Coils

44 object types from idfpy.models.coils · EnergyPlus 26.2

Object Summary
Coil:Cooling:DX New general DX cooling coil supporting on or more speeds and one or or operating modes.
Coil:Cooling:DX:CurveFit:OperatingMode DX cooling coil performance for a single operating mode which may have one or more speeds.
Coil:Cooling:DX:CurveFit:Performance DX cooling coil performance specification referencing one or more operating modes.
Coil:Cooling:DX:CurveFit:Speed DX cooling coil performance for a single speed within a single operating mode.
Coil:Cooling:DX:MultiSpeed Direct expansion (DX) cooling coil and condensing unit (includes electric or engine-driven compressor and …
Coil:Cooling:DX:SingleSpeed Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), …
Coil:Cooling:DX:SingleSpeed:ThermalStorage Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), …
Coil:Cooling:DX:TwoSpeed Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), …
Coil:Cooling:DX:TwoStageWithHumidityControlMode Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), …
Coil:Cooling:DX:VariableRefrigerantFlow Variable refrigerant flow (VRF) direct expansion (DX) cooling coil.
Coil:Cooling:DX:VariableRefrigerantFlow:FluidTemperatureControl This is a key object in the new physics based VRF model applicable for Fluid Temperature Control.
Coil:Cooling:DX:VariableSpeed Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), …
Coil:Cooling:Water Chilled water cooling coil, NTU-effectiveness model, with inputs for design entering and leaving conditions.
Coil:Cooling:Water:DetailedGeometry Chilled water cooling coil, detailed flat fin coil model for continuous plate fins, with inputs for detailed …
Coil:Cooling:WaterToAirHeatPump:EquationFit Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), single-speed, …
Coil:Cooling:WaterToAirHeatPump:ParameterEstimation Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), single-speed, …
Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), variable-speed, …
Coil:DX:ASHRAE205:Performance DX coil performance specification referencing an ASHRAE Standard 205 compliant representation for air-to-air …
Coil:Heating:DX:MultiSpeed Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric or …
Coil:Heating:DX:SingleSpeed Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric compressor …
Coil:Heating:DX:VariableRefrigerantFlow Variable refrigerant flow (VRF) direct expansion (DX) heating coil (air-to-air heat pump).
Coil:Heating:DX:VariableRefrigerantFlow:FluidTemperatureControl This is a key object in the new physics based VRF model applicable for Fluid Temperature Control.
Coil:Heating:DX:VariableSpeed Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric compressor …
Coil:Heating:Desuperheater Desuperheater air heating coil.
Coil:Heating:Electric Electric heating coil.
Coil:Heating:Electric:MultiStage Electric heating coil, multi-stage.
Coil:Heating:Fuel Gas or other fuel heating coil.
Coil:Heating:Gas:MultiStage Gas heating coil, multi-stage.
Coil:Heating:Steam Steam heating coil.
Coil:Heating:Water Hot water heating coil, NTU-effectiveness model, assumes a cross-flow heat exchanger.
Coil:Heating:WaterToAirHeatPump:EquationFit Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), single-speed, …
Coil:Heating:WaterToAirHeatPump:ParameterEstimation Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), single-speed, …
Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), variable-speed, …
Coil:WaterHeating:AirToWaterHeatPump:Pumped Heat pump water heater (HPWH) heating coil, air-to-water direct-expansion (DX) system which includes a water …
Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed variable-speed Heat pump water heater (VSHPWH) heating coil, air-to-water direct-expansion (DX) system which …
Coil:WaterHeating:AirToWaterHeatPump:Wrapped Heat pump water heater (HPWH) heating coil, air-to-water direct-expansion (DX) system which includes a water …
Coil:WaterHeating:Desuperheater Desuperheater air heating coil.
CoilPerformance:DX:Cooling Used to specify DX cooling coil performance for one mode of operation for a …
CoilSystem:Cooling:DX Virtual container component that consists of a DX cooling coil and its associated controls.
CoilSystem:Cooling:DX:HeatExchangerAssisted Virtual component consisting of a direct expansion (DX) cooling coil and an air-to-air heat exchanger.
CoilSystem:Cooling:Water Virtual container component that consists of a water cooling coil and its associated controls.
CoilSystem:Cooling:Water:HeatExchangerAssisted Virtual component consisting of a chilled-water cooling coil and an air-to-air heat exchanger.
CoilSystem:Heating:DX Virtual container component that consists of a DX heating coil (heat pump) and its associated controls.
CoilSystem:IntegratedHeatPump:AirSource This object is used for air-source integrated heat pump, a collection of its working modes.

Coil:Cooling:DX

from idfpy.models import CoilCoolingDX

New general DX cooling coil supporting on or more speeds and one or or operating modes. Includes DX evaporator coil, compressor, and condenser. Object is currently only supported by the AIRLOOPHVAC:UNITARYSYSTEM object. Remaining Coil:Cooling:DX* objects will be deprecated at a future date, after which, this object will replace all other Coil:Cooling:DX* objects.

Field Type Default Details
name
Name required
string
evaporator_inlet_node_name
Evaporator Inlet Node Name required
string
evaporator_outlet_node_name
Evaporator Outlet Node Name required
string
availability_schedule_name
Availability Schedule Name
reference Schedule value > 0 means the coil is available. If this field is blank, the coil is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_zone_name
Condenser Zone Name
reference This input field is name of a conditioned or unconditioned zone where the secondary coil (condenser) of a DX system or heat pump is to be placed. This is an optional input field specified only when the user desires to reject the condenser heat into a zone. The heat rejected is modeled as internal sensible heat gain of the zone.
Names a Zone
condenser_inlet_node_name
Condenser Inlet Node Name required
string This is the name of an air node in the simulation. This may be an explicitly defined outdoor air node, or it may be a separate air node.
condenser_outlet_node_name
Condenser Outlet Node Name required
string This is the name of an air node in the simulation.
performance_object_name
Performance Object Name required
reference Names a Coil:Cooling:DX:CurveFit:Performance, Coil:DX:ASHRAE205:Performance
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
evaporative_condenser_supply_water_storage_tank_name
Evaporative Condenser Supply Water Storage Tank Name
reference Names a WaterUse:Storage
Referenced by 9 object types

AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, CoilSystem:Cooling:DX, CoilSystem:Cooling:DX:HeatExchangerAssisted, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump

Coil:Cooling:DX:CurveFit:OperatingMode

from idfpy.models import CoilCoolingDXCurveFitOperatingMode

DX cooling coil performance for a single operating mode which may have one or more speeds.

Field Type Default Details
name
Name required
string
rated_gross_total_cooling_capacity
Rated Gross Total Cooling Capacity
number or Autosize
W
Autosize Total (sensible+latent) cooling capacity not accounting for the effect of supply air fan heat. Rating point: air entering the evaporator coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the condenser coil at 35 C dry-bulb/23.9 C wet-bulb. gross capacity excluding supply air fan heat
rated_evaporator_air_flow_rate
Rated Evaporator Air Flow Rate
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, Rated SHR and Rated COP. Should be between 0.00004027 m3/s and 0.00006041 m3/s per watt of rated total cooling capacity.
rated_condenser_air_flow_rate
Rated Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use.
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
nominal_time_for_condensate_removal_to_begin
Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
apply_part_load_fraction_to_speeds_greater_than_1
Apply Part Load Fraction to Speeds Greater than 1
choice No One of No, Yes
apply_latent_degradation_to_speeds_greater_than_1
Apply Latent Degradation to Speeds Greater than 1
choice No One of No, Yes
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
nominal_evaporative_condenser_pump_power
Nominal Evaporative Condenser Pump Power
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump
nominal_speed_number
Nominal Speed Number
integer Must be lower than or equal to the highest speed number. If blank, defaults to the highest speed number used.
speed_1_name
Speed 1 Name required
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_2_name
Speed 2 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_3_name
Speed 3 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_4_name
Speed 4 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_5_name
Speed 5 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_6_name
Speed 6 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_7_name
Speed 7 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_8_name
Speed 8 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_9_name
Speed 9 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
speed_10_name
Speed 10 Name
reference Names a Coil:Cooling:DX:CurveFit:Speed
Referenced by 1 object types

Coil:Cooling:DX:CurveFit:Performance

Coil:Cooling:DX:CurveFit:Performance

from idfpy.models import CoilCoolingDXCurveFitPerformance

DX cooling coil performance specification referencing one or more operating modes. Mode 1 is always the base design operating mode. Additional modes are optional states such as subcool reheat for humidity control.

Field Type Default Details
name
Name required
string
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
unit_internal_static_air_pressure
Unit Internal Static Air Pressure
number
Pa
Enter pressure drop for the unit containing the coil. This value is only used to calculate Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity. This value is not used for modeling the evaporator fan during simulations.
Range: > 0
capacity_control_method
Capacity Control Method
choice Discrete One of Continuous, Discrete
evaporative_condenser_basin_heater_capacity
Evaporative Condenser Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
evaporative_condenser_basin_heater_setpoint_temperature
Evaporative Condenser Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
evaporative_condenser_basin_heater_operating_schedule_name
Evaporative Condenser Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
compressor_fuel_type
Compressor Fuel Type
choice Electricity One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
base_operating_mode
Base Operating Mode required
reference Operating Mode 1 is always used as the base design operating mode.
Names a Coil:Cooling:DX:CurveFit:OperatingMode
alternative_operating_mode_1
Alternative Operating Mode 1
reference The alternative operating mode is used for enhanced dehumidification. If this is blank, the coil will always operate in the base operating mode. If an alternate mode is defined here, the coil will use the enhanced mode if activated by the parent system controls.
Names a Coil:Cooling:DX:CurveFit:OperatingMode
alternative_operating_mode_2
Alternative Operating Mode 2
reference The alternative operating mode is used for enhanced dehumidification. If this is blank, the coil will always operate in the base operating mode or Alternative Mode 1. If both Alternative Operating Mode 1 and Mode 2 are defined here, the coil will perform both Subcool and Reheat modes for enhanced dehumidification. Alternative Operating Mode 1 is used as Subcool mode, and Alternative Operating Mode 2 is used as Reheat mode.
Names a Coil:Cooling:DX:CurveFit:OperatingMode
Referenced by 1 object types

Coil:Cooling:DX

Coil:Cooling:DX:CurveFit:Speed

from idfpy.models import CoilCoolingDXCurveFitSpeed

DX cooling coil performance for a single speed within a single operating mode.

Field Type Default Details
name
Name required
string
gross_total_cooling_capacity_fraction
Gross Total Cooling Capacity Fraction required
number Ratio of capacity at this speed to the operating mode Rated Gross Total Cooling Capacity
Range: > 0
evaporator_air_flow_rate_fraction
Evaporator Air Flow Rate Fraction required
number Ratio of capacity at this speed to the operating mode Rated Evaporator Air Flow Rate
Range: > 0
condenser_air_flow_rate_fraction
Condenser Air Flow Rate Fraction
number Ratio of condenser air flow at this speed to the operating mode Rated Condenser Air Flow Rate
Range: > 0
gross_sensible_heat_ratio
Gross Sensible Heat Ratio
number or Autosize Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
gross_cooling_cop
Gross Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and condenser fan. Does not include supply fan heat or supply fan electrical energy input.
Range: > 0
active_fraction_of_coil_face_area
Active Fraction of Coil Face Area
number 1.0 The fraction of the cooling coil face which is actively cooled at this speed. For non-split-face coils, this should be 1.0.
Range: > 0, ≤ 1
n2017_rated_evaporator_fan_power_per_volume_flow_rate
2017 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_rated_evaporator_fan_power_per_volume_flow_rate
2023 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
evaporative_condenser_pump_power_fraction
Evaporative Condenser Pump Power Fraction
number 1.0 Ratio of evaporative condenser pump power at this speed to the operating mode Nominal Evaporative Condenser Pump Power
Range: > 0
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
total_cooling_capacity_modifier_function_of_temperature_curve_name
Total Cooling Capacity Modifier Function of Temperature Curve Name
reference biquadratic curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb quadratic curve = a + b*edb + c*edb**2 wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
total_cooling_capacity_modifier_function_of_air_flow_fraction_curve_name
Total Cooling Capacity Modifier Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
energy_input_ratio_modifier_function_of_temperature_curve_name
Energy Input Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
energy_input_ratio_modifier_function_of_air_flow_fraction_curve_name
Energy Input Ratio Modifier Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_waste_heat_fraction_of_power_input
Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 Recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
waste_heat_modifier_function_of_temperature_curve_name
Waste Heat Modifier Function of Temperature Curve Name
reference curve = a + b*cdb + c*cdb**2 + d*edb + e*edb**2 + f*cdb*edb cdb = entering condenser dry-bulb temperature (C) edb = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_modifier_function_of_temperature_curve_name
Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the DX cooling coil (C) db = entering dry-bulb temperature seen by the DX cooling coil (C) entering temperature can be outside air or pretreated air. If this curve is used and the Sensible Heat Ratio Modifier Function of Flow Fraction (SHRFFF) Curve Name is blank, the SHRFFF is assumed to be a constant value of 1.0.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow If this curve is used and the Sensible Heat Ratio Modifier Function of Temperature Curve Name (SHRFT) Curve Name is blank, the SHRFT is assumed to be a constant value of 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 1 object types

Coil:Cooling:DX:CurveFit:OperatingMode

Coil:Cooling:DX:MultiSpeed

from idfpy.models import CoilCoolingDXMultiSpeed

Direct expansion (DX) cooling coil and condensing unit (includes electric or engine-driven compressor and condenser fan), multi-speed (or variable-speed). Optional moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Requires two to four sets of performance data and will interpolate between speeds. Modeled as a single coil (multi-speed compressor or multiple compressors with row split or intertwined coil).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
apply_part_load_fraction_to_speeds_greater_than_1
Apply Part Load Fraction to Speeds Greater than 1
choice No One of No, Yes
apply_latent_degradation_to_speeds_greater_than_1
Apply Latent Degradation to Speeds Greater than 1
choice No One of No, Yes
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fuel_type
Fuel Type required
choice One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
number_of_speeds
Number of Speeds required
integer Enter the number of the following sets of data for coil capacity, SHR, COP, flow rate, and associated curves.
Range: ≥ 2, ≤ 4
speed_1_gross_rated_total_cooling_capacity
Speed 1 Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat Gross capacity excluding supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb Speed 1 is defined as low speed
speed_1_gross_rated_sensible_heat_ratio
Speed 1 Gross Rated Sensible Heat Ratio required
number or Autosize Gross Rated Sensible Heat Ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include supply fan heat
speed_1_gross_rated_cooling_cop
Speed 1 Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
speed_1_rated_air_flow_rate
Speed 1 Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, rated SHR and rated COP should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity
n2017_speed_1_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_1_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_1_total_cooling_capacity_function_of_temperature_curve_name
Speed 1 Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_cooling_capacity_function_of_flow_fraction_curve_name
Speed 1 Total Cooling Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_part_load_fraction_correlation_curve_name
Speed 1 Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_nominal_time_for_condensate_removal_to_begin
Speed 1 Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
speed_1_ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Speed 1 Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation Rate from the Cooling Coil (when the compressor first turns off) and the Coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_1_maximum_cycling_rate
Speed 1 Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_1_latent_capacity_time_constant
Speed 1 Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
speed_1_rated_waste_heat_fraction_of_power_input
Speed 1 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 Recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_1_waste_heat_function_of_temperature_curve_name
Speed 1 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_evaporative_condenser_effectiveness
Speed 1 Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
speed_1_evaporative_condenser_air_flow_rate
Speed 1 Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
speed_1_rated_evaporative_condenser_pump_power_consumption
Speed 1 Rated Evaporative Condenser Pump Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at high speed
speed_2_gross_rated_total_cooling_capacity
Speed 2 Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat Gross capacity excluding supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
speed_2_gross_rated_sensible_heat_ratio
Speed 2 Gross Rated Sensible Heat Ratio required
number or Autosize Gross Rated Sensible Heat Ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include supply fan heat
speed_2_gross_rated_cooling_cop
Speed 2 Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
speed_2_rated_air_flow_rate
Speed 2 Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, rated SHR and rated COP should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity for Speed 2.
n2017_speed_2_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_2_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_2_total_cooling_capacity_function_of_temperature_curve_name
Speed 2 Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_cooling_capacity_function_of_flow_fraction_curve_name
Speed 2 Total Cooling Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_part_load_fraction_correlation_curve_name
Speed 2 Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (Cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_nominal_time_for_condensate_removal_to_begin
Speed 2 Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
speed_2_ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Speed 2 Ratio of Initial Moisture Evaporation Rate and steady state Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_2_maximum_cycling_rate
Speed 2 Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_2_latent_capacity_time_constant
Speed 2 Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
speed_2_rated_waste_heat_fraction_of_power_input
Speed 2 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 Recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_2_waste_heat_function_of_temperature_curve_name
Speed 2 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_evaporative_condenser_effectiveness
Speed 2 Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
speed_2_evaporative_condenser_air_flow_rate
Speed 2 Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
speed_2_rated_evaporative_condenser_pump_power_consumption
Speed 2 Rated Evaporative Condenser Pump Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at low speed
speed_3_gross_rated_total_cooling_capacity
Speed 3 Gross Rated Total Cooling Capacity
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat Gross capacity excluding supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
speed_3_gross_rated_sensible_heat_ratio
Speed 3 Gross Rated Sensible Heat Ratio
number or Autosize Gross Rated Sensible Heat Ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include supply fan heat
speed_3_gross_rated_cooling_cop
Speed 3 Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
speed_3_rated_air_flow_rate
Speed 3 Rated Air Flow Rate
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, rated SHR and rated COP should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity for Speed 3.
n2017_speed_3_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 3 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_3_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 3 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_3_total_cooling_capacity_function_of_temperature_curve_name
Speed 3 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_total_cooling_capacity_function_of_flow_fraction_curve_name
Speed 3 Total Cooling Capacity Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_part_load_fraction_correlation_curve_name
Speed 3 Part Load Fraction Correlation Curve Name
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (Cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_nominal_time_for_condensate_removal_to_begin
Speed 3 Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
speed_3_ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Speed 3 Ratio of Initial Moisture Evaporation Rate and steady state Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_3_maximum_cycling_rate
Speed 3 Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_3_latent_capacity_time_constant
Speed 3 Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
speed_3_rated_waste_heat_fraction_of_power_input
Speed 3 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 Recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_3_waste_heat_function_of_temperature_curve_name
Speed 3 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_evaporative_condenser_effectiveness
Speed 3 Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
speed_3_evaporative_condenser_air_flow_rate
Speed 3 Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
speed_3_rated_evaporative_condenser_pump_power_consumption
Speed 3 Rated Evaporative Condenser Pump Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at Low speed
speed_4_gross_rated_total_cooling_capacity
Speed 4 Gross Rated Total Cooling Capacity
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat Gross capacity excluding supply air fan heat Rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
speed_4_gross_rated_sensible_heat_ratio
Speed 4 Gross Rated Sensible Heat Ratio
number or Autosize Gross Rated Sensible Heat Ratio (gross sensible capacity/gross total capacity) Sensible and total capacities do not include supply fan heat
speed_4_gross_rated_cooling_cop
Speed 4 Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
speed_4_rated_air_flow_rate
Speed 4 Rated Air Flow Rate
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, rated SHR and rated COP should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity for Speed 4
n2017_speed_4_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 4 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_4_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 4 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_4_total_cooling_capacity_function_of_temperature_curve_name
Speed 4 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_cooling_capacity_function_of_flow_fraction_curve_name
Speed 4 Total Cooling Capacity Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_part_load_fraction_correlation_curve_name
Speed 4 Part Load Fraction Correlation Curve Name
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_nominal_time_for_condensate_removal_to_begin
Speed 4 Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
speed_4_ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Speed 4 Ratio of Initial Moisture Evaporation Rate and steady state Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_4_maximum_cycling_rate
Speed 4 Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
speed_4_latent_capacity_time_constant
Speed 4 Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
speed_4_rated_waste_heat_fraction_of_power_input
Speed 4 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 Recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_4_waste_heat_function_of_temperature_curve_name
Speed 4 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_evaporative_condenser_effectiveness
Speed 4 Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
speed_4_evaporative_condenser_air_flow_rate
Speed 4 Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
speed_4_rated_evaporative_condenser_pump_power_consumption
Speed 4 Rated Evaporative Condenser Pump Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at Speed 4
zone_name_for_condenser_placement
Zone Name for Condenser Placement
reference This input field is name of a conditioned or unconditioned zone where the secondary coil (condenser) of DX system or a heat pump is to be placed. This is an optional input field specified only when user desires to reject the condenser heat into a zone. The heat rejected is modelled as internal sensible heat gain of the zone.
Names a Zone
Referenced by 5 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:WaterHeating:Desuperheater

Coil:Cooling:DX:SingleSpeed

from idfpy.models import CoilCoolingDXSingleSpeed

Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), single-speed. Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
gross_rated_sensible_heat_ratio
Gross Rated Sensible Heat Ratio required
number or Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
gross_rated_cooling_cop
Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, Rated SHR and Rated COP should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity
n2017_rated_evaporator_fan_power_per_volume_flow_rate
2017 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_rated_evaporator_fan_power_per_volume_flow_rate
2023 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
total_cooling_capacity_function_of_temperature_curve_name
Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
total_cooling_capacity_function_of_flow_fraction_curve_name
Total Cooling Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
energy_input_ratio_function_of_temperature_curve_name
Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
energy_input_ratio_function_of_flow_fraction_curve_name
Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
nominal_time_for_condensate_removal_to_begin
Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
evaporative_condenser_air_flow_rate
Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
sensible_heat_ratio_function_of_temperature_curve_name
Sensible Heat Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the DX cooling coil (C) db = entering dry-bulb temperature seen by the DX cooling coil (C) entering temperature can be outside air or pretreated air.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_function_of_flow_fraction_curve_name
Sensible Heat Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
report_ashrae_standard_127_performance_ratings
Report ASHRAE Standard 127 Performance Ratings
choice No when this input field is specified as Yes then the program calculates the net cooling capacity and total electric power input of DX cooling coils per ANSI/ASHRAE 127.
One of No, Yes
zone_name_for_condenser_placement
Zone Name for Condenser Placement
reference This input field is name of a conditioned or unconditioned zone where the secondary coil (condenser) of DX system or a heat pump is to be placed. This is an optional input field specified only when user desires to reject the condenser heat into a zone. The heat rejected is modelled as internal sensible heat gain of the zone.
Names a Zone
Referenced by 15 object types

AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, CoilSystem:Cooling:DX, CoilSystem:Cooling:DX:HeatExchangerAssisted, Dehumidifier:Desiccant:System, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:WindowAirConditioner

Coil:Cooling:DX:SingleSpeed:ThermalStorage

from idfpy.models import CoilCoolingDXSingleSpeedThermalStorage

Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), single-speed with packaged integrated thermal storage for cooling.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
operating_mode_control_method
Operating Mode Control Method required
choice One of EMSControlled, ScheduledModes
operation_mode_control_schedule_name
Operation Mode Control Schedule Name
reference This field is used if the control method is set to ScheduledModes Schedule values control operating mode: 0=off, 1=cooling only, 2= cooling and charge, 3= cooling and discharge, 4= charge only, and 5= discharge only
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
storage_type
Storage Type required
choice One of Ice, UserDefinedFluidType, Water
user_defined_fluid_type
User Defined Fluid Type
reference This field is required when Storage Type is UserDefinedFluidType
Names a FluidProperties:GlycolConcentration, FluidProperties:Name
fluid_storage_volume
Fluid Storage Volume
number or Autocalculate
m3
required field if Storage Type is Water or UserDefinedFluidType
ice_storage_capacity
Ice Storage Capacity
number or Autocalculate
GJ
required field if Storage Type is Ice
storage_capacity_sizing_factor
Storage Capacity Sizing Factor
number
hr
If one of the previous two fields is set to autocalculate, this determines the storage capacity as a function of Cooling Only Mode Rated Total Evaporator Cooling Capacity
storage_tank_ambient_temperature_node_name
Storage Tank Ambient Temperature Node Name required
string
storage_tank_to_ambient_u_value_times_area_heat_transfer_coefficient
Storage Tank to Ambient U-value Times Area Heat Transfer Coefficient required
number
W/K
Range: > 0
fluid_storage_tank_rating_temperature
Fluid Storage Tank Rating Temperature
number
C
required field if Storage Type is Water or UserDefinedFluidType
rated_evaporator_air_flow_rate
Rated Evaporator Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, Rated SHR and Rated COP
evaporator_air_inlet_node_name
Evaporator Air Inlet Node Name required
string
evaporator_air_outlet_node_name
Evaporator Air Outlet Node Name required
string
cooling_only_mode_available
Cooling Only Mode Available required
choice One of No, Yes
cooling_only_mode_rated_total_evaporator_cooling_capacity
Cooling Only Mode Rated Total Evaporator Cooling Capacity
number or Autosize
W
required field if Cooling Only Mode is available or if autocalculating sizes gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
cooling_only_mode_rated_sensible_heat_ratio
Cooling Only Mode Rated Sensible Heat Ratio
number 0.7 required field if Cooling Only Mode is available Rated sensible heat ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
Range: ≥ 0, ≤ 1
cooling_only_mode_rated_cop
Cooling Only Mode Rated COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input required field if Cooling Only Mode is available
Range: > 0
cooling_only_mode_total_evaporator_cooling_capacity_function_of_temperature_curve_name
Cooling Only Mode Total Evaporator Cooling Capacity Function of Temperature Curve Name
reference required field if Cooling Only Mode is available Any curve or table with two independent variables can be used biquadratic curve = a + b*ewb + c*ewb**2 + d*db + e*db**2 + f*ewb*db x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_only_mode_total_evaporator_cooling_capacity_function_of_flow_fraction_curve_name
Cooling Only Mode Total Evaporator Cooling Capacity Function of Flow Fraction Curve Name
reference required field if Cooling Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow rate
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_only_mode_energy_input_ratio_function_of_temperature_curve_name
Cooling Only Mode Energy Input Ratio Function of Temperature Curve Name
reference required field if Cooling Only Mode is available Any curve or table with two independent variables can be used curve = a + b*ewb + c*ewb**2 + d*db + e*db**2 + f*ewb*db x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_only_mode_energy_input_ratio_function_of_flow_fraction_curve_name
Cooling Only Mode Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Cooling Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_only_mode_part_load_fraction_correlation_curve_name
Cooling Only Mode Part Load Fraction Correlation Curve Name
reference required field if Cooling Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_only_mode_sensible_heat_ratio_function_of_temperature_curve_name
Cooling Only Mode Sensible Heat Ratio Function of Temperature Curve Name
reference required field if Cooling Only Mode is available Any curve or table with two independent variables can be used curve = a + b*ewb + c*ewb**2 + d*edb + e*edb**2 + f*ewb*edb x = ewb = evaporator entering wet-bulb temperature seen by the cooling coil (C) y = edb = evaporator entering dry-bulb temperature seen by the cooling coil (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_only_mode_sensible_heat_ratio_function_of_flow_fraction_curve_name
Cooling Only Mode Sensible Heat Ratio Function of Flow Fraction Curve Name
reference required field if Cooling Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_available
Cooling And Charge Mode Available required
choice One of No, Yes
cooling_and_charge_mode_rated_total_evaporator_cooling_capacity
Cooling And Charge Mode Rated Total Evaporator Cooling Capacity
number or Autocalculate
W
required field if Cooling And Charge Mode is available gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb thermal storage tank at Fluid Storage Tank Rating Temperature (water or fluid) or storage faction of 0.5 (ice)
cooling_and_charge_mode_capacity_sizing_factor
Cooling And Charge Mode Capacity Sizing Factor
number 0.5 If previous field is autocalculate, this determines the evaporator capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
cooling_and_charge_mode_rated_storage_charging_capacity
Cooling And Charge Mode Rated Storage Charging Capacity
number or Autocalculate
W
required field if Cooling And Charge Mode is available net capacity including any internal devices rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb thermal storage tank at Fluid Storage Tank Rating Temperature (water or fluid) or storage faction of 0.5 (ice)
cooling_and_charge_mode_storage_capacity_sizing_factor
Cooling And Charge Mode Storage Capacity Sizing Factor
number 0.5 If previous field is autocalculate, this determines the storage cooling capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
cooling_and_charge_mode_rated_sensible_heat_ratio
Cooling And Charge Mode Rated Sensible Heat Ratio
number 0.7 required field if Cooling And Charge Mode is available Rated sensible heat ratio (gross sensible evaporator capacity/gross total evaporator capacity) sensible and total capacities do not include supply fan heat
Range: ≥ 0, ≤ 1
cooling_and_charge_mode_cooling_rated_cop
Cooling And Charge Mode Cooling Rated COP
number
W/W
3.0 Gross evaporator cooling capacity divided by power input to the compressor (for cooling) and outdoor fan, does not include supply fan heat or supply fan electrical energy input required field if Cooling And Charge Mode is available
Range: ≥ 0
cooling_and_charge_mode_charging_rated_cop
Cooling And Charge Mode Charging Rated COP
number
W/W
3.0 net cooling capacity divided by power input to the compressor (for charging) and outdoor fan, includes any internal devices required field if Cooling And Charge Mode is available
Range: > 0
cooling_and_charge_mode_total_evaporator_cooling_capacity_function_of_temperature_curve_name
Cooling And Charge Mode Total Evaporator Cooling Capacity Function of Temperature Curve Name
reference required field if Cooling And Charge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_charge_mode_total_evaporator_cooling_capacity_function_of_flow_fraction_curve_name
Cooling And Charge Mode Total Evaporator Cooling Capacity Function of Flow Fraction Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_evaporator_energy_input_ratio_function_of_temperature_curve_name
Cooling And Charge Mode Evaporator Energy Input Ratio Function of Temperature Curve Name
reference required field if Cooling And Charge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_charge_mode_evaporator_energy_input_ratio_function_of_flow_fraction_curve_name
Cooling And Charge Mode Evaporator Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_evaporator_part_load_fraction_correlation_curve_name
Cooling And Charge Mode Evaporator Part Load Fraction Correlation Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_storage_charge_capacity_function_of_temperature_curve_name
Cooling And Charge Mode Storage Charge Capacity Function of Temperature Curve Name
reference required field if Cooling And Charge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_charge_mode_storage_charge_capacity_function_of_total_evaporator_plr_curve_name
Cooling And Charge Mode Storage Charge Capacity Function of Total Evaporator PLR Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_storage_energy_input_ratio_function_of_temperature_curve_name
Cooling And Charge Mode Storage Energy Input Ratio Function of Temperature Curve Name
reference required field if Cooling And Charge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_charge_mode_storage_energy_input_ratio_function_of_flow_fraction_curve_name
Cooling And Charge Mode Storage Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_storage_energy_part_load_fraction_correlation_curve_name
Cooling And Charge Mode Storage Energy Part Load Fraction Correlation Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_charge_mode_sensible_heat_ratio_function_of_temperature_curve_name
Cooling And Charge Mode Sensible Heat Ratio Function of Temperature Curve Name
reference required field if Cooling And Charge Mode is available Curves or tables with either two or three independent variables can be used. Curve:Biquadratic, Table:Lookup, Curve:Bicubic and Curve:QuadraticLinear allowed curve = a + b*ewb + c*ewb**2 + d*edb + e*edb**2 + f*ewb*edb x = ewb = entering wet-bulb temperature seen by the cooling coil (C) y = edb = entering dry-bulb temperature seen by the cooling coil (C) Also allows Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = edb, z = stes) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:ChillerPartLoadWithLift, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Curve:Triquadratic, Table:Lookup
cooling_and_charge_mode_sensible_heat_ratio_function_of_flow_fraction_curve_name
Cooling And Charge Mode Sensible Heat Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Charge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_available
Cooling And Discharge Mode Available required
choice One of No, Yes
cooling_and_discharge_mode_rated_total_evaporator_cooling_capacity
Cooling And Discharge Mode Rated Total Evaporator Cooling Capacity
number or Autocalculate
W
required field if Cooling And Discharge Mode is available gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb thermal storage tank at Fluid Storage Tank Rating Temperature (water or fluid) or storage faction of 0.5 (ice)
cooling_and_discharge_mode_evaporator_capacity_sizing_factor
Cooling And Discharge Mode Evaporator Capacity Sizing Factor
number 1.0 If previous field is autocalculate, this determines the charging capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
cooling_and_discharge_mode_rated_storage_discharging_capacity
Cooling And Discharge Mode Rated Storage Discharging Capacity
number or Autocalculate
W
required field if Cooling And Discharge Mode is available net capacity including any internal devices rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb thermal storage tank at 26.7 C (water) or storage faction of 0.5 (ice)
cooling_and_discharge_mode_storage_discharge_capacity_sizing_factor
Cooling And Discharge Mode Storage Discharge Capacity Sizing Factor
number 1.0 If previous field is autocalculate, this determines the charging capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
cooling_and_discharge_mode_rated_sensible_heat_ratio
Cooling And Discharge Mode Rated Sensible Heat Ratio
number 0.7 required field if Cooling And Discharge Mode is available Rated sensible heat ratio (gross sensible evaporator capacity/gross total evaporator capacity) sensible and total capacities do not include supply fan heat
Range: ≥ 0, ≤ 1
cooling_and_discharge_mode_cooling_rated_cop
Cooling And Discharge Mode Cooling Rated COP
number
W/W
3.0 Gross evaporator cooling capacity divided by power input to the compressor (for cooling) and outdoor fan, does not include supply fan heat or supply fan electrical energy input required field if Cooling And Discharge Mode is available
Range: ≥ 0
cooling_and_discharge_mode_discharging_rated_cop
Cooling And Discharge Mode Discharging Rated COP
number
W/W
3.0 gross cooling capacity divided by power input to the compressor (for discharging), includes any internal devices for discharging storage but not supply fan required field if Cooling And Discharge Mode is available
Range: > 0
cooling_and_discharge_mode_total_evaporator_cooling_capacity_function_of_temperature_curve_name
Cooling And Discharge Mode Total Evaporator Cooling Capacity Function of Temperature Curve Name
reference required field if Cooling Only Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_discharge_mode_total_evaporator_cooling_capacity_function_of_flow_fraction_curve_name
Cooling And Discharge Mode Total Evaporator Cooling Capacity Function of Flow Fraction Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_evaporator_energy_input_ratio_function_of_temperature_curve_name
Cooling And Discharge Mode Evaporator Energy Input Ratio Function of Temperature Curve Name
reference required field if Cooling And Discharge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_discharge_mode_evaporator_energy_input_ratio_function_of_flow_fraction_curve_name
Cooling And Discharge Mode Evaporator Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_evaporator_part_load_fraction_correlation_curve_name
Cooling And Discharge Mode Evaporator Part Load Fraction Correlation Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_storage_discharge_capacity_function_of_temperature_curve_name
Cooling And Discharge Mode Storage Discharge Capacity Function of Temperature Curve Name
reference required field if Cooling And Discharge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_discharge_mode_storage_discharge_capacity_function_of_flow_fraction_curve_name
Cooling And Discharge Mode Storage Discharge Capacity Function of Flow Fraction Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_storage_discharge_capacity_function_of_total_evaporator_plr_curve_name
Cooling And Discharge Mode Storage Discharge Capacity Function of Total Evaporator PLR Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x =PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_storage_energy_input_ratio_function_of_temperature_curve_name
Cooling And Discharge Mode Storage Energy Input Ratio Function of Temperature Curve Name
reference required field if Cooling And Discharge Mode is available Allowed curve or table objects are Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = db, z = stes) x = ewb = evaporator entering wet-bulb temperature (C) y = db = dry-bulb temperature seen by the condenser (C) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:ChillerPartLoadWithLift, Curve:Triquadratic, Table:Lookup
cooling_and_discharge_mode_storage_energy_input_ratio_function_of_flow_fraction_curve_name
Cooling And Discharge Mode Storage Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_storage_energy_part_load_fraction_correlation_curve_name
Cooling And Discharge Mode Storage Energy Part Load Fraction Correlation Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 x = PLR = part load ratio (evaporator cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_and_discharge_mode_sensible_heat_ratio_function_of_temperature_curve_name
Cooling And Discharge Mode Sensible Heat Ratio Function of Temperature Curve Name
reference required field if Cooling And Discharge Mode is available Curves or tables with either two or three independent variables can be used. curve = a + b*ewb + c*ewb**2 + d*edb + e*edb**2 + f*ewb*edb x = ewb = entering wet-bulb temperature seen by the cooling coil (C) y = edb = entering dry-bulb temperature seen by the cooling coil (C) Also allows Curve:Triquadratic and Table:Lookup curve or table = func(x = ewb, y = edb, z = stes) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:ChillerPartLoadWithLift, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Curve:Triquadratic, Table:Lookup
cooling_and_discharge_mode_sensible_heat_ratio_function_of_flow_fraction_curve_name
Cooling And Discharge Mode Sensible Heat Ratio Function of Flow Fraction Curve Name
reference required field if Cooling And Discharge Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
charge_only_mode_available
Charge Only Mode Available required
choice One of No, Yes
charge_only_mode_rated_storage_charging_capacity
Charge Only Mode Rated Storage Charging Capacity
number or Autocalculate
W
required field if Charge Only Mode is available net capacity including any internal devices air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb thermal storage tank at 26.7 C (water) or storage faction of 0.5 (ice)
charge_only_mode_capacity_sizing_factor
Charge Only Mode Capacity Sizing Factor
number 1.0 If previous field is autocalculate, this determines the charging capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
charge_only_mode_charging_rated_cop
Charge Only Mode Charging Rated COP
number
W/W
3.0 net cooling capacity divided by power input to the compressor (for charging) and outdoor fan, includes any internal devices required field if Charge Only Mode is available
Range: > 0
charge_only_mode_storage_charge_capacity_function_of_temperature_curve_name
Charge Only Mode Storage Charge Capacity Function of Temperature Curve Name
reference required field if Charge Only Mode is available Any curve or table with two independent variables can be used curve = a + b*db + c*db**2 + d*stes + e*stes**2 + f*db*stes x = db = dry-bulb temperature seen by the condenser (C) y = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
charge_only_mode_storage_energy_input_ratio_function_of_temperature_curve_name
Charge Only Mode Storage Energy Input Ratio Function of Temperature Curve Name
reference required field if Charge Only Mode is available Any curve or table with two independent variables can be used curve = a + b*db + c*db**2 + d*stes + e*stes**2 + f*db*stes x = db = dry-bulb temperature seen by the condenser (C) y = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
discharge_only_mode_available
Discharge Only Mode Available required
choice One of No, Yes
discharge_only_mode_rated_storage_discharging_capacity
Discharge Only Mode Rated Storage Discharging Capacity
number or Autocalculate
W
required field if Discharge Only Mode is available net capacity including any internal devices rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and thermal storage tank at 26.7 C (water) or storage faction of 0.5 (ice)
discharge_only_mode_capacity_sizing_factor
Discharge Only Mode Capacity Sizing Factor
number 1.0 If previous field is autocalculate, this determines the discharging capacity as a multiplier on the Cooling Only Mode Rated Total Evaporator Cooling Capacity
discharge_only_mode_rated_sensible_heat_ratio
Discharge Only Mode Rated Sensible Heat Ratio
number required field if Discharge Only Mode is available Rated sensible heat ratio (gross sensible evaporator capacity/gross total evaporator capacity) sensible and total capacities do not include supply fan heat
Range: ≥ 0, ≤ 1
discharge_only_mode_rated_cop
Discharge Only Mode Rated COP
number
W/W
3.0 required field if Discharge Only Mode is available gross cooling capacity divided by power input to the compressor (for discharging), includes any internal devices for discharging storage but not supply fan
Range: > 0
discharge_only_mode_storage_discharge_capacity_function_of_temperature_curve_name
Discharge Only Mode Storage Discharge Capacity Function of Temperature Curve Name
reference required field if Discharge Only Mode is available Any curve or table with two independent variables can be used curve = a + b*ewb + c*ewb**2 + d*stes + e*stes**2 + f*ewb*stes x = ewb = evaporator entering wet-bulb temperature (C) y = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
discharge_only_mode_storage_discharge_capacity_function_of_flow_fraction_curve_name
Discharge Only Mode Storage Discharge Capacity Function of Flow Fraction Curve Name
reference required field if Discharge Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
discharge_only_mode_energy_input_ratio_function_of_temperature_curve_name
Discharge Only Mode Energy Input Ratio Function of Temperature Curve Name
reference required field if Discharge Only Mode is available Any curve or table with two independent variables can be used curve = a + b*ewb + c*ewb**2 + d*stes + e*stes**2 + f*ewb*stes x = ewb = evaporator entering wet-bulb temperature (C) y = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
discharge_only_mode_energy_input_ratio_function_of_flow_fraction_curve_name
Discharge Only Mode Energy Input Ratio Function of Flow Fraction Curve Name
reference required field if Discharge Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 x = ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
discharge_only_mode_part_load_fraction_correlation_curve_name
Discharge Only Mode Part Load Fraction Correlation Curve Name
reference required field if Discharge Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
discharge_only_mode_sensible_heat_ratio_function_of_temperature_curve_name
Discharge Only Mode Sensible Heat Ratio Function of Temperature Curve Name
reference required field if Discharge Only Mode is available Curves or tables with either two or three independent variables can be used. For two independent variables: x = ewb = entering wet-bulb temperature seen by the cooling coil (C) y = edb = entering dry-bulb temperature seen by the cooling coil (C) For three independent variables: curve or table = func(x = ewb, y = edb, z = stes) z = stes = state of thermal energy storage (C or fraction)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:ChillerPartLoadWithLift, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Curve:Triquadratic, Table:Lookup
discharge_only_mode_sensible_heat_ratio_function_of_flow_fraction_curve_name
Discharge Only Mode Sensible Heat Ratio Function of Flow Fraction Curve Name
reference required field if Discharge Only Mode is available Any curve or table with one independent variable can be used quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = Fraction of the full load evaporator air flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
ancillary_electric_power
Ancillary Electric Power
number
W
controls and miscellaneous standby ancillary electric power draw, when available
Range: ≥ 0
cold_weather_operation_minimum_outdoor_air_temperature
Cold Weather Operation Minimum Outdoor Air Temperature
number
C
cold_weather_operation_ancillary_power
Cold Weather Operation Ancillary Power
number
W
Range: ≥ 0
condenser_air_inlet_node_name
Condenser Air Inlet Node Name required
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_air_outlet_node_name
Condenser Air Outlet Node Name required
string
condenser_design_air_flow_rate
Condenser Design Air Flow Rate required
number or Autocalculate
m3/s
Used to calculate condenser leaving conditions and water use if evaporatively cooled.
condenser_air_flow_sizing_factor
Condenser Air Flow Sizing Factor
number 1.0 If previous field is autocalculate, this determines the condenser air flow size as a multiplier on the Rated Evaporator Air Flow Rate.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.7 required field if condenser type is evaporatively cooled
Range: > 0, ≤ 1
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off. If this field is blank, the basin heater is always available.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_availability_schedule_name
Basin Heater Availability Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
storage_tank_plant_connection_inlet_node_name
Storage Tank Plant Connection Inlet Node Name
string
storage_tank_plant_connection_outlet_node_name
Storage Tank Plant Connection Outlet Node Name
string
storage_tank_plant_connection_design_flow_rate
Storage Tank Plant Connection Design Flow Rate
number
m3/s
Range: ≥ 0
storage_tank_plant_connection_heat_transfer_effectiveness
Storage Tank Plant Connection Heat Transfer Effectiveness
number 0.7 Range: ≥ 0, ≤ 1
storage_tank_minimum_operating_limit_fluid_temperature
Storage Tank Minimum Operating Limit Fluid Temperature
number
C
For fluid storage tanks only, minimum limit for storage tank If omitted,then the minimum temperature limit is that used for fluid property data.
storage_tank_maximum_operating_limit_fluid_temperature
Storage Tank Maximum Operating Limit Fluid Temperature
number
C
For fluid storage tanks only, maximum limit for storage tank If omitted,then the maximum temperature limit is that used for fluid property data.
Referenced by 15 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:DX, CoilSystem:Cooling:DX:HeatExchangerAssisted, Dehumidifier:Desiccant:System, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:WindowAirConditioner

Coil:Cooling:DX:TwoSpeed

from idfpy.models import CoilCoolingDXTwoSpeed

Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), two-speed (or variable-speed). Requires two sets of performance data and will interpolate between speeds. Modeled as a single coil (multi-speed compressor or multiple compressors with row split or intertwined coil).

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
high_speed_gross_rated_total_cooling_capacity
High Speed Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
high_speed_rated_sensible_heat_ratio
High Speed Rated Sensible Heat Ratio required
number or Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
high_speed_gross_rated_cooling_cop
High Speed Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
high_speed_rated_air_flow_rate
High Speed Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, Rated SHR and Rated COP. Should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity.
high_speed_2017_rated_evaporator_fan_power_per_volume_flow_rate
High Speed 2017 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
high_speed_2023_rated_evaporator_fan_power_per_volume_flow_rate
High Speed 2023 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
unit_internal_static_air_pressure
Unit Internal Static Air Pressure
number
Pa
Enter pressure drop for the unit containing the coil. This value is only used to calculate Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity. This value is not used for modeling the evaporator fan during simulations.
Range: > 0
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
total_cooling_capacity_function_of_temperature_curve_name
Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
total_cooling_capacity_function_of_flow_fraction_curve_name
Total Cooling Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
energy_input_ratio_function_of_temperature_curve_name
Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
energy_input_ratio_function_of_flow_fraction_curve_name
Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
low_speed_gross_rated_total_cooling_capacity
Low Speed Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
low_speed_gross_rated_sensible_heat_ratio
Low Speed Gross Rated Sensible Heat Ratio required
number or Autosize Gross Rated Sensible Heat Ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
low_speed_gross_rated_cooling_cop
Low Speed Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
low_speed_rated_air_flow_rate
Low Speed Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total cooling capacity, Rated SHR and Rated COP. Should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity.
low_speed_2017_rated_evaporator_fan_power_per_volume_flow_rate
Low Speed 2017 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
low_speed_2023_rated_evaporator_fan_power_per_volume_flow_rate
Low Speed 2023 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), Energy Efficiency Ratio (EER), Integrated Energy Efficiency Ratio (IEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
low_speed_total_cooling_capacity_function_of_temperature_curve_name
Low Speed Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
low_speed_energy_input_ratio_function_of_temperature_curve_name
Low Speed Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
high_speed_evaporative_condenser_effectiveness
High Speed Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
high_speed_evaporative_condenser_air_flow_rate
High Speed Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
high_speed_evaporative_condenser_pump_rated_power_consumption
High Speed Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at high speed
low_speed_evaporative_condenser_effectiveness
Low Speed Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
low_speed_evaporative_condenser_air_flow_rate
Low Speed Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
low_speed_evaporative_condenser_pump_rated_power_consumption
Low Speed Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
Rated power consumed by the evaporative condenser's water pump at low speed
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
sensible_heat_ratio_function_of_temperature_curve_name
Sensible Heat Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the DX cooling coil (C) db = entering dry-bulb temperature seen by the DX cooling coil (C) entering temperature can be outside air or pretreated air.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_function_of_flow_fraction_curve_name
Sensible Heat Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
low_speed_sensible_heat_ratio_function_of_temperature_curve_name
Low Speed Sensible Heat Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the DX cooling coil (C) db = entering dry-bulb temperature seen by the DX cooling coil (C) entering temperature can be outside air or pretreated air.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
low_speed_sensible_heat_ratio_function_of_flow_fraction_curve_name
Low Speed Sensible Heat Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
zone_name_for_condenser_placement
Zone Name for Condenser Placement
reference This input field is name of a conditioned or unconditioned zone where the secondary coil (condenser) of DX system or a heat pump is to be placed. This is an optional input field specified only when user desires to reject the condenser heat into a zone. The heat rejected is modelled as internal sensible heat gain of the zone.
Names a Zone
Referenced by 6 object types

AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, CoilSystem:Cooling:DX

Coil:Cooling:DX:TwoStageWithHumidityControlMode

from idfpy.models import CoilCoolingDXTwoStageWithHumidityControlMode

Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), two-stage with humidity control mode (e.g. sub-cool or hot gas reheat). Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Requires two to four sets of performance data, see CoilPerformance:DX:Cooling. Stages are modeled as a face-split coil.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
number_of_capacity_stages
Number of Capacity Stages
integer 1 Range: ≥ 1, ≤ 2
number_of_enhanced_dehumidification_modes
Number of Enhanced Dehumidification Modes
integer 0 Range: ≥ 0, ≤ 1
normal_mode_stage_1_coil_performance_object_type
Normal Mode Stage 1 Coil Performance Object Type required
choice One of CoilPerformance:DX:Cooling
normal_mode_stage_1_coil_performance_name
Normal Mode Stage 1 Coil Performance Name required
reference Names a CoilPerformance:DX:Cooling
normal_mode_stage_1_2_coil_performance_object_type
Normal Mode Stage 1+2 Coil Performance Object Type
choice One of CoilPerformance:DX:Cooling
normal_mode_stage_1_2_coil_performance_name
Normal Mode Stage 1+2 Coil Performance Name
reference Names a CoilPerformance:DX:Cooling
dehumidification_mode_1_stage_1_coil_performance_object_type
Dehumidification Mode 1 Stage 1 Coil Performance Object Type
choice One of CoilPerformance:DX:Cooling
dehumidification_mode_1_stage_1_coil_performance_name
Dehumidification Mode 1 Stage 1 Coil Performance Name
reference Names a CoilPerformance:DX:Cooling
dehumidification_mode_1_stage_1_2_coil_performance_object_type
Dehumidification Mode 1 Stage 1+2 Coil Performance Object Type
choice One of CoilPerformance:DX:Cooling
dehumidification_mode_1_stage_1_2_coil_performance_name
Dehumidification Mode 1 Stage 1+2 Coil Performance Name
reference Names a CoilPerformance:DX:Cooling
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 8 object types

AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, CoilSystem:Cooling:DX, Dehumidifier:Desiccant:System

Coil:Cooling:DX:VariableRefrigerantFlow

from idfpy.models import CoilCoolingDXVariableRefrigerantFlow

Variable refrigerant flow (VRF) direct expansion (DX) cooling coil. Used with ZoneHVAC:TerminalUnit:VariableRefrigerantFlow. Condensing unit is modeled separately, see AirConditioner:VariableRefrigerantFlow.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat Cooling capacity excluding supply air fan heat
gross_rated_sensible_heat_ratio
Gross Rated Sensible Heat Ratio required
number or Autosize Sensible heat ratio excluding supply air fan heat
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
Volume flow rate corresponding to rated total cooling capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity
cooling_capacity_ratio_modifier_function_of_temperature_curve_name
Cooling Capacity Ratio Modifier Function of Temperature Curve Name required
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
cooling_capacity_modifier_curve_function_of_flow_fraction_name
Cooling Capacity Modifier Curve Function of Flow Fraction Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
coil_air_inlet_node
Coil Air Inlet Node required
string
coil_air_outlet_node
Coil Air Outlet Node required
string
name_of_water_storage_tank_for_condensate_collection
Name of Water Storage Tank for Condensate Collection
reference Names a WaterUse:Storage
Referenced by 1 object types

ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Coil:Cooling:DX:VariableRefrigerantFlow:FluidTemperatureControl

from idfpy.models import CoilCoolingDXVariableRefrigerantFlowFluidTemperatureControl

This is a key object in the new physics based VRF model applicable for Fluid Temperature Control. It describes the the indoor unit coil of the system at cooling mode. Used with ZoneHVAC:TerminalUnit:VariableRefrigerantFlow. Outdoor unit is modeled separately, see AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl or AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Enter the name of a schedule that defines the availability of the coil Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
coil_air_inlet_node
Coil Air Inlet Node required
string the inlet node to the coil
coil_air_outlet_node
Coil Air Outlet Node required
string the outlet node to the coil
rated_total_cooling_capacity
Rated Total Cooling Capacity required
number or Autosize
W
Supply air fan heat is not included
rated_sensible_heat_ratio
Rated Sensible Heat Ratio required
number or Autosize Supply air fan heat is not included
indoor_unit_reference_superheating
Indoor Unit Reference Superheating
number
deltaC
5.0 Range: ≥ 0
indoor_unit_evaporating_temperature_function_of_superheating_curve_name
Indoor Unit Evaporating Temperature Function of Superheating Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
name_of_water_storage_tank_for_condensate_collection
Name of Water Storage Tank for Condensate Collection
reference Names a WaterUse:Storage
Referenced by 1 object types

ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Coil:Cooling:DX:VariableSpeed

from idfpy.models import CoilCoolingDXVariableSpeed

Direct expansion (DX) cooling coil and condensing unit (includes electric compressor and condenser fan), variable-speed. Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Requires two to ten sets of performance data and will interpolate between speeds. Modeled as a single coil with variable-speed compressor.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
indoor_air_inlet_node_name
Indoor Air Inlet Node Name required
string
indoor_air_outlet_node_name
Indoor Air Outlet Node Name required
string
number_of_speeds
Number of Speeds
integer
dimensionless
2 Range: ≥ 1, ≤ 10
nominal_speed_level
Nominal Speed Level
integer
dimensionless
2 must be lower than or equal to the highest speed number
gross_rated_total_cooling_capacity_at_selected_nominal_speed_level
Gross Rated Total Cooling Capacity At Selected Nominal Speed Level
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
rated_air_flow_rate_at_selected_nominal_speed_level
Rated Air Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
nominal_time_for_condensate_to_begin_leaving_the_coil
Nominal Time for Condensate to Begin Leaving the Coil
number
s
0.0 Range: ≥ 0
initial_moisture_evaporation_rate_divided_by_steady_state_ac_latent_capacity
Initial Moisture Evaporation Rate Divided by Steady-State AC Latent Capacity
number
dimensionless
0.0 Range: ≥ 0
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
2.5 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
60.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
fan_delay_time
Fan Delay Time
number
s
60.0 Programmed time delay for fan to shut off after compressor cycle off. Enter 0 when fan operating mode is continuous
Range: ≥ 0
energy_part_load_fraction_curve_name
Energy Part Load Fraction Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-25.0
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
speed_1_reference_unit_gross_rated_total_cooling_capacity
Speed 1 Reference Unit Gross Rated Total Cooling Capacity required
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_1_reference_unit_gross_rated_sensible_heat_ratio
Speed 1 Reference Unit Gross Rated Sensible Heat Ratio required
number
dimensionless
Range: ≥ 0, ≤ 1
speed_1_reference_unit_gross_rated_cooling_cop
Speed 1 Reference Unit Gross Rated Cooling COP required
number
W/W
Range: > 0
speed_1_reference_unit_rated_air_flow_rate
Speed 1 Reference Unit Rated Air Flow Rate required
number
m3/s
Range: ≥ 0
n2017_speed_1_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_1_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_1_reference_unit_rated_condenser_air_flow_rate
Speed 1 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
This field is only used for Condenser Type = EvaporativelyCooled
Range: ≥ 0
speed_1_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 1 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
This field is only used for Condenser Type = EvaporativelyCooled
Range: ≥ 0, ≤ 1
speed_1_total_cooling_capacity_function_of_temperature_curve_name
Speed 1 Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 1 Total Cooling Capacity Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_reference_unit_gross_rated_total_cooling_capacity
Speed 2 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_2_reference_unit_gross_rated_sensible_heat_ratio
Speed 2 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_2_reference_unit_gross_rated_cooling_cop
Speed 2 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_2_reference_unit_rated_air_flow_rate
Speed 2 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_2_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_2_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_2_reference_unit_rated_condenser_air_flow_rate
Speed 2 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_2_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 2 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_2_total_cooling_capacity_function_of_temperature_curve_name
Speed 2 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 2 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_reference_unit_gross_rated_total_cooling_capacity
Speed 3 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_3_reference_unit_gross_rated_sensible_heat_ratio
Speed 3 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_3_reference_unit_gross_rated_cooling_cop
Speed 3 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_3_reference_unit_rated_air_flow_rate
Speed 3 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_3_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 3 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_3_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 3 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_3_reference_unit_rated_condenser_air_flow_rate
Speed 3 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_3_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 3 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_3_total_cooling_capacity_function_of_temperature_curve_name
Speed 3 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 3 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_reference_unit_gross_rated_total_cooling_capacity
Speed 4 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_4_reference_unit_gross_rated_sensible_heat_ratio
Speed 4 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_4_reference_unit_gross_rated_cooling_cop
Speed 4 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_4_reference_unit_rated_air_flow_rate
Speed 4 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_4_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 4 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_4_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 4 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_4_reference_unit_rated_condenser_air_flow_rate
Speed 4 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_4_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 4 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_4_total_cooling_capacity_function_of_temperature_curve_name
Speed 4 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 4 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_reference_unit_gross_rated_total_cooling_capacity
Speed 5 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_5_reference_unit_gross_rated_sensible_heat_ratio
Speed 5 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_5_reference_unit_gross_rated_cooling_cop
Speed 5 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_5_reference_unit_rated_air_flow_rate
Speed 5 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_5_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 5 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_5_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 5 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_5_reference_unit_rated_condenser_air_flow_rate
Speed 5 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_5_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 5 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_5_total_cooling_capacity_function_of_temperature_curve_name
Speed 5 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 5 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_temperature_curve_name
Speed 5 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_reference_unit_gross_rated_total_cooling_capacity
Speed 6 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_6_reference_unit_gross_rated_sensible_heat_ratio
Speed 6 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_6_reference_unit_gross_rated_cooling_cop
Speed 6 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_6_reference_unit_rated_air_flow_rate
Speed 6 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_6_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 6 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_6_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 6 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_6_reference_unit_rated_condenser_air_flow_rate
Speed 6 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_6_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 6 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_6_total_cooling_capacity_function_of_temperature_curve_name
Speed 6 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 6 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_temperature_curve_name
Speed 6 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_reference_unit_gross_rated_total_cooling_capacity
Speed 7 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_7_reference_unit_gross_rated_sensible_heat_ratio
Speed 7 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_7_reference_unit_gross_rated_cooling_cop
Speed 7 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_7_reference_unit_rated_air_flow_rate
Speed 7 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_7_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 7 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_7_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 7 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_7_reference_unit_rated_condenser_air_flow_rate
Speed 7 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_7_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 7 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_7_total_cooling_capacity_function_of_temperature_curve_name
Speed 7 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 7 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_temperature_curve_name
Speed 7 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_reference_unit_gross_rated_total_cooling_capacity
Speed 8 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_8_reference_unit_gross_rated_sensible_heat_ratio
Speed 8 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_8_reference_unit_gross_rated_cooling_cop
Speed 8 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_8_reference_unit_rated_air_flow_rate
Speed 8 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_8_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 8 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_8_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 8 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_8_reference_unit_rated_condenser_air_flow_rate
Speed 8 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
Range: ≥ 0
speed_8_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 8 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
Range: ≥ 0, ≤ 1
speed_8_total_cooling_capacity_function_of_temperature_curve_name
Speed 8 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 8 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_temperature_curve_name
Speed 8 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_reference_unit_gross_rated_total_cooling_capacity
Speed 9 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_9_reference_unit_gross_rated_sensible_heat_ratio
Speed 9 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_9_reference_unit_gross_rated_cooling_cop
Speed 9 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_9_reference_unit_rated_air_flow_rate
Speed 9 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_9_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 9 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_9_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 9 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_9_reference_unit_rated_condenser_air_flow_rate
Speed 9 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
optional
Range: ≥ 0
speed_9_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 9 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
optional
Range: ≥ 0, ≤ 1
speed_9_total_cooling_capacity_function_of_temperature_curve_name
Speed 9 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 9 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_temperature_curve_name
Speed 9 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_reference_unit_gross_rated_total_cooling_capacity
Speed 10 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_10_reference_unit_gross_rated_sensible_heat_ratio
Speed 10 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_10_reference_unit_gross_rated_cooling_cop
Speed 10 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_10_reference_unit_rated_air_flow_rate
Speed 10 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_10_rated_evaporator_fan_power_per_volume_flow_rate
2017 Speed 10 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_10_rated_evaporator_fan_power_per_volume_flow_rate
2023 Speed 10 Rated Evaporator Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the evaporator fan power per air volume flow rate at the rated test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on total cooling capacity. This value is only used to calculate Seasonal Energy Efficiency Ratio (SEER2), and the Standard Rating (Net) Cooling Capacity which will be outputs in the EnergyPlus eio file. This value is not used for modeling the evaporator fan during simulations.
Range: ≥ 0, ≤ 1505
speed_10_reference_unit_rated_condenser_air_flow_rate
Speed 10 Reference Unit Rated Condenser Air Flow Rate
number
m3/s
optional
Range: ≥ 0
speed_10_reference_unit_rated_pad_effectiveness_of_evap_precooling
Speed 10 Reference Unit Rated Pad Effectiveness of Evap Precooling
number
dimensionless
optional
Range: ≥ 0, ≤ 1
speed_10_total_cooling_capacity_function_of_temperature_curve_name
Speed 10 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 10 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_temperature_curve_name
Speed 10 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*odb + e*odb**2 + f*wb*odb wb = entering wet-bulb temperature (C) odb = air entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 16 object types

AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, CoilSystem:Cooling:DX, CoilSystem:Cooling:DX:HeatExchangerAssisted, CoilSystem:IntegratedHeatPump:AirSource, Dehumidifier:Desiccant:System, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:WindowAirConditioner

Coil:Cooling:Water

from idfpy.models import CoilCoolingWater

Chilled water cooling coil, NTU-effectiveness model, with inputs for design entering and leaving conditions.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Autosize
design_air_flow_rate
Design Air Flow Rate
number or Autosize
m3/s
Autosize
design_inlet_water_temperature
Design Inlet Water Temperature
number or Autosize
C
Autosize
design_inlet_air_temperature
Design Inlet Air Temperature
number or Autosize
C
Autosize
design_outlet_air_temperature
Design Outlet Air Temperature
number or Autosize
C
Autosize
design_inlet_air_humidity_ratio
Design Inlet Air Humidity Ratio
number or Autosize
kgWater/kgDryAir
Autosize
design_outlet_air_humidity_ratio
Design Outlet Air Humidity Ratio
number or Autosize
kgWater/kgDryAir
Autosize
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
type_of_analysis
Type of Analysis
choice SimpleAnalysis One of DetailedAnalysis, SimpleAnalysis
heat_exchanger_configuration
Heat Exchanger Configuration
choice CounterFlow One of CounterFlow, CrossFlow
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
design_water_temperature_difference
Design Water Temperature Difference
number
deltaC
This input field is optional. If specified, it is used for sizing the Design Water Flow Rate. If blank or omitted, the Loop Design Temperature Difference value specified in Sizing:Plant object is used for sizing the Design Water Flow Rate.
Range: > 0
Referenced by 14 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:Water, CoilSystem:Cooling:Water:HeatExchangerAssisted, FaultModel:Fouling:Coil, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab

Coil:Cooling:Water:DetailedGeometry

from idfpy.models import CoilCoolingWaterDetailedGeometry

Chilled water cooling coil, detailed flat fin coil model for continuous plate fins, with inputs for detailed coil geometry specifications.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_water_flow_rate
Maximum Water Flow Rate
number or Autosize
m3/s
Autosize
tube_outside_surface_area
Tube Outside Surface Area
number or Autosize
m2
Autosize Tube Primary Surface Area
total_tube_inside_area
Total Tube Inside Area
number or Autosize
m2
Autosize Total tube inside surface area
fin_surface_area
Fin Surface Area
number or Autosize
m2
Autosize
minimum_airflow_area
Minimum Airflow Area
number or Autosize
m2
Autosize
coil_depth
Coil Depth
number or Autosize
m
Autosize
fin_diameter
Fin Diameter
number or Autosize
m
Autosize Fin diameter or the coil height
fin_thickness
Fin Thickness
number
m
0.0015 Range: > 0
tube_inside_diameter
Tube Inside Diameter
number
m
0.01445 Inner diameter of tubes
Range: > 0
tube_outside_diameter
Tube Outside Diameter
number
m
0.0159 Outer diameter of tubes
Range: > 0
tube_thermal_conductivity
Tube Thermal Conductivity
number
W/m-K
386.0 Range: ≥ 1
fin_thermal_conductivity
Fin Thermal Conductivity
number
W/m-K
204.0 Range: ≥ 1
fin_spacing
Fin Spacing
number
m
0.0018 Fin spacing or distance
Range: > 0
tube_depth_spacing
Tube Depth Spacing
number
m
0.026 Range: > 0
number_of_tube_rows
Number of Tube Rows
number 4.0 Range: > 0
number_of_tubes_per_row
Number of Tubes per Row
number or Autosize Autosize
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
condensate_collection_water_storage_tank_name
Condensate Collection Water Storage Tank Name
reference Names a WaterUse:Storage
design_water_temperature_difference
Design Water Temperature Difference
number
deltaC
This input field is optional. If specified, it is used for sizing the Design Water Flow Rate. If blank or omitted, the Loop Design Temperature Difference value specified in Sizing:Plant object is used for sizing the Design Water Flow Rate.
Range: > 0
design_inlet_water_temperature
Design Inlet Water Temperature
number or Autosize
C
Autosize This input field is optional. If specified, it is used for sizing the coil Design Geometry Parameters. If autosized, the Design Loop Exit Temperature value specified in Sizing:Plant object is used for sizing the coil Design Geometry Parameters. If the autosized value is higher than the coil design outlet air temperature, then the design inlet water temperature value is reset to coil design outlet air temperature minus 5.0 DeltaC.
Referenced by 13 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:Water, CoilSystem:Cooling:Water:HeatExchangerAssisted, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab

Coil:Cooling:WaterToAirHeatPump:EquationFit

from idfpy.models import CoilCoolingWaterToAirHeatPumpEquationFit

Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), single-speed, equation-fit model. Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Equation-fit model uses normalized curves to describe the heat pump performance.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
rated_water_flow_rate
Rated Water Flow Rate required
number or Autosize
m3/s
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity at rated conditions not accounting for the effect of supply air fan heat
gross_rated_sensible_cooling_capacity
Gross Rated Sensible Cooling Capacity required
number or Autosize
W
gross_rated_cooling_cop
Gross Rated Cooling COP required
number
W/W
Gross cooling COP at rated conditions
Range: > 0
rated_entering_water_temperature
Rated Entering Water Temperature
number
C
30.0 Rated entering water temperature corresponding to the water-to -air application for which this coil is used. For example: for water loop applications, the rated temperature is 30 degree Celsius
Range: > 0
rated_entering_air_dry_bulb_temperature
Rated Entering Air Dry-Bulb Temperature
number
C
27.0 Rated entering air dry-bulb temperature corresponding to the water-to-air application for which this coil is used. For example: for water loop applications, the rated temperature is 27 degree Celsius
Range: > 0
rated_entering_air_wet_bulb_temperature
Rated Entering Air Wet-Bulb Temperature
number
C
19.0 Rated entering air wet-bulb temperature corresponding to the water-to-air application for which this coil is used. For example: for water loop applications, the rated temperature is 19 degree Celsius
Range: > 0
total_cooling_capacity_curve_name
Total Cooling Capacity Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
sensible_cooling_capacity_curve_name
Sensible Cooling Capacity Curve Name required
reference Names a Curve:QuintLinear, Table:Lookup
cooling_power_consumption_curve_name
Cooling Power Consumption Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
nominal_time_for_condensate_removal_to_begin
Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
fan_delay_time
Fan Delay Time
number
s
60.0 Programmed time delay for heat pump fan to shut off after compressor cycle off. Only required when fan operating mode is cycling Enter 0 when fan operating mode is continuous
Range: ≥ 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, Coil:WaterHeating:Desuperheater, ZoneHVAC:WaterToAirHeatPump

Coil:Cooling:WaterToAirHeatPump:ParameterEstimation

from idfpy.models import CoilCoolingWaterToAirHeatPumpParameterEstimation

Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), single-speed, parameter estimation model. Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Parameter estimation model is a deterministic model that requires a consistent set of parameters to describe the operating conditions of the heat pump components.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
compressor_type
Compressor Type required
choice Parameters 1-5 are as named below. Parameters 6-10 depend on the type of compressor and fluid. Refer to the InputOutputReference on the parameters required
One of Reciprocating, Rotary, Scroll
refrigerant_type
Refrigerant Type
reference R22 Names a FluidProperties:Name
design_source_side_flow_rate
Design Source Side Flow Rate required
number
m3/s
Range: > 0
nominal_cooling_coil_capacity
Nominal Cooling Coil Capacity required
number
W
Range: > 0
nominal_time_for_condensate_removal_to_begin
Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
high_pressure_cutoff
High Pressure Cutoff required
number
Pa
Range: > 0
low_pressure_cutoff
Low Pressure Cutoff required
number
Pa
Range: ≥ 0
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
load_side_total_heat_transfer_coefficient
Load Side Total Heat Transfer Coefficient required
number
W/K
Previously called Parameter 1
Range: > 0
load_side_outside_surface_heat_transfer_coefficient
Load Side Outside Surface Heat Transfer Coefficient required
number
W/K
Previously called Parameter 2
Range: > 0
superheat_temperature_at_the_evaporator_outlet
Superheat Temperature at the Evaporator Outlet required
number
C
Previously called Parameter 3
Range: > 0
compressor_power_losses
Compressor Power Losses required
number
W
Accounts for the loss of work due to mechanical and electrical losses in the compressor. Previously called Parameter 4
Range: > 0
compressor_efficiency
Compressor Efficiency required
number Previously called Parameter 5
Range: > 0
compressor_piston_displacement
Compressor Piston Displacement
number
m3/s
Use when Compressor Type is Reciprocating or Rotary Leave this field blank for Compressor Type is Scroll. Previously part of Parameter 6
Range: > 0
compressor_suction_discharge_pressure_drop
Compressor Suction/Discharge Pressure Drop
number
Pa
Used when Compressor Type is Rotary or Reciprocating Leave this field blank for Compressor Type is Scroll. Previously part of Parameter 7
Range: > 0
compressor_clearance_factor
Compressor Clearance Factor
number
dimensionless
Used when Compressor Type is Reciprocating. Leave this field blank for Compressor Type is Rotary or Scroll. Previously part of Parameter 8
Range: > 0
refrigerant_volume_flow_rate
Refrigerant Volume Flow Rate
number
m3/s
Use when Compressor Type is Scroll Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 6
Range: > 0
volume_ratio
Volume Ratio
number
dimensionless
Use when Compressor Type is Scroll. Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 7
Range: > 0
leak_rate_coefficient
Leak Rate Coefficient
number Use when Compressor Type is Scroll. Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 8
Range: ≥ 0
source_side_heat_transfer_coefficient
Source Side Heat Transfer Coefficient
number
W/K
Use when Source Side Fluid Name is Water Leave this field blank when Source Side Fluid Name is an antifreeze Previously part of Parameter 9
Range: ≥ 0
source_side_heat_transfer_resistance1
Source Side Heat Transfer Resistance1
number
dimensionless
Use when Source Side Fluid Name is an antifreeze Leave this field blank for Source Side Fluid is Water Previously part of Parameter 9
Range: ≥ 0
source_side_heat_transfer_resistance2
Source Side Heat Transfer Resistance2
number
W/K
Use when Source Side Fluid Name is an antifreeze Leave this field blank for Source Side Fluid is Water Previously part of Parameter 10
Range: ≥ 0
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
fan_delay_time
Fan Delay Time
number
s
60.0 Programmed time delay for heat pump fan to shut off after compressor cycle off. Only required when fan operating mode is cycling Enter 0 when fan operating mode is continuous
Range: ≥ 0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, Branch, ZoneHVAC:WaterToAirHeatPump

Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit

from idfpy.models import CoilCoolingWaterToAirHeatPumpVariableSpeedEquationFit

Direct expansion (DX) cooling coil for water-to-air heat pump (includes electric compressor), variable-speed, equation-fit model. Optional inputs for moisture evaporation from wet coil when compressor cycles off with continuous fan operation. Equation-fit model uses normalized curves to describe the heat pump performance. Requires two to ten sets of performance data and will interpolate between speeds. Modeled as a single coil with variable-speed compressor.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_to_refrigerant_hx_water_inlet_node_name
Water-to-Refrigerant HX Water Inlet Node Name required
string
water_to_refrigerant_hx_water_outlet_node_name
Water-to-Refrigerant HX Water Outlet Node Name required
string
indoor_air_inlet_node_name
Indoor Air Inlet Node Name required
string
indoor_air_outlet_node_name
Indoor Air Outlet Node Name required
string
number_of_speeds
Number of Speeds
integer
dimensionless
2 Range: ≥ 1, ≤ 10
nominal_speed_level
Nominal Speed Level
integer
dimensionless
2 must be lower than or equal to the highest speed number
gross_rated_total_cooling_capacity_at_selected_nominal_speed_level
Gross Rated Total Cooling Capacity At Selected Nominal Speed Level
number or Autosize
W
Autosize Total cooling capacity not accounting for the effect of supply air fan heat
rated_air_flow_rate_at_selected_nominal_speed_level
Rated Air Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
rated_water_flow_rate_at_selected_nominal_speed_level
Rated Water Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
nominal_time_for_condensate_to_begin_leaving_the_coil
Nominal Time for Condensate to Begin Leaving the Coil
number
s
0.0 Range: ≥ 0
initial_moisture_evaporation_rate_divided_by_steady_state_ac_latent_capacity
Initial Moisture Evaporation Rate Divided by Steady-State AC Latent Capacity
number
dimensionless
0.0 Range: ≥ 0
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling Rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
fan_delay_time
Fan Delay Time
number
s
60.0 Programmed time delay for heat pump fan to shut off after compressor cycle off. Enter 0 when fan operating mode is continuous
Range: ≥ 0
flag_for_using_hot_gas_reheat_0_or_1
Flag for Using Hot Gas Reheat, 0 or 1
number
dimensionless
0.0 Flag for using hot gas reheat, 0 - not used, 1 - used
Range: ≥ 0
energy_part_load_fraction_curve_name
Energy Part Load Fraction Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_reference_unit_gross_rated_total_cooling_capacity
Speed 1 Reference Unit Gross Rated Total Cooling Capacity required
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_1_reference_unit_gross_rated_sensible_heat_ratio
Speed 1 Reference Unit Gross Rated Sensible Heat Ratio required
number
dimensionless
Range: ≥ 0, ≤ 1
speed_1_reference_unit_gross_rated_cooling_cop
Speed 1 Reference Unit Gross Rated Cooling COP required
number
W/W
Range: > 0
speed_1_reference_unit_rated_air_flow_rate
Speed 1 Reference Unit Rated Air Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_reference_unit_rated_water_flow_rate
Speed 1 Reference Unit Rated Water Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_total_cooling_capacity_function_of_temperature_curve_name
Speed 1 Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 1 Total Cooling Capacity Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 1 Total Cooling Capacity Function of Water Flow Fraction Curve Name required
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Water Flow Fraction Curve Name required
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 1 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions required
number
dimensionless
Range: ≥ 0
speed_1_waste_heat_function_of_temperature_curve_name
Speed 1 Waste Heat Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_reference_unit_gross_rated_total_cooling_capacity
Speed 2 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_2_reference_unit_gross_rated_sensible_heat_ratio
Speed 2 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_2_reference_unit_gross_rated_cooling_cop
Speed 2 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_2_reference_unit_rated_air_flow_rate
Speed 2 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_2_reference_unit_rated_water_flow_rate
Speed 2 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_2_total_cooling_capacity_function_of_temperature_curve_name
Speed 2 Total Cooling Capacity Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 2 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 2 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 2 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_2_waste_heat_function_of_temperature_curve_name
Speed 2 Waste Heat Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_reference_unit_gross_rated_total_cooling_capacity
Speed 3 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_3_reference_unit_gross_rated_sensible_heat_ratio
Speed 3 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_3_reference_unit_gross_rated_cooling_cop
Speed 3 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_3_reference_unit_rated_air_flow_rate
Speed 3 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_3_reference_unit_rated_water_flow_rate
Speed 3 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_3_total_cooling_capacity_function_of_temperature_curve_name
Speed 3 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 3 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 3 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 3 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_3_waste_heat_function_of_temperature_curve_name
Speed 3 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_reference_unit_gross_rated_total_cooling_capacity
Speed 4 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_4_reference_unit_gross_rated_sensible_heat_ratio
Speed 4 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_4_reference_unit_gross_rated_cooling_cop
Speed 4 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_4_reference_unit_rated_air_flow_rate
Speed 4 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_4_reference_unit_rated_water_flow_rate
Speed 4 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_4_total_cooling_capacity_function_of_temperature_curve_name
Speed 4 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 4 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 4 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 4 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_4_waste_heat_function_of_temperature_curve_name
Speed 4 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_reference_unit_gross_rated_total_cooling_capacity
Speed 5 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_5_reference_unit_gross_rated_sensible_heat_ratio
Speed 5 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_5_reference_unit_gross_rated_cooling_cop
Speed 5 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_5_reference_unit_rated_air_flow_rate
Speed 5 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_5_reference_unit_rated_water_flow_rate
Speed 5 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_5_total_cooling_capacity_function_of_temperature_curve_name
Speed 5 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 5 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 5 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_temperature_curve_name
Speed 5 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 5 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_5_waste_heat_function_of_temperature_curve_name
Speed 5 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_reference_unit_gross_rated_total_cooling_capacity
Speed 6 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_6_reference_unit_gross_rated_sensible_heat_ratio
Speed 6 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_6_reference_unit_gross_rated_cooling_cop
Speed 6 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_6_reference_unit_rated_air_flow_rate
Speed 6 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_6_reference_unit_rated_water_flow_rate
Speed 6 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_6_total_cooling_capacity_function_of_temperature_curve_name
Speed 6 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 6 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 6 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_temperature_curve_name
Speed 6 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 6 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_6_waste_heat_function_of_temperature_curve_name
Speed 6 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_reference_unit_gross_rated_total_cooling_capacity
Speed 7 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_7_reference_unit_gross_rated_sensible_heat_ratio
Speed 7 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_7_reference_unit_gross_rated_cooling_cop
Speed 7 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_7_reference_unit_rated_air_flow_rate
Speed 7 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_7_reference_unit_rated_water_flow_rate
Speed 7 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_7_total_cooling_capacity_function_of_temperature_curve_name
Speed 7 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 7 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 7 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_temperature_curve_name
Speed 7 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 7 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_7_waste_heat_function_of_temperature_curve_name
Speed 7 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_reference_unit_gross_rated_total_cooling_capacity
Speed 8 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_8_reference_unit_gross_rated_sensible_heat_ratio
Speed 8 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_8_reference_unit_gross_rated_cooling_cop
Speed 8 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_8_reference_unit_rated_air_flow_rate
Speed 8 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_8_reference_unit_rated_water_flow_rate
Speed 8 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_8_total_cooling_capacity_function_of_temperature_curve_name
Speed 8 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 8 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 8 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_temperature_curve_name
Speed 8 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 8 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_8_waste_heat_function_of_temperature_curve_name
Speed 8 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_reference_unit_gross_rated_total_cooling_capacity
Speed 9 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_9_reference_unit_gross_rated_sensible_heat_ratio
Speed 9 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_9_reference_unit_gross_rated_cooling_cop
Speed 9 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_9_reference_unit_rated_air_flow_rate
Speed 9 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_9_reference_unit_rated_water_flow_rate
Speed 9 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_9_total_cooling_capacity_function_of_temperature_curve_name
Speed 9 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 9 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 9 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_temperature_curve_name
Speed 9 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 9 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_9_waste_heat_function_of_temperature_curve_name
Speed 9 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_reference_unit_gross_rated_total_cooling_capacity
Speed 10 Reference Unit Gross Rated Total Cooling Capacity
number
W
Total cooling capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_10_reference_unit_gross_rated_sensible_heat_ratio
Speed 10 Reference Unit Gross Rated Sensible Heat Ratio
number
dimensionless
Range: ≥ 0, ≤ 1
speed_10_reference_unit_gross_rated_cooling_cop
Speed 10 Reference Unit Gross Rated Cooling COP
number
W/W
Range: > 0
speed_10_reference_unit_rated_air_flow_rate
Speed 10 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_10_reference_unit_rated_water_flow_rate
Speed 10 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_10_total_cooling_capacity_function_of_temperature_curve_name
Speed 10 Total Cooling Capacity Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_total_cooling_capacity_function_of_air_flow_fraction_curve_name
Speed 10 Total Cooling Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_total_cooling_capacity_function_of_water_flow_fraction_curve_name
Speed 10 Total Cooling Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_temperature_curve_name
Speed 10 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 10 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_10_waste_heat_function_of_temperature_curve_name
Speed 10 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, Coil:WaterHeating:Desuperheater, ZoneHVAC:WaterToAirHeatPump

Coil:DX:ASHRAE205:Performance

from idfpy.models import CoilDXASHRAE205Performance

DX coil performance specification referencing an ASHRAE Standard 205 compliant representation for air-to-air direct expansion refrigerant system (Representation Specification RS0004). As RS0004 files are intended to support both heating and cooling performance, this object may referenced by the Coil:Cooling:DX and the corresponding Coil:Heating:DX object (planned for future addition).

Field Type Default Details
name
Name required
string
representation_file_name
Representation File Name required
string The name of the ASHRAE 205 RS0004 (air-to-air direct expansion refrigerant system) representation file
performance_interpolation_method
Performance Interpolation Method
choice Linear One of Cubic, Linear
rated_total_cooling_capacity
Rated Total Cooling Capacity
number or Autosize
W
Autosize Not yet implemented / reserved for future use. Full load cooling capacity at AHRI 210/240 "A" test conditions. Used to scale representation data.
rated_steady_state_heating_capacity
Rated Steady-State Heating Capacity
number or Autosize
W
Autosize Not yet implemented / reserved for future use. Full load heating capacity at AHRI 210/240 "H1" test conditions. Used to scale representation data.
Referenced by 1 object types

Coil:Cooling:DX

Coil:Heating:DX:MultiSpeed

from idfpy.models import CoilHeatingDXMultiSpeed

Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric or engine-driven compressor and outdoor fan), multi-speed (or variable-speed), with defrost controls. Requires two to four sets of performance data and will interpolate between speeds.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-8.0
outdoor_dry_bulb_temperature_to_turn_on_compressor
Outdoor Dry-Bulb Temperature to Turn On Compressor
number
C
The outdoor temperature when the compressor is automatically turned back on following an automatic shut off because of low outdoor dry-bulb temperature. This field is only used for the calculation of HSPF. If this field is not provided, then outdoor bin temperature used in the HSPF calculation is always considered to be greater than this temperature and 'Minimum Outdoor Dry-Bulb Temperature for Compressor Operation' field described above. This assumption is based on AHRI standard 210/240 (2008) and can introduce significant error in the final value of HSPF.
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
defrost_energy_input_ratio_function_of_temperature_curve_name
Defrost Energy Input Ratio Function of Temperature Curve Name
reference biquadratic curve = a + b*wb + c*wb**2 + d*oat + e*oat**2 + f*wb*oat wb = wet-bulb temperature (C) of air entering the indoor coil oat = outdoor air dry-bulb temperature (C) only required if ReverseCycle defrost strategy is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-Bulb Temperature for Defrost Operation
number
C
5.0 Range: ≥ 0, ≤ 7.22
defrost_strategy
Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed One of OnDemand, Timed
defrost_time_period_fraction
Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 only applicable if resistive defrost strategy is specified
apply_part_load_fraction_to_speeds_greater_than_1
Apply Part Load Fraction to Speeds Greater than 1
choice No One of No, Yes
fuel_type
Fuel Type required
choice One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
region_number_for_calculating_hspf
Region number for Calculating HSPF
integer 4 Standard Region number for which HSPF and other standard ratings are calculated
Range: ≥ 1, ≤ 6
number_of_speeds
Number of Speeds required
integer Enter the number of the following sets of data for coil capacity, COP, flow rate, and associated curves.
Range: ≥ 2, ≤ 4
speed_1_gross_rated_heating_capacity
Speed 1 Gross Rated Heating Capacity required
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
speed_1_gross_rated_heating_cop
Speed 1 Gross Rated Heating COP required
number
W/W
Rated heating capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy
Range: > 0
speed_1_rated_air_flow_rate
Speed 1 Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total heating capacity
n2017_speed_1_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 1 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_1_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 1 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_1_heating_capacity_function_of_temperature_curve_name
Speed 1 Heating Capacity Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the heating capacity to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_1_heating_capacity_function_of_flow_fraction_curve_name
Speed 1 Heating Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the energy input ratio to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_1_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_part_load_fraction_correlation_curve_name
Speed 1 Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (sensible heating load/steady state heating capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_rated_waste_heat_fraction_of_power_input
Speed 1 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_1_waste_heat_function_of_temperature_curve_name
Speed 1 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_gross_rated_heating_capacity
Speed 2 Gross Rated Heating Capacity required
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
speed_2_gross_rated_heating_cop
Speed 2 Gross Rated Heating COP required
number
W/W
Rated heating capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy
Range: > 0
speed_2_rated_air_flow_rate
Speed 2 Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total heating capacity
n2017_speed_2_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 2 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 2 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_2_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 2 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 2 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_2_heating_capacity_function_of_temperature_curve_name
Speed 2 Heating Capacity Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the heating capacity to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_2_heating_capacity_function_of_flow_fraction_curve_name
Speed 2 Heating Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the energy input ratio to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_2_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_part_load_fraction_correlation_curve_name
Speed 2 Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (sensible heating load/steady state heating capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_rated_waste_heat_fraction_of_power_input
Speed 2 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_2_waste_heat_function_of_temperature_curve_name
Speed 2 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_gross_rated_heating_capacity
Speed 3 Gross Rated Heating Capacity
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
speed_3_gross_rated_heating_cop
Speed 3 Gross Rated Heating COP
number
W/W
Rated heating capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy
Range: > 0
speed_3_rated_air_flow_rate
Speed 3 Rated Air Flow Rate
number or Autosize
m3/s
Flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total heating capacity
n2017_speed_3_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 3 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 3 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_3_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 3 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 3 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_3_heating_capacity_function_of_temperature_curve_name
Speed 3 Heating Capacity Function of Temperature Curve Name
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the heating capacity to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_3_heating_capacity_function_of_flow_fraction_curve_name
Speed 3 Heating Capacity Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the energy input ratio to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_3_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_part_load_fraction_correlation_curve_name
Speed 3 Part Load Fraction Correlation Curve Name
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (sensible heating load/steady state heating capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_rated_waste_heat_fraction_of_power_input
Speed 3 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_3_waste_heat_function_of_temperature_curve_name
Speed 3 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_gross_rated_heating_capacity
Speed 4 Gross Rated Heating Capacity
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
speed_4_gross_rated_heating_cop
Speed 4 Gross Rated Heating COP
number
W/W
Rated heating capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy
Range: > 0
speed_4_rated_air_flow_rate
Speed 4 Rated Air Flow Rate
number or Autosize
m3/s
Flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total heating capacity
n2017_speed_4_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 4 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 4 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_4_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 4 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 4 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_4_heating_capacity_function_of_temperature_curve_name
Speed 4 Heating Capacity Function of Temperature Curve Name
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the heating capacity to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_4_heating_capacity_function_of_flow_fraction_curve_name
Speed 4 Heating Capacity Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the energy input ratio to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_4_energy_input_ratio_function_of_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_part_load_fraction_correlation_curve_name
Speed 4 Part Load Fraction Correlation Curve Name
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (sensible heating load/steady state heating capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_rated_waste_heat_fraction_of_power_input
Speed 4 Rated Waste Heat Fraction of Power Input
number
dimensionless
0.2 recoverable waste heat at full load and rated conditions
Range: > 0, ≤ 1
speed_4_waste_heat_function_of_temperature_curve_name
Speed 4 Waste Heat Function of Temperature Curve Name
reference curve = a + b*odb + c*odb**2 + d*db + e*db**2 + f*odb*db odb = Outdoor air dry-bulb temperature (C) db = entering coil dry-bulb temperature (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
zone_name_for_evaporator_placement
Zone Name for Evaporator Placement
string This input field is name of a conditioned or unconditioned zone where the secondary coil (evaporator) of a heat pump is to be placed. This is an optional input field specified only when user desires to extract heat from the zone. The heat extracted is modeled as internal heat gain of the zone. If the primary DX system is a heat pump, then the zone name should be the same as the zone name specified for placing the secondary cooling DX coil.
speed_1_secondary_coil_air_flow_rate
Speed 1 Secondary Coil Air Flow Rate
number or Autosize
m3/s
This input value is the secondary coil (evaporator) air flow rate when the heat pump is working in heating mode or the secondary DX coil (condenser) air flow rate when the heat pump is working in cooling mode.
speed_1_secondary_coil_fan_flow_scaling_factor
Speed 1 Secondary Coil Fan Flow Scaling Factor
number
m3/s
1.25 This input field is scaling factor for autosizing the secondary DX coil fan flow rate. The secondary air flow rate is determined by multiplying the primary DX coil rated air flow rate by the fan flow scaling factor. Default value is 1.25. If the secondary coil fan flow rate is not autosized, then the secondary coil fan flow scaling factor is set to 1.0.
Range: > 0
speed_1_nominal_sensible_heat_ratio_of_secondary_coil
Speed 1 Nominal Sensible Heat Ratio of Secondary Coil
number
m3/s
This input value is the nominal sensible heat ratio used to split the heat extracted by a secondary DX coil (evaporator) of a heat pump into sensible and latent components. This is an optional input field. If this input field is left blank, then pure sensible internal heat gain is assumed, i.e., sensible heat ratio of 1.0.
Range: > 0, ≤ 1
speed_1_sensible_heat_ratio_modifier_function_of_temperature_curve_name
Speed 1 Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the secondary DX coil (C) db = entering dry-bulb temperature seen by the primary DX coil (C) This input field is name of sensible heat ratio modifier biquadratic curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary zone air node wet-bulb temperature and the heating DX coil entering air dry-bulb temperature. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified in the field above will be used.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Speed 1 Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = secondary air flow fraction of the full load flow This input field is name of sensible heat ratio modifier curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary coil air flow fraction. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified will be used.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_secondary_coil_air_flow_rate
Speed 2 Secondary Coil Air Flow Rate
number or Autosize
m3/s
This input value is the secondary coil (evaporator) air flow rate when the heat pump is working in heating mode or the secondary DX coil (condenser) air flow rate when the heat pump is working in cooling mode.
speed_2_secondary_coil_fan_flow_scaling_factor
Speed 2 Secondary Coil Fan Flow Scaling Factor
number
m3/s
1.25 This input field is scaling factor for autosizing the secondary DX coil fan flow rate. The secondary air flow rate is determined by multiplying the primary DX coil rated air flow rate by the fan flow scaling factor. Default value is 1.25. If the secondary coil fan flow rate is not autosized, then the secondary coil fan flow scaling factor is set to 1.0.
Range: > 0
speed_2_nominal_sensible_heat_ratio_of_secondary_coil
Speed 2 Nominal Sensible Heat Ratio of Secondary Coil
number
m3/s
This input value is the nominal sensible heat ratio used to split the heat extracted by a secondary DX coil (evaporator) of a heat pump into sensible and latent components. This is an optional input field. If this input field is left blank, then pure sensible internal heat gain is assumed, i.e., sensible heat ratio of 1.0.
Range: > 0, ≤ 1
speed_2_sensible_heat_ratio_modifier_function_of_temperature_curve_name
Speed 2 Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the secondary DX coil (C) db = entering dry-bulb temperature seen by the primary DX coil (C) This input field is name of sensible heat ratio modifier biquadratic curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary zone air node wet-bulb temperature and the heating DX coil entering air dry-bulb temperature. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified in the field above will be used.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Speed 2 Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = secondary air flow fraction of the full load flow This input field is name of sensible heat ratio modifier curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary coil air flow fraction. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified will be used.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_secondary_coil_air_flow_rate
Speed 3 Secondary Coil Air Flow Rate
number or Autosize
m3/s
This input value is the secondary coil (evaporator) air flow rate when the heat pump is working in heating mode or the secondary DX coil (condenser) air flow rate when the heat pump is working in cooling mode.
speed_3_secondary_coil_fan_flow_scaling_factor
Speed 3 Secondary Coil Fan Flow Scaling Factor
number
m3/s
1.25 This input field is scaling factor for autosizing the secondary DX coil fan flow rate. The secondary air flow rate is determined by multiplying the primary DX coil rated air flow rate by the fan flow scaling factor. Default value is 1.25. If the secondary coil fan flow rate is not autosized, then the secondary coil fan flow scaling factor is set to 1.0.
Range: > 0
speed_3_nominal_sensible_heat_ratio_of_secondary_coil
Speed 3 Nominal Sensible Heat Ratio of Secondary Coil
number
m3/s
This input value is the nominal sensible heat ratio used to split the heat extracted by a secondary DX coil (evaporator) of a heat pump into sensible and latent components. This is an optional input field. If this input field is left blank, then pure sensible internal heat gain is assumed, i.e., sensible heat ratio of 1.0.
Range: > 0, ≤ 1
speed_3_sensible_heat_ratio_modifier_function_of_temperature_curve_name
Speed 3 Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the secondary DX coil (C) db = entering dry-bulb temperature seen by the primary DX coil (C) This input field is name of sensible heat ratio modifier biquadratic curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary zone air node wet-bulb temperature and the heating DX coil entering air dry-bulb temperature. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified in the field above will be used.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Speed 3 Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = secondary air flow fraction of the full load flow This input field is name of sensible heat ratio modifier curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary coil air flow fraction. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified will be used.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_secondary_coil_air_flow_rate
Speed 4 Secondary Coil Air Flow Rate
number or Autosize
m3/s
This input value is the secondary coil (evaporator) air flow rate when the heat pump is working in heating mode or the secondary DX coil (condenser) air flow rate when the heat pump is working in cooling mode.
speed_4_secondary_coil_fan_flow_scaling_factor
Speed 4 Secondary Coil Fan Flow Scaling Factor
number
m3/s
1.25 This input field is scaling factor for autosizing the secondary DX coil fan flow rate. The secondary air flow rate is determined by multiplying the primary DX coil rated air flow rate by the fan flow scaling factor. Default value is 1.25. If the secondary coil fan flow rate is not autosized, then the secondary coil fan flow scaling factor is set to 1.0.
Range: > 0
speed_4_nominal_sensible_heat_ratio_of_secondary_coil
Speed 4 Nominal Sensible Heat Ratio of Secondary Coil
number
m3/s
This input value is the nominal sensible heat ratio used to split the heat extracted by a secondary DX coil (evaporator) of a heat pump into sensible and latent components. This is an optional input field. If this input field is left blank, then pure sensible internal heat gain is assumed, i.e., sensible heat ratio of 1.0.
Range: > 0, ≤ 1
speed_4_sensible_heat_ratio_modifier_function_of_temperature_curve_name
Speed 4 Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the secondary DX coil (C) db = entering dry-bulb temperature seen by the primary DX coil (C) This input field is name of sensible heat ratio modifier biquadratic curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary zone air node wet-bulb temperature and the heating DX coil entering air dry-bulb temperature. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified in the field above will be used.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Speed 4 Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = secondary air flow fraction of the full load flow This input field is name of sensible heat ratio modifier curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary coil air flow fraction. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified will be used.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 4 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage

Coil:Heating:DX:SingleSpeed

from idfpy.models import CoilHeatingDXSingleSpeed

Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric compressor and outdoor fan), single-speed, with defrost controls.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_heating_capacity
Gross Rated Heating Capacity required
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outdoor dry-bulb temp 8.33 C, outdoor wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wet-bulb 15.55 C
gross_rated_heating_cop
Gross Rated Heating COP required
number
W/W
Rated heating capacity divided by power input to the compressor and outdoor fan, does not include supply air fan heat or supply air fan electrical energy does not include supply air fan heat or supply air fan electrical energy
Range: > 0
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated heating capacity
n2017_rated_supply_fan_power_per_volume_flow_rate
2017 Rated Supply Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply fan power per air volume flow rate at the rated test conditions. as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply (condenser) fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_rated_supply_fan_power_per_volume_flow_rate
2023 Rated Supply Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply fan power per air volume flow rate at the rated test conditions. as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply (condenser) fan during simulations.
Range: ≥ 0, ≤ 1505
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
heating_capacity_function_of_temperature_curve_name
Heating Capacity Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) Biquadratic curve is recommended if sufficient manufacturer data is available for the heating capacity to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_capacity_function_of_flow_fraction_curve_name
Heating Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
energy_input_ratio_function_of_temperature_curve_name
Energy Input Ratio Function of Temperature Curve Name required
reference quadratic curve = a + b*oat + c*oat**2 cubic curve = a + b*oat + c*oat**2 + d*oat**3 biquadratic curve = a + b*iat + c*iat**2 + d*oat + e*oat**2 + f*iat*oat oat = outdoor air dry-bulb temperature (C) iat = indoor air dry-bulb temperature (C) biquadratic curve is recommended if sufficient manufacturer data is available for the energy input ratio to be sensitive to both iat and oat.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
energy_input_ratio_function_of_flow_fraction_curve_name
Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (sensible heating load/steady state heating capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
defrost_energy_input_ratio_function_of_temperature_curve_name
Defrost Energy Input Ratio Function of Temperature Curve Name
reference biquadratic curve = a + b*wb + c*wb**2 + d*oat + e*oat**2 + f*wb*oat wb = wet-bulb temperature (C) of air entering the indoor coil oat = outdoor air dry-bulb temperature (C) only required if ReverseCycle defrost strategy is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-8.0
outdoor_dry_bulb_temperature_to_turn_on_compressor
Outdoor Dry-Bulb Temperature to Turn On Compressor
number
C
The outdoor temperature when the compressor is automatically turned back on following an automatic shut off because of low outdoor dry-bulb temperature. This field is only used for the calculation of HSPF. If this field is not provided, then outdoor bin temperature used in the HSPF calculation is always considered to be greater than this temperature and 'Minimum Outdoor Dry-Bulb Temperature for Compressor Operation' field described above. This assumption is based on AHRI standard 210/240 (2008) and can introduce significant error in the final value of HSPF.
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-Bulb Temperature for Defrost Operation
number
C
5.0 Range: ≥ 0, ≤ 7.22
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
defrost_strategy
Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed One of OnDemand, Timed
defrost_time_period_fraction
Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 only applicable if resistive defrost strategy is specified
region_number_for_calculating_hspf
Region number for calculating HSPF
integer 4 Standard Region number for which HSPF and other standard ratings are calculated
Range: ≥ 1, ≤ 6
evaporator_air_inlet_node_name
Evaporator Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
zone_name_for_evaporator_placement
Zone Name for Evaporator Placement
string This input field is name of a conditioned or unconditioned zone where the secondary coil (evaporator) of a heat pump is to be placed. This is an optional input field specified only when user desires to extract heat from the zone. The heat extracted is modelled as internal gain of the zone. If the primary DX system is a heat pump, then the zone name should be the same as the zone name specified for placing the secondary cooling DX coil.
secondary_coil_air_flow_rate
Secondary Coil Air Flow Rate
number or Autosize
m3/s
This input value is the secondary coil (evaporator) air flow rate when the heat pump is working in heating mode or the secondary DX coil (condenser) air flow rate when the heat pump is working in cooling mode.
secondary_coil_fan_flow_scaling_factor
Secondary Coil Fan Flow Scaling Factor
number
m3/s
1.25 This input field is scaling factor for autosizing the secondary DX coil fan flow rate. The secondary air flow rate is determined by multiplying the primary DX coil rated air flow rate by the fan flow scaling factor. Default value is 1.25. If the secondary coil fan flow rate is not autosized, then the secondary coil fan flow scaling factor is set to 1.0.
Range: > 0
nominal_sensible_heat_ratio_of_secondary_coil
Nominal Sensible Heat Ratio of Secondary Coil
number
m3/s
This input value is the nominal sensible heat ratio used to split the heat extracted by a secondary DX coil (evaporator) of a heat pump into sensible and latent components. This is an optional input field. If this input field is left blank, then pure sensible internal heat gain is assumed, i.e., sensible heat ratio of 1.0.
Range: > 0, ≤ 1
sensible_heat_ratio_modifier_function_of_temperature_curve_name
Sensible Heat Ratio Modifier Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the secondary DX coil (C) db = entering dry-bulb temperature seen by the primary DX coil (C) This input field is name of sensible heat ratio modifier biquadratic curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary zone air node wet-bulb temperature and the heating DX coil entering air dry-bulb temperature. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified in the field above will be used.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_modifier_function_of_flow_fraction_curve_name
Sensible Heat Ratio Modifier Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = secondary air flow fraction of the full load flow This input field is name of sensible heat ratio modifier curve. The value of this curve modifies the nominal sensible heat ratio for current time step depending on the secondary coil air flow fraction. This is an optional input field. If this input field is left blank, then the nominal sensible heat ratio specified will be used.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 6 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, CoilSystem:Heating:DX, ZoneHVAC:PackagedTerminalHeatPump

Coil:Heating:DX:VariableRefrigerantFlow

from idfpy.models import CoilHeatingDXVariableRefrigerantFlow

Variable refrigerant flow (VRF) direct expansion (DX) heating coil (air-to-air heat pump). Used with ZoneHVAC:TerminalUnit:VariableRefrigerantFlow. Condensing unit is modeled separately, see AirConditioner:VariableRefrigerantFlow.

Field Type Default Details
name
Name required
string
availability_schedule
Availability Schedule
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_heating_capacity
Gross Rated Heating Capacity required
number or Autosize
W
Heating capacity not accounting for the effect of supply air fan heat capacity excluding supply air fan heat rating point outside dry-bulb temp 8.33 C, outside wet-bulb temp 6.11 C rating point heating coil entering air dry-bulb 21.11 C, coil entering wetbulb 15.55 C
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
volume flow rate corresponding to rated total capacity should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated heating capacity
coil_air_inlet_node
Coil Air Inlet Node required
string
coil_air_outlet_node
Coil Air Outlet Node required
string
heating_capacity_ratio_modifier_function_of_temperature_curve_name
Heating Capacity Ratio Modifier Function of Temperature Curve Name required
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_capacity_modifier_function_of_flow_fraction_curve_name
Heating Capacity Modifier Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 5 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, CoilSystem:Heating:DX, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Coil:Heating:DX:VariableRefrigerantFlow:FluidTemperatureControl

from idfpy.models import CoilHeatingDXVariableRefrigerantFlowFluidTemperatureControl

This is a key object in the new physics based VRF model applicable for Fluid Temperature Control. It describes the the indoor unit coil of the system at heating mode. Used with ZoneHVAC:TerminalUnit:VariableRefrigerantFlow. Outdoor unit is modeled separately, see AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl or AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR

Field Type Default Details
name
Name required
string
availability_schedule
Availability Schedule
reference Enter the name of a schedule that defines the availability of the coil Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
coil_air_inlet_node
Coil Air Inlet Node required
string the inlet node to the coil
coil_air_outlet_node
Coil Air Outlet Node required
string the outlet node to the coil
rated_total_heating_capacity
Rated Total Heating Capacity required
number or Autosize
W
Supply air fan heat is not included
indoor_unit_reference_subcooling
Indoor Unit Reference Subcooling
number
deltaC
5.0 Range: ≥ 0
indoor_unit_condensing_temperature_function_of_subcooling_curve_name
Indoor Unit Condensing Temperature Function of Subcooling Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 1 object types

ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Coil:Heating:DX:VariableSpeed

from idfpy.models import CoilHeatingDXVariableSpeed

Direct expansion (DX) heating coil (air-to-air heat pump) and compressor unit (includes electric compressor and outdoor fan), variable-speed, with defrost controls. Requires two to ten sets of performance data and will interpolate between speeds.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
indoor_air_inlet_node_name
Indoor Air Inlet Node Name required
string
indoor_air_outlet_node_name
Indoor Air Outlet Node Name required
string
number_of_speeds
Number of Speeds
integer
dimensionless
2 Range: ≥ 1, ≤ 10
nominal_speed_level
Nominal Speed Level
integer
dimensionless
2 must be lower than or equal to the highest speed number
rated_heating_capacity_at_selected_nominal_speed_level
Rated Heating Capacity At Selected Nominal Speed Level
number or Autosize
W
Autosize
rated_air_flow_rate_at_selected_nominal_speed_level
Rated Air Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
energy_part_load_fraction_curve_name
Energy Part Load Fraction Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (heating load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
defrost_energy_input_ratio_function_of_temperature_curve_name
Defrost Energy Input Ratio Function of Temperature Curve Name
reference biquadratic curve = a + b*wb + c*wb**2 + d*oat + e*oat**2 + f*wb*oat wb = wet-bulb temperature (C) of air entering the indoor coil oat = outdoor air dry-bulb temperature (C) only required if ReverseCycle defrost strategy is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
minimum_outdoor_dry_bulb_temperature_for_compressor_operation
Minimum Outdoor Dry-Bulb Temperature for Compressor Operation
number
C
-8.0
outdoor_dry_bulb_temperature_to_turn_on_compressor
Outdoor Dry-Bulb Temperature to Turn On Compressor
number
C
The outdoor temperature when the compressor is automatically turned back on following an automatic shut off because of low outdoor dry-bulb temperature. This field is only used for the calculation of HSPF. If this field is not provided, then outdoor bin temperature used in the HSPF calculation is always considered to be greater than this temperature and 'Minimum Outdoor Dry-Bulb Temperature for Compressor Operation' field described above. This assumption is based on AHRI standard 210/240 (2008) and can introduce significant error in the final value of HSPF.
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-Bulb Temperature for Defrost Operation
number
C
5.0 Range: ≥ 0, ≤ 7.22
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater_operation
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation
number
C
10.0 Range: ≥ 0
defrost_strategy
Defrost Strategy
choice ReverseCycle One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed One of OnDemand, Timed
defrost_time_period_fraction
Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 only applicable if resistive defrost strategy is specified
speed_1_reference_unit_gross_rated_heating_capacity
Speed 1 Reference Unit Gross Rated Heating Capacity required
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_1_reference_unit_gross_rated_heating_cop
Speed 1 Reference Unit Gross Rated Heating COP required
number
W/W
Range: > 0
speed_1_reference_unit_rated_air_flow_rate
Speed 1 Reference Unit Rated Air Flow Rate required
number
m3/s
Range: ≥ 0
n2017_speed_1_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 1 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_1_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 1 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_1_heating_capacity_function_of_temperature_curve_name
Speed 1 Heating Capacity Function of Temperature Curve Name required
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 1 Total Heating Capacity Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_reference_unit_gross_rated_heating_capacity
Speed 2 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_2_reference_unit_gross_rated_heating_cop
Speed 2 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_2_reference_unit_rated_air_flow_rate
Speed 2 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_2_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 2 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_2_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 2 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_2_heating_capacity_function_of_temperature_curve_name
Speed 2 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 2 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_reference_unit_gross_rated_heating_capacity
Speed 3 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_3_reference_unit_gross_rated_heating_cop
Speed 3 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_3_reference_unit_rated_air_flow_rate
Speed 3 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_3_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 3 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_3_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 3 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_3_heating_capacity_function_of_temperature_curve_name
Speed 3 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
speed_3_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 3 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_reference_unit_gross_rated_heating_capacity
Speed 4 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_4_reference_unit_gross_rated_heating_cop
Speed 4 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_4_reference_unit_rated_air_flow_rate
Speed 4 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_4_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 4 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_4_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 4 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_4_heating_capacity_function_of_temperature_curve_name
Speed 4 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 4 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_reference_unit_gross_rated_heating_capacity
Speed 5 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_5_reference_unit_gross_rated_heating_cop
Speed 5 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_5_reference_unit_rated_air_flow_rate
Speed 5 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_5_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 5 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_5_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 5 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_5_heating_capacity_function_of_temperature_curve_name
Speed 5 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 5 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_temperature_curve_name
Speed 5 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_reference_unit_gross_rated_heating_capacity
Speed 6 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_6_reference_unit_gross_rated_heating_cop
Speed 6 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_6_reference_unit_rated_air_flow_rate
Speed 6 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_6_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 6 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_6_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 6 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_6_heating_capacity_function_of_temperature_curve_name
Speed 6 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 6 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_temperature_curve_name
Speed 6 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_reference_unit_gross_rated_heating_capacity
Speed 7 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_7_reference_unit_gross_rated_heating_cop
Speed 7 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_7_reference_unit_rated_air_flow_rate
Speed 7 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_7_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 7 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_7_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 7 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_7_heating_capacity_function_of_temperature_curve_name
Speed 7 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 7 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_temperature_curve_name
Speed 7 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_reference_unit_gross_rated_heating_capacity
Speed 8 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_8_reference_unit_gross_rated_heating_cop
Speed 8 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_8_reference_unit_rated_air_flow_rate
Speed 8 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_8_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 8 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_8_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 8 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_8_heating_capacity_function_of_temperature_curve_name
Speed 8 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 8 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_temperature_curve_name
Speed 8 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_reference_unit_gross_rated_heating_capacity
Speed 9 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_9_reference_unit_gross_rated_heating_cop
Speed 9 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_9_reference_unit_rated_air_flow_rate
Speed 9 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_9_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 9 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_9_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 9 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_9_heating_capacity_function_of_temperature_curve_name
Speed 9 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 9 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_temperature_curve_name
Speed 9 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_reference_unit_gross_rated_heating_capacity
Speed 10 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_10_reference_unit_gross_rated_heating_cop
Speed 10 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_10_reference_unit_rated_air_flow_rate
Speed 10 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
n2017_speed_10_rated_supply_air_fan_power_per_volume_flow_rate
2017 Speed 10 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
773.3 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2017 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1250
n2023_speed_10_rated_supply_air_fan_power_per_volume_flow_rate
2023 Speed 10 Rated Supply Air Fan Power Per Volume Flow Rate
number
W/(m3/s)
934.4 Enter the supply air fan power per air volume flow rate at the rated speed 1 test conditions as defined in the 2023 version of ANSI/AHRI Standard 210/240. The test conditions vary external static pressure based on heating capacity. This value is only used to calculate Heating Seasonal Performance Factor(HSPF). This value is not used for modeling the supply air fan during simulations.
Range: ≥ 0, ≤ 1505
speed_10_heating_capacity_function_of_temperature_curve_name
Speed 10 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 10 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_temperature_curve_name
Speed 10 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*oat + e*oat**2 + f*db*oat db = entering air dry-bulb temperature (C) oat = air entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 8 object types

AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, CoilSystem:Heating:DX, CoilSystem:IntegratedHeatPump:AirSource, ZoneHVAC:PackagedTerminalHeatPump

Coil:Heating:Desuperheater

from idfpy.models import CoilHeatingDesuperheater

Desuperheater air heating coil. The heating energy provided by this coil is reclaimed from the superheated refrigerant gas leaving a compressor and does not impact the performance of the compressor. If the coil is located directly in an air loop branch or outdoor air equipment list, then it is controlled on leaving air temperature and the Temperature Setpoint Node Name must be specified. If the coil is contained within another component such as a unitary system, then the coil is controlled by the parent component and the setpoint node name is not entered.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_reclaim_recovery_efficiency
Heat Reclaim Recovery Efficiency
number Range: ≥ 0
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
heating_source_object_type
Heating Source Object Type required
choice One of Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Refrigeration:CompressorRack, Refrigeration:Condenser:AirCooled, Refrigeration:Condenser:EvaporativeCooled, Refrigeration:Condenser:WaterCooled
heating_source_name
Heating Source Name required
reference Names a Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Refrigeration:CompressorRack, Refrigeration:Condenser:AirCooled, Refrigeration:Condenser:EvaporativeCooled, Refrigeration:Condenser:WaterCooled
temperature_setpoint_node_name
Temperature Setpoint Node Name
string Required if coil is temperature controlled. Temperature-based control requires the use of a SetpointManager object
on_cycle_parasitic_electric_load
On Cycle Parasitic Electric Load
number
W
parasitic electric load associated with the desuperheater coil operation such as solenoid valves, etc.
Range: ≥ 0
Referenced by 6 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, FaultModel:TemperatureSensorOffset:CoilSupplyAir

Coil:Heating:Electric

from idfpy.models import CoilHeatingElectric

Electric heating coil. If the coil is located directly in an air loop branch or outdoor air equipment list, then it is controlled on leaving air temperature and the Temperature Setpoint Node Name must be specified. If the coil is contained within another component such as an air terminal unit, zone HVAC equipment, or unitary system, then the coil is controlled by the parent component and the setpoint node name is not entered.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
efficiency
Efficiency
number 1.0 Range: > 0, ≤ 1
nominal_capacity
Nominal Capacity
number or Autosize
W
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
temperature_setpoint_node_name
Temperature Setpoint Node Name
string Required if coil is temperature controlled.
Referenced by 32 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:Unitary:Furnace:HeatOnly, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatOnly, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, Dehumidifier:Desiccant:NoFans, Dehumidifier:Desiccant:System, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:Electric:MultiStage

from idfpy.models import CoilHeatingElectricMultiStage

Electric heating coil, multi-stage. If the coil is located directly in an air loop branch or outdoor air equipment list, then it is controlled on leaving air temperature and the Temperature Setpoint Node Name must be specified. If the coil is contained within another component such as an air terminal unit, zone HVAC equipment, or unitary system, then the coil is controlled by the parent component and the setpoint node name is not entered.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
temperature_setpoint_node_name
Temperature Setpoint Node Name
string Required if coil is temperature controlled. controlled
number_of_stages
Number of Stages required
integer Enter the number of the following sets of data for coil capacity and Efficiency.
Range: ≥ 1, ≤ 4
stage_1_efficiency
Stage 1 Efficiency required
number
W/W
Range: > 0
stage_1_nominal_capacity
Stage 1 Nominal Capacity required
number or Autosize
W
stage_2_efficiency
Stage 2 Efficiency
number
W/W
Range: > 0
stage_2_nominal_capacity
Stage 2 Nominal Capacity
number or Autosize
W
stage_3_efficiency
Stage 3 Efficiency
number
W/W
Range: > 0
stage_3_nominal_capacity
Stage 3 Nominal Capacity
number or Autosize
W
stage_4_efficiency
Stage 4 Efficiency
number
W/W
Range: > 0
stage_4_nominal_capacity
Stage 4 Nominal Capacity
number or Autosize
W
Referenced by 3 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitarySystem, FaultModel:TemperatureSensorOffset:CoilSupplyAir

Coil:Heating:Fuel

from idfpy.models import CoilHeatingFuel

Gas or other fuel heating coil. If the coil is located directly in an air loop branch or outdoor air equipment list, then it is controlled on leaving air temperature and the Temperature Setpoint Node Name must be specified. If the coil is contained within another component such as an air terminal unit, zone HVAC equipment, or unitary system, then the coil is controlled by the parent component and the setpoint node name is not entered.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fuel_type
Fuel Type
choice NaturalGas One of Coal, Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
burner_efficiency
Burner Efficiency
number 0.8 Range: ≥ 0, ≤ 1
nominal_capacity
Nominal Capacity
number or Autosize
W
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
temperature_setpoint_node_name
Temperature Setpoint Node Name
string optional, used if coil is temperature control and not load-base controlled
on_cycle_parasitic_electric_load
On Cycle Parasitic Electric Load
number
W
parasitic electric load associated with the coil operation such as an inducer fan, etc... This will be modified by the part load ratio to reflect the time of operation in a timestep.
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference quadratic curve, PLF = a + b*PLR + c*PLR**2 cubic curve, PLF = a + b*PLR + c*PLR**2 + d*PLR**3 PLF = part load fraction PLR = part load ratio (sensible heating load/steady state heating capacity) Coil runtime fraction = Part Load Ratio / PLF This part load degradation is for coil performance & will increase the fuel consumption of the coil due to transient coil operation.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
off_cycle_parasitic_fuel_load
Off Cycle Parasitic Fuel Load
number
W
parasitic fuel load when the coil is not operating (i.e., standing pilot)
Referenced by 31 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:Unitary:Furnace:HeatOnly, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatOnly, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, Dehumidifier:Desiccant:NoFans, Dehumidifier:Desiccant:System, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:Gas:MultiStage

from idfpy.models import CoilHeatingGasMultiStage

Gas heating coil, multi-stage. If the coil is located directly in an air loop branch or outdoor air equipment list, then it is controlled on leaving air temperature and the Temperature Setpoint Node Name must be specified. If the coil is contained within another component such as an air terminal unit, zone HVAC equipment, or unitary system, then the coil is controlled by the parent component and the setpoint node name is not entered.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
temperature_setpoint_node_name
Temperature Setpoint Node Name
string optional, used if coil is temperature control and not load-base controlled.
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference quadratic curve, PLF = a + b*PLR + c*PLR**2 cubic curve, PLF = a + b*PLR + c*PLR**2 + d*PLR**3 PLF = part load fraction PLR = part load ratio (sensible heating load/steady state heating capacity) Coil runtime fraction = Part Load Ratio / PLF This part load degradation is for coil performance & will increase the gas consumption of the coil due to transient coil operation.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
off_cycle_parasitic_gas_load
Off Cycle Parasitic Gas Load
number
W
parasitic gas load when the gas coil is not operating (i.e., standing pilot)
number_of_stages
Number of Stages required
integer Enter the number of the following sets of data for coil capacity and Gas Burner Efficiency.
Range: ≥ 1, ≤ 4
stage_1_gas_burner_efficiency
Stage 1 Gas Burner Efficiency required
number
W/W
Range: > 0
stage_1_nominal_capacity
Stage 1 Nominal Capacity required
number or Autosize
W
stage_1_on_cycle_parasitic_electric_load
Stage 1 On Cycle Parasitic Electric Load
number
W
Stage 1 parasitic electric load associated with the gas coil operation such as an inducer fan, etc. This will be modified by the part load ratio to reflect the time of operation in a timestep.
stage_2_gas_burner_efficiency
Stage 2 Gas Burner Efficiency
number
W/W
Range: > 0
stage_2_nominal_capacity
Stage 2 Nominal Capacity
number or Autosize
W
stage_2_on_cycle_parasitic_electric_load
Stage 2 On Cycle Parasitic Electric Load
number
W
Stage 2 parasitic electric load associated with the gas coil operation such as an inducer fan, etc. This will be modified by the part load ratio to reflect the time of operation in a timestep.
stage_3_gas_burner_efficiency
Stage 3 Gas Burner Efficiency
number
W/W
Range: > 0
stage_3_nominal_capacity
Stage 3 Nominal Capacity
number or Autosize
W
stage_3_on_cycle_parasitic_electric_load
Stage 3 On Cycle Parasitic Electric Load
number
W
Stage 3 parasitic electric load associated with the gas coil operation such as an inducer fan, etc. This will be modified by the part load ratio to reflect the time of operation in a timestep.
stage_4_gas_burner_efficiency
Stage 4 Gas Burner Efficiency
number
W/W
Range: > 0
stage_4_nominal_capacity
Stage 4 Nominal Capacity
number or Autosize
W
stage_4_on_cycle_parasitic_electric_load
Stage 4 On Cycle Parasitic Electric Load
number
W
Stage 4 parasitic electric load associated with the gas coil operation such as an inducer fan, etc. This will be modified by the part load ratio to reflect the time of operation in a timestep.
Referenced by 3 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitarySystem, FaultModel:TemperatureSensorOffset:CoilSupplyAir

Coil:Heating:Steam

from idfpy.models import CoilHeatingSteam

Steam heating coil. Condenses and sub-cools steam at loop pressure and discharges condensate through steam traps to low pressure condensate line.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_steam_flow_rate
Maximum Steam Flow Rate
number or Autosize
m3/s
degree_of_subcooling
Degree of SubCooling
number
C
Range: ≥ 1, ≤ 5
degree_of_loop_subcooling
Degree of Loop SubCooling
number
C
20.0 Range: ≥ 10
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
coil_control_type
Coil Control Type
choice Use ZoneLoadControl if the coil is contained within another component such as an air terminal unit, zone HVAC equipment, or unitary system. Use TemperatureSetpointControl if the coil is located directly in an air loop branch or outdoor air equipment list.
One of TemperatureSetpointControl, ZoneLoadControl
temperature_setpoint_node_name
Temperature Setpoint Node Name
string Required if Coil Control Type is TemperatureSetpointControl
Referenced by 29 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:Unitary:Furnace:HeatOnly, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatOnly, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan, Branch, Dehumidifier:Desiccant:NoFans, Dehumidifier:Desiccant:System, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:Water

from idfpy.models import CoilHeatingWater

Hot water heating coil, NTU-effectiveness model, assumes a cross-flow heat exchanger. Two options for capacity inputs: UA and water flow rate or capacity and design temperatures.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
u_factor_times_area_value
U-Factor Times Area Value
number or Autosize
W/K
Autosize UA value under rating conditions
maximum_water_flow_rate
Maximum Water Flow Rate
number or Autosize
m3/s
Autosize
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
performance_input_method
Performance Input Method
choice UFactorTimesAreaAndDesignWaterFlowRate One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
rated_capacity
Rated Capacity
number or Autosize
W
Autosize
rated_inlet_water_temperature
Rated Inlet Water Temperature
number
C
82.2
rated_inlet_air_temperature
Rated Inlet Air Temperature
number
C
16.6
rated_outlet_water_temperature
Rated Outlet Water Temperature
number
C
71.1
rated_outlet_air_temperature
Rated Outlet Air Temperature
number
C
32.2
rated_ratio_for_air_and_water_convection
Rated Ratio for Air and Water Convection
number 0.5 Range: > 0
design_water_temperature_difference
Design Water Temperature Difference
number
deltaC
This input field is optional. If specified, it is used for sizing the Design Water Flow Rate. If blank or omitted, the Loop Design Temperature Difference value specified in Sizing:Plant object is used for sizing the Design Water Flow Rate.
Range: > 0
Referenced by 33 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:Unitary:Furnace:HeatOnly, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatOnly, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitaryHeatPump:AirToAir:MultiSpeed, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirTerminal:SingleDuct:ConstantVolume:FourPipeInduction, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirTerminal:SingleDuct:SeriesPIU:Reheat, AirTerminal:SingleDuct:VAV:HeatAndCool:Reheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:SingleDuct:VAV:Reheat:VariableSpeedFan, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, Dehumidifier:Desiccant:NoFans, Dehumidifier:Desiccant:System, FaultModel:Fouling:Coil, FaultModel:TemperatureSensorOffset:CoilSupplyAir, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:WaterToAirHeatPump:EquationFit

from idfpy.models import CoilHeatingWaterToAirHeatPumpEquationFit

Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), single-speed, equation-fit model. Equation-fit model uses normalized curves to describe the heat pump performance.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
rated_water_flow_rate
Rated Water Flow Rate required
number or Autosize
m3/s
gross_rated_heating_capacity
Gross Rated Heating Capacity required
number or Autosize
W
Heating capacity at rated conditions not accounting for the effect of supply air fan heat
gross_rated_heating_cop
Gross Rated Heating COP required
number
W/W
Gross heating COP at rated conditions
Range: > 0
rated_entering_water_temperature
Rated Entering Water Temperature
number
C
20.0 Rated entering water temperature corresponding to the water-to -air application for which this coil is used. For example: for water loop applications, the rated temperature is 20 degree Celsius.
rated_entering_air_dry_bulb_temperature
Rated Entering Air Dry-Bulb Temperature
number
C
20.0 Rated entering air dry-bulb temperature corresponding to the water-to-air application for which this coil is used. For example: for water loop applications, the rated temperature is 20 degree Celsius.
Range: > 0
ratio_of_rated_heating_capacity_to_rated_cooling_capacity
Ratio of Rated Heating Capacity to Rated Cooling Capacity
number 1.0 Ratio of rated heating capacity to rated cooling capacity. This input is used to calculate the heating or cooling capacity when autosizing. This input is only used if a companion cooling coil of the same type (Coil:Cooling:WaterToAirHeatPump:EquationFit) is used. This input is only used when a sizing run for the system which uses this object is requested and when the coil capacity is autosized.
Range: > 0
heating_capacity_curve_name
Heating Capacity Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
heating_power_consumption_curve_name
Heating Power Consumption Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (heat load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:WaterToAirHeatPump:ParameterEstimation

from idfpy.models import CoilHeatingWaterToAirHeatPumpParameterEstimation

Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), single-speed, parameter estimation model. Parameter estimation model is a deterministic model that requires a consistent set of parameters to describe the operating conditions of the heat pump components.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
compressor_type
Compressor Type required
choice Parameters 1-4 are as named below. Parameters 5-9 depend on the type of compressor. Refer to the InputOutputReference on the parameters required
One of Reciprocating, Rotary, Scroll
refrigerant_type
Refrigerant Type
reference R22 Names a FluidProperties:Name
design_source_side_flow_rate
Design Source Side Flow Rate required
number
m3/s
Range: > 0
gross_rated_heating_capacity
Gross Rated Heating Capacity required
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: > 0
high_pressure_cutoff
High Pressure Cutoff required
number
Pa
Range: > 0
low_pressure_cutoff
Low Pressure Cutoff required
number
Pa
Range: ≥ 0
water_inlet_node_name
Water Inlet Node Name required
string
water_outlet_node_name
Water Outlet Node Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
load_side_total_heat_transfer_coefficient
Load Side Total Heat Transfer Coefficient required
number
W/K
Previously called Parameter 1
Range: > 0
superheat_temperature_at_the_evaporator_outlet
Superheat Temperature at the Evaporator Outlet required
number
C
Previously called Parameter 2
Range: > 0
compressor_power_losses
Compressor Power Losses required
number
W
Accounts for the loss of work due to mechanical and electrical losses in the compressor. Previously called Parameter 3
Range: > 0
compressor_efficiency
Compressor Efficiency required
number Previously called Parameter 4
Range: > 0
compressor_piston_displacement
Compressor Piston Displacement
number
m3/s
Use when Compressor Type is Reciprocating or Rotary Leave this field blank for Compressor Type is Scroll. Previously part of Parameter 5
Range: > 0
compressor_suction_discharge_pressure_drop
Compressor Suction/Discharge Pressure Drop
number
Pa
Used when Compressor Type is Rotary or Reciprocating Leave this field blank for Compressor Type is Scroll. Previously part of Parameter 6
Range: > 0
compressor_clearance_factor
Compressor Clearance Factor
number
dimensionless
Used when Compressor Type is Reciprocating. Leave this field blank for Compressor Type is Rotary or Scroll. Previously part of Parameter 7
Range: > 0
refrigerant_volume_flow_rate
Refrigerant Volume Flow Rate
number
m3/s
Use when Compressor Type is Scroll Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 5
Range: > 0
volume_ratio
Volume Ratio
number
dimensionless
Use when Compressor Type is Scroll. Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 6
Range: > 0
leak_rate_coefficient
Leak Rate Coefficient
number
dimensionless
Use when Compressor Type is Scroll. Leave this field blank for Compressor Type is Rotary or Reciprocating. Previously part of Parameter 7
Range: ≥ 0
source_side_heat_transfer_coefficient
Source Side Heat Transfer Coefficient
number
W/K
Use when Source Side Fluid Name is Water Leave this field blank when Source Side Fluid is an antifreeze Previously part of Parameter 8
Range: ≥ 0
source_side_heat_transfer_resistance1
Source Side Heat Transfer Resistance1
number
dimensionless
Use when Source Side Fluid Name is an antifreeze Leave this field blank for Source Side Fluid is Water Previously part of Parameter 8
Range: ≥ 0
source_side_heat_transfer_resistance2
Source Side Heat Transfer Resistance2
number
W/K
Use when Source Side Fluid Name is an antifreeze Leave this field blank for Source Side Fluid is Water Previously part of Parameter 9
Range: ≥ 0
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (heating load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, Branch, ZoneHVAC:WaterToAirHeatPump

Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit

from idfpy.models import CoilHeatingWaterToAirHeatPumpVariableSpeedEquationFit

Direct expansion (DX) heating coil for water-to-air heat pump (includes electric compressor), variable-speed, equation-fit model. Equation-fit model uses normalized curves to describe the heat pump performance. Requires two to ten sets of performance data and will interpolate between speeds.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_to_refrigerant_hx_water_inlet_node_name
Water-to-Refrigerant HX Water Inlet Node Name required
string
water_to_refrigerant_hx_water_outlet_node_name
Water-to-Refrigerant HX Water Outlet Node Name required
string
indoor_air_inlet_node_name
Indoor Air Inlet Node Name required
string
indoor_air_outlet_node_name
Indoor Air Outlet Node Name required
string
number_of_speeds
Number of Speeds
integer
dimensionless
2 Range: ≥ 1, ≤ 10
nominal_speed_level
Nominal Speed Level
integer
dimensionless
2 must be lower than or equal to the highest speed number
rated_heating_capacity_at_selected_nominal_speed_level
Rated Heating Capacity At Selected Nominal Speed Level
number or Autosize
W
Autosize
rated_air_flow_rate_at_selected_nominal_speed_level
Rated Air Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
rated_water_flow_rate_at_selected_nominal_speed_level
Rated Water Flow Rate At Selected Nominal Speed Level
number or Autosize
m3/s
Autosize
energy_part_load_fraction_curve_name
Energy Part Load Fraction Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (heating load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_reference_unit_gross_rated_heating_capacity
Speed 1 Reference Unit Gross Rated Heating Capacity required
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_1_reference_unit_gross_rated_heating_cop
Speed 1 Reference Unit Gross Rated Heating COP required
number
W/W
Range: > 0
speed_1_reference_unit_rated_air_flow_rate
Speed 1 Reference Unit Rated Air Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_reference_unit_rated_water_flow_rate
Speed 1 Reference Unit Rated Water Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_heating_capacity_function_of_temperature_curve_name
Speed 1 Heating Capacity Function of Temperature Curve Name required
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 1 Total Heating Capacity Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 1 Heating Capacity Function of Water Flow Fraction Curve Name required
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_temperature_curve_name
Speed 1 Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Air Flow Fraction Curve Name required
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 1 Energy Input Ratio Function of Water Flow Fraction Curve Name required
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 1 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions required
number
dimensionless
Range: ≥ 0
speed_1_waste_heat_function_of_temperature_curve_name
Speed 1 Waste Heat Function of Temperature Curve Name required
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_reference_unit_gross_rated_heating_capacity
Speed 2 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_2_reference_unit_gross_rated_heating_cop
Speed 2 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_2_reference_unit_rated_air_flow_rate
Speed 2 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_2_reference_unit_rated_water_flow_rate
Speed 2 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_2_heating_capacity_function_of_temperature_curve_name
Speed 2 Heating Capacity Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 2 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 2 Heating Capacity Function of Water Flow Fraction Curve Name
reference quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_temperature_curve_name
Speed 2 Energy Input Ratio Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 2 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 2 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_2_waste_heat_function_of_temperature_curve_name
Speed 2 Waste Heat Function of Temperature Curve Name
reference curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_reference_unit_gross_rated_heating_capacity
Speed 3 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_3_reference_unit_gross_rated_heating_cop
Speed 3 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_3_reference_unit_rated_air_flow_rate
Speed 3 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_3_reference_unit_rated_water_flow_rate
Speed 3 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_3_heating_capacity_function_of_temperature_curve_name
Speed 3 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 3 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 3 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_temperature_curve_name
Speed 3 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 3 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 3 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_3_waste_heat_function_of_temperature_curve_name
Speed 3 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_reference_unit_gross_rated_heating_capacity
Speed 4 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_4_reference_unit_gross_rated_heating_cop
Speed 4 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_4_reference_unit_rated_air_flow_rate
Speed 4 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_4_reference_unit_rated_water_flow_rate
Speed 4 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_4_heating_capacity_function_of_temperature_curve_name
Speed 4 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 4 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 4 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_temperature_curve_name
Speed 4 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 4 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 4 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_4_waste_heat_function_of_temperature_curve_name
Speed 4 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_reference_unit_gross_rated_heating_capacity
Speed 5 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_5_reference_unit_gross_rated_heating_cop
Speed 5 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_5_reference_unit_rated_air_flow_rate
Speed 5 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_5_reference_unit_rated_water_flow_rate
Speed 5 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_5_heating_capacity_function_of_temperature_curve_name
Speed 5 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 5 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 5 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_temperature_curve_name
Speed 5 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 5 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 5 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_5_waste_heat_function_of_temperature_curve_name
Speed 5 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_reference_unit_gross_rated_heating_capacity
Speed 6 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_6_reference_unit_gross_rated_heating_cop
Speed 6 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_6_reference_unit_rated_air_flow_rate
Speed 6 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_6_reference_unit_rated_water_flow_rate
Speed 6 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_6_heating_capacity_function_of_temperature_curve_name
Speed 6 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 6 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 6 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_temperature_curve_name
Speed 6 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 6 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 6 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_6_waste_heat_function_of_temperature_curve_name
Speed 6 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_reference_unit_gross_rated_heating_capacity
Speed 7 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_7_reference_unit_gross_rated_heating_cop
Speed 7 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_7_reference_unit_rated_air_flow_rate
Speed 7 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_7_reference_unit_rated_water_flow_rate
Speed 7 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_7_heating_capacity_function_of_temperature_curve_name
Speed 7 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 7 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 7 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_temperature_curve_name
Speed 7 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 7 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 7 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_7_waste_heat_function_of_temperature_curve_name
Speed 7 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_reference_unit_gross_rated_heating_capacity
Speed 8 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_8_reference_unit_gross_rated_heating_cop
Speed 8 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_8_reference_unit_rated_air_flow_rate
Speed 8 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_8_reference_unit_rated_water_flow_rate
Speed 8 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_8_heating_capacity_function_of_temperature_curve_name
Speed 8 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 8 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 8 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_temperature_curve_name
Speed 8 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 8 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 8 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_8_waste_heat_function_of_temperature_curve_name
Speed 8 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_reference_unit_gross_rated_heating_capacity
Speed 9 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_9_reference_unit_gross_rated_heating_cop
Speed 9 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_9_reference_unit_rated_air_flow_rate
Speed 9 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_9_reference_unit_rated_water_flow_rate
Speed 9 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_9_heating_capacity_function_of_temperature_curve_name
Speed 9 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 9 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 9 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_temperature_curve_name
Speed 9 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 9 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 9 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_9_waste_heat_function_of_temperature_curve_name
Speed 9 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_reference_unit_gross_rated_heating_capacity
Speed 10 Reference Unit Gross Rated Heating Capacity
number
W
Heating capacity not accounting for the effect of supply air fan heat
Range: ≥ 0
speed_10_reference_unit_gross_rated_heating_cop
Speed 10 Reference Unit Gross Rated Heating COP
number
W/W
Range: > 0
speed_10_reference_unit_rated_air_flow_rate
Speed 10 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_10_reference_unit_rated_water_flow_rate
Speed 10 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_10_heating_capacity_function_of_temperature_curve_name
Speed 10 Heating Capacity Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_total_heating_capacity_function_of_air_flow_fraction_curve_name
Speed 10 Total Heating Capacity Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_heating_capacity_function_of_water_flow_fraction_curve_name
Speed 10 Heating Capacity Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_temperature_curve_name
Speed 10 Energy Input Ratio Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_energy_input_ratio_function_of_air_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Air Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_energy_input_ratio_function_of_water_flow_fraction_curve_name
Speed 10 Energy Input Ratio Function of Water Flow Fraction Curve Name
reference optional quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_reference_unit_waste_heat_fraction_of_input_power_at_rated_conditions
Speed 10 Reference Unit Waste Heat Fraction of Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_10_waste_heat_function_of_temperature_curve_name
Speed 10 Waste Heat Function of Temperature Curve Name
reference optional curve = a + b*db + c*db**2 + d*ewt + e*ewt**2 + f*db*ewt db = entering air dry-bulb temperature (C) ewt = water entering temperature seen by the evaporator (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:UnitaryHeatPump:WaterToAir, AirLoopHVAC:UnitarySystem, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Linkage, Branch, ZoneHVAC:WaterToAirHeatPump

Coil:WaterHeating:AirToWaterHeatPump:Pumped

from idfpy.models import CoilWaterHeatingAirToWaterHeatPumpPumped

Heat pump water heater (HPWH) heating coil, air-to-water direct-expansion (DX) system which includes a water heating coil, evaporator air coil, evaporator fan, electric compressor, and water pump. Part of a WaterHeater:HeatPump:PumpedCondenser system.

Field Type Default Details
name
Name required
string Unique name for this instance of a heat pump water heater DX coil.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_heating_capacity
Rated Heating Capacity required
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
rated_cop
Rated COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
rated_sensible_heat_ratio
Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
rated_evaporator_inlet_air_dry_bulb_temperature
Rated Evaporator Inlet Air Dry-Bulb Temperature
number
C
19.7 Evaporator inlet air dry-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_evaporator_inlet_air_wet_bulb_temperature
Rated Evaporator Inlet Air Wet-Bulb Temperature
number
C
13.5 Evaporator inlet air wet-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_condenser_inlet_water_temperature
Rated Condenser Inlet Water Temperature
number
C
57.5 Condenser inlet water temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 25
rated_evaporator_air_flow_rate
Rated Evaporator Air Flow Rate
number or Autocalculate
m3/s
Evaporator air flow rate corresponding to rated coil performance (heating capacity, COP and SHR). Default is 5.035E-5 m3/s/W (31.25 cfm/MBH) of rated heating capacity when autocalculated.
rated_condenser_water_flow_rate
Rated Condenser Water Flow Rate
number or Autocalculate
m3/s
Condenser water flow rate corresponding to rated coil performance (heating capacity, COP and SHR). Default is 4.487E-8 m3/s/W (0.208 gpm/MBH) of rated heating capacity when autocalculated. A warning message will be issued if the ratio of Rated Condenser Water Flow Rate to Heating Capacity is less than 1.79405E-8 m3/s/W (0.083 gpm/MBH) or greater than 8.97024E-8 m3/s/W (0.417 gpm/MBH), but the simulation will continue.
evaporator_fan_power_included_in_rated_cop
Evaporator Fan Power Included in Rated COP
choice Yes Select Yes if the evaporator fan power is included in the rated COP. This choice field impacts the calculation of compressor electric power.
One of No, Yes
condenser_pump_power_included_in_rated_cop
Condenser Pump Power Included in Rated COP
choice No Select Yes if the condenser pump power is included in the rated COP. This choice field impacts the calculation of compressor electric power.
One of No, Yes
condenser_pump_heat_included_in_rated_heating_capacity_and_rated_cop
Condenser Pump Heat Included in Rated Heating Capacity and Rated COP
choice No Select Yes if the condenser pump heat is included in the rated heating capacity and rated COP. This choice field impacts the calculation of water heating capacity.
One of No, Yes
condenser_water_pump_power
Condenser Water Pump Power
number
W
0.0 A warning message will be issued if the ratio of Condenser Water Pump Power to Rated Heating Capacity exceeds 0.1422 W/W (41.67 Watts/MBH), but the simulation will continue.
Range: ≥ 0
fraction_of_condenser_pump_heat_to_water
Fraction of Condenser Pump Heat to Water
number 0.2 Fraction of pump heat transferred to the condenser water. The pump is assumed to be located downstream of the condenser.
Range: ≥ 0, ≤ 1
evaporator_air_inlet_node_name
Evaporator Air Inlet Node Name required
string The node from which the DX coil draws its inlet air.
evaporator_air_outlet_node_name
Evaporator Air Outlet Node Name required
string The node to which the DX coil sends its outlet air.
condenser_water_inlet_node_name
Condenser Water Inlet Node Name required
string The node from which the DX coil condenser draws its inlet water. This name should match the source side outlet node name in the associated water heater tank object.
condenser_water_outlet_node_name
Condenser Water Outlet Node Name required
string The node to which the DX coil condenser sends its outlet water. This name should match the source side inlet node name in the associated water heater tank object.
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Ambient Temperature for Crankcase Heater Operation and the DX coil is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump:PumpedCondenser parent object (field Compressor Location).
Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_ambient_temperature_for_crankcase_heater_operation
Maximum Ambient Temperature for Crankcase Heater Operation
number
C
10.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Outdoor Temperature for Crankcase Heater Operation and the unit is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump:PumpedCondenser parent object (field Compressor Location).
Range: ≥ 0
evaporator_air_temperature_type_for_curve_objects
Evaporator Air Temperature Type for Curve Objects
choice WetBulbTemperature Determines temperature type for heating capacity curves and heating COP curves. This input determines whether the inlet air dry-bulb or wet-bulb temperature is used to evaluate these curves.
One of DryBulbTemperature, WetBulbTemperature
heating_capacity_function_of_temperature_curve_name
Heating Capacity Function of Temperature Curve Name
reference Heating capacity modifier curve (function of temperature) should be biquadratic or cubic. Biquadratic curve = a + b(ta) + c(ta)^2 + d(tw) + e(tw)^2 + f(ta)(tw). Cubic curve = a + b(ta) + c(ta)^2 + d(ta)^3. ta = evaporator inlet air [dry-bulb or wet-bulb] temperature (C). tw = condenser inlet water temperature (C). The field Evaporator Air Temperature Type for Curve Objects determines if dry-bulb or wet-bulb is used as the evaporator inlet air temperature (ta).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_capacity_function_of_air_flow_fraction_curve_name
Heating Capacity Function of Air Flow Fraction Curve Name
reference Heating capacity modifier curve (function of air flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated evaporator air flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in air flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_capacity_function_of_water_flow_fraction_curve_name
Heating Capacity Function of Water Flow Fraction Curve Name
reference Heating capacity modifier curve (function of water flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated condenser water flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in water flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_cop_function_of_temperature_curve_name
Heating COP Function of Temperature Curve Name
reference Heating COP modifier curve (function of temperature) should be biquadratic or cubic. Biquadratic curve = a + b(ta) + c(ta)^2 + d(tw) + e(tw)^2 + f(ta)(tw). Cubic curve = a + b(ta) + c(ta)^2 + d(ta)^3. ta = evaporator inlet air [dry-bulb or wet-bulb] temperature (C). tw = condenser inlet water temperature (C). The field Evaporator Air Temperature Type for Curve Objects determines if dry-bulb or wet-bulb is used as the evaporator inlet air temperature (ta).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_cop_function_of_air_flow_fraction_curve_name
Heating COP Function of Air Flow Fraction Curve Name
reference Heating COP modifier curve (function of air flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated evaporator air flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in air flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_cop_function_of_water_flow_fraction_curve_name
Heating COP Function of Water Flow Fraction Curve Name
reference Heating COP modifier curve (function of water flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated condenser water flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in water flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference Part Load Fraction Correlation (function of part load ratio) should be quadratic or cubic. Quadratic curve = a + b(PLR) + c(PLR)^2. Cubic curve = a + b(PLR) + c(PLR)^2 + d(PLR)^3. PLR = part load ratio (heating delivered/steady state heating capacity). Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in part load ratio.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 1 object types

WaterHeater:HeatPump:PumpedCondenser

Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed

from idfpy.models import CoilWaterHeatingAirToWaterHeatPumpVariableSpeed

variable-speed Heat pump water heater (VSHPWH) heating coil, air-to-water direct-expansion (DX) system which includes a variable-speed water heating coil, evaporator air coil, evaporator fan, electric compressor, and water pump. Part of a WaterHeater:HeatPump system.

Field Type Default Details
name
Name required
string Unique name for this instance of a variable-speed heat pump water heater DX coil.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_speeds
Number of Speeds
integer
dimensionless
1 Range: ≥ 1, ≤ 10
nominal_speed_level
Nominal Speed Level
integer
dimensionless
1 must be lower than or equal to the highest speed number
rated_water_heating_capacity
Rated Water Heating Capacity required
number
W
Water Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
rated_evaporator_inlet_air_dry_bulb_temperature
Rated Evaporator Inlet Air Dry-Bulb Temperature
number
C
19.7 Evaporator inlet air dry-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_evaporator_inlet_air_wet_bulb_temperature
Rated Evaporator Inlet Air Wet-Bulb Temperature
number
C
13.5 Evaporator inlet air wet-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_condenser_inlet_water_temperature
Rated Condenser Inlet Water Temperature
number
C
57.5 Condenser inlet water temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 25
rated_evaporator_air_flow_rate
Rated Evaporator Air Flow Rate
number or Autocalculate
m3/s
Evaporator air flow rate corresponding to rated coil performance (heating capacity, COP and SHR). Default is 5.035E-5 m3/s/W (31.25 cfm/MBH) of rated heating capacity when autocalculated.
rated_condenser_water_flow_rate
Rated Condenser Water Flow Rate
number or Autocalculate
m3/s
Condenser water flow rate corresponding to rated coil performance (heating capacity, COP and SHR). Default is 4.487E-8 m3/s/W (0.208 gpm/MBH) of rated heating capacity when autocalculated. A warning message will be issued if the ratio of Rated Condenser Water Flow Rate to Heating Capacity is less than 1.79405E-8 m3/s/W (0.083 gpm/MBH) or greater than 8.97024E-8 m3/s/W (0.417 gpm/MBH), but the simulation will continue.
evaporator_fan_power_included_in_rated_cop
Evaporator Fan Power Included in Rated COP
choice Yes Select Yes if the evaporator fan power is included in the rated COP. This choice field impacts the calculation of compressor electric power.
One of No, Yes
condenser_pump_power_included_in_rated_cop
Condenser Pump Power Included in Rated COP
choice No Select Yes if the condenser pump power is included in the rated COP. This choice field impacts the calculation of compressor electric power.
One of No, Yes
condenser_pump_heat_included_in_rated_heating_capacity_and_rated_cop
Condenser Pump Heat Included in Rated Heating Capacity and Rated COP
choice No Select Yes if the condenser pump heat is included in the rated heating capacity and rated COP. This choice field impacts the calculation of water heating capacity.
One of No, Yes
fraction_of_condenser_pump_heat_to_water
Fraction of Condenser Pump Heat to Water
number 0.2 Fraction of pump heat transferred to the condenser water. The pump is assumed to be located downstream of the condenser.
Range: ≥ 0, ≤ 1
evaporator_air_inlet_node_name
Evaporator Air Inlet Node Name required
string The node from which the DX coil draws its inlet air.
evaporator_air_outlet_node_name
Evaporator Air Outlet Node Name required
string The node to which the DX coil sends its outlet air.
condenser_water_inlet_node_name
Condenser Water Inlet Node Name required
string The node from which the DX coil condenser draws its inlet water. This name should match the source side outlet node name in the associated water heater tank object.
condenser_water_outlet_node_name
Condenser Water Outlet Node Name required
string The node to which the DX coil condenser sends its outlet water. This name should match the source side inlet node name in the associated water heater tank object.
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Ambient Temperature for Crankcase Heater Operation and the DX coil is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump parent object (field Compressor Location).
Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_ambient_temperature_for_crankcase_heater_operation
Maximum Ambient Temperature for Crankcase Heater Operation
number
C
10.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Outdoor Temperature for Crankcase Heater Operation and the unit is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump parent object (field Compressor Location).
Range: ≥ 0
evaporator_air_temperature_type_for_curve_objects
Evaporator Air Temperature Type for Curve Objects
choice WetBulbTemperature Determines temperature type for heating capacity curves and heating COP curves. This input determines whether the inlet air dry-bulb or wet-bulb temperature is used to evaluate these curves.
One of DryBulbTemperature, WetBulbTemperature
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference Table:Lookup object can also be used Part Load Fraction Correlation (function of part load ratio) should be quadratic or cubic. Quadratic curve = a + b(PLR) + c(PLR)^2. Cubic curve = a + b(PLR) + c(PLR)^2 + d(PLR)^3. PLR = part load ratio (heating delivered/steady state heating capacity). Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in part load ratio.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_rated_water_heating_capacity
Speed 1 Rated Water Heating Capacity required
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_1_rated_water_heating_cop
Speed 1 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_1_rated_sensible_heat_ratio
Speed 1 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_1_reference_unit_rated_air_flow_rate
Speed 1 Reference Unit Rated Air Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_reference_unit_rated_water_flow_rate
Speed 1 Reference Unit Rated Water Flow Rate required
number
m3/s
Range: ≥ 0
speed_1_reference_unit_water_pump_input_power_at_rated_conditions
Speed 1 Reference Unit Water Pump Input Power At Rated Conditions required
number
W
Range: ≥ 0
speed_1_total_wh_capacity_function_of_temperature_curve_name
Speed 1 Total WH Capacity Function of Temperature Curve Name required
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 1 Total WH Capacity Function of Air Flow Fraction Curve Name required
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 1 Total WH Capacity Function of Water Flow Fraction Curve Name required
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_cop_function_of_temperature_curve_name
Speed 1 COP Function of Temperature Curve Name required
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_1_cop_function_of_air_flow_fraction_curve_name
Speed 1 COP Function of Air Flow Fraction Curve Name required
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_1_cop_function_of_water_flow_fraction_curve_name
Speed 1 COP Function of Water Flow Fraction Curve Name required
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_rated_water_heating_capacity
Speed 2 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_2_rated_water_heating_cop
Speed 2 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_2_rated_sensible_heat_ratio
Speed 2 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_2_reference_unit_rated_air_flow_rate
Speed 2 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_2_reference_unit_rated_water_flow_rate
Speed 2 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_2_reference_unit_water_pump_input_power_at_rated_conditions
Speed 2 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_2_total_wh_capacity_function_of_temperature_curve_name
Speed 2 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 2 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 2 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_cop_function_of_temperature_curve_name
Speed 2 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_2_cop_function_of_air_flow_fraction_curve_name
Speed 2 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_2_cop_function_of_water_flow_fraction_curve_name
Speed 2 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_rated_water_heating_capacity
Speed 3 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_3_rated_water_heating_cop
Speed 3 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_3_rated_sensible_heat_ratio
Speed 3 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_3_reference_unit_rated_air_flow_rate
Speed 3 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_3_reference_unit_rated_water_flow_rate
Speed 3 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_3_reference_unit_water_pump_input_power_at_rated_conditions
Speed 3 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_3_total_wh_capacity_function_of_temperature_curve_name
Speed 3 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 3 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 3 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_cop_function_of_temperature_curve_name
Speed 3 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_3_cop_function_of_air_flow_fraction_curve_name
Speed 3 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_3_cop_function_of_water_flow_fraction_curve_name
Speed 3 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_rated_water_heating_capacity
Speed 4 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_4_rated_water_heating_cop
Speed 4 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_4_rated_sensible_heat_ratio
Speed 4 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_4_reference_unit_rated_air_flow_rate
Speed 4 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_4_reference_unit_rated_water_flow_rate
Speed 4 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_4_reference_unit_water_pump_input_power_at_rated_conditions
Speed 4 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_4_total_wh_capacity_function_of_temperature_curve_name
Speed 4 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 4 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 4 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_cop_function_of_temperature_curve_name
Speed 4 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_4_cop_function_of_air_flow_fraction_curve_name
Speed 4 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_4_cop_function_of_water_flow_fraction_curve_name
Speed 4 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_rated_water_heating_capacity
Speed 5 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_5_rated_water_heating_cop
Speed 5 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_5_rated_sensible_heat_ratio
Speed 5 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_5_reference_unit_rated_air_flow_rate
Speed 5 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_5_reference_unit_rated_water_flow_rate
Speed 5 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_5_reference_unit_water_pump_input_power_at_rated_conditions
Speed 5 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_5_total_wh_capacity_function_of_temperature_curve_name
Speed 5 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 5 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 5 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_cop_function_of_temperature_curve_name
Speed 5 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_5_cop_function_of_air_flow_fraction_curve_name
Speed 5 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_5_cop_function_of_water_flow_fraction_curve_name
Speed 5 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_rated_water_heating_capacity
Speed 6 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_6_rated_water_heating_cop
Speed 6 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_6_rated_sensible_heat_ratio
Speed 6 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_6_reference_unit_rated_air_flow_rate
Speed 6 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_6_reference_unit_rated_water_flow_rate
Speed 6 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_6_reference_unit_water_pump_input_power_at_rated_conditions
Speed 6 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_6_total_wh_capacity_function_of_temperature_curve_name
Speed 6 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 6 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 6 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_cop_function_of_temperature_curve_name
Speed 6 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_6_cop_function_of_air_flow_fraction_curve_name
Speed 6 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_6_cop_function_of_water_flow_fraction_curve_name
Speed 6 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_rated_water_heating_capacity
Speed 7 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_7_rated_water_heating_cop
Speed 7 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_7_rated_sensible_heat_ratio
Speed 7 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_7_reference_unit_rated_air_flow_rate
Speed 7 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_7_reference_unit_rated_water_flow_rate
Speed 7 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_7_reference_unit_water_pump_input_power_at_rated_conditions
Speed 7 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_7_total_wh_capacity_function_of_temperature_curve_name
Speed 7 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 7 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 7 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_cop_function_of_temperature_curve_name
Speed 7 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_7_cop_function_of_air_flow_fraction_curve_name
Speed 7 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_7_cop_function_of_water_flow_fraction_curve_name
Speed 7 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_rated_water_heating_capacity
Speed 8 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_8_rated_water_heating_cop
Speed 8 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_8_rated_sensible_heat_ratio
Speed 8 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_8_reference_unit_rated_air_flow_rate
Speed 8 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_8_reference_unit_rated_water_flow_rate
Speed 8 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_8_reference_unit_water_pump_input_power_at_rated_conditions
Speed 8 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_8_total_wh_capacity_function_of_temperature_curve_name
Speed 8 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 8 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 8 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_cop_function_of_temperature_curve_name
Speed 8 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_8_cop_function_of_air_flow_fraction_curve_name
Speed 8 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_8_cop_function_of_water_flow_fraction_curve_name
Speed 8 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_rated_water_heating_capacity
Speed 9 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_9_rated_water_heating_cop
Speed 9 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_9_rated_sensible_heat_ratio
Speed 9 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_9_reference_unit_rated_air_flow_rate
Speed 9 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_9_reference_unit_rated_water_flow_rate
Speed 9 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_9_reference_unit_water_pump_input_power_at_rated_conditions
Speed 9 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_9_total_wh_capacity_function_of_temperature_curve_name
Speed 9 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 9 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 9 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_cop_function_of_temperature_curve_name
Speed 9 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_9_cop_function_of_air_flow_fraction_curve_name
Speed 9 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_9_cop_function_of_water_flow_fraction_curve_name
Speed 9 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_rated_water_heating_capacity
Speed 10 Rated Water Heating Capacity
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
speed_10_rated_water_heating_cop
Speed 10 Rated Water Heating COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air and water temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
speed_10_rated_sensible_heat_ratio
Speed 10 Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
speed_10_reference_unit_rated_air_flow_rate
Speed 10 Reference Unit Rated Air Flow Rate
number
m3/s
Range: ≥ 0
speed_10_reference_unit_rated_water_flow_rate
Speed 10 Reference Unit Rated Water Flow Rate
number
m3/s
Range: ≥ 0
speed_10_reference_unit_water_pump_input_power_at_rated_conditions
Speed 10 Reference Unit Water Pump Input Power At Rated Conditions
number
dimensionless
Range: ≥ 0
speed_10_total_wh_capacity_function_of_temperature_curve_name
Speed 10 Total WH Capacity Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_total_wh_capacity_function_of_air_flow_fraction_curve_name
Speed 10 Total WH Capacity Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_total_wh_capacity_function_of_water_flow_fraction_curve_name
Speed 10 Total WH Capacity Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_cop_function_of_temperature_curve_name
Speed 10 COP Function of Temperature Curve Name
reference Table:Lookup object can also be used curve = a + b*wb + c*wb**2 + d*ewt + e*ewt**2 + f*wb*ewt wb = entering wet-bulb temperature or dry bulb temperature upon selection (C) ewt = water entering temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
speed_10_cop_function_of_air_flow_fraction_curve_name
Speed 10 COP Function of Air Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffa + c*ffa**2 cubic curve = a + b*ffa + c*ffa**2 + d*ffa**3 ffa = Fraction of the full load Air Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
speed_10_cop_function_of_water_flow_fraction_curve_name
Speed 10 COP Function of Water Flow Fraction Curve Name
reference Table:Lookup object can also be used quadratic curve = a + b*ffw + c*ffw**2 cubic curve = a + b*ffw + c*ffw**2 + d*ffw**3 ffw = Fraction of the full load Water Flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 2 object types

CoilSystem:IntegratedHeatPump:AirSource, WaterHeater:HeatPump:PumpedCondenser

Coil:WaterHeating:AirToWaterHeatPump:Wrapped

from idfpy.models import CoilWaterHeatingAirToWaterHeatPumpWrapped

Heat pump water heater (HPWH) heating coil, air-to-water direct-expansion (DX) system which includes a water heating coil, evaporator air coil, evaporator fan, electric compressor, and water pump. Part of a WaterHeater:HeatPump:WrappedCondenser system.

Field Type Default Details
name
Name required
string Unique name for this instance of a heat pump water heater DX coil.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_heating_capacity
Rated Heating Capacity required
number
W
Heating capacity at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump heat.
Range: > 0
rated_cop
Rated COP
number
W/W
3.2 Heating coefficient of performance at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Can optionally include condenser pump power and evaporator fan power (see fields below).
Range: > 0
rated_sensible_heat_ratio
Rated Sensible Heat Ratio
number 0.85 Gross air-side sensible heat ratio at the rated inlet air temperatures, rated condenser inlet water temperature, rated air flow rate, and rated water flow rate. Sensible heat ratio equals gross sensible cooling capacity divided by gross total cooling capacity. Rated SHR (gross) should not include evaporator fan heat, only sensible cooling and dehumidification by the coil alone.
Range: ≥ 0.5, ≤ 1
rated_evaporator_inlet_air_dry_bulb_temperature
Rated Evaporator Inlet Air Dry-Bulb Temperature
number
C
19.7 Evaporator inlet air dry-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_evaporator_inlet_air_wet_bulb_temperature
Rated Evaporator Inlet Air Wet-Bulb Temperature
number
C
13.5 Evaporator inlet air wet-bulb temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 5
rated_condenser_water_temperature
Rated Condenser Water Temperature
number
C
57.5 Condenser inlet water temperature corresponding to rated coil performance (heating capacity, COP and SHR).
Range: > 25
rated_evaporator_air_flow_rate
Rated Evaporator Air Flow Rate
number or Autocalculate
m3/s
Evaporator air flow rate corresponding to rated coil performance (heating capacity, COP and SHR). Default is 5.035E-5 m3/s/W (31.25 cfm/MBH) of rated heating capacity when autocalculated.
evaporator_fan_power_included_in_rated_cop
Evaporator Fan Power Included in Rated COP
choice Yes Select Yes if the evaporator fan power is included in the rated COP. This choice field impacts the calculation of compressor electric power.
One of No, Yes
evaporator_air_inlet_node_name
Evaporator Air Inlet Node Name required
string The node from which the DX coil draws its inlet air.
evaporator_air_outlet_node_name
Evaporator Air Outlet Node Name required
string The node to which the DX coil sends its outlet air.
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Ambient Temperature for Crankcase Heater Operation and the DX coil is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump:WrappedCondenser parent object (field Compressor Location).
Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_ambient_temperature_for_crankcase_heater_operation
Maximum Ambient Temperature for Crankcase Heater Operation
number
C
10.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Outdoor Temperature for Crankcase Heater Operation and the unit is off. The ambient temperature surrounding the compressor is set by the WaterHeater:HeatPump:WrappedCondenser parent object (field Compressor Location).
Range: ≥ 0
evaporator_air_temperature_type_for_curve_objects
Evaporator Air Temperature Type for Curve Objects
choice WetBulbTemperature Determines temperature type for heating capacity curves and heating COP curves. This input determines whether the inlet air dry-bulb or wet-bulb temperature is used to evaluate these curves.
One of DryBulbTemperature, WetBulbTemperature
heating_capacity_function_of_temperature_curve_name
Heating Capacity Function of Temperature Curve Name
reference Heating capacity modifier curve (function of temperature) should be biquadratic or cubic. Biquadratic curve = a + b(ta) + c(ta)^2 + d(tw) + e(tw)^2 + f(ta)(tw). Cubic curve = a + b(ta) + c(ta)^2 + d(ta)^3. ta = evaporator inlet air [dry-bulb or wet-bulb] temperature (C). tw = condenser inlet water temperature (C). The field Evaporator Air Temperature Type for Curve Objects determines if dry-bulb or wet-bulb is used as the evaporator inlet air temperature (ta).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_capacity_function_of_air_flow_fraction_curve_name
Heating Capacity Function of Air Flow Fraction Curve Name
reference Heating capacity modifier curve (function of air flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated evaporator air flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in air flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_cop_function_of_temperature_curve_name
Heating COP Function of Temperature Curve Name
reference Heating COP modifier curve (function of temperature) should be biquadratic or cubic. Biquadratic curve = a + b(ta) + c(ta)^2 + d(tw) + e(tw)^2 + f(ta)(tw). Cubic curve = a + b(ta) + c(ta)^2 + d(ta)^3. ta = evaporator inlet air [dry-bulb or wet-bulb] temperature (C). tw = condenser inlet water temperature (C). The field Evaporator Air Temperature Type for Curve Objects determines if dry-bulb or wet-bulb is used as the evaporator inlet air temperature (ta).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_cop_function_of_air_flow_fraction_curve_name
Heating COP Function of Air Flow Fraction Curve Name
reference Heating COP modifier curve (function of air flow fraction) should be quadratic or cubic. Quadratic curve = a + b(ff) + c(ff)^2. Cubic curve = a + b(ff) + c(ff)^2 + d(ff)^3. ff = fraction of the rated evaporator air flow rate. Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in air flow rate fraction.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name
reference Part Load Fraction Correlation (function of part load ratio) should be quadratic or cubic. Quadratic curve = a + b(PLR) + c(PLR)^2. Cubic curve = a + b(PLR) + c(PLR)^2 + d(PLR)^3. PLR = part load ratio (heating delivered/steady state heating capacity). Use curve coefficients of 1,0,0 or leave this field blank when neglecting performance impacts due to variations in part load ratio.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 1 object types

WaterHeater:HeatPump:WrappedCondenser

Coil:WaterHeating:Desuperheater

from idfpy.models import CoilWaterHeatingDesuperheater

Desuperheater air heating coil. The heating energy provided by this coil is reclaimed from the superheated refrigerant gas leaving a compressor and does not impact the performance of the compressor. This coil must be used with a water heater tank, see Water Heater:Mixed.

Field Type Default Details
name
Name required
string Unique name for this instance of a desuperheater water heating coil.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Schedule values of 0 denote the desuperheater heating coil is off and the parasitic electric energy is also off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
setpoint_temperature_schedule_name
Setpoint Temperature Schedule Name required
reference Defines the cut-out temperature where the desuperheater water heating coil turns off. The desuperheater heating coil setpoint temperature should always be greater than the water tank's heater (element or burner) setpoint temperature. Temperature schedule values should be in degrees C.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dead_band_temperature_difference
Dead Band Temperature Difference
number
deltaC
5.0 Setpoint temperature minus the dead band temperature difference defines the cut-in temperature where the desuperheater water heating coil turns on. The water tank's heater (element or burner) setpoint temperature should always be less than the desuperheater heating coil cut-in temperature.
Range: > 0, ≤ 20
rated_heat_reclaim_recovery_efficiency
Rated Heat Reclaim Recovery Efficiency
number Enter the fraction of waste heat reclaimed by the desuperheater water heating coil.
Range: > 0
rated_inlet_water_temperature
Rated Inlet Water Temperature required
number
C
The inlet water temperature corresponding to the rated heat reclaim recovery efficiency.
rated_outdoor_air_temperature
Rated Outdoor Air Temperature required
number
C
The outdoor air dry-bulb temperature corresponding to the rated heat reclaim recovery efficiency.
maximum_inlet_water_temperature_for_heat_reclaim
Maximum Inlet Water Temperature for Heat Reclaim required
number
C
The desuperheater water heating coil is off when the inlet water temperature is above the maximum inlet water temperature for heat reclaim.
heat_reclaim_efficiency_function_of_temperature_curve_name
Heat Reclaim Efficiency Function of Temperature Curve Name
reference A biquadratic curve defining the performance of the desuperheater heating coil. Performance can be specified as a function of inlet water temperature, outdoor air dry-bulb temperature, or both. Curve = a + b*Tw + c*Tw**2 + d*odb + e*odb**2 + f*Tw*odb. Tw = desuperheater heating coil entering water temperature (C). Odb = outdoor dry-bulb temperature at DX system condenser (C).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
water_inlet_node_name
Water Inlet Node Name required
string The node from which the desuperheater heating coil draws its inlet water. This name should match the source side outlet node name in the associated water heater tank object.
water_outlet_node_name
Water Outlet Node Name required
string The node to which the desuperheater heating coil sends its outlet water. This name should match the source side inlet node name in the associated water heater tank object.
tank_object_type
Tank Object Type
choice WaterHeater:Mixed Specify the type of water heater tank used by this desuperheater water heating coil.
One of WaterHeater:Mixed, WaterHeater:Stratified
tank_name
Tank Name required
reference The name of the water heater tank used by this desuperheater water heating coil. Needs to match the name used in the corresponding water heater object.
Names a WaterHeater:Mixed, WaterHeater:Stratified
heating_source_object_type
Heating Source Object Type required
choice The type of DX system that is providing waste heat for reclaim.
One of Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Refrigeration:CompressorRack, Refrigeration:Condenser:AirCooled, Refrigeration:Condenser:EvaporativeCooled, Refrigeration:Condenser:WaterCooled
heating_source_name
Heating Source Name required
reference The name of the DX system used for heat reclaim.
Names a Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Refrigeration:CompressorRack, Refrigeration:Condenser:AirCooled, Refrigeration:Condenser:EvaporativeCooled, Refrigeration:Condenser:WaterCooled
water_flow_rate
Water Flow Rate required
number
m3/s
The operating water flow rate.
Range: > 0
water_pump_power
Water Pump Power
number
W
0.0 The water circulation pump electric power.
Range: ≥ 0
fraction_of_pump_heat_to_water
Fraction of Pump Heat to Water
number 0.2 The fraction of pump heat transferred to the water. The pump is assumed to be downstream of the desuperheater water heating coil.
Range: ≥ 0, ≤ 1
on_cycle_parasitic_electric_load
On-Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric power consumed when the desuperheater water heating coil operates. Parasitic electric load does not contribute to water heating or the zone air heat balance.
Range: ≥ 0
off_cycle_parasitic_electric_load
Off-Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric load consumed when the desuperheater water heating coil is off. Parasitic electric load does not contribute to water heating or the zone air heat balance. Off-cycle parasitic power is 0 when the availability schedule is 0.
Range: ≥ 0

CoilPerformance:DX:Cooling

from idfpy.models import CoilPerformanceDXCooling

Used to specify DX cooling coil performance for one mode of operation for a Coil:Cooling:DX:TwoStageWithHumidityControlMode object which may reference one to four CoilPerformance:DX:Cooling objects depending on the specified number of stages and dehumidification modes. In nearly all cases, the Rated Air Flow Rate will be the same for all performance objects associated with a given coil. If bypass is specified, the Rated Air Flow Rate includes both the bypassed flow and the flow through the active part of the coil.

Field Type Default Details
name
Name required
string
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity required
number or Autosize
W
Total cooling capacity not accounting for the effect of supply air fan heat gross capacity excluding supply air fan heat rating point: air entering the cooling coil at 26.7 C dry-bulb/19.4 C wet-bulb, and air entering the outdoor condenser coil at 35 C dry-bulb/23.9 C wet-bulb
gross_rated_sensible_heat_ratio
Gross Rated Sensible Heat Ratio required
number or Autosize Rated sensible heat ratio (gross sensible capacity/gross total capacity) sensible and total capacities do not include supply fan heat
gross_rated_cooling_cop
Gross Rated Cooling COP
number
W/W
3.0 Gross cooling capacity divided by power input to the compressor and outdoor fan, does not include supply fan heat or supply fan electrical energy input
Range: > 0
rated_air_flow_rate
Rated Air Flow Rate required
number or Autosize
m3/s
Flow rate corresponding to Rated total Cooling capacity, Rated SHR and Rated COP
fraction_of_air_flow_bypassed_around_coil
Fraction of Air Flow Bypassed Around Coil
number 0.0 Fraction of Rated Air Flow Rate which bypasses the cooling coil in this performance mode. The remaining portion of the flow should be between 0.00004027 m3/s and .00006041 m3/s per watt of rated total cooling capacity. This is used to model face-split coils on multi-stage units or bypass dampers. If total flow rate varies during simulation, the same fraction is bypassed.
Range: ≥ 0, < 1
total_cooling_capacity_function_of_temperature_curve_name
Total Cooling Capacity Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
total_cooling_capacity_function_of_flow_fraction_curve_name
Total Cooling Capacity Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
energy_input_ratio_function_of_temperature_curve_name
Energy Input Ratio Function of Temperature Curve Name required
reference curve = a + b*wb + c*wb**2 + d*edb + e*edb**2 + f*wb*edb wb = entering wet-bulb temperature (C) edb = dry-bulb temperature seen by the condenser (C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
energy_input_ratio_function_of_flow_fraction_curve_name
Energy Input Ratio Function of Flow Fraction Curve Name required
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
part_load_fraction_correlation_curve_name
Part Load Fraction Correlation Curve Name required
reference quadratic curve = a + b*PLR + c*PLR**2 cubic curve = a + b*PLR + c*PLR**2 + d*PLR**3 PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
nominal_time_for_condensate_removal_to_begin
Nominal Time for Condensate Removal to Begin
number
s
0.0 The nominal time for condensate to begin leaving the coil's condensate drain line at the coil's rated air flow rate and temperature conditions. Nominal time is equal to the ratio of the energy of the coil's maximum condensate holding capacity (J) to the coil's steady state latent capacity (W). Suggested value is 1000; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 3000
ratio_of_initial_moisture_evaporation_rate_and_steady_state_latent_capacity
Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity
number
dimensionless
0.0 Ratio of the initial moisture evaporation rate from the cooling coil (when the compressor first turns off) and the coil's steady state latent capacity at rated air flow rate and temperature conditions. Suggested value is 1.5; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
maximum_cycling_rate
Maximum Cycling Rate
number
cycles/hr
0.0 The maximum on-off cycling rate for the compressor, which occurs at 50% run time fraction. Suggested value is 3; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 5
latent_capacity_time_constant
Latent Capacity Time Constant
number
s
0.0 Time constant for the cooling coil's latent capacity to reach steady state after startup. Suggested value is 45; zero value means latent degradation model is disabled.
Range: ≥ 0, ≤ 500
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Enter the name of an outdoor air node. This node name is also specified in an OutdoorAir:Node or OutdoorAir:NodeList object.
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Range: ≥ 0, ≤ 1
evaporative_condenser_air_flow_rate
Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump
sensible_heat_ratio_function_of_temperature_curve_name
Sensible Heat Ratio Function of Temperature Curve Name
reference curve = a + b*wb + c*wb**2 + d*db + e*db**2 + f*wb*db wb = entering wet-bulb temperature seen by the DX cooling coil (C) db = entering dry-bulb temperature seen by the DX cooling coil (C) entering temperature can be outside air or pretreated air.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
sensible_heat_ratio_function_of_flow_fraction_curve_name
Sensible Heat Ratio Function of Flow Fraction Curve Name
reference quadratic curve = a + b*ff + c*ff**2 cubic curve = a + b*ff + c*ff**2 + d*ff**3 ff = fraction of the full load flow
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 1 object types

Coil:Cooling:DX:TwoStageWithHumidityControlMode

CoilSystem:Cooling:DX

from idfpy.models import CoilSystemCoolingDX

Virtual container component that consists of a DX cooling coil and its associated controls. This control object supports several different types of DX cooling coils and may be placed directly in an air loop branch or outdoor air equipment list.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dx_cooling_coil_system_inlet_node_name
DX Cooling Coil System Inlet Node Name required
string
dx_cooling_coil_system_outlet_node_name
DX Cooling Coil System Outlet Node Name required
string
dx_cooling_coil_system_sensor_node_name
DX Cooling Coil System Sensor Node Name required
string
cooling_coil_object_type
Cooling Coil Object Type required
choice One of Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only Multimode = activate enhanced dehumidification mode as needed and meet sensible load. If no sensible load exists, and Run on Latent Load = Yes, and a latent load exists, the unit will operate to meet the latent load. Valid only with Coil:Cooling:DX:TwoStageWithHumidityControlMode or CoilSystem:Cooling:DX:HeatExchangerAssisted. CoolReheat = cool beyond the dry-bulb setpoint. as required to meet the humidity setpoint. Valid for all coil types. For all dehumidification controls, the max humidity setpoint on the Sensor Node is used. SetpointManager:SingleZone:Humidity:Maximum, SetpointManager:MultiZone:Humidity:Maximum, or SetpointManager:MultiZone:MaximumHumidity:Average, and SetpointManager:OutdoorAirPretreat (optional) objects.
One of CoolReheat, Multimode, None
run_on_sensible_load
Run on Sensible Load
choice Yes If Yes, unit will run if there is a sensible load. If No, unit will not run if there is only a sensible load. Dehumidification controls will be active if specified.
One of No, Yes
run_on_latent_load
Run on Latent Load
choice No If Yes, unit will run if there is a latent load. even if there is no sensible load. If No, unit will not run only if there is a latent load. Dehumidification controls will be active if specified.
One of No, Yes
use_outdoor_air_dx_cooling_coil
Use Outdoor Air DX Cooling Coil
choice No This input field is designed for use with DX cooling coils with low air flow to capacity ratio range (100 - 300 cfm/ton). Typical application is 100% dedicated outdoor air system (DOAS). Other air loop or zone HVAC systems with low flow to capacity ratio range may also use this input field. If Yes, the DX cooling coil runs as 100% DOAS DX coil or low flow to capacity ratio range. If No, the DX cooling coil runs as a regular DX coil. If left blank the default is regular DX coil.
One of No, Yes
outdoor_air_dx_cooling_coil_leaving_minimum_air_temperature
Outdoor Air DX Cooling Coil Leaving Minimum Air Temperature
number
C
2.0 DX cooling coil leaving minimum air temperature defines the minimum DX cooling coil leaving air temperature that should be maintained to avoid frost formation. This input field is optional and only used along with the input field above.
Range: ≥ 0, ≤ 7.2
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch, FaultModel:TemperatureSensorOffset:CoilSupplyAir

CoilSystem:Cooling:DX:HeatExchangerAssisted

from idfpy.models import CoilSystemCoolingDXHeatExchangerAssisted

Virtual component consisting of a direct expansion (DX) cooling coil and an air-to-air heat exchanger. The air-to-air heat exchanger precools the air entering the cooling coil and reuses this energy to reheat the supply air leaving the cooling coil. This heat exchange process improves the latent removal performance of the cooling coil (lower sensible heat ratio).

Field Type Default Details
name
Name required
string
heat_exchanger_object_type
Heat Exchanger Object Type required
choice One of HeatExchanger:AirToAir:FlatPlate, HeatExchanger:AirToAir:SensibleAndLatent, HeatExchanger:Desiccant:BalancedFlow
heat_exchanger_name
Heat Exchanger Name required
reference Names a HeatExchanger:AirToAir:FlatPlate, HeatExchanger:AirToAir:SensibleAndLatent, HeatExchanger:Desiccant:BalancedFlow
cooling_coil_object_type
Cooling Coil Object Type required
choice One of Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:VariableSpeed
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:DX, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
Referenced by 11 object types

AirLoopHVAC:Unitary:Furnace:HeatCool, AirLoopHVAC:UnitaryHeatCool, AirLoopHVAC:UnitaryHeatCool:VAVChangeoverBypass, AirLoopHVAC:UnitaryHeatPump:AirToAir, AirLoopHVAC:UnitarySystem, CoilSystem:Cooling:DX, CoilSystem:Cooling:DX:HeatExchangerAssisted, Dehumidifier:Desiccant:System, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:WindowAirConditioner

CoilSystem:Cooling:Water

from idfpy.models import CoilSystemCoolingWater

Virtual container component that consists of a water cooling coil and its associated controls. This control object supports the available water coil types and may be placed directly on an air loop branch or in an outdoor air equipment list.

Field Type Default Details
name
Name required
string
air_inlet_node_name
Air Inlet Node Name required
string
air_outlet_node_name
Air Outlet Node Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cooling_coil_object_type
Cooling Coil Object Type required
choice One of Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, CoilSystem:Cooling:Water:HeatExchangerAssisted
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, CoilSystem:Cooling:Water:HeatExchangerAssisted
dehumidification_control_type
Dehumidification Control Type
choice None None = meet sensible load only. Valid with all cooling coil types. When a heat exchanger assisted cooling coil is used, the heat exchanger is locked on at all times. Multimode = activate water coil and meet sensible load. If no sensible load exists, and Run on Latent Load = Yes, and a latent load exists, the coil will operate to meet the latent load. If the latent load cannot be met the heat exchanger will be activated. Valid only with cooling coil type CoilSystem:Cooling:Water:HeatExchangerAssisted. CoolReheat = cool beyond the dry-bulb setpoint as required to meet the humidity setpoint. Valid with all cooling coil types. When a heat exchanger assisted cooling coil is used, the heat exchanger is locked on at all times. For all dehumidification controls, the max humidity setpoint on the Sensor Node is used. SetpointManager:SingleZone:Humidity:Maximum, SetpointManager:MultiZone:Humidity:Maximum, or SetpointManager:MultiZone:MaximumHumidity:Average, and SetpointManager:OutdoorAirPretreat (optional) objects.
One of CoolReheat, Multimode, None
run_on_sensible_load
Run on Sensible Load
choice Yes If Yes, unit will run if there is a sensible load. If No, unit will not run if there is only a sensible load. Dehumidification controls will be active if specified.
One of No, Yes
run_on_latent_load
Run on Latent Load
choice No If Yes, unit will run if there is a latent load. even if there is no sensible load. If No, unit will not run if there is only a latent load. Dehumidification controls will be active if specified.
One of No, Yes
minimum_air_to_water_temperature_offset
Minimum Air To Water Temperature Offset
number
deltaC
0.0 Coil will turn on as required when inlet air temperature is above water temperature by amount of offset. To model a waterside economizer connect to condenser loop and increase offset as desired.
Range: ≥ 0
economizer_lockout
Economizer Lockout
choice Yes Yes means that the heat exchanger will be locked out (off)
One of No, Yes
minimum_water_loop_temperature_for_heat_recovery
Minimum Water Loop Temperature For Heat Recovery
number
C
0.0 Only used for heat recovery loops. Loop will turn off below this temperature.
companion_coil_used_for_heat_recovery
Companion Coil Used For Heat Recovery
reference Only used for heat recovery loops. Entering a coil name indicates a heat recovery loop is specified. Coil listed is connected in series with this objects coil on demand side branch of a plant loop. A dedicated plant loop with no supply side equipment, other than a pump, is currently required. Only Coil:Cooling:Water coil type is currently allowed for heat recovery loops.
Names a Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, CoilSystem:Cooling:Water:HeatExchangerAssisted
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch

CoilSystem:Cooling:Water:HeatExchangerAssisted

from idfpy.models import CoilSystemCoolingWaterHeatExchangerAssisted

Virtual component consisting of a chilled-water cooling coil and an air-to-air heat exchanger. The air-to-air heat exchanger precools the air entering the cooling coil and reuses this energy to reheat the supply air leaving the cooling coil. This heat exchange process improves the latent removal performance of the cooling coil (lower sensible heat ratio).

Field Type Default Details
name
Name required
string
heat_exchanger_object_type
Heat Exchanger Object Type required
choice One of HeatExchanger:AirToAir:FlatPlate, HeatExchanger:AirToAir:SensibleAndLatent
heat_exchanger_name
Heat Exchanger Name required
string
cooling_coil_object_type
Cooling Coil Object Type required
choice One of Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry
cooling_coil_name
Cooling Coil Name required
reference Names a Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirLoopHVAC:UnitarySystem, Branch, CoilSystem:Cooling:Water, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab

CoilSystem:Heating:DX

from idfpy.models import CoilSystemHeatingDX

Virtual container component that consists of a DX heating coil (heat pump) and its associated controls. This control object supports two different types of DX heating coils and may be placed directly in an air loop branch or outdoor air equipment list.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heating_coil_object_type
Heating Coil Object Type required
choice One of Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed
heating_coil_name
Heating Coil Name required
reference Names a Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableRefrigerantFlow, Coil:Heating:DX:VariableSpeed
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch, FaultModel:TemperatureSensorOffset:CoilSupplyAir

CoilSystem:IntegratedHeatPump:AirSource

from idfpy.models import CoilSystemIntegratedHeatPumpAirSource

This object is used for air-source integrated heat pump, a collection of its working modes.

Field Type Default Details
name
Name required
string Unique name for this instance of an air-source integrated heat pump.
supply_hot_water_flow_sensor_node_name
Supply Hot Water Flow Sensor Node Name required
string
space_cooling_coil_name
Space Cooling Coil Name required
reference Must match the name used in the corresponding Coil:Cooling:DX:VariableSpeed object.
Names a Coil:Cooling:DX:VariableSpeed
space_heating_coil_name
Space Heating Coil Name
reference Must match the name used in the corresponding Coil:Heating:DX:VariableSpeed object.
Names a Coil:Heating:DX:VariableSpeed
dedicated_water_heating_coil_name
Dedicated Water Heating Coil Name
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed object.
Names a Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed
scwh_coil_name
SCWH Coil Name
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed object.
Names a Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed
scdwh_cooling_coil_name
SCDWH Cooling Coil Name
reference Must match the name used in the corresponding Coil:Cooling:DX:VariableSpeed object.
Names a Coil:Cooling:DX:VariableSpeed
scdwh_water_heating_coil_name
SCDWH Water Heating Coil Name
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed object.
Names a Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed
shdwh_heating_coil_name
SHDWH Heating Coil Name
reference Must match the name used in the corresponding Coil:Heating:DX:VariableSpeed object.
Names a Coil:Heating:DX:VariableSpeed
shdwh_water_heating_coil_name
SHDWH Water Heating Coil Name
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed object.
Names a Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed
indoor_temperature_limit_for_scwh_mode
Indoor Temperature Limit for SCWH Mode
number
C
20.0 Indoor Temperature above which Indoor Overcooling is Allowed during Cooling Operation
Range: > 15
ambient_temperature_limit_for_scwh_mode
Ambient Temperature Limit for SCWH Mode
number
C
27.0 Ambient Temperature above which Indoor Overcooling is Allowed during Cooling Operation
Range: > 20
indoor_temperature_above_which_wh_has_higher_priority
Indoor Temperature above Which WH has Higher Priority
number
C
20.0 Indoor Temperature above which Water Heating has the higher priority and Space Heating Call Can be ignored.
Range: > 15
ambient_temperature_above_which_wh_has_higher_priority
Ambient Temperature above Which WH has Higher Priority
number
C
20.0 Ambient Temperature above which Water Heating has the higher priority and Space Heating Call Can be ignored.
Range: > 15
flag_to_indicate_load_control_in_scwh_mode
Flag to Indicate Load Control in SCWH Mode
integer
dimensionless
0 0: match space cooling load in SCWH mode, 1: match water heating load in SCWH mode
minimum_speed_level_for_scwh_mode
Minimum Speed Level for SCWH Mode
integer
dimensionless
1 Range: > 0, < 10
maximum_water_flow_volume_before_switching_from_scdwh_to_scwh_mode
Maximum Water Flow Volume before Switching from SCDWH to SCWH Mode
number
m3
0.0
minimum_speed_level_for_scdwh_mode
Minimum Speed Level for SCDWH Mode
integer
dimensionless
1 Range: > 0, < 10
maximum_running_time_before_allowing_electric_resistance_heat_use_during_shdwh_mode
Maximum Running Time before Allowing Electric Resistance Heat Use during SHDWH Mode
number
s
360.0 Range: > 0
minimum_speed_level_for_shdwh_mode
Minimum Speed Level for SHDWH Mode
integer
dimensionless
1 Range: > 0, < 10
Referenced by 2 object types

AirLoopHVAC:UnitaryHeatPump:AirToAir, WaterHeater:HeatPump:PumpedCondenser