Unitary Equipment

10 object types from idfpy.models.unitary · EnergyPlus 26.2

Object Summary
AirLoopHVAC:Unitary:Furnace:HeatCool Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion …
AirLoopHVAC:Unitary:Furnace:HeatOnly Unitary system, heating-only with constant volume supply fan (continuous or cycling) and heating coil (gas, …
AirLoopHVAC:UnitaryHeatCool Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion …
AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion …
AirLoopHVAC:UnitaryHeatOnly Unitary system, heating-only with constant volume supply fan (continuous or cycling) and heating coil (gas, …
AirLoopHVAC:UnitaryHeatPump:AirToAir Unitary heat pump system, heating and cooling, single-speed with supply fan, direct expansion (DX) cooling …
AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed Unitary system, heating and cooling, multi-speed with constant volume supply fan (continuous or cycling), …
AirLoopHVAC:UnitaryHeatPump:WaterToAir Unitary heat pump system, heating and cooling, single-speed with constant volume supply fan (continuous or …
AirLoopHVAC:UnitarySystem AirloopHVAC:UnitarySystem is a generic HVAC system type that allows any configuration of coils and/or fan.
UnitarySystemPerformance:Multispeed The UnitarySystemPerformance object is used to specify the air flow ratio at each operating speed.

AirLoopHVAC:Unitary:Furnace:HeatCool

from idfpy.models import AirLoopHVACUnitaryFurnaceHeatCool

Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion (DX) cooling coil, heating coil (gas, electric, hot water, or steam), and optional reheat coil for dehumidification control. Identical to AirLoopHVAC:UnitaryHeatCool.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. A schedule value greater than zero (usually 1 is used) indicates that the unit is available to operate as needed. A value less than or equal to zero (usually zero is used) denotes that the unit must be off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
furnace_air_inlet_node_name
Furnace Air Inlet Node Name required
string
furnace_air_outlet_node_name
Furnace Air Outlet Node Name required
string
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the cooling or heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of cooling or heating coil operation). Provide a schedule with non-zero values when high humidity control is specified. Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_supply_air_temperature
Maximum Supply Air Temperature
number or Autosize
C
80.0
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow fate.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate. Only used when fan operating mode is continuous (disregarded for cycling fan mode). This air flow rate is used when no heating or cooling is required (i.e., the DX coil compressor and heating coil are off). If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_fan_object_type
Supply Fan Object Type required
choice Fan:ConstantVolume only works with continuous fan operating mode (i.e. supply air fan operating mode schedule values not equal to 0).
One of Fan:ConstantVolume, Fan:OnOff
supply_fan_name
Supply Fan Name required
reference Names a Fan:ConstantVolume, Fan:OnOff
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
heating_coil_object_type
Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
cooling_coil_object_type
Cooling Coil Object Type required
choice Only works with DX cooling coil types
One of Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with cooling coil type CoilSystem:Cooling:DX:HeatExchangerAssisted. This control mode allows the heat exchanger to be turned on and off based on the zone dehumidification requirements. A ZoneControl:Humidistat object is also required. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted cooling coil is used, the heat exchanger is locked on at all times. A ZoneControl:Humidistat object is also required.
One of CoolReheat, Multimode, None
reheat_coil_object_type
Reheat Coil Object Type
choice Only required if dehumidification control type is "CoolReheat" works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name
reference Only required if dehumidification control type is "CoolReheat"
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:Unitary:Furnace:HeatOnly

from idfpy.models import AirLoopHVACUnitaryFurnaceHeatOnly

Unitary system, heating-only with constant volume supply fan (continuous or cycling) and heating coil (gas, electric, hot water, or steam). Identical to AirLoopHVAC:UnitaryHeatOnly.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
furnace_air_inlet_node_name
Furnace Air Inlet Node Name required
string
furnace_air_outlet_node_name
Furnace Air Outlet Node Name required
string
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of heating coil operation). Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_supply_air_temperature
Maximum Supply Air Temperature
number or Autosize
C
80.0
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
This value should be > 0 and <= than the fan air flow rate.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_fan_object_type
Supply Fan Object Type required
choice Fan:ConstantVolume only works with continuous fan operating mode (i.e. fan operating mode schedule values are greater than 0).
One of Fan:ConstantVolume, Fan:OnOff
supply_fan_name
Supply Fan Name required
reference Names a Fan:ConstantVolume, Fan:OnOff
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
heating_coil_object_type
Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatCool

from idfpy.models import AirLoopHVACUnitaryHeatCool

Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion (DX) cooling coil, heating coil (gas, electric, hot water, or steam), and optional reheat coil for dehumidification control. Identical to AirLoopHVAC:Unitary:Furnace:HeatCool.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
unitary_system_air_inlet_node_name
Unitary System Air Inlet Node Name required
string
unitary_system_air_outlet_node_name
Unitary System Air Outlet Node Name required
string
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the cooling or heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of cooling or heating coil operation). Provide a schedule with non-zero values when high humidity control is specified. Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_supply_air_temperature
Maximum Supply Air Temperature
number or Autosize
C
80.0
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate. Only used when fan operating mode is continuous (disregarded for cycling fan mode). This air flow rate is used when no heating or cooling is required (i.e., the DX coil compressor and heating coil are off). If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_fan_object_type
Supply Fan Object Type required
choice Fan:ConstantVolume only works with continuous fan operating mode (i.e. supply air fan operating mode schedule values not equal to 0).
One of Fan:ConstantVolume, Fan:OnOff
supply_fan_name
Supply Fan Name required
reference Names a Fan:ConstantVolume, Fan:OnOff
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
heating_coil_object_type
Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
cooling_coil_object_type
Cooling Coil Object Type required
choice Only works with DX cooling coil types or Coil:Cooling:DX:VariableSpeed.
One of Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with cooling coil type CoilSystem:Cooling:DX:HeatExchangerAssisted. This control mode allows the heat exchanger to be turned on and off based on the zone dehumidification requirements. A ZoneControl:Humidistat object is also required. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted Cooling coil is used, the heat exchanger is locked on at all times. A ZoneControl:Humidistat object is also required.
One of CoolReheat, Multimode, None
reheat_coil_object_type
Reheat Coil Object Type
choice Only required if dehumidification control type is "CoolReheat" works with gas, electric, desuperheating, hot water and steam heating coils
One of Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
reheat_coil_name
Reheat Coil Name
reference Only required if dehumidification control type is "CoolReheat"
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass

from idfpy.models import AirLoopHVACUnitaryHeatCoolVAVChangeoverBypass

Unitary system, heating and cooling with constant volume supply fan (continuous or cycling), direct expansion (DX) cooling coil, heating coil (gas, electric, hot water, steam, or DX air-to-air heat pump) and bypass damper for variable volume flow to terminal units. Used with AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat or AirTerminal:SingleDuct:VAV:HeatAndCool:NoReheat.

Field Type Default Details
name
Name required
string Enter a unique name for this unitary system.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Enter the availability schedule name. Schedule values of zero denote system is Off. Non-zero schedule values denote system is available to operate.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate required
number or Autosize
m3/s
Enter the system air flow rate during cooling operation or specify autosize.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
Enter the system air flow rate during heating operation or specify autosize.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Only used when the supply air fan operating mode is continuous (see field Supply air fan operating mode schedule name). This system air flow rate is used when no heating or cooling is required and the coils are off. If this field is left blank or zero, the system air flow rate from the previous on cycle (either cooling or heating) is used.
cooling_outdoor_air_flow_rate
Cooling Outdoor Air Flow Rate required
number or Autosize
m3/s
Enter the outdoor air flow rate during cooling operation or specify autosize.
heating_outdoor_air_flow_rate
Heating Outdoor Air Flow Rate required
number or Autosize
m3/s
Enter the outdoor air flow rate during heating operation or specify autosize.
no_load_outdoor_air_flow_rate
No Load Outdoor Air Flow Rate
number or Autosize
m3/s
Only used when the supply air fan operating mode is continuous (see field Supply air fan operating mode schedule name). This outdoor air flow rate is used when no heating or cooling is required and the coils are off. If this field is left blank or zero, the outdoor air flow rate from the previous on cycle (either cooling or heating) is used.
outdoor_air_flow_rate_multiplier_schedule_name
Outdoor Air Flow Rate Multiplier Schedule Name
reference Enter the name of a schedule that contains multipliers for the outdoor air flow rates. Schedule values must be from 0 to 1. If field is left blank, model assumes multiplier is 1 for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string Enter the name of the unitary system's air inlet node.
bypass_duct_mixer_node_name
Bypass Duct Mixer Node Name required
string Enter the name of the bypass duct mixer node. This name should be the name of the return air node for the outdoor air mixer associated with this system. This node name must be different from the air inlet node name.
bypass_duct_splitter_node_name
Bypass Duct Splitter Node Name required
string Enter the name of the bypass duct splitter node. This splitter air node is the outlet node of the last component in this unitary system. For blow through fan placement, the splitter air node is the outlet node of the heating coil. For draw through fan placement, the splitter node is the outlet node of the supply air fan.
air_outlet_node_name
Air Outlet Node Name required
string Enter the name of the unitary system's air outlet node.
outdoor_air_mixer_object_type
Outdoor Air Mixer Object Type required
choice currently only one type OutdoorAir:Mixer object is available.
One of OutdoorAir:Mixer
outdoor_air_mixer_name
Outdoor Air Mixer Name required
reference Enter the name of the outdoor air mixer used with this unitary system.
Names a OutdoorAir:Mixer
supply_air_fan_object_type
Supply Air Fan Object Type required
choice Specify the type of supply air fan used in this unitary system.
One of Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel
supply_air_fan_name
Supply Air Fan Name required
reference Enter the name of the supply air fan used in this unitary system.
Names a Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel
supply_air_fan_placement
Supply Air Fan Placement required
choice Specify supply air fan placement as either blow through or draw through. BlowThrough means the supply air fan is located before the cooling coil. DrawThrough means the supply air fan is located after the heating coil.
One of BlowThrough, DrawThrough
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference Enter the name of a schedule to control the supply air fan. Schedule Name values of zero mean that the supply air fan will cycle off if there is no cooling or heating load in any of the zones being served by this system. Non-zero schedule values mean that the supply air fan will operate continuously even if there is no cooling or heating load in any of the zones being served. If this field is left blank, the supply air fan will operate continuously for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_object_type
Cooling Coil Object Type required
choice Specify the type of cooling coil used in this unitary system.
One of Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name required
reference Enter the name of the cooling coil used in this unitary system.
Names a Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
heating_coil_object_type
Heating Coil Object Type required
choice works with DX, gas, electric, hot water and steam heating coils Specify the type of heating coil used in this unitary system.
One of Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Enter the name of the heating coil used in this unitary system.
Names a Coil:Heating:DX:VariableSpeed, Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
priority_control_mode
Priority Control Mode
choice ZonePriority CoolingPriority = system provides cooling if any zone requires cooling. HeatingPriority = system provides heating if any zone requires heating. ZonePriority = system controlled based on the total number of zones requiring cooling or heating (highest number of zones in cooling or heating determines the system's operating mode). LoadPriority = system provides cooling or heating based on total zone loads.
One of CoolingPriority, HeatingPriority, LoadPriority, ZonePriority
minimum_outlet_air_temperature_during_cooling_operation
Minimum Outlet Air Temperature During Cooling Operation
number
C
8.0 Specify the minimum outlet air temperature allowed for this unitary system during cooling operation. This value should be less than the maximum outlet air temperature during heating operation.
Range: > 0
maximum_outlet_air_temperature_during_heating_operation
Maximum Outlet Air Temperature During Heating Operation
number
C
50.0 Specify the maximum outlet air temperature allowed for this unitary system during heating operation. This value should be greater than the minimum outlet air temperature during cooling operation.
Range: > 0
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with Coil:Cooling:DX:TwoStageWithHumidityControlMode. CoolReheat = cool beyond the Dry-Bulb temperature setpoint as required to meet the humidity setpoint. Valid only with Coil:Cooling:DX:TwoStageWithHumidityControlMode. For all dehumidification controls, the max humidity setpoint on this unitary system's air outlet node is used. This must be set using ZoneControl:Humidistat and SetpointManager:SingleZone:Humidity:Maximum, SetpointManager:MultiZone:Humidity:Maximum or SetpointManager:MultiZone:MaximumHumidity:Average objects.
One of CoolReheat, Multimode, None
plenum_or_mixer_inlet_node_name
Plenum or Mixer Inlet Node Name
string Enter the name of the bypass duct node connected to a plenum or mixer. This field is required when this HVAC System is connected to a plenum or mixer. This is a different node name than that entered in the Bypass Duct Splitter Node Name field.
minimum_runtime_before_operating_mode_change
Minimum Runtime Before Operating Mode Change
number
hr
0.25 This is the minimum amount of time the unit operates in cooling or heating mode before changing modes.
Range: ≥ 0
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatOnly

from idfpy.models import AirLoopHVACUnitaryHeatOnly

Unitary system, heating-only with constant volume supply fan (continuous or cycling) and heating coil (gas, electric, hot water, or steam). Identical to AirLoopHVAC:Unitary:Furnace:HeatOnly.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
unitary_system_air_inlet_node_name
Unitary System Air Inlet Node Name required
string
unitary_system_air_outlet_node_name
Unitary System Air Outlet Node Name required
string
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of heating coil operation). Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_supply_air_temperature
Maximum Supply Air Temperature
number or Autosize
C
80.0
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
This value should be > 0 and <= than the fan air flow rate.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_fan_object_type
Supply Fan Object Type required
choice Fan:ConstantVolume only works with continuous fan operating mode (i.e. fan operating mode schedule values are greater than 0).
One of Fan:ConstantVolume, Fan:OnOff
supply_fan_name
Supply Fan Name required
reference Names a Fan:ConstantVolume, Fan:OnOff
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
heating_coil_object_type
Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatPump:AirToAir

from idfpy.models import AirLoopHVACUnitaryHeatPumpAirToAir

Unitary heat pump system, heating and cooling, single-speed with supply fan, direct expansion (DX) cooling coil, DX heating coil (air-to-air heat pump), and supplemental heating coil (gas, electric, hot water, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. A schedule value greater than zero (usually 1 is used) indicates that the unit is available to operate as needed. A value less than or equal to zero (usually zero is used) denotes that the unit must be off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate.
heating_supply_air_flow_rate
Heating Supply Air Flow Rate required
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate.
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Must be less than or equal to the fan's maximum flow rate. Only used when fan operating mode is continuous (disregarded for cycling fan mode). This air flow rate is used when no heating or cooling is required (i.e., the DX coil compressor and supplemental heating coil are off). If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_air_fan_object_type
Supply Air Fan Object Type required
choice Fan:ConstantVolume only works with continuous fan operating mode (i.e. fan operating mode schedule values are greater than 0 or the fan operating mode schedule name field is left blank).
One of Fan:ConstantVolume, Fan:OnOff
supply_air_fan_name
Supply Air Fan Name required
reference Needs to match in the fan object
Names a Fan:ConstantVolume, Fan:OnOff
heating_coil_object_type
Heating Coil Object Type required
choice Only works with Coil:Heating:DX:SingleSpeed or Coil:Heating:DX:VariableSpeed or CoilSystem:IntegratedHeatPump:AirSource
One of Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed, CoilSystem:IntegratedHeatPump:AirSource
heating_coil_name
Heating Coil Name required
reference Needs to match in the DX heating coil object
Names a Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableRefrigerantFlow, Coil:Heating:DX:VariableSpeed, CoilSystem:IntegratedHeatPump:AirSource
cooling_coil_object_type
Cooling Coil Object Type required
choice Only works with Coil:Cooling:DX:SingleSpeed or CoilSystem:Cooling:DX:HeatExchangerAssisted or Coil:Cooling:DX:VariableSpeed or CoilSystem:IntegratedHeatPump:AirSource
One of Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted, CoilSystem:IntegratedHeatPump:AirSource
cooling_coil_name
Cooling Coil Name required
reference Needs to match in the DX cooling coil object
Names a Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted, CoilSystem:IntegratedHeatPump:AirSource
supplemental_heating_coil_object_type
Supplemental Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
supplemental_heating_coil_name
Supplemental Heating Coil Name required
reference Needs to match in the supplemental heating coil object
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_supply_air_temperature_from_supplemental_heater
Maximum Supply Air Temperature from Supplemental Heater required
number or Autosize
C
maximum_outdoor_dry_bulb_temperature_for_supplemental_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation
number
C
21.0 Range: ≤ 21
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the cooling or heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of cooling or heating coil operation). Leaving this schedule name blank will default to cycling fan mode for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with cooling coil type CoilSystem:Cooling:DX:HeatExchangerAssisted. This control mode allows the heat exchanger to be turned on and off based on the zone dehumidification requirements. A ZoneControl:Humidistat object is also required. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted Cooling coil is used, the heat exchanger is locked on at all times. A ZoneControl:Humidistat object is also required.
One of CoolReheat, Multimode, None
dx_heating_coil_sizing_ratio
DX Heating Coil Sizing Ratio
number 1.0 Used to adjust heat pump heating capacity with respect to DX cooling capacity used only for heat pump configurations (i.e., a DX cooling and DX heating coil is used).
Range: > 0
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed

from idfpy.models import AirLoopHVACUnitaryHeatPumpAirToAirMultiSpeed

Unitary system, heating and cooling, multi-speed with constant volume supply fan (continuous or cycling), direct expansion (DX) cooling coil, heating coil (DX air-to-air heat pump, gas, electric, hot water, or steam), and supplemental heating coil (gas, electric, hot water, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_air_fan_object_type
Supply Air Fan Object Type required
choice Select the type of supply air fan used in this unitary system.
One of Fan:ConstantVolume, Fan:OnOff
supply_air_fan_name
Supply Air Fan Name required
reference Enter the name of the supply air fan used in this unitary system.
Names a Fan:ConstantVolume, Fan:OnOff
supply_air_fan_placement
Supply Air Fan Placement required
choice Select supply air fan placement as either BlowThrough or DrawThrough. BlowThrough means the supply air fan is located before the cooling coil. DrawThrough means the supply air fan is located after the heating coil but before the optional supplemental heating coil.
One of BlowThrough, DrawThrough
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference Enter the name of a schedule to control the supply air fan. Schedule values of zero mean that the supply air fan will cycle off if there is no cooling or heating load in the control zone. Non-zero schedule values mean that the supply air fan will operate continuously even if there is no cooling or heating load in the control zone. If this field is left blank, the supply air fan will operate continuously for the entire simulation period.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_object_type
Heating Coil Object Type required
choice Multi Speed DX, Electric, Gas, and Single speed Water and Steam coils
One of Coil:Heating:DX:MultiSpeed, Coil:Heating:Electric:MultiStage, Coil:Heating:Gas:MultiStage, Coil:Heating:Steam, Coil:Heating:Water
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:DX:MultiSpeed, Coil:Heating:Electric:MultiStage, Coil:Heating:Gas:MultiStage
dx_heating_coil_sizing_ratio
DX Heating Coil Sizing Ratio
number 1.0 Used to adjust heat pump heating capacity with respect to DX cooling capacity used only for heat pump configurations (i.e., a DX cooling and DX heating coil is used).
Range: > 0
cooling_coil_object_type
Cooling Coil Object Type required
choice Only works with Coil:Cooling:DX:MultiSpeed
One of Coil:Cooling:DX:MultiSpeed
cooling_coil_name
Cooling Coil Name required
reference Needs to match in the DX Cooling Coil object
Names a Coil:Cooling:DX:MultiSpeed
supplemental_heating_coil_object_type
Supplemental Heating Coil Object Type
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
supplemental_heating_coil_name
Supplemental Heating Coil Name
reference Needs to match in the supplemental heating coil object
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_supply_air_temperature_from_supplemental_heater
Maximum Supply Air Temperature from Supplemental Heater
number or Autosize
C
maximum_outdoor_dry_bulb_temperature_for_supplemental_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation
number
C
21.0 Range: ≤ 21
auxiliary_on_cycle_electric_power
Auxiliary On-Cycle Electric Power
number
W
0.0 Range: ≥ 0
auxiliary_off_cycle_electric_power
Auxiliary Off-Cycle Electric Power
number
W
0.0 Range: ≥ 0
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered. Used for heat recovery to an EnergyPlus plant loop.
Range: ≥ 0
maximum_temperature_for_heat_recovery
Maximum Temperature for Heat Recovery
number
C
80.0 Range: ≥ 0, ≤ 100
heat_recovery_water_inlet_node_name
Heat Recovery Water Inlet Node Name
string
heat_recovery_water_outlet_node_name
Heat Recovery Water Outlet Node Name
string
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Only used when the supply air fan operating mode is continuous (see field Supply Air Fan Operating Mode Schedule Name). This air flow rate is used when no heating or cooling is required and the coils are off. If this field is left blank or zero, the supply air flow rate from the previous on cycle (either cooling or heating) is used.
number_of_speeds_for_heating
Number of Speeds for Heating required
integer Enter the number of the following sets of data for air flow rates. If Heating Coil Object Type is Coil:Heating:Water or Coil:Heating:Steam, this field should be 1.
Range: ≥ 1, ≤ 4
number_of_speeds_for_cooling
Number of Speeds for Cooling required
integer Enter the number of the following sets of data for air flow rates.
Range: ≥ 2, ≤ 4
heating_speed_1_supply_air_flow_rate
Heating Speed 1 Supply Air Flow Rate required
number or Autosize
m3/s
Enter the operating supply air flow rate during heating operation or specify autosize.
heating_speed_2_supply_air_flow_rate
Heating Speed 2 Supply Air Flow Rate
number or Autosize
m3/s
Enter the operating supply air flow rate during heating operation or specify autosize.
heating_speed_3_supply_air_flow_rate
Heating Speed 3 Supply Air Flow Rate
number or Autosize
m3/s
Enter the operating supply air flow rate during heating operation or specify autosize.
heating_speed_4_supply_air_flow_rate
Heating Speed 4 Supply Air Flow Rate
number or Autosize
m3/s
Enter the operating supply air flow rate during heating operation or specify autosize.
cooling_speed_1_supply_air_flow_rate
Cooling Speed 1 Supply Air Flow Rate required
number or Autosize
m3/s
Enter the operating supply air flow rate during cooling operation or specify autosize.
cooling_speed_2_supply_air_flow_rate
Cooling Speed 2 Supply Air Flow Rate required
number or Autosize
m3/s
Enter the operating supply air flow rate during cooling operation or specify autosize.
cooling_speed_3_supply_air_flow_rate
Cooling Speed 3 Supply Air Flow Rate
number or Autosize
m3/s
Enter the operating supply air flow rate during cooling operation or specify autosize.
cooling_speed_4_supply_air_flow_rate
Cooling Speed 4 Supply Air Flow Rate
number or Autosize
m3/s
Enter the operating supply air flow rate during cooling operation or specify autosize.
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitaryHeatPump:WaterToAir

from idfpy.models import AirLoopHVACUnitaryHeatPumpWaterToAir

Unitary heat pump system, heating and cooling, single-speed with constant volume supply fan (continuous or cycling), direct expansion (DX) cooling coil, DX heating coil (water-to-air heat pump), and supplemental heating coil (gas, electric, hot water, or steam).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
supply_air_flow_rate
Supply Air Flow Rate required
number or Autosize
m3/s
This value should be > 0 and <= than the fan air flow rate.
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location required
reference Names a Zone
supply_air_fan_object_type
Supply Air Fan Object Type required
choice Only works with On/Off Fan
One of Fan:OnOff
supply_air_fan_name
Supply Air Fan Name required
reference Needs to match Fan:OnOff object
Names a Fan:OnOff
heating_coil_object_type
Heating Coil Object Type required
choice One of Coil:Heating:WaterToAirHeatPump:EquationFit, Coil:Heating:WaterToAirHeatPump:ParameterEstimation, Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit
heating_coil_name
Heating Coil Name required
reference Needs to match in the water-to-air heat pump heating coil object
Names a Coil:Heating:WaterToAirHeatPump:EquationFit, Coil:Heating:WaterToAirHeatPump:ParameterEstimation, Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit
heating_convergence
Heating Convergence
number 0.001 Range: > 0
cooling_coil_object_type
Cooling Coil Object Type required
choice One of Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:ParameterEstimation, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit
cooling_coil_name
Cooling Coil Name required
reference Needs to match in the water-to-air heat pump cooling coil object
Names a Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:ParameterEstimation, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit
cooling_convergence
Cooling Convergence
number 0.001 Range: > 0
supplemental_heating_coil_object_type
Supplemental Heating Coil Object Type required
choice works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
supplemental_heating_coil_name
Supplemental Heating Coil Name required
reference Needs to match in the supplemental heating coil object
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
maximum_supply_air_temperature_from_supplemental_heater
Maximum Supply Air Temperature from Supplemental Heater required
number or Autosize
C
maximum_outdoor_dry_bulb_temperature_for_supplemental_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation
number
C
21.0 Range: ≤ 21
outdoor_dry_bulb_temperature_sensor_node_name
Outdoor Dry-Bulb Temperature Sensor Node Name
string
fan_placement
Fan Placement
choice BlowThrough One of BlowThrough, DrawThrough
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference Enter the name of a schedule that controls fan operation. Schedule values of 0 denote cycling fan operation (fan cycles with cooling or heating coil). Schedule values greater than 0 denote constant fan operation (fan runs continually regardless of coil operation). The fan operating mode defaults to cycling fan operation if this field is left blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid only with Coil:Cooling:WaterToAirHeatPump:EquationFit or Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit
One of CoolReheat, None
heat_pump_coil_water_flow_mode
Heat Pump Coil Water Flow Mode
choice Cycling used only when the heat pump coils are of the type WaterToAirHeatPump:EquationFit Constant results in 100% water flow regardless of compressor PLR Cycling results in water flow that matches compressor PLR ConstantOnDemand results in 100% water flow whenever the coil is on, but is 0% whenever the coil has no load
One of Constant, ConstantOnDemand, Cycling
dx_heating_coil_sizing_ratio
DX Heating Coil Sizing Ratio
number 1.0 Used to adjust heat pump heating capacity with respect to DX cooling capacity used only for heat pump configurations (i.e., a DX cooling and DX heating coil is used).
Range: > 0
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirLoopHVAC:UnitarySystem

from idfpy.models import AirLoopHVACUnitarySystem

AirloopHVAC:UnitarySystem is a generic HVAC system type that allows any configuration of coils and/or fan. This object is a replacement of other AirloopHVAC objects. This object can be used in outdoor air systems, outdoor air units, air loops, and as zone equipment if desired.

Field Type Default Details
name
Name required
string Unique name for the Unitary System.
control_type
Control Type
choice Load Load control requires a Controlling Zone name. SetPoint control requires set points at coil outlet node. SingleZoneVAV also requires a Controlling Zone name and allows load control at low speed fan until the load exceeds capacity or outlet air temperature limits. The fan speed is then increased.
One of Load, SetPoint, SingleZoneVAV
controlling_zone_or_thermostat_location
Controlling Zone or Thermostat Location
reference Used only for Load based control Zone name where thermostat is located. Required when Control Type = Load.
Names a Zone
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only. Required when Control Type = SingleZoneVAV. Multimode = activate enhanced dehumidification mode as needed and meet sensible load. Valid only with cooling coil type Coil:Cooling:DX:TwoStageWithHumidityControlMode or CoilSystem:Cooling:DX:HeatExchangerAssisted. This control mode either switches the coil mode or allows the heat exchanger to be turned on and off based on the zone dehumidification requirements. A ZoneControl:Humidistat object is also required. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted cooling coil is used, the heat exchanger is locked on at all times. A ZoneControl:Humidistat object is also required.
One of CoolReheat, Multimode, None
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. A schedule value greater than zero (usually 1 is used) indicates that the unit is available to operate as needed. A value less than or equal to zero (usually zero is used) denotes that the unit must be off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string Enter the node name used as the inlet air node for the unitary system.
air_outlet_node_name
Air Outlet Node Name required
string Enter the node name used as the outlet air node for the unitary system.
supply_fan_object_type
Supply Fan Object Type
choice Enter the type of supply air fan if included in the unitary system. Fan:ConstantVolume only works with continuous fan operating mode (i.e. supply air fan operating mode schedule values greater than 0). Specify a Fan:SystemModel or a Fan:OnOff object when the Supply Air Fan Operating Mode Schedule Name input field above is left blank. Specify a Fan:SystemModel or a Fan:VariableVolume when modeling VAV systems which used setpoint based control if the fan is included in the unitary system object. The ComponentModel fan type may be substituted for the ConstantVolume or VariableVolume fan types when more detailed fan modeling is required. The variable or constant volume fan may be specified on the branch instead of contained within the unitary system object (i.e., this field may be blank for certain configurations).
One of Fan:ComponentModel, Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel, Fan:VariableVolume
supply_fan_name
Supply Fan Name
reference Enter the name of the supply air fan if included in the unitary system.
Names a Fan:ComponentModel, Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel, Fan:VariableVolume
fan_placement
Fan Placement
choice Enter the type of supply air fan if included in the unitary system.
One of BlowThrough, DrawThrough
supply_air_fan_operating_mode_schedule_name
Supply Air Fan Operating Mode Schedule Name
reference A fan operating mode schedule value of 0 indicates cycling fan mode (supply air fan cycles on and off in tandem with the cooling or heating coil). Any other schedule value indicates continuous fan mode (supply air fan operates continuously regardless of cooling or heating coil operation). Provide a schedule with non-zero values when high humidity control is specified. Leaving this schedule name blank will default to constant fan mode for the entire simulation period. This field is not used when set point based control is used where a set point controls the coil. SingleZoneVAV control type is only active when constant fan operating mode is active.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_object_type
Heating Coil Object Type
choice Enter the type of heating coil if included in the unitary system.
One of Coil:Heating:DX:MultiSpeed, Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed, Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:MultiStage, Coil:Heating:Fuel, Coil:Heating:Gas:MultiStage, Coil:Heating:Steam, Coil:Heating:Water, Coil:Heating:WaterToAirHeatPump:EquationFit, Coil:Heating:WaterToAirHeatPump:ParameterEstimation, Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:UserDefined
heating_coil_name
Heating Coil Name
reference Enter the name of the heating coil if included in the unitary system.
Names a Coil:Heating:DX:MultiSpeed, Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableRefrigerantFlow, Coil:Heating:DX:VariableSpeed, Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:MultiStage, Coil:Heating:Fuel, Coil:Heating:Gas:MultiStage, Coil:Heating:Steam, Coil:Heating:Water, Coil:Heating:WaterToAirHeatPump:EquationFit and 3 more
dx_heating_coil_sizing_ratio
DX Heating Coil Sizing Ratio
number 1.0 Used to adjust heat pump heating capacity with respect to DX cooling capacity used only for heat pump configurations (i.e., a DX cooling and DX heating coil is used).
Range: > 0
cooling_coil_object_type
Cooling Coil Object Type
choice Enter the type of cooling coil if included in the unitary system.
One of Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:ParameterEstimation, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:UserDefined, CoilSystem:Cooling:DX:HeatExchangerAssisted, CoilSystem:Cooling:Water:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name
reference Enter the name of the cooling coil if included in the unitary system.
Names a Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:ParameterEstimation, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit and 3 more
use_doas_dx_cooling_coil
Use DOAS DX Cooling Coil
choice No If Yes, the DX cooling coil runs as 100% DOAS DX coil. If No, the DX cooling coil runs as a regular DX coil. If left blank the default is regular dx coil.
One of No, Yes
minimum_supply_air_temperature
Minimum Supply Air Temperature
number or Autosize
C
2.0 When Use DOAS DX Cooling Coil is specified as Yes, Minimum Supply Air Temperature defines the minimum DOAS DX cooling coil leaving air temperature that should be maintained to avoid frost formation. This field is not autosizable when the input for Use DOAS DX Cooling Coil = Yes. When Control Type = SingleZoneVAV, enter the minimum air temperature limit for reduced fan speed.
latent_load_control
Latent Load Control
choice SensibleOnlyLoadControl SensibleOnlyLoadControl is selected when thermostat or SingleZoneVAV control is used. LatentOnlyLoadControl is selected when humidistat control is used. LatentWithSensibleLoadControl is selected when thermostat control is used and dehumidification is required only when a sensible load exists. LatentOrSensibleLoadControl is selected when thermostat control is used and dehumidification is required any time the humidistat set point is exceeded.
One of LatentOnlyLoadControl, LatentOrSensibleLoadControl, LatentWithSensibleLoadControl, SensibleOnlyLoadControl
supplemental_heating_coil_object_type
Supplemental Heating Coil Object Type
choice Enter the type of supplemental heating or reheat coil if included in the unitary system. Only required if dehumidification control type is "CoolReheat". This coil supplements heating mode operation or reheats the supply air during dehumidification mode operation. If set point based control is used the coils operate to meet their respective supply air temperature set point.
One of Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:Multistage, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water, Coil:UserDefined
supplemental_heating_coil_name
Supplemental Heating Coil Name
reference Enter the name of the supplemental heating coil if included in the unitary system. Only required if dehumidification control type is "CoolReheat".
Names a Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:MultiStage, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water, Coil:UserDefined
cooling_supply_air_flow_rate_method
Cooling Supply Air Flow Rate Method
choice Enter the method used to determine the cooling supply air volume flow rate. None is used when a cooling coil is not included in the unitary system or this field may be blank. SupplyAirFlowRate is selected when the magnitude of the supply air volume is used. FlowPerFloorArea is selected when the supply air volume flow rate is based on total floor area served by the unitary system. FractionOfAutosizedCoolingValue is selected when the supply air volume is a fraction of the value determined by the simulation. FlowPerCoolingCapacity is selected when the supply air volume is a fraction of the cooling capacity as determined by the simulation.
One of FlowPerCoolingCapacity, FlowPerFloorArea, FractionOfAutosizedCoolingValue, None, SupplyAirFlowRate
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of the supply air volume flow rate during cooling operation. Required field when Cooling Supply Air Flow Rate Method is SupplyAirFlowRate. This field may be blank if a cooling coil is not included in the unitary system.
cooling_supply_air_flow_rate_per_floor_area
Cooling Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the supply air volume flow rate per total floor area fraction. Required field when Cooling Supply Air Flow Rate Method is FlowPerFloorArea. This field may be blank if a cooling coil is not included in the unitary system.
Range: ≥ 0
cooling_fraction_of_autosized_cooling_supply_air_flow_rate
Cooling Fraction of Autosized Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when Cooling Supply Air Flow Rate Method is FractionOfAutosizedCoolingValue. This field may be blank if a cooling coil is not included in the unitary system.
Range: ≥ 0
cooling_supply_air_flow_rate_per_unit_of_capacity
Cooling Supply Air Flow Rate Per Unit of Capacity
number
m3/s-W
Enter the supply air volume flow rate as a fraction of the cooling capacity. Required field when Cooling Supply Air Flow Rate Method is FlowPerCoolingCapacity. This field may be blank if a cooling coil is not included in the unitary system.
Range: ≥ 0
heating_supply_air_flow_rate_method
Heating Supply Air Flow Rate Method
choice Enter the method used to determine the heating supply air volume flow rate. None is used when a heating coil is not included in the unitary system or this field may be blank. SupplyAirFlowRate is selected when the magnitude of the supply air volume is used. FlowPerFloorArea is selected when the supply air volume flow rate is based on total floor area served by the unitary system. FractionOfAutosizedHeatingValue is selected when the supply air volume is a fraction of the value determined by the simulation. FlowPerHeatingCapacity is selected when the supply air volume is a fraction of the heating capacity as determined by the simulation.
One of FlowPerFloorArea, FlowPerHeatingCapacity, FractionOfAutosizedHeatingValue, None, SupplyAirFlowRate
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of the supply air volume flow rate during heating operation. Required field when Heating Supply Air Flow Rate Method is SupplyAirFlowRate. This field may be blank if a heating coil is not included in the unitary system.
heating_supply_air_flow_rate_per_floor_area
Heating Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the supply air volume flow rate per total floor area fraction. Required field when Heating Supply Air Flow Rate Method is FlowPerFloorArea. This field may be blank if a heating coil is not included in the unitary system.
Range: ≥ 0
heating_fraction_of_autosized_heating_supply_air_flow_rate
Heating Fraction of Autosized Heating Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the heating supply air flow rate. Required field when Heating Supply Air Flow Rate Method is FractionOfAutosizedHeatingValue. This field may be blank if a heating coil is not included in the unitary system.
Range: ≥ 0
heating_supply_air_flow_rate_per_unit_of_capacity
Heating Supply Air Flow Rate Per Unit of Capacity
number
m3/s-W
Enter the supply air volume flow rate as a fraction of the heating capacity. Required field when Heating Supply Air Flow Rate Method is FlowPerHeatingCapacity. This field may be blank if a heating coil is not included in the unitary system.
Range: ≥ 0
no_load_supply_air_flow_rate_method
No Load Supply Air Flow Rate Method
choice Enter the method used to determine the supply air volume flow rate when no cooling or heating is required. None is used when a cooling and heating coil is not included in the unitary system or this field may be blank. SupplyAirFlowRate is selected when the magnitude of the supply air volume is used. FlowPerFloorArea is selected when the supply air volume flow rate is based on total floor area served by the unitary system. FractionOfAutosizedCoolingValue is selected when the supply air volume is a fraction of the cooling value determined by the simulation. FractionOfAutosizedHeatingValue is selected when the supply air volume is a fraction of the heating value determined by the simulation. FlowPerCoolingCapacity is selected when the supply air volume is a fraction of the cooling capacity as determined by the simulation. FlowPerHeatingCapacity is selected when the supply air volume is a fraction of the heating capacity as determined by the simulation.
One of FlowPerCoolingCapacity, FlowPerFloorArea, FlowPerHeatingCapacity, FractionOfAutosizedCoolingValue, FractionOfAutosizedHeatingValue, None, SupplyAirFlowRate
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of the supply air volume flow rate during when no cooling or heating is required. Required field when No Load Supply Air Flow Rate Method is SupplyAirFlowRate.
no_load_supply_air_flow_rate_per_floor_area
No Load Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the supply air volume flow rate per total floor area fraction. Required field when No Load Supply Air Flow Rate Method is FlowPerFloorArea.
Range: ≥ 0
no_load_fraction_of_autosized_cooling_supply_air_flow_rate
No Load Fraction of Autosized Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when No Load Supply Air Flow Rate Method is FractionOfAutosizedCoolingValue.
Range: ≥ 0
no_load_fraction_of_autosized_heating_supply_air_flow_rate
No Load Fraction of Autosized Heating Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the heating supply air flow rate. Required field when No Load Supply Air Flow Rate Method is FractionOfAutosizedHeatingValue.
Range: ≥ 0
no_load_supply_air_flow_rate_per_unit_of_capacity_during_cooling_operation
No Load Supply Air Flow Rate Per Unit of Capacity During Cooling Operation
number
m3/s-W
Enter the supply air volume flow rate as a fraction of the cooling capacity. Required field when No Load Supply Air Flow Rate Method is FlowPerCoolingCapacity.
Range: ≥ 0
no_load_supply_air_flow_rate_per_unit_of_capacity_during_heating_operation
No Load Supply Air Flow Rate Per Unit of Capacity During Heating Operation
number
m3/s-W
Enter the supply air volume flow rate as a fraction of the heating capacity. Required field when No Load Supply Air Flow Rate Method is FlowPerHeatingCapacity.
Range: ≥ 0
no_load_supply_air_flow_rate_control_set_to_low_speed
No Load Supply Air Flow Rate Control Set To Low Speed
choice Yes This field is not used when Design Specification Multispeed Object Type input is present When Yes is selected the minimum air flow rate is used. When No is selected the maximum air flow rate is used.
One of No, Yes
maximum_supply_air_temperature
Maximum Supply Air Temperature
number or Autosize
C
80.0 Enter the maximum supply air temperature leaving the heating coil. When Control Type = SingleZoneVAV, enter the maximum air temperature limit for reduced fan speed.
maximum_outdoor_dry_bulb_temperature_for_supplemental_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation
number
C
21.0 Enter the maximum outdoor dry-bulb temperature for supplemental heater operation.
outdoor_dry_bulb_temperature_sensor_node_name
Outdoor Dry-Bulb Temperature Sensor Node Name
string If this field is blank, outdoor temperature from the weather file is used. If this field is not blank, the node name specified determines the outdoor temperature used for controlling supplemental heater operation.
ancillary_on_cycle_electric_power
Ancillary On-Cycle Electric Power
number
W
0.0 Enter the value of ancillary electric power for controls or other devices consumed during the on cycle.
Range: ≥ 0
ancillary_off_cycle_electric_power
Ancillary Off-Cycle Electric Power
number
W
0.0 Enter the value of ancillary electric power for controls or other devices consumed during the off cycle.
Range: ≥ 0
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered. Used for heat recovery to an EnergyPlus plant loop.
Range: ≥ 0
maximum_temperature_for_heat_recovery
Maximum Temperature for Heat Recovery
number
C
80.0 Enter the maximum heat recovery inlet temperature allowed for heat recovery.
Range: ≥ 0, ≤ 100
heat_recovery_water_inlet_node_name
Heat Recovery Water Inlet Node Name
string Enter the name of the heat recovery water inlet node if plant water loop connections are present.
heat_recovery_water_outlet_node_name
Heat Recovery Water Outlet Node Name
string Enter the name of the heat recovery water outlet node if plant water loop connections are present.
design_specification_multispeed_object_type
Design Specification Multispeed Object Type
choice Enter the type of performance specification object used to describe the multispeed coil.
One of UnitarySystemPerformance:Multispeed
design_specification_multispeed_object_name
Design Specification Multispeed Object Name
reference The name of the performance specification object used to describe the multispeed coil.
Names a UnitarySystemPerformance:Multispeed
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirTerminal:SingleDuct:Mixer, Branch, FaultModel:TemperatureSensorOffset:CoilSupplyAir, SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList

UnitarySystemPerformance:Multispeed

from idfpy.models import UnitarySystemPerformanceMultispeed extensible

The UnitarySystemPerformance object is used to specify the air flow ratio at each operating speed. This object is primarily used for multispeed DX and water coils to allow operation at alternate flow rates different from those specified in the coil object.

Field Type Default Details
name
Name required
string
number_of_speeds_for_heating
Number of Speeds for Heating required
integer Used only for Multi speed coils Enter the number of the following sets of data for air flow rates.
Range: ≥ 0, ≤ 10
number_of_speeds_for_cooling
Number of Speeds for Cooling required
integer Used only for Multi speed coils Enter the number of the following sets of data for air flow rates.
Range: ≥ 0, ≤ 10
single_mode_operation
Single Mode Operation
choice No Controls coil operation during each HVAC timestep. This choice does not apply to speed 1 operation. Yes = operate at the highest speed possible without exceeding the current load. No = allow operation at the average of two adjacent speeds to match the current load.
One of No, Yes
no_load_supply_air_flow_rate_ratio
No Load Supply Air Flow Rate Ratio
number 1.0 Used to define the no load operating air flow rate when the system fan is specified to operate continuously.
Range: ≥ 0, ≤ 1
flow_ratios list Each item: heating_speed_supply_air_flow_ratio, cooling_speed_supply_air_flow_ratio
Referenced by 3 object types

AirLoopHVAC:UnitarySystem, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:WaterToAirHeatPump