load Outdoor Air Flow Rate |
number or Autosizem3/s |
Autosize |
If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero. |
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Air Fan placement |
choice | BlowThrough |
Select fan placement as either blow through or draw through. One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
75.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | VariableRefrigerantFlowDX |
One of None, VariableRefrigerantFlowDX |
cooling_Cooling Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
heat_Heat Pump Heating Coil Type |
choice | VariableRefrigerantFlowDX |
One of None, VariableRefrigerantFlowDX |
heat_Heat Pump Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
heat_Heat Pump Heating Coil Gross Rated Capacity |
number or AutosizeW |
Autosize |
Capacity excluding supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C |
zone_Zone Terminal Unit On Parasitic Electric Energy Use |
number W |
0.0 |
Range: ≥ 0 |
zone_Zone Terminal Unit Off Parasitic Electric Energy Use |
number W |
0.0 |
Range: ≥ 0 |
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
14.0 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |
HVACTemplate:Zone:WaterToAirHeatPump¶
from idfpy.models import HVACTemplateZoneWaterToAirHeatPump
Water to Air Heat Pump to be used with HVACTemplate:Plant:MixedWaterLoop
| Field | Type | Default | Details |
|---|---|---|---|
zone_Zone Name required |
reference | Zone name must match a building zone name Names a Zone |
|
template_Template Thermostat Name |
reference | Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone. Names a HVACTemplate:Thermostat |
|
cooling_Cooling Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
heating_Heating Supply Air Flow Rate |
number or Autosizem3/s |
Autosize |
Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers. |
no_No Load Supply Air Flow Rate |
number or Autosizem3/s |
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers. | |
zone_Zone Heating Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
zone_Zone Cooling Sizing Factor |
number | If blank, value from Sizing:Parameters will be used. Range: ≥ 0 |
|
outdoor_Outdoor Air Method |
choice | Flow/Person |
Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name. One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum |
outdoor_Outdoor Air Flow Rate per Person |
number m3/s |
0.00944 |
Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone Floor Area |
number m3/s-m2 |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum |
outdoor_Outdoor Air Flow Rate per Zone |
number m3/s |
0.0 |
This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum |
system_System Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Operating Mode Schedule Name |
reference | Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used. Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supply_Supply Fan Placement |
choice | DrawThrough |
One of BlowThrough, DrawThrough |
supply_Supply Fan Total Efficiency |
number | 0.7 |
Range: > 0, ≤ 1 |
supply_Supply Fan Delta Pressure |
number Pa |
75.0 |
Range: ≥ 0 |
supply_Supply Fan Motor Efficiency |
number | 0.9 |
Range: > 0, ≤ 1 |
cooling_Cooling Coil Type |
choice | Coil:Cooling:WaterToAirHeatPump:EquationFit |
One of Coil:Cooling:WaterToAirHeatPump:EquationFit |
cooling_Cooling Coil Gross Rated Total Capacity |
number or AutosizeW |
Autosize |
Total cooling capacity not accounting for the effect of supply air fan heat |
cooling_Cooling Coil Gross Rated Sensible Heat Ratio |
number or Autosize |
Autosize |
Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat |
cooling_Cooling Coil Gross Rated COP |
number W/W |
3.5 |
Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input Range: > 0 |
heat_Heat Pump Heating Coil Type |
choice | Coil:Heating:WaterToAirHeatPump:EquationFit |
One of Coil:Heating:WaterToAirHeatPump:EquationFit |
heat_Heat Pump Heating Coil Gross Rated Capacity |
number or AutosizeW |
Autosize |
Capacity excluding supply air fan heat |
heat_Heat Pump Heating Coil Gross Rated COP |
number W/W |
4.2 |
Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electric power input Range: > 0 |
supplemental_Supplemental Heating Coil Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
supplemental_Supplemental Heating Coil Capacity |
number or AutosizeW |
Autosize |
|
maximum_Maximum Cycling Rate |
number cycles/hr |
2.5 |
The maximum on-off cycling rate for the compressor Suggested value is 2.5 for a typical heat pump Range: ≥ 0, ≤ 5 |
latent_Latent Capacity Time Constant |
number s |
60.0 |
Time constant for the cooling coil's capacity to reach steady state after startup Suggested value is 60 for a typical heat pump Range: ≥ 0, ≤ 500 |
heat_Heat Pump Fan Delay Time |
number s |
60.0 |
Programmed time delay for heat pump fan to shut off after compressor cycle off. Only required when fan operating mode is cycling Enter 0 when fan operating mode is continuous Range: ≥ 0 |
dedicated_Dedicated Outdoor Air System Name |
reference | Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone. Names a HVACTemplate:System:DedicatedOutdoorAir |
|
supplemental_Supplemental Heating Coil Type |
choice | Electric |
One of Electric, HotWater |
zone_Zone Cooling Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Cooling Design Supply Air Temperature |
number C |
14.0 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Cooling Design Supply Air Temperature Difference |
number deltaC |
11.11 |
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature. |
zone_Zone Heating Design Supply Air Temperature Input Method |
choice | SupplyAirTemperature |
SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference One of SupplyAirTemperature, TemperatureDifference |
zone_Zone Heating Design Supply Air Temperature |
number C |
50.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature |
zone_Zone Heating Design Supply Air Temperature Difference |
number deltaC |
30.0 |
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature. |
heat_Heat Pump Coil Water Flow Mode |
choice | Cycling |
used only when the heat pump coils are of the type WaterToAirHeatPump:EquationFit Constant results in 100% water flow regardless of compressor PLR Cycling results in water flow that matches compressor PLR ConstantOnDemand results in 100% water flow whenever the coil is on, but is 0% whenever the coil has no load One of Constant, ConstantOnDemand, Cycling |
design_Design Specification Outdoor Air Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList |
|
design_Design Specification Zone Air Distribution Object Name |
reference | This field is used only when Outdoor Air Method=DetailedSpecification. Names a DesignSpecification:ZoneAirDistribution |
|
baseboard_Baseboard Heating Type |
choice | None |
One of Electric, HotWater, None |
baseboard_Baseboard Heating Availability Schedule Name |
reference | If blank, always on Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
baseboard_Baseboard Heating Capacity |
number or AutosizeW |
Autosize |