HVAC Templates

32 object types from idfpy.models.hvac_templates · EnergyPlus 26.2

Object Summary
HVACTemplate:Plant:Boiler This object adds a boiler to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop.
HVACTemplate:Plant:Boiler:ObjectReference This object references a detailed boiler object and adds it to an HVACTemplate:Plant:HotWaterLoop or …
HVACTemplate:Plant:ChilledWaterLoop Plant and condenser loops to serve all HVACTemplate chilled water coils, chillers, and towers.
HVACTemplate:Plant:Chiller This object adds a chiller to an HVACTemplate:Plant:ChilledWaterLoop.
HVACTemplate:Plant:Chiller:ObjectReference This object references a detailed chiller object and adds it to an HVACTemplate:Plant:ChilledWaterLoop.
HVACTemplate:Plant:HotWaterLoop Plant loop to serve all HVACTemplate hot water coils and boilers.
HVACTemplate:Plant:MixedWaterLoop Central plant loop portion of a water source heat pump system.
HVACTemplate:Plant:Tower This object adds a cooling tower to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop.
HVACTemplate:Plant:Tower:ObjectReference This object references a detailed cooling tower object and adds it to an HVACTemplate:Plant:ChilledWaterLoop …
HVACTemplate:System:ConstantVolume Constant Air Volume air loop with optional chilled water cooling coil, optional heating coil and optional …
HVACTemplate:System:DedicatedOutdoorAir This object creates a dedicated outdoor air system that must be used with HVACTemplate:Zone:* objects for …
HVACTemplate:System:DualDuct Dual-duct constant volume or variable volume air loop
HVACTemplate:System:PackagedVAV Packaged Variable Air Volume (PVAV) air loop with optional heating coil and optional preheat.
HVACTemplate:System:Unitary Unitary furnace with air conditioner
HVACTemplate:System:UnitaryHeatPump:AirToAir Unitary furnace with electric air-to-air heat pump
HVACTemplate:System:UnitarySystem Unitary HVAC system with optional cooling and heating.
HVACTemplate:System:VAV Variable Air Volume (VAV) air loop with optional heating coil and optional preheat.
HVACTemplate:System:VRF Variable refrigerant flow (VRF) heat pump condensing unit.
HVACTemplate:Thermostat Zone thermostat control.
HVACTemplate:Zone:BaseboardHeat Zone baseboard heating system.
HVACTemplate:Zone:ConstantVolume Zone terminal unit, constant volume, reheat optional.
HVACTemplate:Zone:DualDuct Zone terminal unit, dual-duct, constant or variable volume.
HVACTemplate:Zone:FanCoil 4 pipe fan coil unit with optional outdoor air.
HVACTemplate:Zone:IdealLoadsAirSystem Zone with ideal air system that meets heating or cooling loads
HVACTemplate:Zone:PTAC Packaged Terminal Air Conditioner
HVACTemplate:Zone:PTHP Packaged Terminal Heat Pump
HVACTemplate:Zone:Unitary Zone terminal unit, constant volume, no controls.
HVACTemplate:Zone:VAV Zone terminal unit, variable volume, reheat optional.
HVACTemplate:Zone:VAV:FanPowered Zone terminal unit, fan powered variable volume, reheat optional.
HVACTemplate:Zone:VAV:HeatAndCool VAV system with VAV for both heating and cooling and optional reheat coil.
HVACTemplate:Zone:VRF Zone terminal unit with variable refrigerant flow (VRF) DX cooling and heating coils (air-to-air or …
HVACTemplate:Zone:WaterToAirHeatPump Water to Air Heat Pump to be used with HVACTemplate:Plant:MixedWaterLoop

HVACTemplate:Plant:Boiler

from idfpy.models import HVACTemplatePlantBoiler

This object adds a boiler to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop.

Field Type Default Details
name
Name required
string
boiler_type
Boiler Type required
choice One of CondensingHotWaterBoiler, DistrictHotWater, HotWaterBoiler
capacity
Capacity
number or Autosize
W
Autosize
efficiency
Efficiency
number 0.8 Not applicable if Boiler Type is DistrictHotWater
Range: ≥ 0, ≤ 1
fuel_type
Fuel Type
choice Not applicable if Boiler Type is DistrictHotWater
One of Coal, Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
priority
Priority
string If Hot Water Plant Operation Scheme Type=Default in HVACTemplate:Plant:HotWaterLoop, then equipment operates in priority order, 1, 2, 3, etc.
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.1 Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 Range: ≥ 0
water_outlet_upper_temperature_limit
Water Outlet Upper Temperature Limit
number
C
100.0
template_plant_loop_type
Template Plant Loop Type
choice Specifies if this boiler serves a template hot water loop or mixed water loop If left blank, will serve a hot water loop if present, or a mixed water loop (if no hot water loop is present).
One of HotWater, MixedWater

HVACTemplate:Plant:Boiler:ObjectReference

from idfpy.models import HVACTemplatePlantBoilerObjectReference

This object references a detailed boiler object and adds it to an HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop. The user must create a complete detailed boiler object with all required curve or performance objects.

Field Type Default Details
name
Name required
string The name of this object.
boiler_object_type
Boiler Object Type
choice Boiler:HotWater One of Boiler:HotWater
boiler_name
Boiler Name required
reference The name of the detailed boiler object.
Names a Boiler:HotWater
priority
Priority
number If Hot Water Plant Operation Scheme Type=Default in HVACTemplate:Plant:HotWaterLoop or MixedWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.
template_plant_loop_type
Template Plant Loop Type
choice Specifies if this boiler serves a template hot water loop or mixed water loop If left blank, will serve a hot water loop if present, or a mixed water loop (if no hot water loop is present).
One of HotWater, MixedWater

HVACTemplate:Plant:ChilledWaterLoop

from idfpy.models import HVACTemplatePlantChilledWaterLoop unique

Plant and condenser loops to serve all HVACTemplate chilled water coils, chillers, and towers.

Field Type Default Details
name
Name required
string
pump_schedule_name
Pump Schedule Name
reference If blank, always available Applies to both chilled water and condenser loop pumps
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
pump_control_type
Pump Control Type
choice Intermittent Applies to both chilled water and condenser loop pumps
One of Continuous, Intermittent
chiller_plant_operation_scheme_type
Chiller Plant Operation Scheme Type
choice Default Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Chiller objects.
One of Default, UserDefined
chiller_plant_equipment_operation_schemes_name
Chiller Plant Equipment Operation Schemes Name
reference Name of a PlantEquipmentOperationSchemes object Ignored if Chiller Plant Operation Scheme Type = Default
Names a PlantEquipmentOperationSchemes
chilled_water_setpoint_schedule_name
Chilled Water Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
chilled_water_design_setpoint
Chilled Water Design Setpoint
number
C
7.22 Used for sizing and as constant setpoint if no Chilled Water Setpoint Schedule Name is specified.
chilled_water_pump_configuration
Chilled Water Pump Configuration
choice ConstantPrimaryNoSecondary VariablePrimaryNoSecondary - variable flow to chillers and coils ConstantPrimaryNoSecondary - constant flow to chillers and coils, excess bypassed ConstantPrimaryVariableSecondary - constant flow to chillers, variable flow to coils VariablePrimaryConstantSecondary - currently unsupported - variable flow to chillers, constant flow to coils
One of ConstantPrimaryNoSecondary, ConstantPrimaryVariableSecondary, VariablePrimaryNoSecondary
primary_chilled_water_pump_rated_head
Primary Chilled Water Pump Rated Head
number
Pa
179352.0 default head is 60 feet H2O
Range: ≥ 0
secondary_chilled_water_pump_rated_head
Secondary Chilled Water Pump Rated Head
number
Pa
179352.0 default head is 60 feet H2O
Range: ≥ 0
condenser_plant_operation_scheme_type
Condenser Plant Operation Scheme Type
choice Default Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Tower objects. May be left blank if not serving any water cooled chillers
One of Default, UserDefined
condenser_equipment_operation_schemes_name
Condenser Equipment Operation Schemes Name
reference Name of a CondenserEquipmentOperationSchemes object Ignored if Condenser Plant Operation Scheme Type = Default May be left blank if not serving any water cooled chillers
Names a CondenserEquipmentOperationSchemes
condenser_water_temperature_control_type
Condenser Water Temperature Control Type
choice May be left blank if not serving any water cooled chillers
One of OutdoorWetBulbTemperature, SpecifiedSetpoint
condenser_water_setpoint_schedule_name
Condenser Water Setpoint Schedule Name
reference Leave blank if constant setpoint May be left blank if not serving any water cooled chillers
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_water_design_setpoint
Condenser Water Design Setpoint
number
C
29.4 Used for sizing and as constant setpoint if no Condenser Water Setpoint Schedule Name is specified. May be left blank if not serving any water cooled chillers
condenser_water_pump_rated_head
Condenser Water Pump Rated Head
number
Pa
179352.0 May be left blank if not serving any water cooled chillers default head is 60 feet H2O
Range: ≥ 0
chilled_water_setpoint_reset_type
Chilled Water Setpoint Reset Type
choice None Overrides Chilled Water Setpoint Schedule Name
One of None, OutdoorAirTemperatureReset
chilled_water_setpoint_at_outdoor_dry_bulb_low
Chilled Water Setpoint at Outdoor Dry-Bulb Low
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
chilled_water_reset_outdoor_dry_bulb_low
Chilled Water Reset Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control.
chilled_water_setpoint_at_outdoor_dry_bulb_high
Chilled Water Setpoint at Outdoor Dry-Bulb High
number
C
6.7 Applicable only for OutdoorAirTemperatureReset control.
chilled_water_reset_outdoor_dry_bulb_high
Chilled Water Reset Outdoor Dry-Bulb High
number
C
26.7 Applicable only for OutdoorAirTemperatureReset control.
chilled_water_primary_pump_type
Chilled Water Primary Pump Type
choice SinglePump Describes the type of pump configuration used for the primary portion of the chilled water loop.
One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerChiller, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps
chilled_water_secondary_pump_type
Chilled Water Secondary Pump Type
choice SinglePump Describes the type of pump configuration used for the secondary portion of the chilled water loop.
One of FiveHeaderedPumps, FourHeaderedPumps, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps
condenser_water_pump_type
Condenser Water Pump Type
choice SinglePump Describes the type of pump configuration used for the condenser water loop.
One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerTower, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps
chilled_water_supply_side_bypass_pipe
Chilled Water Supply Side Bypass Pipe
choice Yes Determines if a supply side bypass pipe is present in the chilled water loop.
One of No, Yes
chilled_water_demand_side_bypass_pipe
Chilled Water Demand Side Bypass Pipe
choice Yes Determines if a demand side bypass pipe is present in the chilled water loop.
One of No, Yes
condenser_water_supply_side_bypass_pipe
Condenser Water Supply Side Bypass Pipe
choice Yes Determines if a supply side bypass pipe is present in the condenser water loop.
One of No, Yes
condenser_water_demand_side_bypass_pipe
Condenser Water Demand Side Bypass Pipe
choice Yes Determines if a demand side bypass pipe is present in the condenser water loop.
One of No, Yes
fluid_type
Fluid Type
choice Water One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water
loop_design_delta_temperature
Loop Design Delta Temperature
number
deltaC
6.67 The temperature difference used in sizing the loop flow rate.
minimum_outdoor_dry_bulb_temperature
Minimum Outdoor Dry Bulb Temperature
number
C
The minimum outdoor dry-bulb temperature that the chilled water loops operate. Leave blank for no limit.
chilled_water_load_distribution_scheme
Chilled Water Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR
condenser_water_load_distribution_scheme
Condenser Water Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR

HVACTemplate:Plant:Chiller

from idfpy.models import HVACTemplatePlantChiller

This object adds a chiller to an HVACTemplate:Plant:ChilledWaterLoop.

Field Type Default Details
name
Name required
string
chiller_type
Chiller Type required
choice One of DistrictChilledWater, ElectricCentrifugalChiller, ElectricReciprocatingChiller, ElectricScrewChiller
capacity
Capacity
number or Autosize
W
Autosize
nominal_cop
Nominal COP required
number
W/W
Not applicable if Chiller Type is DistrictChilledWater Electric Reciprocating Chiller
Range: > 0
condenser_type
Condenser Type
choice WaterCooled Not applicable if Chiller Type is DistrictChilledWater
One of AirCooled, EvaporativelyCooled, WaterCooled
priority
Priority
string If Chiller Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Part load ratio below which the chiller starts cycling on/off to meet the load. Must be less than or equal to Maximum Part Load Ratio.
Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Maximum allowable part load ratio. Must be greater than or equal to Minimum Part Load Ratio.
Range: > 0
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 Optimum part load ratio where the chiller is most efficient. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: > 0
minimum_unloading_ratio
Minimum Unloading Ratio
number 0.25 Part load ratio where the chiller can no longer unload and false loading begins. Minimum unloading ratio must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: ≥ 0
leaving_chilled_water_lower_temperature_limit
Leaving Chilled Water Lower Temperature Limit
number
C
5.0

HVACTemplate:Plant:Chiller:ObjectReference

from idfpy.models import HVACTemplatePlantChillerObjectReference

This object references a detailed chiller object and adds it to an HVACTemplate:Plant:ChilledWaterLoop. The user must create a complete detailed chiller object with all required curve or performance objects.

Field Type Default Details
name
Name required
string The name of this object.
chiller_object_type
Chiller Object Type
choice Chiller:Electric:EIR One of Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR
chiller_name
Chiller Name required
reference The name of the detailed chiller object.
Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven
priority
Priority
number If Chiller Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.

HVACTemplate:Plant:HotWaterLoop

from idfpy.models import HVACTemplatePlantHotWaterLoop unique

Plant loop to serve all HVACTemplate hot water coils and boilers.

Field Type Default Details
name
Name required
string
pump_schedule_name
Pump Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
pump_control_type
Pump Control Type
choice Intermittent One of Continuous, Intermittent
hot_water_plant_operation_scheme_type
Hot Water Plant Operation Scheme Type
choice Default Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Boiler objects.
One of Default, UserDefined
hot_water_plant_equipment_operation_schemes_name
Hot Water Plant Equipment Operation Schemes Name
reference Name of a PlantEquipmentOperationSchemes object Ignored if Plant Operation Scheme Type = Default
Names a PlantEquipmentOperationSchemes
hot_water_setpoint_schedule_name
Hot Water Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
hot_water_design_setpoint
Hot Water Design Setpoint
number
C
82.0 Used for sizing and as constant setpoint if no Setpoint Schedule Name is specified.
hot_water_pump_configuration
Hot Water Pump Configuration
choice ConstantFlow VariableFlow - variable flow to boilers and coils, excess bypassed ConstantFlow - constant flow to boilers and coils, excess bypassed
One of ConstantFlow, VariableFlow
hot_water_pump_rated_head
Hot Water Pump Rated Head
number
Pa
179352.0 Default head is 60 feet H2O
Range: ≥ 0
hot_water_setpoint_reset_type
Hot Water Setpoint Reset Type
choice None Overrides Hot Water Setpoint Schedule Name
One of None, OutdoorAirTemperatureReset
hot_water_setpoint_at_outdoor_dry_bulb_low
Hot Water Setpoint at Outdoor Dry-Bulb Low
number
C
82.2 Applicable only for OutdoorAirTemperatureReset control.
hot_water_reset_outdoor_dry_bulb_low
Hot Water Reset Outdoor Dry-Bulb Low
number
C
-6.7 Applicable only for OutdoorAirTemperatureReset control.
hot_water_setpoint_at_outdoor_dry_bulb_high
Hot Water Setpoint at Outdoor Dry-Bulb High
number
C
65.6 Applicable only for OutdoorAirTemperatureReset control.
hot_water_reset_outdoor_dry_bulb_high
Hot Water Reset Outdoor Dry-Bulb High
number
C
10.0 Applicable only for OutdoorAirTemperatureReset control.
hot_water_pump_type
Hot Water Pump Type
choice SinglePump Describes the type of pump configuration used for the hot water loop.
One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerBoiler, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps
supply_side_bypass_pipe
Supply Side Bypass Pipe
choice Yes Determines if a supply side bypass pipe is present in the hot water loop.
One of No, Yes
demand_side_bypass_pipe
Demand Side Bypass Pipe
choice Yes Determines if a demand side bypass pipe is present in the hot water loop.
One of No, Yes
fluid_type
Fluid Type
choice Water One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water
loop_design_delta_temperature
Loop Design Delta Temperature
number
deltaC
11.0 The temperature difference used in sizing the loop flow rate.
maximum_outdoor_dry_bulb_temperature
Maximum Outdoor Dry Bulb Temperature
number
C
The maximum outdoor dry-bulb temperature that the hot water loops operate. Leave blank for no limit.
load_distribution_scheme
Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR

HVACTemplate:Plant:MixedWaterLoop

from idfpy.models import HVACTemplatePlantMixedWaterLoop unique

Central plant loop portion of a water source heat pump system.

Field Type Default Details
name
Name required
string
pump_schedule_name
Pump Schedule Name
reference If blank, always available Applies to both chilled water and condenser loop pumps
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
pump_control_type
Pump Control Type
choice Intermittent Applies to both chilled water and condenser loop pumps
One of Continuous, Intermittent
operation_scheme_type
Operation Scheme Type
choice Default Default operation type makes all equipment available at all times operating in order of Priority specified in HVACTemplate:Plant:Boiler and HVACTemplate:Plant:Tower objects.
One of Default, UserDefined
equipment_operation_schemes_name
Equipment Operation Schemes Name
reference Name of a PlantEquipmentOperationSchemes object Ignored if Plant Operation Scheme Type = Default
Names a PlantEquipmentOperationSchemes
high_temperature_setpoint_schedule_name
High Temperature Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
high_temperature_design_setpoint
High Temperature Design Setpoint
number
C
33.0 Used for sizing and as constant setpoint if no Setpoint Schedule Name is specified.
low_temperature_setpoint_schedule_name
Low Temperature Setpoint Schedule Name
reference Leave blank if constant setpoint May be left blank if not serving any water cooled chillers
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
low_temperature_design_setpoint
Low Temperature Design Setpoint
number
C
20.0 Used for sizing and as constant setpoint if no Condenser Water Setpoint Schedule Name is specified. May be left blank if not serving any water cooled chillers
water_pump_configuration
Water Pump Configuration
choice ConstantFlow VariableFlow - variable flow to boilers and coils, excess bypassed ConstantFlow - constant flow to boilers and coils, excess bypassed
One of ConstantFlow, VariableFlow
water_pump_rated_head
Water Pump Rated Head
number
Pa
179352.0 May be left blank if not serving any water cooled chillers default head is 60 feet H2O
Range: ≥ 0
water_pump_type
Water Pump Type
choice SinglePump Describes the type of pump configuration used for the mixed water loop.
One of FiveHeaderedPumps, FourHeaderedPumps, PumpPerTowerOrBoiler, SinglePump, ThreeHeaderedPumps, TwoHeaderedPumps
supply_side_bypass_pipe
Supply Side Bypass Pipe
choice Yes Determines if a supply side bypass pipe is present in the hot water loop.
One of No, Yes
demand_side_bypass_pipe
Demand Side Bypass Pipe
choice Yes Determines if a demand side bypass pipe is present in the hot water loop.
One of No, Yes
fluid_type
Fluid Type
choice Water One of EthyleneGlycol30, EthyleneGlycol40, EthyleneGlycol50, EthyleneGlycol60, PropyleneGlycol30, PropyleneGlycol40, PropyleneGlycol50, PropyleneGlycol60, Water
loop_design_delta_temperature
Loop Design Delta Temperature
number
deltaC
5.6 The temperature difference used in sizing the loop flow rate.
load_distribution_scheme
Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR

HVACTemplate:Plant:Tower

from idfpy.models import HVACTemplatePlantTower

This object adds a cooling tower to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop.

Field Type Default Details
name
Name required
string
tower_type
Tower Type required
choice One of SingleSpeed, TwoSpeed
high_speed_nominal_capacity
High Speed Nominal Capacity
number or Autosize
W
Autosize Applicable for tower type SingleSpeed and TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at high speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt(3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
high_speed_fan_power
High Speed Fan Power
number or Autosize
W
Autosize Applicable for tower type SingleSpeed and TwoSpeed
low_speed_nominal_capacity
Low Speed Nominal Capacity
number or Autosize
W
Autosize Applicable only for Tower Type TwoSpeed Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at low speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
low_speed_fan_power
Low Speed Fan Power
number or Autosize
W
Autosize Applicable only for Tower Type TwoSpeed
free_convection_capacity
Free Convection Capacity
number or Autosize
W
Autosize Applicable for Tower Type SingleSpeed and TwoSpeed Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Tower free convection capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
priority
Priority
string Applicable for all Tower Types If Condenser Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
template_plant_loop_type
Template Plant Loop Type
choice Specifies if this tower serves a template chilled water loop or mixed water loop If left blank, will serve a chilled water loop if present, or a mixed water loop (if no chilled water loop is present).
One of ChilledWater, MixedWater

HVACTemplate:Plant:Tower:ObjectReference

from idfpy.models import HVACTemplatePlantTowerObjectReference

This object references a detailed cooling tower object and adds it to an HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop. The user must create a complete detailed cooling tower object with all required curve or performance objects.

Field Type Default Details
name
Name required
string The name of this object.
cooling_tower_object_type
Cooling Tower Object Type
choice CoolingTower:SingleSpeed One of CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed
cooling_tower_name
Cooling Tower Name required
reference The name of the detailed cooling tower object.
Names a CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed, CoolingTower:VariableSpeed:Merkel
priority
Priority
number If Condenser Plant Operation Scheme Type=Default in HVACTemplate:Plant:ChilledWaterLoop or MixedWaterLoop, then equipment operates in Priority order, 1, 2, 3, etc.
template_plant_loop_type
Template Plant Loop Type
choice Specifies if this tower serves a template chilled water loop or mixed water loop If left blank, will serve a chilled water loop if present, or a mixed water loop (if no chilled water loop is present).
One of ChilledWater, MixedWater

HVACTemplate:System:ConstantVolume

from idfpy.models import HVACTemplateSystemConstantVolume

Constant Air Volume air loop with optional chilled water cooling coil, optional heating coil and optional preheat.

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_maximum_flow_rate
Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
600.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
cooling_coil_type
Cooling Coil Type
choice ChilledWater One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, None
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_control_type
Cooling Coil Setpoint Control Type
choice FixedSetpoint One of ControlZone, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled, Warmest
cooling_coil_control_zone_name
Cooling Coil Control Zone name
reference name of the HVACTemplate:ZoneConstantVolume object that contains the cooling thermostat when Cooling Coil Setpoint Control Type = ControlZone
Names a HVACTemplate:Zone:ConstantVolume
cooling_coil_design_setpoint_temperature
Cooling Coil Design Setpoint Temperature
number
C
12.8 Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified.
cooling_coil_setpoint_schedule_name
Cooling Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_at_outdoor_dry_bulb_low
Cooling Coil Setpoint at Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_low
Cooling Coil Reset Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F)
cooling_coil_setpoint_at_outdoor_dry_bulb_high
Cooling Coil Setpoint at Outdoor Dry-Bulb High
number
C
12.8 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_high
Cooling Coil Reset Outdoor Dry-Bulb High
number
C
23.3 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_type
Heating Coil Type
choice HotWater One of Electric, Gas, HotWater, None
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_control_type
Heating Coil Setpoint Control Type
choice FixedSetpoint One of ControlZone, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled
heating_coil_control_zone_name
Heating Coil Control Zone name
reference name of the HVACTemplate:ZoneConstantVolume object that contains the heating thermostat
Names a HVACTemplate:Zone:ConstantVolume
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
10.0 Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified.
heating_coil_setpoint_schedule_name
Heating Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_at_outdoor_dry_bulb_low
Heating Coil Setpoint at Outdoor Dry-Bulb Low
number
C
15.0 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_reset_outdoor_dry_bulb_low
Heating Coil Reset Outdoor Dry-Bulb Low
number
C
7.8 Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F)
heating_coil_setpoint_at_outdoor_dry_bulb_high
Heating Coil Setpoint at Outdoor Dry-Bulb High
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_reset_outdoor_dry_bulb_high
Heating Coil Reset Outdoor Dry-Bulb High
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_capacity
Heating Coil Capacity
number or Autosize
W
Autosize
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
preheat_coil_type
Preheat Coil Type
choice None One of Electric, Gas, HotWater, None
preheat_coil_availability_schedule_name
Preheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
preheat_coil_design_setpoint
Preheat Coil Design Setpoint
number
C
7.2 Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified.
preheat_coil_setpoint_schedule_name
Preheat Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gas_preheat_coil_efficiency
Gas Preheat Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_preheat_coil_parasitic_electric_load
Gas Preheat Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_upper_temperature_limit
Economizer Upper Temperature Limit
number
C
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_lower_temperature_limit
Economizer Lower Temperature Limit
number
C
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_upper_enthalpy_limit
Economizer Upper Enthalpy Limit
number
J/kg
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Range: ≥ 0, ≤ 1
heat_recovery_heat_exchanger_type
Heat Recovery Heat Exchanger Type
choice Plate One of Plate, Rotary
heat_recovery_frost_control_type
Heat Recovery Frost Control Type
choice None One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint.
One of CoolReheat, None
dehumidification_control_zone_name
Dehumidification Control Zone Name
reference Zone name where humidistat is located
Names a Zone
dehumidification_relative_humidity_setpoint
Dehumidification Relative Humidity Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
dehumidification_relative_humidity_setpoint_schedule_name
Dehumidification Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_relative_humidity_setpoint
Humidifier Relative Humidity Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
humidifier_relative_humidity_setpoint_schedule_name
Humidifier Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
300.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:ConstantVolume

HVACTemplate:System:DedicatedOutdoorAir

from idfpy.models import HVACTemplateSystemDedicatedOutdoorAir

This object creates a dedicated outdoor air system that must be used with HVACTemplate:Zone:* objects for BaseboardHeat FanCoil PTAC PTHP WaterToAirHeatPump and VRF. Does not support HVACTemplate:Zone:VAV or other central multizone systems

Field Type Default Details
name
Name
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; DOAS System always on. Schedule is used in availability manager and fan scheduling.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_outlet_type
Air Outlet Type
choice DirectIntoZone One of DirectIntoZone
supply_fan_flow_rate
Supply Fan Flow Rate
number or Autosize
m3/s
Autosize
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
cooling_coil_type
Cooling Coil Type
choice ChilledWater One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, HeatExchangerAssistedDX, None, TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_control_type
Cooling Coil Setpoint Control Type
choice FixedSetpoint One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled
cooling_coil_design_setpoint
Cooling Coil Design Setpoint
number
C
12.8 Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified.
cooling_coil_setpoint_schedule_name
Cooling Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_at_outdoor_dry_bulb_low
Cooling Coil Setpoint at Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_low
Cooling Coil Reset Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F)
cooling_coil_setpoint_at_outdoor_dry_bulb_high
Cooling Coil Setpoint at Outdoor Dry-Bulb High
number
C
12.8 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_high
Cooling Coil Reset Outdoor Dry-Bulb High
number
C
23.3 Applicable only for OutdoorAirTemperatureReset control.
dx_cooling_coil_gross_rated_total_capacity
DX Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
dx_cooling_coil_gross_rated_sensible_heat_ratio
DX Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Gross SHR
dx_cooling_coil_gross_rated_cop
DX Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
heating_coil_type
Heating Coil Type
choice HotWater One of Electric, Gas, HotWater, None
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_control_type
Heating Coil Setpoint Control Type
choice FixedSetpoint When selecting OutdoorAirTemperatureReset, the Heating Coil Design Setpoint may need to be changed
One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
12.2 Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified.
heating_coil_setpoint_schedule_name
Heating Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_at_outdoor_dry_bulb_low
Heating Coil Setpoint at Outdoor Dry-Bulb Low
number
C
15.0 Applicable only for OutdoorAirTemperatureReset control. Defaults 15.0C (59F) at 7.8C (46F) to 12.2C (54F) at 12.2C (54F)
heating_coil_reset_outdoor_dry_bulb_low
Heating Coil Reset Outdoor Dry-Bulb Low
number
C
7.8 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_setpoint_at_outdoor_dry_bulb_high
Heating Coil Setpoint at Outdoor Dry-Bulb High
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_reset_outdoor_dry_bulb_high
Heating Coil Reset Outdoor Dry-Bulb High
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
heat_recovery_sensible_effectiveness
Heat Recovery Sensible Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
heat_recovery_latent_effectiveness
Heat Recovery Latent Effectiveness
number 0.65 Range: ≥ 0, ≤ 1
heat_recovery_heat_exchanger_type
Heat Recovery Heat Exchanger Type
choice Plate One of Plate, Rotary
heat_recovery_frost_control_type
Heat Recovery Frost Control Type
choice None One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheatHeatingCoil = cool beyond the dry-bulb setpoint, reheat with heating coil Valid for all cooling coil types. If no heating coil specified, cold supply temps may occur. CoolReheatDesuperheater = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with desuperheater coil. Valid only for Cooling Coil Type = TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX, or HeatExchangerAssistedDX. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only for Cooling Coil Type = TwoStageHumidityControlDX or HeatExchangerAssistedDX
One of CoolReheatDesuperheater, CoolReheatHeatingCoil, Multimode, None
dehumidification_setpoint
Dehumidification Setpoint
number
kgWater/kgDryAir
0.00924 The supply air humidity ratio for dehumidification control. Default of 0.00924 kgWater/kgDryAir is equivalent to 12.8C (55F) dewpoint. Ignored if Dehumidification Setpoint Schedule specified below
Range: ≥ 0, ≤ 1
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_constant_setpoint
Humidifier Constant Setpoint
number
kgWater/kgDryAir
0.003 The supply air humidity ratio for humidification control. Ignored if Humidifier Setpoint Schedule specified below
Range: ≥ 0, ≤ 1
dehumidification_setpoint_schedule_name
Dehumidification Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Dehumidification Setpoint above. Schedule values must be in units of humidity ratio (kgWater/kgDryAir or lbWater/lbDryAir)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_setpoint_schedule_name
Humidifier Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Humidifier Constant Setpoint above. Schedule values must be in units of humidity ratio (kgWater/kgDryAir or lbWater/lbDryAir)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 7 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump

HVACTemplate:System:DualDuct

from idfpy.models import HVACTemplateSystemDualDuct

Dual-duct constant volume or variable volume air loop

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
system_configuration_type
System Configuration Type
choice SingleFanConstantVolume SingleFan - a single supply fan before the split to dual ducts DualFan - two supply fans, one each for the cold and hot ducts ConstantVolume - constant volume VariableVolume - variable volume
One of DualFanConstantVolume, DualFanVariableVolume, SingleFanConstantVolume, SingleFanVariableVolume
main_supply_fan_maximum_flow_rate
Main Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
main_supply_fan_minimum_flow_fraction
Main Supply Fan Minimum Flow Fraction
number 0.2 Range: ≥ 0, ≤ 1
main_supply_fan_total_efficiency
Main Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
main_supply_fan_delta_pressure
Main Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
main_supply_fan_motor_efficiency
Main Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
main_supply_fan_motor_in_air_stream_fraction
Main Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
main_supply_fan_part_load_power_coefficients
Main Supply Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
cold_duct_supply_fan_maximum_flow_rate
Cold Duct Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
cold_duct_supply_fan_minimum_flow_fraction
Cold Duct Supply Fan Minimum Flow Fraction
number 0.2 Range: ≥ 0, ≤ 1
cold_duct_supply_fan_total_efficiency
Cold Duct Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
cold_duct_supply_fan_delta_pressure
Cold Duct Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
cold_duct_supply_fan_motor_efficiency
Cold Duct Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
cold_duct_supply_fan_motor_in_air_stream_fraction
Cold Duct Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cold_duct_supply_fan_part_load_power_coefficients
Cold Duct Supply Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
cold_duct_supply_fan_placement
Cold Duct Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
hot_duct_supply_fan_maximum_flow_rate
Hot Duct Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
hot_duct_supply_fan_minimum_flow_fraction
Hot Duct Supply Fan Minimum Flow Fraction
number 0.2 Range: ≥ 0, ≤ 1
hot_duct_supply_fan_total_efficiency
Hot Duct Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
hot_duct_supply_fan_delta_pressure
Hot Duct Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
hot_duct_supply_fan_motor_efficiency
Hot Duct Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
hot_duct_supply_fan_motor_in_air_stream_fraction
Hot Duct Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
hot_duct_supply_fan_part_load_power_coefficients
Hot Duct Supply Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
hot_duct_supply_fan_placement
Hot Duct Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
cooling_coil_type
Cooling Coil Type
choice ChilledWater One of ChilledWater, ChilledWaterDetailedFlatModel, None
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_control_type
Cooling Coil Setpoint Control Type
choice FixedSetpoint One of FixedSetpoint, OutdoorAirTemperatureReset, Scheduled, Warmest
cooling_coil_design_setpoint_temperature
Cooling Coil Design Setpoint Temperature
number
C
12.8 Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified.
cooling_coil_setpoint_schedule_name
Cooling Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_at_outdoor_dry_bulb_low
Cooling Coil Setpoint at Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_low
Cooling Coil Reset Outdoor Dry-Bulb Low
number
C
15.6 Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F)
cooling_coil_setpoint_at_outdoor_dry_bulb_high
Cooling Coil Setpoint at Outdoor Dry-Bulb High
number
C
12.8 Applicable only for OutdoorAirTemperatureReset control.
cooling_coil_reset_outdoor_dry_bulb_high
Cooling Coil Reset Outdoor Dry-Bulb High
number
C
23.3 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_type
Heating Coil Type
choice HotWater One of Electric, Gas, HotWater, None
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_control_type
Heating Coil Setpoint Control Type
choice FixedSetpoint One of Coldest, FixedSetpoint, OutdoorAirTemperatureReset, Scheduled
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
50.0 Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified.
heating_coil_setpoint_schedule_name
Heating Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_at_outdoor_dry_bulb_low
Heating Coil Setpoint at Outdoor Dry-Bulb Low
number
C
50.0 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_reset_outdoor_dry_bulb_low
Heating Coil Reset Outdoor Dry-Bulb Low
number
C
7.8 Applicable only for OutdoorAirTemperatureReset control. Defaults are 15.6C (60F) at 15.6C (60F) to 12.8C (55F) at 23.3C (74F)
heating_coil_setpoint_at_outdoor_dry_bulb_high
Heating Coil Setpoint at Outdoor Dry-Bulb High
number
C
20.0 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_reset_outdoor_dry_bulb_high
Heating Coil Reset Outdoor Dry-Bulb High
number
C
12.2 Applicable only for OutdoorAirTemperatureReset control.
heating_coil_capacity
Heating Coil Capacity
number or Autosize
W
Autosize
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
preheat_coil_type
Preheat Coil Type
choice None One of Electric, Gas, HotWater, None
preheat_coil_availability_schedule_name
Preheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
preheat_coil_design_setpoint
Preheat Coil Design Setpoint
number
C
7.2 Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified.
preheat_coil_setpoint_schedule_name
Preheat Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gas_preheat_coil_efficiency
Gas Preheat Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_preheat_coil_parasitic_electric_load
Gas Preheat Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_control_type
Minimum Outdoor Air Control Type
choice ProportionalMinimum One of FixedMinimum, ProportionalMinimum
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of NoLockout
economizer_upper_temperature_limit
Economizer Upper Temperature Limit
number
C
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_lower_temperature_limit
Economizer Lower Temperature Limit
number
C
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_upper_enthalpy_limit
Economizer Upper Enthalpy Limit
number
J/kg
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
cold_supply_plenum_name
Cold Supply Plenum Name
reference Plenum zone name. Supply plenum serves the cold inlets of all zones on this system. Blank if none.
Names a Zone
hot_supply_plenum_name
Hot Supply Plenum Name
reference Plenum zone name. Supply plenum serves the hot inlets of all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Range: ≥ 0, ≤ 1
heat_recovery_heat_exchanger_type
Heat Recovery Heat Exchanger Type
choice Plate One of Plate, Rotary
heat_recovery_frost_control_type
Heat Recovery Frost Control Type
choice None One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint.
One of CoolReheat, None
dehumidification_control_zone_name
Dehumidification Control Zone Name
reference Zone name where humidistat is located
Names a Zone
dehumidification_relative_humidity_setpoint
Dehumidification Relative Humidity Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
dehumidification_relative_humidity_setpoint_schedule_name
Dehumidification Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_relative_humidity_setpoint
Humidifier Relative Humidity Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
humidifier_relative_humidity_setpoint_schedule_name
Humidifier Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
sizing_option
Sizing Option
choice NonCoincident Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates.
One of Coincident, NonCoincident
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
500.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
return_fan_part_load_power_coefficients
Return Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:DualDuct

HVACTemplate:System:PackagedVAV

from idfpy.models import HVACTemplateSystemPackagedVAV

Packaged Variable Air Volume (PVAV) air loop with optional heating coil and optional preheat.

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; PVAV System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_maximum_flow_rate
Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_minimum_flow_rate
Supply Fan Minimum Flow Rate
number or Autosize
m3/s
Autosize This field is only used to set a minimum part load on the VAV fan power curve. Autosize or zero is recommended.
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice TwoSpeedDX One of TwoSpeedDX, TwoSpeedHumidControlDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_schedule_name
Cooling Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_design_setpoint
Cooling Coil Design Setpoint
number
C
12.8 Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified.
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Gross SHR
cooling_coil_gross_rated_cop
Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input
Range: > 0
heating_coil_type
Heating Coil Type
choice None One of Electric, Gas, HotWater, None
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_schedule_name
Heating Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
10.0 Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified.
heating_coil_capacity
Heating Coil Capacity
number or Autosize
W
Autosize
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_control_type
Minimum Outdoor Air Control Type
choice ProportionalMinimum One of FixedMinimum, ProportionalMinimum
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of LockoutWithCompressor, LockoutWithHeating, NoLockout
economizer_maximum_limit_dry_bulb_temperature
Economizer Maximum Limit Dry-Bulb Temperature
number
C
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_maximum_limit_enthalpy
Economizer Maximum Limit Enthalpy
number
J/kg
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_minimum_limit_dry_bulb_temperature
Economizer Minimum Limit Dry-Bulb Temperature
number
C
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
supply_fan_part_load_power_coefficients
Supply Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Range: ≥ 0, ≤ 1
cooling_coil_setpoint_reset_type
Cooling Coil Setpoint Reset Type
choice None Overrides Cooling Coil Setpoint Schedule Name None = no reset, control to Cooling Coil Design Setpoint Temperature or Schedule Warmest = reset as warm as possible yet meet all zone cooling loads at max supply air flow rate OutdoorAirTemperatureReset = reset based on outdoor air temperature (18.0C at 15.6C ODB, to the Cooling Design Setpoint at 26.7C) WarmestTemperatureFirst = reset as warm as possible yet meet all zone cooling loads at min supply air flow rate
One of None, OutdoorAirTemperatureReset, Warmest, WarmestTemperatureFirst
heating_coil_setpoint_reset_type
Heating Coil Setpoint Reset Type
choice None Overrides Heating Coil Setpoint Schedule Name None = no reset, control to Heating Coil Design Setpoint Temperature or Schedule OutdoorAirTemperatureReset = reset based on outdoor air temperature (Heating Design Setpoint at -6.7C ODB to Heating Design Setpoint minus 5.2C at 10C ODB) min supply air flow rate
One of None, OutdoorAirTemperatureReset
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint.
One of CoolReheat, None
dehumidification_control_zone_name
Dehumidification Control Zone Name
reference Zone name where humidistat is located
Names a Zone
dehumidification_setpoint
Dehumidification Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_setpoint
Humidifier Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
sizing_option
Sizing Option
choice NonCoincident Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates.
One of Coincident, NonCoincident
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
500.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
return_fan_part_load_power_coefficients
Return Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
Referenced by 4 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool

HVACTemplate:System:Unitary

from idfpy.models import HVACTemplateSystemUnitary

Unitary furnace with air conditioner

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; Unitary System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_zone_or_thermostat_location_name
Control Zone or Thermostat Location Name required
reference Names a Zone
supply_fan_maximum_flow_rate
Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
600.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice SingleSpeedDX One of None, SingleSpeedDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_design_supply_air_temperature
Cooling Design Supply Air Temperature
number
C
12.8 Used for sizing.
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Gross SHR
cooling_coil_gross_rated_cop
Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electric power
Range: > 0
heating_coil_type
Heating Coil Type required
choice One of Electric, Gas, HotWater
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_design_supply_air_temperature
Heating Design Supply Air Temperature
number
C
50.0 Used for sizing.
heating_coil_capacity
Heating Coil Capacity
number or Autosize
W
Autosize
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the minimum outdoor air flow rate If blank, always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of LockoutWithCompressor, LockoutWithHeating, NoLockout
economizer_upper_temperature_limit
Economizer Upper Temperature Limit
number
C
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_lower_temperature_limit
Economizer Lower Temperature Limit
number
C
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_upper_enthalpy_limit
Economizer Upper Enthalpy Limit
number
J/kg
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum serves all zones on this system. Blank if none.
Names a Zone
supply_fan_placement
Supply Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Applicable only if Heat Recovery Type is Enthalpy.
Range: ≥ 0, ≤ 1
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible cooling load only CoolReheatHeatingCoil = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with main heating coil. CoolReheatDesuperheater = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint, reheat with desuperheater coil.
One of CoolReheatDesuperheater, CoolReheatHeatingCoil, None
dehumidification_setpoint
Dehumidification Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_setpoint
Humidifier Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
500.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary

HVACTemplate:System:UnitaryHeatPump:AirToAir

from idfpy.models import HVACTemplateSystemUnitaryHeatPumpAirToAir

Unitary furnace with electric air-to-air heat pump

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; Unitary System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_zone_or_thermostat_location_name
Control Zone or Thermostat Location Name required
reference Names a Zone
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is Continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_placement
Supply Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
600.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice SingleSpeedDX One of SingleSpeedDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_design_supply_air_temperature
Cooling Design Supply Air Temperature
number
C
12.8 Used for sizing.
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
cooling_coil_gross_rated_cop
Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input
Range: > 0
heat_pump_heating_coil_type
Heat Pump Heating Coil Type
choice SingleSpeedDXHeatPump One of SingleSpeedDXHeatPump
heat_pump_heating_coil_availability_schedule_name
Heat Pump Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_design_supply_air_temperature
Heating Design Supply Air Temperature
number
C
50.0 Used for sizing.
heat_pump_heating_coil_gross_rated_capacity
Heat Pump Heating Coil Gross Rated Capacity
number or Autosize
W
Autosize Rated heating capacity excluding the effect of supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
heat_pump_heating_coil_rated_cop
Heat Pump Heating Coil Rated COP
number
W/W
2.75 Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy. Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
Range: > 0
heat_pump_heating_minimum_outdoor_dry_bulb_temperature
Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature
number
C
-8.0 Range: ≥ -20
heat_pump_defrost_maximum_outdoor_dry_bulb_temperature
Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature
number
C
5.0 Range: ≥ 0, ≤ 7.22
heat_pump_defrost_strategy
Heat Pump Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
heat_pump_defrost_control
Heat Pump Defrost Control
choice Timed One of OnDemand, Timed
heat_pump_defrost_time_period_fraction
Heat Pump Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if Timed defrost control is specified
Range: ≥ 0
supplemental_heating_coil_type
Supplemental Heating Coil Type
choice Electric One of Electric, Gas, HotWater
supplemental_heating_coil_availability_schedule_name
Supplemental Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supplemental_heating_coil_capacity
Supplemental Heating Coil Capacity
number or Autosize
W
Autosize
supplemental_heating_coil_maximum_outdoor_dry_bulb_temperature
Supplemental Heating Coil Maximum Outdoor Dry-Bulb Temperature
number
C
21.0 Supplemental heater will not operate when outdoor temperature exceeds this value.
Range: ≤ 21
supplemental_gas_heating_coil_efficiency
Supplemental Gas Heating Coil Efficiency
number 0.8 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0, ≤ 1
supplemental_gas_heating_coil_parasitic_electric_load
Supplemental Gas Heating Coil Parasitic Electric Load
number
W
0.0 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the minimum outdoor air flow rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of LockoutWithCompressor, LockoutWithHeating, NoLockout
economizer_maximum_limit_dry_bulb_temperature
Economizer Maximum Limit Dry-Bulb Temperature
number
C
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_maximum_limit_enthalpy
Economizer Maximum Limit Enthalpy
number
J/kg
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_minimum_limit_dry_bulb_temperature
Economizer Minimum Limit Dry-Bulb Temperature
number
C
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum serves all zones on this system. Blank if none.
Names a Zone
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Applicable only if Heat Recovery Type is Enthalpy.
Range: ≥ 0, ≤ 1
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_setpoint
Humidifier Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
500.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary

HVACTemplate:System:UnitarySystem

from idfpy.models import HVACTemplateSystemUnitarySystem

Unitary HVAC system with optional cooling and heating. Supports DX and chilled water, cooling, gas, electric, and hot water heating, air-to-air and water-to-air heat pumps.

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always available. Also see Supply Fan Operating Mode Schedule Name field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_type
Control Type
choice Load Load control requires a Controlling Zone name. SetPoint control requires set points at coil outlet nodes. The user must add appropriate SetpointManager objects to the idf file.
One of Load, SetPoint
control_zone_or_thermostat_location_name
Control Zone or Thermostat Location Name
reference This field is required if Control Type is Load.
Names a Zone
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is Continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_placement
Supply Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
600.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice SingleSpeedDX One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater, HeatExchangerAssistedDX, MultiSpeedDX, None, SingleSpeedDX, SingleSpeedDXWaterCooled, TwoSpeedDX, TwoStageDX, TwoStageHumidityControlDX
number_of_speeds_for_cooling
Number of Speeds for Cooling
integer 1 Used only for Cooling Coil Type = MultiSpeedDX.
Range: ≥ 0, ≤ 4
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_design_supply_air_temperature
Cooling Design Supply Air Temperature
number
C
12.8 Used for sizing.
dx_cooling_coil_gross_rated_total_capacity
DX Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
dx_cooling_coil_gross_rated_sensible_heat_ratio
DX Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
dx_cooling_coil_gross_rated_cop
DX Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input
Range: > 0
heating_coil_type
Heating Coil Type
choice Gas One of Electric, Gas, HotWater, MultiSpeedDXHeatPumpAirSource, MultiStageElectric, MultiStageGas, None, SingleSpeedDXHeatPumpAirSource, SingleSpeedDXHeatPumpWaterSource
number_of_speeds_or_stages_for_heating
Number of Speeds or Stages for Heating
integer 1 Used only for Heating Coil Type = MultiSpeedDXHeatPumpAirSource), MultiStageElectric, or MultiStageGas.
Range: ≥ 0, ≤ 4
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_design_supply_air_temperature
Heating Design Supply Air Temperature
number
C
50.0 Used for sizing.
heating_coil_gross_rated_capacity
Heating Coil Gross Rated Capacity
number or Autosize
W
Autosize Rated heating capacity excluding the effect of supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
heat_pump_heating_coil_gross_rated_cop
Heat Pump Heating Coil Gross Rated COP
number
W/W
2.75 Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy. Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C Applies only to DX coils
Range: > 0
heat_pump_heating_minimum_outdoor_dry_bulb_temperature
Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature
number
C
-8.0 Range: ≥ -20
heat_pump_defrost_maximum_outdoor_dry_bulb_temperature
Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature
number
C
5.0 Range: ≥ 0, ≤ 7.22
heat_pump_defrost_strategy
Heat Pump Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
heat_pump_defrost_control
Heat Pump Defrost Control
choice Timed One of OnDemand, Timed
heat_pump_defrost_time_period_fraction
Heat Pump Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if Timed defrost control is specified
Range: ≥ 0
supplemental_heating_or_reheat_coil_type
Supplemental Heating or Reheat Coil Type
choice None One of DesuperHeater, Electric, Gas, HotWater, None
supplemental_heating_or_reheat_coil_availability_schedule_name
Supplemental Heating or Reheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supplemental_heating_or_reheat_coil_capacity
Supplemental Heating or Reheat Coil Capacity
number or Autosize
W
Autosize
supplemental_heating_or_reheat_coil_maximum_outdoor_dry_bulb_temperature
Supplemental Heating or Reheat Coil Maximum Outdoor Dry-Bulb Temperature
number
C
21.0 Supplemental heater will not operate when outdoor temperature exceeds this value.
Range: ≤ 21
supplemental_gas_heating_or_reheat_coil_efficiency
Supplemental Gas Heating or Reheat Coil Efficiency
number 0.8 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0, ≤ 1
supplemental_gas_heating_or_reheat_coil_parasitic_electric_load
Supplemental Gas Heating or Reheat Coil Parasitic Electric Load
number
W
0.0 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the minimum outdoor air flow rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of LockoutWithCompressor, LockoutWithHeating, NoLockout
economizer_maximum_limit_dry_bulb_temperature
Economizer Maximum Limit Dry-Bulb Temperature
number
C
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_maximum_limit_enthalpy
Economizer Maximum Limit Enthalpy
number
J/kg
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_minimum_limit_dry_bulb_temperature
Economizer Minimum Limit Dry-Bulb Temperature
number
C
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum serves all zones on this system. Blank if none.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Applicable only if Heat Recovery Type is Enthalpy.
Range: ≥ 0, ≤ 1
heat_recovery_heat_exchanger_type
Heat Recovery Heat Exchanger Type
choice Plate One of Plate, Rotary
heat_recovery_frost_control_type
Heat Recovery Frost Control Type
choice None One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint, reheat with reheat coil If no reheat coil specified, cold supply temps may occur. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only for Cooling Coil Type = TwoStageHumidityControlDX or HeatExchangerAssistedDX
One of CoolReheat, Multimode, None
dehumidification_relative_humidity_setpoint
Dehumidification Relative Humidity Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100) Ignored if Dehumidification Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
dehumidification_relative_humidity_setpoint_schedule_name
Dehumidification Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Dehumidification Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_relative_humidity_setpoint
Humidifier Relative Humidity Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100). Ignored if Humidifier Relative Humidity Setpoint Schedule specified below
Range: ≥ 0, ≤ 100
humidifier_relative_humidity_setpoint_schedule_name
Humidifier Relative Humidity Setpoint Schedule Name
reference Leave blank to use constant setpoint specified in Humidifier Relative Humidity Setpoint above. Schedule values must be in percent relative humidity (0 to 100).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
sizing_option
Sizing Option
choice NonCoincident Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates.
One of Coincident, NonCoincident
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
300.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:Unitary

HVACTemplate:System:VAV

from idfpy.models import HVACTemplateSystemVAV

Variable Air Volume (VAV) air loop with optional heating coil and optional preheat.

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on; VAV System always on. Schedule is used in availability manager and fan scheduling. Also see "Night Cycle Control" field.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_maximum_flow_rate
Supply Fan Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers a value entered here must be large enough to serve the multiplied zones.
supply_fan_minimum_flow_rate
Supply Fan Minimum Flow Rate
number or Autosize
m3/s
Autosize This field is only used to set a minimum part load on the VAV fan power curve. Autosize or zero is recommended.
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice ChilledWater One of ChilledWater, ChilledWaterDetailedFlatModel
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_setpoint_schedule_name
Cooling Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_design_setpoint
Cooling Coil Design Setpoint
number
C
12.8 Used for sizing and as constant setpoint if no Cooling Coil Setpoint Schedule Name is specified.
heating_coil_type
Heating Coil Type
choice None One of Electric, Gas, HotWater, None
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_setpoint_schedule_name
Heating Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
10.0 Used for sizing and as constant setpoint if no Heating Coil Setpoint Schedule Name is specified.
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
preheat_coil_type
Preheat Coil Type
choice None One of Electric, Gas, HotWater, None
preheat_coil_availability_schedule_name
Preheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
preheat_coil_setpoint_schedule_name
Preheat Coil Setpoint Schedule Name
reference Leave blank if constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
preheat_coil_design_setpoint
Preheat Coil Design Setpoint
number
C
7.2 Used for sizing and as constant setpoint if no Preheat Coil Setpoint Schedule Name specified.
gas_preheat_coil_efficiency
Gas Preheat Coil Efficiency
number 0.8 Range: ≥ 0, ≤ 1
gas_preheat_coil_parasitic_electric_load
Gas Preheat Coil Parasitic Electric Load
number
W
0.0 Range: ≥ 0
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
minimum_outdoor_air_control_type
Minimum Outdoor Air Control Type
choice ProportionalMinimum One of FixedMinimum, ProportionalMinimum
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the Minimum Outdoor Air Flow Rate If blank, multiplier is always one
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
economizer_type
Economizer Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_lockout
Economizer Lockout
choice NoLockout One of NoLockout
economizer_upper_temperature_limit
Economizer Upper Temperature Limit
number
C
Outdoor temperature above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_lower_temperature_limit
Economizer Lower Temperature Limit
number
C
Outdoor temperature below which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_upper_enthalpy_limit
Economizer Upper Enthalpy Limit
number
J/kg
Outdoor enthalpy above which economizer is disabled and heat recovery is enabled (if available). Blank means no limit.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Supply plenum serves all zones on this system. Blank if none.
Names a Zone
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
supply_fan_part_load_power_coefficients
Supply Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
night_cycle_control
Night Cycle Control
choice StayOff One of CycleOnAny, CycleOnAnyZoneFansOnly, CycleOnControlZone, StayOff
night_cycle_control_zone_name
Night Cycle Control Zone Name
reference Applicable only if Night Cycle Control is Cycle On Control Zone.
Names a Zone
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number 0.65 Range: ≥ 0, ≤ 1
cooling_coil_setpoint_reset_type
Cooling Coil Setpoint Reset Type
choice None Overrides Cooling Coil Setpoint Schedule Name None = no reset, control to Cooling Coil Design Setpoint Temperature or Schedule Warmest = reset as warm as possible yet meet all zone cooling loads at max supply air flow rate OutdoorAirTemperatureReset = reset based on outdoor air temperature (18.0C at 15.6C ODB, to the Cooling Design Setpoint at 26.7C) WarmestTemperatureFirst = reset as warm as possible yet meet all zone cooling loads at min supply air flow rate
One of None, OutdoorAirTemperatureReset, Warmest, WarmestTemperatureFirst
heating_coil_setpoint_reset_type
Heating Coil Setpoint Reset Type
choice None Overrides Heating Coil Setpoint Schedule Name None = no reset, control to Heating Coil Design Setpoint Temperature or Schedule OutdoorAirTemperatureReset = reset based on outdoor air temperature (Heating Design Setpoint at -6.7C ODB to Heating Design Setpoint minus 5.2C at 10C ODB) min supply air flow rate
One of None, OutdoorAirTemperatureReset
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint.
One of CoolReheat, None
dehumidification_control_zone_name
Dehumidification Control Zone Name
reference Zone name where humidistat is located
Names a Zone
dehumidification_setpoint
Dehumidification Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
humidifier_type
Humidifier Type
choice None One of ElectricSteam, None
humidifier_availability_schedule_name
Humidifier Availability Schedule Name
reference If blank, always available
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
humidifier_rated_capacity
Humidifier Rated Capacity
number
m3/s
1e-06 Moisture output rate at full rated power input. The humidifier does not currently autosize, so the default is very large to allow for adequate capacity.
Range: ≥ 0
humidifier_rated_electric_power
Humidifier Rated Electric Power
number or Autosize
W
Autosize Electric power input at rated capacity moisture output. Power consumption is proportional to moisture output with no part-load penalty.
humidifier_control_zone_name
Humidifier Control Zone Name
reference Zone name where humidistat is located
Names a Zone
humidifier_setpoint
Humidifier Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
sizing_option
Sizing Option
choice NonCoincident Select whether autosized system supply flow rate is the sum of Coincident or NonCoincident zone air flow rates.
One of Coincident, NonCoincident
return_fan
Return Fan
choice No Specifies if the system has a return fan.
One of No, Yes
return_fan_total_efficiency
Return Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
return_fan_delta_pressure
Return Fan Delta Pressure
number
Pa
500.0 Range: ≥ 0
return_fan_motor_efficiency
Return Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
return_fan_motor_in_air_stream_fraction
Return Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
return_fan_part_load_power_coefficients
Return Fan Part-Load Power Coefficients
choice InletVaneDampers This field selects a predefined set of fan power coefficients. The ASHRAE 90.1-2004 Appendix G coefficients are from TABLE G3.1.3.15, Method 2. The other sets of coefficients are from the EnergyPlus Input Output Reference, Fan Coefficient Values table.
One of ASHRAE90.1-2004AppendixG, InletVaneDampers, OutletDampers, VariableSpeedMotor, VariableSpeedMotorPressureReset
Referenced by 4 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool

HVACTemplate:System:VRF

from idfpy.models import HVACTemplateSystemVRF

Variable refrigerant flow (VRF) heat pump condensing unit. Serves one or more VRF zone terminal units (HVACTemplate:Zone:VRF).

Field Type Default Details
name
Name required
string
system_availability_schedule_name
System Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity
number or Autosize
W
Autosize Enter the total cooling capacity in watts at rated conditions or set to autosize. Total cooling capacity not accounting for the effect of supply air fan heat
gross_rated_cooling_cop
Gross Rated Cooling COP
number
W/W
3.3 Enter the coefficient of performance at rated conditions or leave blank to use default. COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electric power input
Range: > 0
minimum_outdoor_temperature_in_cooling_mode
Minimum Outdoor Temperature in Cooling Mode
number
C
-6.0 Enter the minimum outdoor temperature allowed for cooling operation. Cooling is disabled below this temperature.
maximum_outdoor_temperature_in_cooling_mode
Maximum Outdoor Temperature in Cooling Mode
number
C
43.0 Enter the maximum outdoor temperature allowed for cooling operation. Cooling is disabled above this temperature.
gross_rated_heating_capacity
Gross Rated Heating Capacity
number or Autosize
W
Autosize Enter the heating capacity in watts at rated conditions or set to autosize. Heating capacity not accounting for the effect of supply air fan heat
rated_heating_capacity_sizing_ratio
Rated Heating Capacity Sizing Ratio
number
W/W
1.0 If the Gross Rated Heating Capacity is autosized, the heating capacity is sized to be equal to the cooling capacity multiplied by this sizing ratio. The zone terminal unit heating coils are also sized using this ratio unless the sizing ratio input in the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object is entered.
Range: ≥ 1
gross_rated_heating_cop
Gross Rated Heating COP
number
W/W
3.4 COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electrical energy input
Range: > 0
minimum_outdoor_temperature_in_heating_mode
Minimum Outdoor Temperature in Heating Mode
number
C
-20.0 Enter the minimum outdoor temperature allowed for heating operation.
maximum_outdoor_temperature_in_heating_mode
Maximum Outdoor Temperature in Heating Mode
number
C
16.0 Enter the maximum outdoor temperature allowed for heating operation.
minimum_heat_pump_part_load_ratio
Minimum Heat Pump Part-Load Ratio
number
dimensionless
0.15 Enter the minimum heat pump part-load ratio (PLR). When the cooling or heating PLR is below this value, the heat pump compressor will cycle to meet the cooling or heating demand.
zone_name_for_master_thermostat_location
Zone Name for Master Thermostat Location
reference Enter the name of the zone where the master thermostat is located.
Names a Zone
master_thermostat_priority_control_type
Master Thermostat Priority Control Type
choice MasterThermostatPriority Choose a thermostat control logic scheme. If these control types fail to control zone temperature within a reasonable limit, consider using multiple VRF systems
One of LoadPriority, MasterThermostatPriority, Scheduled, ThermostatOffsetPriority, ZonePriority
thermostat_priority_schedule_name
Thermostat Priority Schedule Name
reference this field is required if Master Thermostat Priority Control Type is Scheduled. Schedule values of 0 denote cooling, 1 for heating, and all other values disable the system.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_pump_waste_heat_recovery
Heat Pump Waste Heat Recovery
choice No This field is reserved for future use. The only valid choice is No.
One of No, Yes
equivalent_piping_length_used_for_piping_correction_factor_in_cooling_mode
Equivalent Piping Length used for Piping Correction Factor in Cooling Mode
number
m
30.0 Enter the equivalent length of the farthest terminal unit from the condenser
vertical_height_used_for_piping_correction_factor
Vertical Height used for Piping Correction Factor
number
m
10.0 Enter the height difference between the highest and lowest terminal unit
equivalent_piping_length_used_for_piping_correction_factor_in_heating_mode
Equivalent Piping Length used for Piping Correction Factor in Heating Mode
number
m
30.0 Enter the equivalent length of the farthest terminal unit from the condenser
crankcase_heater_power_per_compressor
Crankcase Heater Power per Compressor
number
W
33.0 Enter the value of the resistive heater located in the compressor(s). This heater is used to warm the refrigerant and oil when the compressor is off.
number_of_compressors
Number of Compressors
integer
dimensionless
2 Enter the total number of compressor. This input is used only for crankcase heater calculations.
ratio_of_compressor_size_to_total_compressor_capacity
Ratio of Compressor Size to Total Compressor Capacity
number
W/W
0.5 Enter the ratio of the first stage compressor to total compressor capacity. All other compressors are assumed to be equally sized. This inputs is used only for crankcase heater calculations.
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater
Maximum Outdoor Dry-bulb Temperature for Crankcase Heater
number
C
5.0 Enter the maximum outdoor temperature above which the crankcase heaters are disabled.
defrost_strategy
Defrost Strategy
choice Resistive Select a defrost strategy. Reverse cycle reverses the operating mode from heating to cooling to melt frost formation on the condenser coil. The resistive strategy uses a resistive heater to melt the frost.
One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed Choose a defrost control type. Either use a fixed Timed defrost period or select OnDemand to defrost only when necessary.
One of OnDemand, Timed
defrost_time_period_fraction
Defrost Time Period Fraction
number
dimensionless
0.058333 Fraction of time in defrost mode. Only applicable if timed defrost control is specified.
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
Autosize Enter the size of the resistive defrost heating element. Only applicable if resistive defrost strategy is specified
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-bulb Temperature for Defrost Operation
number
C
5.0 Enter the maximum outdoor temperature above which defrost operation is disabled.
condenser_type
Condenser Type
choice AirCooled Select either an air cooled or evaporatively cooled condenser.
One of AirCooled, EvaporativelyCooled, WaterCooled
water_condenser_volume_flow_rate
Water Condenser Volume Flow Rate
number or Autosize
m3/s
Autosize Only used when Condenser Type = WaterCooled.
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Enter the effectiveness of the evaporatively cooled condenser. This field is only used when the Condenser Type = EvaporativelyCooled.
Range: ≥ 0, ≤ 1
evaporative_condenser_air_flow_rate
Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Autosize Used to calculate evaporative condenser water use. This field is only used when the Condenser Type = EvaporativelyCooled.
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump. This field is only used when the Condenser Type = EvaporativelyCooled.
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fuel_type
Fuel Type
choice Electricity One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
minimum_outdoor_temperature_in_heat_recovery_mode
Minimum Outdoor Temperature in Heat Recovery Mode
number
C
-15.0 The minimum outdoor temperature below which heat recovery mode will not operate.
maximum_outdoor_temperature_in_heat_recovery_mode
Maximum Outdoor Temperature in Heat Recovery Mode
number
C
45.0 The maximum outdoor temperature above which heat recovery mode will not operate.
Referenced by 2 object types

AvailabilityManager:HybridVentilation, HVACTemplate:Zone:VRF

HVACTemplate:Thermostat

from idfpy.models import HVACTemplateThermostat

Zone thermostat control. Referenced schedules must be defined elsewhere in the idf. Thermostat control type is dual setpoint with deadband. It is not necessary to create a thermostat object for every zone, only for each unique set of setpoint schedules. For example, an office building may have two thermostat objects, one for "Office" and one for "Storage".

Field Type Default Details
name
Name required
string This name is referenced by HVACTemplate:Zone:* objects
heating_setpoint_schedule_name
Heating Setpoint Schedule Name
reference Leave blank if constant setpoint specified below, must enter schedule or constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
constant_heating_setpoint
Constant Heating Setpoint
number
C
Ignored if schedule specified above, must enter schedule or constant setpoint
cooling_setpoint_schedule_name
Cooling Setpoint Schedule Name
reference Leave blank if constant setpoint specified below, must enter schedule or constant setpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
constant_cooling_setpoint
Constant Cooling Setpoint
number
C
Ignored if schedule specified above, must enter schedule or constant setpoint
Referenced by 13 object types

HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:ConstantVolume, HVACTemplate:Zone:DualDuct, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:IdealLoadsAirSystem, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:Unitary, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump

HVACTemplate:Zone:BaseboardHeat

from idfpy.models import HVACTemplateZoneBaseboardHeat

Zone baseboard heating system.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
baseboard_heating_type
Baseboard Heating Type
choice HotWater One of Electric, HotWater
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution

HVACTemplate:Zone:ConstantVolume

from idfpy.models import HVACTemplateZoneConstantVolume

Zone terminal unit, constant volume, reheat optional. Referenced schedules must be defined elsewhere in the idf.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_constant_volume_system_name
Template Constant Volume System Name required
reference Name of a HVACTemplate:System:ConstantVolume object serving this zone
Names a HVACTemplate:System:ConstantVolume
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
reheat_coil_type
Reheat Coil Type
choice None One of Electric, Gas, HotWater, None
reheat_coil_availability_schedule_name
Reheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum runs through only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum runs through only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature
Referenced by 1 object types

HVACTemplate:System:ConstantVolume

HVACTemplate:Zone:DualDuct

from idfpy.models import HVACTemplateZoneDualDuct

Zone terminal unit, dual-duct, constant or variable volume.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_dual_duct_system_name
Template Dual Duct System Name required
reference Name of a HVACTemplate:System:DualDuct object serving this zone
Names a HVACTemplate:System:DualDuct
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_minimum_air_flow_fraction
Zone Minimum Air Flow Fraction
number 0.2 This field is the Zone Minimum Air Flow Fraction specified as a fraction of the maximum air flow rate. This field is ignored if the system serving this zone is constant volume.
Range: ≥ 0, ≤ 1
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name_for_sizing
Design Specification Outdoor Air Object Name for Sizing
reference This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
design_specification_outdoor_air_object_name_for_control
Design Specification Outdoor Air Object Name for Control
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow. Note that this field is used only for specifying the design outdoor air flow rate used for control. The field Design Specification Outdoor Air Object Name for Sizing (see below) is used to specify the design outdoor air flow rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
cold_supply_plenum_name
Cold Supply Plenum Name
reference Plenum zone name. Cold supply plenum that serves only this zone. Blank if none.
Names a Zone
hot_supply_plenum_name
Hot Supply Plenum Name
reference Plenum zone name. Hot supply plenum that serves only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum that serves only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:DualDuct Cooling Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:DualDuct Heating Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.

HVACTemplate:Zone:FanCoil

from idfpy.models import HVACTemplateZoneFanCoil

4 pipe fan coil unit with optional outdoor air.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
75.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_fan_motor_in_air_stream_fraction
Supply Fan Motor in Air Stream Fraction
number 1.0 Range: ≥ 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice ChilledWater One of ChilledWater, ChilledWaterDetailedFlatModel, HeatExchangerAssistedChilledWater
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_design_setpoint
Cooling Coil Design Setpoint
number
C
14.0 Used for sizing when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
heating_coil_type
Heating Coil Type
choice HotWater One of Electric, HotWater
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_design_setpoint
Heating Coil Design Setpoint
number
C
50.0 Used for sizing when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Cooling Coil Design Setpoint (above) TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Heating Coil Design Setpoint (above) TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
capacity_control_method
Capacity Control Method
choice If this field is left blank, it will default to CyclingFan if a Dedicated Outdoor Air System is specified (see above), otherwise it will default to ConstantFanVariableFlow.
One of ASHRAE90VariableFan, ConstantFanVariableFlow, CyclingFan, MultiSpeedFan, VariableFanConstantFlow, VariableFanVariableFlow
low_speed_supply_air_flow_ratio
Low Speed Supply Air Flow Ratio
number 0.33 Range: > 0
medium_speed_supply_air_flow_ratio
Medium Speed Supply Air Flow Ratio
number 0.66 Medium Speed Supply Air Flow Ratio should be greater than Low Speed Supply Air Flow Ratio
Range: > 0
outdoor_air_schedule_name
Outdoor Air Schedule Name
reference Value of schedule multiplies maximum outdoor air flow rate This schedule is ignored if this zone is served by an HVACTemplate dedicated outdoor air system.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize

HVACTemplate:Zone:IdealLoadsAirSystem

from idfpy.models import HVACTemplateZoneIdealLoadsAirSystem

Zone with ideal air system that meets heating or cooling loads

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_heating_supply_air_temperature
Maximum Heating Supply Air Temperature
number
C
50.0 Range: > 0, < 100
minimum_cooling_supply_air_temperature
Minimum Cooling Supply Air Temperature
number
C
13.0 Range: > -100, < 50
maximum_heating_supply_air_humidity_ratio
Maximum Heating Supply Air Humidity Ratio
number
kgWater/kgDryAir
0.0156 Range: > 0
minimum_cooling_supply_air_humidity_ratio
Minimum Cooling Supply Air Humidity Ratio
number
kgWater/kgDryAir
0.0077 Range: > 0
heating_limit
Heating Limit
choice NoLimit One of LimitCapacity, LimitFlowRate, LimitFlowRateAndCapacity, NoLimit
maximum_heating_air_flow_rate
Maximum Heating Air Flow Rate
number or Autosize
m3/s
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit.
maximum_sensible_heating_capacity
Maximum Sensible Heating Capacity
number or Autosize
W
This field is ignored if Heating Limit = NoLimit If this field is blank, there is no limit.
cooling_limit
Cooling Limit
choice NoLimit One of LimitCapacity, LimitFlowRate, LimitFlowRateAndCapacity, NoLimit
maximum_cooling_air_flow_rate
Maximum Cooling Air Flow Rate
number or Autosize
m3/s
This field is ignored if Cooling Limit = NoLimit This field is required if Outdoor Air Economizer Type is anything other than NoEconomizer.
maximum_total_cooling_capacity
Maximum Total Cooling Capacity
number or Autosize
W
This field is ignored if Cooling Limit = NoLimit
heating_availability_schedule_name
Heating Availability Schedule Name
reference If blank, heating is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_availability_schedule_name
Cooling Availability Schedule Name
reference If blank, cooling is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dehumidification_control_type
Dehumidification Control Type
choice ConstantSensibleHeatRatio ConstantSensibleHeatRatio means that the ideal loads system will be controlled to meet the sensible cooling load, and the latent cooling rate will be computed using a constant sensible heat ratio (SHR) Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. None means that there is no dehumidification. ConstantSupplyHumidityRatio means that during cooling the supply air will always be at the Minimum Cooling Supply Humidity Ratio.
One of ConstantSensibleHeatRatio, ConstantSupplyHumidityRatio, Humidistat, None
cooling_sensible_heat_ratio
Cooling Sensible Heat Ratio
number
dimensionless
0.7 This field is applicable only when Dehumidification Control Type is ConstantSensibleHeatRatio
Range: > 0, ≤ 1
dehumidification_setpoint
Dehumidification Setpoint
number
percent
60.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
humidification_control_type
Humidification Control Type
choice None None means that there is no humidification. Humidistat means that there is a ZoneControl:Humidistat for this zone and the ideal loads system will attempt to satisfy the humidistat. ConstantSupplyHumidityRatio means that during heating the supply air will always be at the Maximum Heating Supply Humidity Ratio.
One of ConstantSupplyHumidityRatio, Humidistat, None
humidification_setpoint
Humidification Setpoint
number
percent
30.0 Zone relative humidity setpoint in percent (0 to 100)
Range: ≥ 0, ≤ 100
outdoor_air_method
Outdoor Air Method
choice None None means there is no outdoor air and all related fields will be ignored Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, None, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference When the name of a DesignSpecification:OutdoorAir object is entered, the minimum outdoor air flow rate will be computed using these specifications. The outdoor air flow rate will also be affected by the next two fields. If this field is blank, there will be no outdoor air and the remaining fields will be ignored.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
demand_controlled_ventilation_type
Demand Controlled Ventilation Type
choice None This field controls how the minimum outdoor air flow rate is calculated. None means that design occupancy will be used to compute the minimum outdoor air flow rate OccupancySchedule means that current occupancy level will be used. CO2Setpoint means that the design occupancy will be used to compute the minimum outdoor air flow rate and the outdoor air flow rate may be increased if necessary to maintain the indoor air carbon dioxide setpoint defined in a ZoneControl:ContaminantController object.
One of CO2Setpoint, None, OccupancySchedule
outdoor_air_economizer_type
Outdoor Air Economizer Type
choice NoEconomizer DifferentialDryBulb and DifferentialEnthalpy will increase the outdoor air flow rate when there is a cooling load and the outdoor air temperature or enthalpy is below the zone exhaust air temperature or enthalpy.
One of DifferentialDryBulb, DifferentialEnthalpy, NoEconomizer
heat_recovery_type
Heat Recovery Type
choice None One of Enthalpy, None, Sensible
sensible_heat_recovery_effectiveness
Sensible Heat Recovery Effectiveness
number
dimensionless
0.7 Range: ≥ 0, ≤ 1
latent_heat_recovery_effectiveness
Latent Heat Recovery Effectiveness
number
dimensionless
0.65 Applicable only if Heat Recovery Type is Enthalpy.
Range: ≥ 0, ≤ 1

HVACTemplate:Zone:PTAC

from idfpy.models import HVACTemplateZonePTAC

Packaged Terminal Air Conditioner

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule Name values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
75.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice SingleSpeedDX One of SingleSpeedDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
cooling_coil_gross_rated_cooling_cop
Cooling Coil Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
heating_coil_type
Heating Coil Type
choice Electric One of Electric, Gas, HotWater
heating_coil_availability_schedule_name
Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_capacity
Heating Coil Capacity
number or Autosize
W
Autosize
gas_heating_coil_efficiency
Gas Heating Coil Efficiency
number 0.8 Applies only if Heating Coil Type is Gas
Range: ≥ 0, ≤ 1
gas_heating_coil_parasitic_electric_load
Gas Heating Coil Parasitic Electric Load
number
W
0.0 Applies only if Heating Coil Type is Gas
Range: ≥ 0
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
14.0 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
capacity_control_method
Capacity Control Method
choice None One of None, SingleZoneVAV

HVACTemplate:Zone:PTHP

from idfpy.models import HVACTemplateZonePTHP

Packaged Terminal Heat Pump

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required and the DX coil compressor is off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
75.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice SingleSpeedDX One of SingleSpeedDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
cooling_coil_gross_rated_cop
Cooling Coil Gross Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
heat_pump_heating_coil_type
Heat Pump Heating Coil Type
choice SingleSpeedDXHeatPump One of SingleSpeedDXHeatPump
heat_pump_heating_coil_availability_schedule_name
Heat Pump Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_pump_heating_coil_gross_rated_capacity
Heat Pump Heating Coil Gross Rated Capacity
number or Autosize
W
Autosize Capacity excluding supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
heat_pump_heating_coil_gross_rated_cop
Heat Pump Heating Coil Gross Rated COP
number
W/W
2.75 Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, Does not include supply air fan heat or supply air fan electrical energy Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
Range: > 0
heat_pump_heating_minimum_outdoor_dry_bulb_temperature
Heat Pump Heating Minimum Outdoor Dry-Bulb Temperature
number
C
-8.0 Range: ≥ -20
heat_pump_defrost_maximum_outdoor_dry_bulb_temperature
Heat Pump Defrost Maximum Outdoor Dry-Bulb Temperature
number
C
5.0 Range: ≥ 0, ≤ 7.22
heat_pump_defrost_strategy
Heat Pump Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
heat_pump_defrost_control
Heat Pump Defrost Control
choice Timed One of OnDemand, Timed
heat_pump_defrost_time_period_fraction
Heat Pump Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if Timed defrost control is specified
Range: ≥ 0
supplemental_heating_coil_type
Supplemental Heating Coil Type
choice Electric One of Electric, Gas, HotWater
supplemental_heating_coil_availability_schedule_name
Supplemental Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supplemental_heating_coil_capacity
Supplemental Heating Coil Capacity
number or Autosize
W
Autosize
supplemental_heating_coil_maximum_outdoor_dry_bulb_temperature
Supplemental Heating Coil Maximum Outdoor Dry-Bulb Temperature
number
C
21.0 Supplemental heater will not operate when outdoor temperature exceeds this value.
Range: ≤ 21
supplemental_gas_heating_coil_efficiency
Supplemental Gas Heating Coil Efficiency
number 0.8 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0, ≤ 1
supplemental_gas_heating_coil_parasitic_electric_load
Supplemental Gas Heating Coil Parasitic Electric Load
number
W
0.0 Applies only if Supplemental Heating Coil Type is Gas
Range: ≥ 0
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
14.0 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
capacity_control_method
Capacity Control Method
choice None One of None, SingleZoneVAV

HVACTemplate:Zone:Unitary

from idfpy.models import HVACTemplateZoneUnitary

Zone terminal unit, constant volume, no controls.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_unitary_system_name
Template Unitary System Name required
reference Enter the name of an HVACTemplate:System:Unitary, HVACTemplate:System:UnitaryHeatPump:AirToAir, or HVACTemplate:System:UnitarySystem object serving this zone.
Names a HVACTemplate:System:Unitary, HVACTemplate:System:UnitaryHeatPump:AirToAir, HVACTemplate:System:UnitarySystem
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum runs through only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum runs through only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:Unitary or HVACTemplate:System:UnitaryHeatPump:AirToAir Cooling Design Supply Air Temperature
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:Unitary or HVACTemplate:System:UnitaryHeatPump:AirToAir Heating Design Supply Air Temperature
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution

HVACTemplate:Zone:VAV

from idfpy.models import HVACTemplateZoneVAV

Zone terminal unit, variable volume, reheat optional. For heating, this unit activates reheat coil first, then increases airflow (if reverse action specified).

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_vav_system_name
Template VAV System Name required
reference Name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone
Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_minimum_air_flow_input_method
Zone Minimum Air Flow Input Method
choice Constant Constant = Constant Minimum Air Flow Fraction (a fraction of Maximum Air Flow Rate) FixedFlowRate = Fixed Minimum Air Flow Rate (a fixed minimum air volume flow rate) Scheduled = Scheduled Minimum Air Flow Fraction (a fraction of Maximum Air Flow
One of Constant, FixedFlowRate, Scheduled
constant_minimum_air_flow_fraction
Constant Minimum Air Flow Fraction
number 0.2 This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used.
Range: ≥ 0, ≤ 1
fixed_minimum_air_flow_rate
Fixed Minimum Air Flow Rate
number
m3/s
This field is used if the field Zone Minimum Air Flow Input Method is FixedFlowRate. If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the previous field are entered, the larger result is used.
minimum_air_flow_fraction_schedule_name
Minimum Air Flow Fraction Schedule Name
reference This field is used if the field Zone Minimum Air Flow Input Method is Scheduled Schedule values are fractions, 0.0 to 1.0. If the field Constant Minimum Air Flow Fraction is blank, then the average of the minimum and maximum schedule values is used for sizing normal-action reheat coils.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
reheat_coil_type
Reheat Coil Type
choice None One of Electric, Gas, HotWater, None
reheat_coil_availability_schedule_name
Reheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
damper_heating_action
Damper Heating Action
choice Reverse One of Normal, Reverse
maximum_flow_per_zone_floor_area_during_reheat
Maximum Flow per Zone Floor Area During Reheat
number or Autocalculate
m3/s-m2
Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = Reverse When autocalculating, the maximum flow per zone is set to 0.002032 m3/s-m2 (0.4 cfm/sqft) This optional field limits the maximum flow allowed in reheat mode. If this field and the following field are left blank, the maximum flow will not be limited. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate.
maximum_flow_fraction_during_reheat
Maximum Flow Fraction During Reheat
number or Autocalculate Used only when Reheat Coil Object Type = Coil:Heating:Water and Damper Heating Action = Reverse When autocalculating, the maximum flow fraction is set to the ratio of 0.002032 m3/s-m2 (0.4 cfm/sqft) multiplied by the zone floor area and the Maximum Air Flow Rate. This optional field limits the maximum flow allowed in reheat mode. If this field and the previous field are left blank, the maximum flow will not be limited. At no time will the maximum flow rate calculated here exceed the value of Maximum Air Flow Rate.
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
design_specification_outdoor_air_object_name_for_control
Design Specification Outdoor Air Object Name for Control
reference When the name of a DesignSpecification:OutdoorAir object is entered, the terminal unit will increase flow as needed to meet this outdoor air requirement. If Outdoor Air Flow per Person is non-zero, then the outdoor air requirement will be computed based on the current number of occupants in the zone. At no time will the supply air flow rate exceed the value for Maximum Air Flow Rate. If this field is blank, then the terminal unit will not be controlled for outdoor air flow. Note that this field is used only for specifying the design outdoor air flow rate used for control. The field Design Specification Outdoor Air Object Name for Sizing (see below) is used to specify the design outdoor air flow rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum runs through only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum runs through only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
design_specification_outdoor_air_object_name_for_sizing
Design Specification Outdoor Air Object Name for Sizing
reference This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution

HVACTemplate:Zone:VAV:FanPowered

from idfpy.models import HVACTemplateZoneVAVFanPowered

Zone terminal unit, fan powered variable volume, reheat optional. Referenced schedules must be defined elsewhere in the idf.

Field Type Default Details
zone_name
Zone Name required
reference Zone Name must match a building zone name
Names a Zone
template_vav_system_name
Template VAV System Name required
reference Enter the name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone.
Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
primary_supply_air_maximum_flow_rate
Primary Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
primary_supply_air_minimum_flow_fraction
Primary Supply Air Minimum Flow Fraction
number or Autosize Autosize
secondary_supply_air_maximum_flow_rate
Secondary Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
flow_type
Flow Type
choice Parallel One of Parallel, ParallelFromPlenum, Series, SeriesFromPlenum
parallel_fan_on_flow_fraction
Parallel Fan On Flow Fraction
number or Autosize Autosize The fraction of the primary air flow at which fan turns on Applicable only to Parallel Flow Type
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
reheat_coil_type
Reheat Coil Type
choice Electric One of Electric, Gas, HotWater
reheat_coil_availability_schedule_name
Reheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fan_total_efficiency
Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
fan_delta_pressure
Fan Delta Pressure
number
Pa
1000.0 Range: ≥ 0
fan_motor_efficiency
Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum runs through only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum runs through only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
zone_piu_fan_schedule_name
Zone PIU Fan Schedule Name
reference This is the operating schedule for the zone PIU fan. For a parallel PIU, the fan operates only when the primary air flow is below the Parallel Fan On Flow Fraction and the Zone PIU Fan Schedule is on, or it is activated by an availability manager. For a series PIU, the zone fan operates whenever the Zone PIU Fan Schedule is on, or it is activated by an availability manager. If this field is left blank, the System Availability Schedule for the HVACTemplate:System serving this zone will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference Names a DesignSpecification:ZoneAirDistribution

HVACTemplate:Zone:VAV:HeatAndCool

from idfpy.models import HVACTemplateZoneVAVHeatAndCool

VAV system with VAV for both heating and cooling and optional reheat coil. For heating, this unit increases airflow first, then activates reheat coil.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_vav_system_name
Template VAV System Name required
reference Name of a HVACTemplate:System:VAV or HVACTemplate:System:PackagedVAV object serving this zone
Names a HVACTemplate:System:PackagedVAV, HVACTemplate:System:VAV
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
supply_air_maximum_flow_rate
Supply Air Maximum Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
constant_minimum_air_flow_fraction
Constant Minimum Air Flow Fraction
number 0.2 This field is used if the field Zone Minimum Air Flow Input Method is Constant If the field Zone Minimum Air Flow Input Method is Scheduled, then this field is optional. If a value is entered, then it is used for sizing normal-action reheat coils. If both this field and the following field are entered, the larger result is used.
Range: ≥ 0, ≤ 1
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name_for_sizing
Design Specification Outdoor Air Object Name for Sizing
reference This field is used only when Outdoor Air Method=DetailedSpecification. Note that this field is used only for specifying the design outdoor air flow rate used for sizing. The field Design Specification Outdoor Air Object Name for Control (see above) is used to actively control the VAV terminal air flow rate.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
reheat_coil_type
Reheat Coil Type
choice None One of Electric, Gas, HotWater, None
reheat_coil_availability_schedule_name
Reheat Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_reheat_air_temperature
Maximum Reheat Air Temperature
number
C
Specifies the maximum allowable supply air temperature leaving the reheat coil. If left blank, there is no limit and no default. If unknown, 35C (95F) is recommended.
Range: > 0
supply_plenum_name
Supply Plenum Name
reference Plenum zone name. Supply plenum runs through only this zone. Blank if none.
Names a Zone
return_plenum_name
Return Plenum Name
reference Plenum zone name. Return plenum runs through only this zone. Blank if none.
Names a Zone
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SystemSupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Cooling Coil Design Setpoint
One of SupplyAirTemperature, SystemSupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
12.8 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature SystemSupplyAirTemperature = use the value from HVACTemplate:System:VAV Heating Coil Design Setpoint TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.

HVACTemplate:Zone:VRF

from idfpy.models import HVACTemplateZoneVRF

Zone terminal unit with variable refrigerant flow (VRF) DX cooling and heating coils (air-to-air or water-to-air heat pump). The VRF terminal units are served by an HVACTemplate:System:VRF system.

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_vrf_system_name
Template VRF System Name required
reference Name of a HVACTemplate:System:VRF object serving this zone
Names a HVACTemplate:System:VRF
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
rated_total_heating_capacity_sizing_ratio
Rated Total Heating Capacity Sizing Ratio
number
W/W
1.0 If this terminal unit's heating coil is autosized, the heating capacity is sized to be equal to the cooling capacity multiplied by this sizing ratio. This input applies to the terminal unit heating coil and overrides the sizing ratio entered in the HVACTemplate:System:VRF object.
Range: ≥ 1
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
no_cooling_supply_air_flow_rate
No Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize This flow rate is used when the terminal is not cooling and the previous mode was cooling. This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
no_heating_supply_air_flow_rate
No Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize This flow rate is used when the terminal is not heating and the previous mode was heating. This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
cooling_outdoor_air_flow_rate
Cooling Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero.
heating_outdoor_air_flow_rate
Heating Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero.
no_load_outdoor_air_flow_rate
No Load Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize If this field is set to autosize it will be sized based on the outdoor air inputs below, unless a dedicated outdoor air system is specified for this zone and then it will be set to zero.
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_air_fan_placement
Supply Air Fan placement
choice BlowThrough Select fan placement as either blow through or draw through.
One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
75.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice VariableRefrigerantFlowDX One of None, VariableRefrigerantFlowDX
cooling_coil_availability_schedule_name
Cooling Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
heat_pump_heating_coil_type
Heat Pump Heating Coil Type
choice VariableRefrigerantFlowDX One of None, VariableRefrigerantFlowDX
heat_pump_heating_coil_availability_schedule_name
Heat Pump Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_pump_heating_coil_gross_rated_capacity
Heat Pump Heating Coil Gross Rated Capacity
number or Autosize
W
Autosize Capacity excluding supply air fan heat Rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C Rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
zone_terminal_unit_on_parasitic_electric_energy_use
Zone Terminal Unit On Parasitic Electric Energy Use
number
W
0.0 Range: ≥ 0
zone_terminal_unit_off_parasitic_electric_energy_use
Zone Terminal Unit Off Parasitic Electric Energy Use
number
W
0.0 Range: ≥ 0
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
14.0 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize

HVACTemplate:Zone:WaterToAirHeatPump

from idfpy.models import HVACTemplateZoneWaterToAirHeatPump

Water to Air Heat Pump to be used with HVACTemplate:Plant:MixedWaterLoop

Field Type Default Details
zone_name
Zone Name required
reference Zone name must match a building zone name
Names a Zone
template_thermostat_name
Template Thermostat Name
reference Enter the name of a HVACTemplate:Thermostat object. If blank, then it is assumed that standard thermostat objects have been defined for this zone.
Names a HVACTemplate:Thermostat
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during cooling operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Autosize Supply air flow rate during heating operation This field may be set to "autosize". If a value is entered, it will be multiplied by the Supply Air Sizing Factor and by zone multipliers.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Supply air flow rate when no cooling or heating is needed Only used when heat pump fan operating mode is continuous. This air flow rate is used when no heating or cooling is required. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used. A value entered in this field will *not* be multiplied by the sizing factor or by zone multipliers. It is best to autosize or leave blank when using zone multipliers.
zone_heating_sizing_factor
Zone Heating Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number If blank, value from Sizing:Parameters will be used.
Range: ≥ 0
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person, Flow/Zone, Flow/Area, Sum, and Maximum use the values in the next three fields: Outdoor Air Flow Rate per Person, Outdoor Air Flow Rate per Zone Floor Area, and Outdoor Air Flow Rate per Zone. DetailedSpecification ignores these three Outdoor Air Flow Rate fields and instead references design specification objects named in the fields Design Specification Outdoor Air Object Name and Design Specification Zone Air Distribution Object Name.
One of DetailedSpecification, Flow/Area, Flow/Person, Flow/Zone, Maximum, Sum
outdoor_air_flow_rate_per_person
Outdoor Air Flow Rate per Person
number
m3/s
0.00944 Default 0.00944 is 20 cfm per person This input is used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum
outdoor_air_flow_rate_per_zone_floor_area
Outdoor Air Flow Rate per Zone Floor Area
number
m3/s-m2
0.0 This input is used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
outdoor_air_flow_rate_per_zone
Outdoor Air Flow Rate per Zone
number
m3/s
0.0 This input is used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
system_availability_schedule_name
System Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_operating_mode_schedule_name
Supply Fan Operating Mode Schedule Name
reference Refers to a schedule to specify unitary supply fan operating mode. Schedule values of 0 indicate cycling fan (auto) Schedule values of 1 indicate continuous fan (on) If this field is left blank, a schedule of always zero (cycling fan) will be used.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_fan_placement
Supply Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
supply_fan_total_efficiency
Supply Fan Total Efficiency
number 0.7 Range: > 0, ≤ 1
supply_fan_delta_pressure
Supply Fan Delta Pressure
number
Pa
75.0 Range: ≥ 0
supply_fan_motor_efficiency
Supply Fan Motor Efficiency
number 0.9 Range: > 0, ≤ 1
cooling_coil_type
Cooling Coil Type
choice Coil:Cooling:WaterToAirHeatPump:EquationFit One of Coil:Cooling:WaterToAirHeatPump:EquationFit
cooling_coil_gross_rated_total_capacity
Cooling Coil Gross Rated Total Capacity
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
cooling_coil_gross_rated_sensible_heat_ratio
Cooling Coil Gross Rated Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include effect of supply fan heat
cooling_coil_gross_rated_cop
Cooling Coil Gross Rated COP
number
W/W
3.5 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electric power input
Range: > 0
heat_pump_heating_coil_type
Heat Pump Heating Coil Type
choice Coil:Heating:WaterToAirHeatPump:EquationFit One of Coil:Heating:WaterToAirHeatPump:EquationFit
heat_pump_heating_coil_gross_rated_capacity
Heat Pump Heating Coil Gross Rated Capacity
number or Autosize
W
Autosize Capacity excluding supply air fan heat
heat_pump_heating_coil_gross_rated_cop
Heat Pump Heating Coil Gross Rated COP
number
W/W
4.2 Heat Pump Heating Coil Rated Capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electric power input
Range: > 0
supplemental_heating_coil_availability_schedule_name
Supplemental Heating Coil Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supplemental_heating_coil_capacity
Supplemental Heating Coil Capacity
number or Autosize
W
Autosize
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
2.5 The maximum on-off cycling rate for the compressor Suggested value is 2.5 for a typical heat pump
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
60.0 Time constant for the cooling coil's capacity to reach steady state after startup Suggested value is 60 for a typical heat pump
Range: ≥ 0, ≤ 500
heat_pump_fan_delay_time
Heat Pump Fan Delay Time
number
s
60.0 Programmed time delay for heat pump fan to shut off after compressor cycle off. Only required when fan operating mode is cycling Enter 0 when fan operating mode is continuous
Range: ≥ 0
dedicated_outdoor_air_system_name
Dedicated Outdoor Air System Name
reference Enter the name of an HVACTemplate:System:DedicatedOutdoorAir object if this zone is served by a separate dedicated outdoor air system (DOAS). Leave field blank if no DOAS serves this zone.
Names a HVACTemplate:System:DedicatedOutdoorAir
supplemental_heating_coil_type
Supplemental Heating Coil Type
choice Electric One of Electric, HotWater
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Cooling Design Supply Air Temperature TemperatureDifference = use the value from Zone Cooling Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
14.0 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
11.11 Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature SupplyAirTemperature = use the value from Zone Heating Design Supply Air Temperature TemperatureDifference = use the value from Zone Heating Design Supply Air Temperature Difference
One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
50.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
30.0 Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
heat_pump_coil_water_flow_mode
Heat Pump Coil Water Flow Mode
choice Cycling used only when the heat pump coils are of the type WaterToAirHeatPump:EquationFit Constant results in 100% water flow regardless of compressor PLR Cycling results in water flow that matches compressor PLR ConstantOnDemand results in 100% water flow whenever the coil is on, but is 0% whenever the coil has no load
One of Constant, ConstantOnDemand, Cycling
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference This field is used only when Outdoor Air Method=DetailedSpecification.
Names a DesignSpecification:ZoneAirDistribution
baseboard_heating_type
Baseboard Heating Type
choice None One of Electric, HotWater, None
baseboard_heating_availability_schedule_name
Baseboard Heating Availability Schedule Name
reference If blank, always on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
baseboard_heating_capacity
Baseboard Heating Capacity
number or Autosize
W
Autosize