Condenser Equipment and Heat Exchangers

21 object types from idfpy.models.condensers · EnergyPlus 26.2

Object Summary
CoolingTower:SingleSpeed This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 …
CoolingTower:TwoSpeed This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 …
CoolingTower:VariableSpeed This open wet tower model is based on purely empirical algorithms derived from manufacturer's performance …
CoolingTower:VariableSpeed:Merkel This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 …
CoolingTowerPerformance:CoolTools This object is used to define coefficients for the approach temperature correlation for a variable speed …
CoolingTowerPerformance:YorkCalc This object is used to define coefficients for the approach temperature correlation for a variable speed …
EvaporativeFluidCooler:SingleSpeed This model is based on Merkel's theory, which is also the basis for the cooling tower model in EnergyPlus.
EvaporativeFluidCooler:TwoSpeed This model is based on Merkel's theory, which is also the basis for the cooling tower model in EnergyPlus.
FluidCooler:SingleSpeed The fluid cooler is modeled as a cross flow heat exchanger (both streams unmixed) with single-speed fans …
FluidCooler:TwoSpeed The fluid cooler is modeled as a cross flow heat exchanger (both streams unmixed) with two-speed fans …
GroundHeatExchanger:HorizontalTrench This models a horizontal heat exchanger placed in a series of trenches The model uses the …
GroundHeatExchanger:Pond A model of a shallow pond with immersed pipe loops.
GroundHeatExchanger:ResponseFactors Response factor definitions from third-party tool, commonly referred to a "g-functions"
GroundHeatExchanger:Slinky This models a slinky horizontal heat exchanger placed in a series of trenches The model uses the model …
GroundHeatExchanger:Surface A hydronic surface/panel consisting of a multi-layer construction with embedded rows of tubes.
GroundHeatExchanger:System Models vertical ground heat exchangers systems using the response factor approach developed by Eskilson.
GroundHeatExchanger:Vertical:Array
GroundHeatExchanger:Vertical:Properties Properties for vertical ground heat exchanger systems
GroundHeatExchanger:Vertical:Single
GroundHeatExchanger:Vertical:Sizing:Rectangle Specifies parameters to be used for Ground Heat Exchanger borehole field design and sizing.
HeatExchanger:FluidToFluid A fluid/fluid heat exchanger designed to couple the supply side of one loop to the demand side of another …

CoolingTower:SingleSpeed

from idfpy.models import CoolingTowerSingleSpeed

This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 Toolkit. The open wet cooling tower is modeled as a counter flow heat exchanger with a single-speed fan drawing air through the tower (induced-draft configuration). Added fluid bypass as an additional capacity control. 8/2008. For a multi-cell tower, the capacity and air/water flow rate inputs are for the entire tower.

Field Type Default Details
name
Name required
string Tower Name
water_inlet_node_name
Water Inlet Node Name required
string Name of tower water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of tower water outlet node
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Leave field blank if tower performance input method is NominalCapacity
design_air_flow_rate
Design Air Flow Rate required
number or Autosize
m3/s
design_fan_power
Design Fan Power required
number or Autosize
W
This is the fan motor electric input power
design_u_factor_times_area_value
Design U-Factor Times Area Value
number or Autosize
W/K
Leave field blank if tower performance input method is NominalCapacity
free_convection_regime_air_flow_rate
Free Convection Regime Air Flow Rate
number or Autocalculate
m3/s
0.0
free_convection_regime_air_flow_rate_sizing_factor
Free Convection Regime Air Flow Rate Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate.
Range: > 0, < 1
free_convection_regime_u_factor_times_area_value
Free Convection Regime U-Factor Times Area Value
number or Autocalculate
W/K
0.0
free_convection_u_factor_times_area_value_sizing_factor
Free Convection U-Factor Times Area Value Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate and the Performance Input Method is UFactorTimesAreaAndDesignWaterFlowRate
Range: > 0, < 1
performance_input_method
Performance Input Method
choice UFactorTimesAreaAndDesignWaterFlowRate User can define tower thermal performance by specifying the tower UA, the Design Air Flow Rate and the Design Water Flow Rate, or by specifying the tower nominal capacity
One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
heat_rejection_capacity_and_nominal_capacity_sizing_ratio
Heat Rejection Capacity and Nominal Capacity Sizing Ratio
number 1.25
nominal_capacity
Nominal Capacity
number
W
Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt (3 gpm/ton). Nominal tower capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
Range: > 0
free_convection_capacity
Free Convection Capacity
number or Autocalculate
W
Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt of nominal tower capacity (3 gpm/ton). Tower free convection capacity times (1.25) gives the actual tower heat rejection at these operating conditions.
free_convection_nominal_capacity_sizing_factor
Free Convection Nominal Capacity Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate
Range: > 0, < 1
design_inlet_air_dry_bulb_temperature
Design Inlet Air Dry-Bulb Temperature
number
C
35.0 Enter the tower's design inlet air dry-bulb temperature
Range: ≥ 20
design_inlet_air_wet_bulb_temperature
Design Inlet Air Wet-Bulb Temperature
number
C
25.6 Enter the tower's design inlet air wet-bulb temperature
Range: ≥ 10
design_approach_temperature
Design Approach Temperature
number or Autosize
deltaC
Autosize Enter the approach temperature corresponding to the design inlet air wet-bulb temperature and design range temperature. Design approach temp = outlet water temperature minus inlet air wet-bulb temperature at design conditions. Autosized to 3.9 deltaC.
design_range_temperature
Design Range Temperature
number or Autosize
deltaC
Autosize Enter the range temperature corresponding to the design inlet air wet-bulb temperature and design approach temperature. Design range = inlet water temperature minus outlet water temperature at design conditions. Autosized to 5.5 deltaC.
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when water is not flowing through the tower.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature when the basin heater turns on
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
0.2 Rate of water evaporation from the cooling tower and lost to the outdoor air [%/K] Evaporation loss is calculated as percentage of the circulating condenser water rate Value entered here is percent-per-degree K of temperature drop in the condenser water Typical values are from 0.15 to 0.27 [%/K].
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Rate of drift loss as a percentage of circulating condenser water flow rate Typical values are between 0.002 and 0.2% The default value is 0.008%
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the cooling tower. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining a small amount of water in the tower basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
capacity_control
Capacity Control
choice FanCycling One of FanCycling, FluidBypass
number_of_cells
Number of Cells
integer 1 Range: ≥ 1
cell_control
Cell Control
choice MaximalCell One of MaximalCell, MinimalCell
cell_minimum_water_flow_rate_fraction
Cell Minimum Water Flow Rate Fraction
number 0.33 The allowable minimal fraction of the nominal flow rate per cell
Range: > 0, ≤ 1
cell_maximum_water_flow_rate_fraction
Cell Maximum Water Flow Rate Fraction
number 2.5 The allowable maximal fraction of the nominal flow rate per cell
Range: ≥ 1
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, FaultModel:Fouling:CoolingTower, FaultModel:TemperatureSensorOffset:CondenserSupplyWater, HVACTemplate:Plant:Tower:ObjectReference, PlantEquipmentList

CoolingTower:TwoSpeed

from idfpy.models import CoolingTowerTwoSpeed

This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 Toolkit. The open wet cooling tower is modeled as a counter flow heat exchanger with a two-speed fan drawing air through the tower (induced-draft configuration). For a multi-cell tower, the capacity and air/water flow rate inputs are for the entire tower.

Field Type Default Details
name
Name required
string Tower Name
water_inlet_node_name
Water Inlet Node Name required
string Name of tower Water Inlet Node
water_outlet_node_name
Water Outlet Node Name required
string Name of tower Water Outlet Node
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Leave field blank if Tower Performance Input Method is NominalCapacity
high_fan_speed_air_flow_rate
High Fan Speed Air Flow Rate required
number or Autosize
m3/s
high_fan_speed_fan_power
High Fan Speed Fan Power required
number or Autosize
W
This is the fan motor electric input power at high speed
high_fan_speed_u_factor_times_area_value
High Fan Speed U-Factor Times Area Value
number or Autosize
W/K
Leave field blank if Tower Performance Input Method is NominalCapacity
low_fan_speed_air_flow_rate
Low Fan Speed Air Flow Rate required
number or Autocalculate
m3/s
Low speed air flow rate must be less than high speed air flow rate Low speed air flow rate must be greater than free convection air flow rate
low_fan_speed_air_flow_rate_sizing_factor
Low Fan Speed Air Flow Rate Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate.
Range: > 0, < 1
low_fan_speed_fan_power
Low Fan Speed Fan Power required
number or Autocalculate
W
This is the fan motor electric input power at low speed
low_fan_speed_fan_power_sizing_factor
Low Fan Speed Fan Power Sizing Factor
number 0.16 This field is only used if the previous field is set to autocalculate.
Range: > 0, < 1
low_fan_speed_u_factor_times_area_value
Low Fan Speed U-Factor Times Area Value
number or Autocalculate
W/K
Leave field blank if tower Performance Input Method is NominalCapacity Low speed tower UA must be less than high speed tower UA Low speed tower UA must be greater than free convection tower UA
low_fan_speed_u_factor_times_area_sizing_factor
Low Fan Speed U-Factor Times Area Sizing Factor
number 0.6 This field is only used if the previous field is set to autocalculate and the Performance Input Method is UFactorTimesAreaAndDesignWaterFlowRate
Range: > 0, < 1
free_convection_regime_air_flow_rate
Free Convection Regime Air Flow Rate
number or Autocalculate
m3/s
0.0
free_convection_regime_air_flow_rate_sizing_factor
Free Convection Regime Air Flow Rate Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate.
Range: > 0, < 1
free_convection_regime_u_factor_times_area_value
Free Convection Regime U-Factor Times Area Value
number or Autocalculate
W/K
0.0 Leave field blank if Tower Performance Input Method is NominalCapacity
free_convection_u_factor_times_area_value_sizing_factor
Free Convection U-Factor Times Area Value Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate and the Performance Input Method is UFactorTimesAreaAndDesignWaterFlowRate
Range: > 0, < 1
performance_input_method
Performance Input Method
choice UFactorTimesAreaAndDesignWaterFlowRate User can define tower thermal performance by specifying the tower UA, the Design Air Flow Rate and the Design Water Flow Rate, or by specifying the tower nominal capacity
One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
heat_rejection_capacity_and_nominal_capacity_sizing_ratio
Heat Rejection Capacity and Nominal Capacity Sizing Ratio
number 1.25
high_speed_nominal_capacity
High Speed Nominal Capacity
number
W
Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at high speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt(3 gpm/ton). Nominal tower capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual tower heat rejection at these operating conditions.
Range: > 0
low_speed_nominal_capacity
Low Speed Nominal Capacity
number or Autocalculate
W
Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at low speed. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Nominal tower capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual tower heat rejection at these operating conditions.
low_speed_nominal_capacity_sizing_factor
Low Speed Nominal Capacity Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate
Range: > 0, < 1
free_convection_nominal_capacity
Free Convection Nominal Capacity
number or Autocalculate
W
Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt of tower high-speed nominal capacity (3 gpm/ton). Tower free convection capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual tower heat rejection at these operating conditions
free_convection_nominal_capacity_sizing_factor
Free Convection Nominal Capacity Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate
Range: > 0, < 1
design_inlet_air_dry_bulb_temperature
Design Inlet Air Dry-Bulb Temperature
number
C
35.0 Enter the tower's design inlet air dry-bulb temperature
Range: ≥ 20
design_inlet_air_wet_bulb_temperature
Design Inlet Air Wet-Bulb Temperature
number
C
25.6 Enter the tower's design inlet air wet-bulb temperature
Range: ≥ 10
design_approach_temperature
Design Approach Temperature
number or Autosize
deltaC
Autosize Enter the approach temperature corresponding to the design inlet air wet-bulb temperature and design range temperature. Design approach temp = outlet water temperature minus inlet air wet-bulb temperature at design conditions. Autosized to 3.9 deltaC.
design_range_temperature
Design Range Temperature
number or Autosize
deltaC
Autosize Enter the range temperature corresponding to the design inlet air wet-bulb temperature and design approach temperature. Design range = inlet water temperature minus outlet water temperature at design conditions. Autosized to 5.5 deltaC.
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when water is not flowing through the tower.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature when the basin heater turns on
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
0.2 Rate of water evaporated from the cooling tower and lost to the outdoor air [%/K] Evaporation loss is calculated as percentage of the circulating condenser water rate Value entered here is percent-per-degree K of temperature drop in the condenser water Typical values are from 0.15 to 0.27 [%/K].
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Rate of drift loss as a percentage of circulating condenser water flow rate Typical values are between 0.002 and 0.2% The default value is 0.008%
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the cooling tower. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining some amount of water in the tower basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
number_of_cells
Number of Cells
integer 1 Range: ≥ 1
cell_control
Cell Control
choice MaximalCell One of MaximalCell, MinimalCell
cell_minimum_water_flow_rate_fraction
Cell Minimum Water Flow Rate Fraction
number 0.33 The allowable minimal fraction of the nominal flow rate per cell
Range: > 0, ≤ 1
cell_maximum_water_flow_rate_fraction
Cell Maximum Water Flow Rate Fraction
number 2.5 The allowable maximal fraction of the nominal flow rate per cell
Range: ≥ 1
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, FaultModel:Fouling:CoolingTower, FaultModel:TemperatureSensorOffset:CondenserSupplyWater, HVACTemplate:Plant:Tower:ObjectReference, PlantEquipmentList

CoolingTower:VariableSpeed

from idfpy.models import CoolingTowerVariableSpeed

This open wet tower model is based on purely empirical algorithms derived from manufacturer's performance data or field measurements. The user can select from two existing algorithms (CoolTools or YorkCalc), or they can enter their own correlation for approach temperature by using a variable speed tower model coefficient object. For a multi-cell tower, the capacity and air/water flow rate inputs are for the entire tower.

Field Type Default Details
name
Name required
string Tower Name
water_inlet_node_name
Water Inlet Node Name required
string Name of tower water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of tower water outlet node
model_type
Model Type
choice YorkCalc Determines the coefficients and form of the equation for calculating approach temperature
One of CoolToolsCrossFlow, CoolToolsUserDefined, YorkCalc, YorkCalcUserDefined
model_coefficient_name
Model Coefficient Name
reference Name of the tower model coefficient object. Used only when tower Model Type is either CoolToolsUserDefined or YorkCalcUserDefined.
Names a CoolingTowerPerformance:CoolTools, CoolingTowerPerformance:YorkCalc
design_inlet_air_wet_bulb_temperature
Design Inlet Air Wet-Bulb Temperature
number
C
25.6 Enter the tower's design inlet air wet-bulb temperature
Range: ≥ 10
design_approach_temperature
Design Approach Temperature
number
deltaC
3.9 Enter the approach temperature corresponding to the design inlet air wet-bulb temperature and design range temperature. Design approach temp = outlet water temperature minus inlet air wet-bulb temperature at design conditions.
Range: > 0
design_range_temperature
Design Range Temperature
number
deltaC
5.6 Enter the range temperature corresponding to the design inlet air wet-bulb temperature and design approach temperature. Design range = inlet water temperature minus outlet water temperature at design conditions.
Range: > 0
design_water_flow_rate
Design Water Flow Rate required
number or Autosize
m3/s
Water flow rate through the tower at design conditions
design_air_flow_rate
Design Air Flow Rate required
number or Autosize
m3/s
Design (maximum) air flow rate through the tower
design_fan_power
Design Fan Power required
number or Autosize
W
Enter the fan motor electric input power at design (max) air flow through the tower Standard conversion for horsepower is 1 HP = 745.7 W
fan_power_ratio_function_of_air_flow_rate_ratio_curve_name
Fan Power Ratio Function of Air Flow Rate Ratio Curve Name
reference FPR = a + b*AFR + c*AFR**2 + d*AFR**3 FPR = fraction of the design fan power AFR = fraction of the design air flow rate If left blank, then fan power is assumed to be proportional to (air flow rate ratio)^3
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_air_flow_rate_ratio
Minimum Air Flow Rate Ratio
number 0.2 Enter the minimum air flow rate ratio. This is typically determined by the variable speed drive that controls the fan motor speed. Valid entries are from 0.2 to 0.5.
Range: ≥ 0.2, ≤ 0.5
fraction_of_tower_capacity_in_free_convection_regime
Fraction of Tower Capacity in Free Convection Regime
number 0.125 Enter the fraction of tower capacity in the free convection regime. This is the fraction of the tower capacity, at the current inlet air wet-bulb temperature, that is available when the tower fan is off. Manufacturers typically estimate the free convection capacity at approximately 10-15%. Values are entered as a fraction and can range from 0 to 0.2.
Range: ≥ 0, ≤ 0.2
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when water is not flowing through the tower.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature when the basin heater turns on
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
0.2 Rate of water evaporated from the cooling tower and lost to the outdoor air [%/K] Evaporation loss is calculated as percentage of the circulating condenser water rate Value entered here is percent-per-degree K of temperature drop in the condenser water Typical values are from 0.15 to 0.27 [percent/K].
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Rate of drift loss as a percentage of circulating condenser water flow rate Typical values are between 0.002 and 0.2% The default value is 0.008%
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the cooling tower. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining a small amount of water in the tower basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
number_of_cells
Number of Cells
integer 1 Range: ≥ 1
cell_control
Cell Control
choice MaximalCell One of MaximalCell, MinimalCell
cell_minimum_water_flow_rate_fraction
Cell Minimum Water Flow Rate Fraction
number 0.33 The allowable minimal fraction of the nominal flow rate per cell
Range: > 0, ≤ 1
cell_maximum_water_flow_rate_fraction
Cell Maximum Water Flow Rate Fraction
number 2.5 The allowable maximal fraction of the nominal flow rate per cell
Range: ≥ 1
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 6 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, FaultModel:TemperatureSensorOffset:CondenserSupplyWater, HVACTemplate:Plant:Tower:ObjectReference, PlantEquipmentList

CoolingTower:VariableSpeed:Merkel

from idfpy.models import CoolingTowerVariableSpeedMerkel

This tower model is based on Merkel's theory, which is also the basis for the tower model in ASHRAE's HVAC1 Toolkit. The open wet cooling tower is modeled as a counter flow heat exchanger with a variable-speed fan drawing air through the tower (induced-draft configuration). For a multi-cell tower, the capacity and air/water flow rate inputs are for the entire tower.

Field Type Default Details
name
Name required
string Tower Name
water_inlet_node_name
Water Inlet Node Name required
string Name of tower water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of tower water outlet node
performance_input_method
Performance Input Method
choice NominalCapacity User can define tower thermal performance by specifying the tower UA, the Design Air Flow Rate and the Design Water Flow Rate, or by specifying the tower nominal capacity
One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
heat_rejection_capacity_and_nominal_capacity_sizing_ratio
Heat Rejection Capacity and Nominal Capacity Sizing Ratio
number 1.25
nominal_capacity
Nominal Capacity
number or Autosize
W
Nominal tower capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature, with the tower fan operating at Design Air Flow Rate (full speed). Design water flow rate is as set in Design Water Flow Rate per Unit of Nominal Capacity. Nominal tower capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual tower heat rejection at these operating conditions.
free_convection_nominal_capacity
Free Convection Nominal Capacity
number or Autocalculate
W
required field when performance method is NominalCapacity Tower capacity in free convection regime with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate is as set in Design Water Flow Rate per Unit of Nominal Capacity. Tower free convection capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual tower heat rejection at these operating conditions
free_convection_nominal_capacity_sizing_factor
Free Convection Nominal Capacity Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate
Range: > 0, < 1
design_water_flow_rate
Design Water Flow Rate required
number or Autosize
m3/s
design_water_flow_rate_per_unit_of_nominal_capacity
Design Water Flow Rate per Unit of Nominal Capacity
number
m3/s-W
5.382e-08 This field is only used if the previous is set to autocalculate and performance input method is NominalCapacity
design_air_flow_rate
Design Air Flow Rate required
number or Autocalculate
m3/s
This is the air flow rate at full fan speed
design_air_flow_rate_per_unit_of_nominal_capacity
Design Air Flow Rate Per Unit of Nominal Capacity
number
m3/s-W
2.76316e-05 This field is only used if the previous is set to autocalculate When field is left blank the default scaling factor is adjusted for elevation to increase volume flow at altitude When field has a value the scaling factor is used without adjusting for elevation
minimum_air_flow_rate_ratio
Minimum Air Flow Rate Ratio
number 0.2 Enter the minimum air flow rate ratio. This is typically determined by the variable speed drive that controls the fan motor speed. Valid entries are from 0.1 to 0.5.
Range: ≥ 0.1, ≤ 0.5
design_fan_power
Design Fan Power required
number or Autocalculate
W
This is the fan motor electric input power at high speed
design_fan_power_per_unit_of_nominal_capacity
Design Fan Power Per Unit of Nominal Capacity
number
dimensionless
0.0105 This field is only used if the previous is set to autocalculate [W/W] Watts of fan power per Watt of tower nominal capacity
fan_power_modifier_function_of_air_flow_rate_ratio_curve_name
Fan Power Modifier Function of Air Flow Rate Ratio Curve Name required
reference Any curve or table with one independent variable can be used cubic curve = a + b*AFR + c*AFR**2 + d*AFR**3 quartic curve = a + b*AFR + c*AFR**2 + d*AFR**3 + e*AFR**4 x = AFR = Ratio of current operating air flow rate to Design Air Flow Rate
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
free_convection_regime_air_flow_rate
Free Convection Regime Air Flow Rate
number or Autocalculate
m3/s
0.0
free_convection_regime_air_flow_rate_sizing_factor
Free Convection Regime Air Flow Rate Sizing Factor
number 0.1 This field is only used if the previous field is set to autocalculate.
Range: > 0, < 1
design_air_flow_rate_u_factor_times_area_value
Design Air Flow Rate U-Factor Times Area Value
number or Autosize
W/K
required field when performance method is UFactorTimesAreaAndDesignWaterFlowRate when performance method is NominalCapacity the program will solve for this UA
free_convection_regime_u_factor_times_area_value
Free Convection Regime U-Factor Times Area Value
number or Autocalculate
W/K
0.0 required field when performance input method is UFactorTimesAreaAndDesignWaterFlowRate Leave field blank if performance input method is NominalCapacity
free_convection_u_factor_times_area_value_sizing_factor
Free Convection U-Factor Times Area Value Sizing Factor
number 0.1 required field when performance input method is UFactorTimesAreaAndDesignWaterFlowRate This field is only used if the previous field is set to autocalculate and the performance input method is UFactorTimesAreaAndDesignWaterFlowRate
Range: > 0, < 1
u_factor_times_area_modifier_function_of_air_flow_ratio_curve_name
U-Factor Times Area Modifier Function of Air Flow Ratio Curve Name required
reference This curve describes how tower's design UA changes with variable air flow rate Any curve or table with one independent variable can be used cubic curve = a + b*AFR + c*AFR**2 + d*AFR**3 quartic curve = a + b*AFR + c*AFR**2 + d*AFR**3 + e*AFR**4 x = AFR = Ratio of current operating air flow rate to Design Air Flow Rate
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
u_factor_times_area_modifier_function_of_wetbulb_temperature_difference_curve_name
U-Factor Times Area Modifier Function of Wetbulb Temperature Difference Curve Name required
reference curve describes how tower UA changes with outdoor air wet-bulb temperature difference from design wet-bulb Any curve or table with one independent variable can be used cubic curve = a + b*DeltaWB + c*DeltaWB**2 + d*DeltaWB**3 quartic curve = a + b*DeltaWB + c*DeltaWB**2 + d*DeltaWB**3 + e*DeltaWB**4 x = DeltaWB = (design wet-bulb temperature in C - current wet-bulb temperature in C) where design wet-bulb temperature of entering air is 25.56C (78F)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
u_factor_times_area_modifier_function_of_water_flow_ratio_curve_name
U-Factor Times Area Modifier Function of Water Flow Ratio Curve Name required
reference curve describes how tower UA changes with the flow rate of condenser water through the tower Any curve or table with one independent variable can be used cubic curve = a + b*WFR + c*WFR**2 + d*WFR**3 quartic curve = a + b*WFR + c*WFR**2 + d*WFR**3 + e*WFR**4 x = WFR = Ratio of current operating water flow rate to Design Water Flow Rate
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
design_inlet_air_dry_bulb_temperature
Design Inlet Air Dry-Bulb Temperature
number
C
35.0 Enter the tower's design inlet air dry-bulb temperature
Range: ≥ 20
design_inlet_air_wet_bulb_temperature
Design Inlet Air Wet-Bulb Temperature
number
C
25.6 Enter the tower's design inlet air wet-bulb temperature
Range: ≥ 10
design_approach_temperature
Design Approach Temperature
number or Autosize
deltaC
Autosize Enter the approach temperature corresponding to the design inlet air wet-bulb temperature and design range temperature. Design approach temp = outlet water temperature minus inlet air wet-bulb temperature at design conditions. Autosized to 3.9 deltaC.
design_range_temperature
Design Range Temperature
number or Autosize
deltaC
Autosize Enter the range temperature corresponding to the design inlet air wet-bulb temperature and design approach temperature. Design range = inlet water temperature minus outlet water temperature at design conditions. Autosized to 5.5 deltaC.
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when water is not flowing through the tower.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature when the basin heater turns on
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
0.2 Rate of water evaporated from the cooling tower and lost to the outdoor air [%/K] Evaporation loss is calculated as percentage of the circulating condenser water rate Value entered here is percent-per-degree K of temperature drop in the condenser water Typical values are from 0.15 to 0.27 [%/K].
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Rate of drift loss as a percentage of circulating condenser water flow rate Typical values are between 0.002 and 0.2% The default value is 0.008%
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the cooling tower. Blowdown is water intentionally drained from the tower in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Typical values for tower operation are 3 to 5. The default value is 3.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining some amount of water in the tower basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
number_of_cells
Number of Cells
integer 1 Range: ≥ 1
cell_control
Cell Control
choice MaximalCell One of MaximalCell, MinimalCell
cell_minimum_water_flow_rate_fraction
Cell Minimum Water Flow Rate Fraction
number 0.33 The allowable minimal fraction of the nominal flow rate per cell
Range: > 0, ≤ 1
cell_maximum_water_flow_rate_fraction
Cell Maximum Water Flow Rate Fraction
number 2.5 The allowable maximal fraction of the nominal flow rate per cell
Range: ≥ 1
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, FaultModel:Fouling:CoolingTower, FaultModel:TemperatureSensorOffset:CondenserSupplyWater, HVACTemplate:Plant:Tower:ObjectReference, PlantEquipmentList

CoolingTowerPerformance:CoolTools

from idfpy.models import CoolingTowerPerformanceCoolTools

This object is used to define coefficients for the approach temperature correlation for a variable speed cooling tower when tower Model Type is specified as CoolToolsUserDefined in the object CoolingTower:VariableSpeed.

Field Type Default Details
name
Name required
string
minimum_inlet_air_wet_bulb_temperature
Minimum Inlet Air Wet-Bulb Temperature required
number
C
Minimum valid inlet air wet-bulb temperature for this approach temperature correlation.
maximum_inlet_air_wet_bulb_temperature
Maximum Inlet Air Wet-Bulb Temperature required
number
C
Maximum valid inlet air wet-bulb temperature for this approach temperature correlation.
minimum_range_temperature
Minimum Range Temperature required
number
deltaC
Minimum valid range temperature for this approach temperature correlation.
maximum_range_temperature
Maximum Range Temperature required
number
deltaC
Maximum valid range temperature for this approach temperature correlation.
minimum_approach_temperature
Minimum Approach Temperature required
number
deltaC
Minimum valid approach temperature for this correlation.
maximum_approach_temperature
Maximum Approach Temperature required
number
deltaC
Maximum valid approach temperature for this correlation.
minimum_water_flow_rate_ratio
Minimum Water Flow Rate Ratio required
number Minimum valid water flow rate ratio for this approach temperature correlation.
maximum_water_flow_rate_ratio
Maximum Water Flow Rate Ratio required
number Maximum valid water flow rate ratio for this approach temperature correlation.
coefficient_1
Coefficient 1 required
number
coefficient_2
Coefficient 2 required
number
coefficient_3
Coefficient 3 required
number
coefficient_4
Coefficient 4 required
number
coefficient_5
Coefficient 5 required
number
coefficient_6
Coefficient 6 required
number
coefficient_7
Coefficient 7 required
number
coefficient_8
Coefficient 8 required
number
coefficient_9
Coefficient 9 required
number
coefficient_10
Coefficient 10 required
number
coefficient_11
Coefficient 11 required
number
coefficient_12
Coefficient 12 required
number
coefficient_13
Coefficient 13 required
number
coefficient_14
Coefficient 14 required
number
coefficient_15
Coefficient 15 required
number
coefficient_16
Coefficient 16 required
number
coefficient_17
Coefficient 17 required
number
coefficient_18
Coefficient 18 required
number
coefficient_19
Coefficient 19 required
number
coefficient_20
Coefficient 20 required
number
coefficient_21
Coefficient 21 required
number
coefficient_22
Coefficient 22 required
number
coefficient_23
Coefficient 23 required
number
coefficient_24
Coefficient 24 required
number
coefficient_25
Coefficient 25 required
number
coefficient_26
Coefficient 26 required
number
coefficient_27
Coefficient 27 required
number
coefficient_28
Coefficient 28 required
number
coefficient_29
Coefficient 29 required
number
coefficient_30
Coefficient 30 required
number
coefficient_31
Coefficient 31 required
number
coefficient_32
Coefficient 32 required
number
coefficient_33
Coefficient 33 required
number
coefficient_34
Coefficient 34 required
number
coefficient_35
Coefficient 35 required
number
Referenced by 1 object types

CoolingTower:VariableSpeed

CoolingTowerPerformance:YorkCalc

from idfpy.models import CoolingTowerPerformanceYorkCalc

This object is used to define coefficients for the approach temperature correlation for a variable speed cooling tower when tower Model Type is specified as YorkCalcUserDefined in the object CoolingTower:VariableSpeed.

Field Type Default Details
name
Name required
string
minimum_inlet_air_wet_bulb_temperature
Minimum Inlet Air Wet-Bulb Temperature required
number
C
Minimum valid inlet air wet-bulb temperature for this approach temperature correlation.
maximum_inlet_air_wet_bulb_temperature
Maximum Inlet Air Wet-Bulb Temperature required
number
C
Maximum valid inlet air wet-bulb temperature for this approach temperature correlation.
minimum_range_temperature
Minimum Range Temperature required
number
deltaC
Minimum valid range temperature for this approach temperature correlation.
maximum_range_temperature
Maximum Range Temperature required
number
deltaC
Maximum valid range temperature for this approach temperature correlation.
minimum_approach_temperature
Minimum Approach Temperature required
number
deltaC
Minimum valid approach temperature for this correlation.
maximum_approach_temperature
Maximum Approach Temperature required
number
deltaC
Maximum valid approach temperature for this correlation.
minimum_water_flow_rate_ratio
Minimum Water Flow Rate Ratio required
number Minimum valid water flow rate ratio for this approach temperature correlation.
maximum_water_flow_rate_ratio
Maximum Water Flow Rate Ratio required
number Maximum valid water flow rate ratio for this approach temperature correlation.
maximum_liquid_to_gas_ratio
Maximum Liquid to Gas Ratio required
number Maximum liquid (water) to gas (air) ratio for this approach temperature correlation.
coefficient_1
Coefficient 1 required
number
coefficient_2
Coefficient 2 required
number
coefficient_3
Coefficient 3 required
number
coefficient_4
Coefficient 4 required
number
coefficient_5
Coefficient 5 required
number
coefficient_6
Coefficient 6 required
number
coefficient_7
Coefficient 7 required
number
coefficient_8
Coefficient 8 required
number
coefficient_9
Coefficient 9 required
number
coefficient_10
Coefficient 10 required
number
coefficient_11
Coefficient 11 required
number
coefficient_12
Coefficient 12 required
number
coefficient_13
Coefficient 13 required
number
coefficient_14
Coefficient 14 required
number
coefficient_15
Coefficient 15 required
number
coefficient_16
Coefficient 16 required
number
coefficient_17
Coefficient 17 required
number
coefficient_18
Coefficient 18 required
number
coefficient_19
Coefficient 19 required
number
coefficient_20
Coefficient 20 required
number
coefficient_21
Coefficient 21 required
number
coefficient_22
Coefficient 22 required
number
coefficient_23
Coefficient 23 required
number
coefficient_24
Coefficient 24 required
number
coefficient_25
Coefficient 25 required
number
coefficient_26
Coefficient 26 required
number
coefficient_27
Coefficient 27 required
number
Referenced by 1 object types

CoolingTower:VariableSpeed

EvaporativeFluidCooler:SingleSpeed

from idfpy.models import EvaporativeFluidCoolerSingleSpeed

This model is based on Merkel's theory, which is also the basis for the cooling tower model in EnergyPlus. The Evaporative fluid cooler is modeled as a counter flow heat exchanger.

Field Type Default Details
name
Name required
string Fluid Cooler Name
water_inlet_node_name
Water Inlet Node Name required
string Name of Fluid Cooler water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of Fluid Cooler water outlet node
design_air_flow_rate
Design Air Flow Rate required
number or Autosize
m3/s
design_air_flow_rate_fan_power
Design Air Flow Rate Fan Power required
number or Autosize
W
This is the fan motor electric input power
design_spray_water_flow_rate
Design Spray Water Flow Rate required
number
m3/s
Range: > 0
performance_input_method
Performance Input Method required
choice User can define fluid cooler thermal performance by specifying the fluid cooler UA and the Design Water Flow Rate, or by specifying the fluid cooler Standard Design Capacity or by specifying Design Capacity for Non standard conditions.
One of StandardDesignCapacity, UFactorTimesAreaAndDesignWaterFlowRate, UserSpecifiedDesignCapacity
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
heat_rejection_capacity_and_nominal_capacity_sizing_ratio
Heat Rejection Capacity and Nominal Capacity Sizing Ratio
number 1.25
standard_design_capacity
Standard Design Capacity
number
W
Standard design capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt (3 gpm/ton). Standard design capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual fluid cooler heat rejection at these operating conditions. Only used for Performance Input Method = StandardDesignCapacity; for other input methods, this field is ignored. The standard conditions mentioned above for Standard design capacity are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (as specified in CondenserLoop object).
Range: > 0
design_air_flow_rate_u_factor_times_area_value
Design Air Flow Rate U-factor Times Area Value
number or Autosize
W/K
Only used for Performance Input Method = UFactorTimesAreaAndDesignWaterFlowRate; for other Performance Input Methods, this field is ignored.
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Input value is ignored if fluid cooler Performance Input Method= StandardDesignCapacity.
user_specified_design_capacity
User Specified Design Capacity
number
W
Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored.
Range: > 0
design_entering_water_temperature
Design Entering Water Temperature
number or Autosize
C
Autosize Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Water Temperature must be greater than Design Entering Air Temperature.
design_entering_air_temperature
Design Entering Air Temperature
number
C
35.0 Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Air Temperature must be greater than Design Entering Air Wet-bulb Temperature.
Range: > 0
design_entering_air_wet_bulb_temperature
Design Entering Air Wet-bulb Temperature
number
C
25.6 Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Air Wet-bulb Temperature must be less than Design Entering Air Temperature.
Range: > 0
capacity_control
Capacity Control
choice FanCycling One of FanCycling, FluidBypass
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
Rate of water evaporation from the Fluid Cooler and lost to the outdoor air [%/K] Empirical correlation is used to calculate default loss factor if it not explicitly provided.
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Rate of drift loss as a percentage of circulating spray water flow rate Default value for this field is under investigation. For now Cooling tower's drift loss percent default value is taken here.
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the Evaporative Fluid Cooler. Blowdown is water intentionally drained from the basin in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Default value for this field is under investigation. For now Cooling tower's Blowdown Concentration Ratio percent default value is taken here.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining a small amount of water in the Fluid Cooler basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

EvaporativeFluidCooler:TwoSpeed

from idfpy.models import EvaporativeFluidCoolerTwoSpeed

This model is based on Merkel's theory, which is also the basis for the cooling tower model in EnergyPlus. The Evaporative fluid cooler is modeled as a counter flow heat exchanger.

Field Type Default Details
name
Name required
string fluid cooler name
water_inlet_node_name
Water Inlet Node Name required
string Name of fluid cooler water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of fluid cooler water outlet node
high_fan_speed_air_flow_rate
High Fan Speed Air Flow Rate required
number or Autosize
m3/s
high_fan_speed_fan_power
High Fan Speed Fan Power required
number or Autosize
W
This is the fan motor electric input power at high speed
low_fan_speed_air_flow_rate
Low Fan Speed Air Flow Rate required
number or Autocalculate
m3/s
Low speed air flow rate must be less than high speed air flow rate
low_fan_speed_air_flow_rate_sizing_factor
Low Fan Speed Air Flow Rate Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate
low_fan_speed_fan_power
Low Fan Speed Fan Power required
number or Autocalculate
W
This is the fan motor electric input power at low speed
low_fan_speed_fan_power_sizing_factor
Low Fan Speed Fan Power Sizing Factor
number 0.16 This field is only used if the previous field is set to autocalculate.
design_spray_water_flow_rate
Design Spray Water Flow Rate required
number
m3/s
Range: > 0
performance_input_method
Performance Input Method required
choice User can define fluid cooler thermal performance by specifying the fluid cooler UA and the Design Water Flow Rate, or by specifying the fluid cooler Standard Design Capacity or by specifying Design Capacity for Non standard conditions.
One of StandardDesignCapacity, UFactorTimesAreaAndDesignWaterFlowRate, UserSpecifiedDesignCapacity
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
heat_rejection_capacity_and_nominal_capacity_sizing_ratio
Heat Rejection Capacity and Nominal Capacity Sizing Ratio
number 1.25
high_speed_standard_design_capacity
High Speed Standard Design Capacity
number
W
Standard design capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt (3 gpm/ton). Standard design capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual fluid cooler heat rejection at these operating conditions. Only used for Performance Input Method = StandardDesignCapacity; for other input methods, this field is ignored. The standard conditions mentioned above for Standard design capacity are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (as specified in CondenserLoop object).
Range: > 0
low_speed_standard_design_capacity
Low Speed Standard Design Capacity
number or Autocalculate
W
Standard design capacity with entering water at 35C (95F), leaving water at 29.44C (85F), entering air at 25.56C (78F) wet-bulb temperature and 35C (95F) dry-bulb temperature. Design water flow rate assumed to be 5.382E-8 m3/s per watt (3 gpm/ton). Standard design capacity times the Heat Rejection Capacity and Nominal Capacity Sizing Ratio (e.g. 1.25) gives the actual fluid cooler heat rejection at these operating conditions. Only used for Performance Input Method = StandardDesignCapacity; for other input methods, this field is ignored. The standard conditions mentioned above for Standard design capacity are already specified in the EnergyPlus. So the input fields such as design entering water temp., design entering air wet-bulb and dry-bulb temp. and design water flow rate, if provided in the input, will be ignored for the StandardDesignCapacity performance input method. Also, the standard conditions are for water as a fluid type so this performance input method can only be used with water as a fluid type (as specified in CondenserLoop object).
low_speed_standard_capacity_sizing_factor
Low Speed Standard Capacity Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate
high_fan_speed_u_factor_times_area_value
High Fan Speed U-factor Times Area Value
number or Autosize
W/K
Only used for Performance Input Method = UFactorTimesAreaAndDesignWaterFlowRate; for other Performance Input Methods, this field is ignored.
low_fan_speed_u_factor_times_area_value
Low Fan Speed U-factor Times Area Value
number or Autocalculate
W/K
Only used for Performance Input Method = UFactorTimesAreaAndDesignWaterFlowRate; for other input methods, this field is ignored. Low speed fluid cooler UA must be less than high speed fluid cooler UA
low_fan_speed_u_factor_times_area_sizing_factor
Low Fan Speed U-Factor Times Area Sizing Factor
number 0.6 This field is only used if the previous field is set to autocalculate and the Performance Input Method is UFactorTimesAreaAndDesignWaterFlowRate
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Input value is ignored if fluid cooler Performance Input Method= StandardDesignCapacity
high_speed_user_specified_design_capacity
High Speed User Specified Design Capacity
number
W
Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored.
Range: > 0
low_speed_user_specified_design_capacity
Low Speed User Specified Design Capacity
number or Autocalculate
W
Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored.
low_speed_user_specified_design_capacity_sizing_factor
Low Speed User Specified Design Capacity Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate
design_entering_water_temperature
Design Entering Water Temperature
number or Autosize
C
Autosize Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Water Temperature must be greater than Design Entering Air Temperature.
design_entering_air_temperature
Design Entering Air Temperature
number
C
35.0 Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Air Temperature must be greater than Design Entering Air Wet-bulb Temperature.
Range: > 0
design_entering_air_wet_bulb_temperature
Design Entering Air Wet-bulb Temperature
number
C
25.6 Only used for Performance Input Method = UserSpecifiedDesignCapacity; for other Performance Input Methods, this field is ignored. Design Entering Air Wet-bulb Temperature must be less than Design Entering Air Temperature.
Range: > 0
high_speed_sizing_factor
High Speed Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
evaporation_loss_mode
Evaporation Loss Mode
choice SaturatedExit One of LossFactor, SaturatedExit
evaporation_loss_factor
Evaporation Loss Factor
number
percent/K
Rate of water evaporation from the Fluid Cooler and lost to the outdoor air [%/K] Empirical correlation is used to calculate default loss factor if it not explicitly provided.
drift_loss_percent
Drift Loss Percent
number
percent
0.008 Default value is under investigation. For now cooling tower's default value is taken.
blowdown_calculation_mode
Blowdown Calculation Mode
choice ConcentrationRatio One of ConcentrationRatio, ScheduledRate
blowdown_concentration_ratio
Blowdown Concentration Ratio
number 3.0 Characterizes the rate of blowdown in the Evaporative Fluid Cooler. Blowdown is water intentionally drained from the Evaporative Fluid Cooler in order to offset the build up of solids in the water that would otherwise occur because of evaporation. Ratio of solids in the blowdown water to solids in the make up water. Default value is under investigation. For now cooling tower's default value is taken.
Range: ≥ 2
blowdown_makeup_water_usage_schedule_name
Blowdown Makeup Water Usage Schedule Name
reference Makeup water usage due to blowdown results from occasionally draining some amount of water in the Evaporative Fluid Cooler basin to purge scale or other contaminants to reduce their concentration in order to maintain an acceptable level of water quality. Schedule values should reflect water usage in m3/s.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference Names a WaterUse:Storage
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

FluidCooler:SingleSpeed

from idfpy.models import FluidCoolerSingleSpeed

The fluid cooler is modeled as a cross flow heat exchanger (both streams unmixed) with single-speed fans (induced draft configuration).

Field Type Default Details
name
Name required
string fluid cooler name
water_inlet_node_name
Water Inlet Node Name required
string Name of fluid cooler water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of fluid cooler water outlet node
performance_input_method
Performance Input Method
choice NominalCapacity User can define fluid cooler thermal performance by specifying the fluid cooler UA and the Design Water Flow Rate, or by specifying the fluid cooler nominal capacity
One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
design_air_flow_rate_u_factor_times_area_value
Design Air Flow Rate U-factor Times Area Value
number or Autosize
W/K
Leave field blank if fluid cooler Performance Input Method is NominalCapacity
nominal_capacity
Nominal Capacity
number
W
Nominal fluid cooler capacity
Range: > 0
design_entering_water_temperature
Design Entering Water Temperature required
number
C
Design Entering Water Temperature must be specified for both the performance input methods and its value must be greater than Design Entering Air Temperature.
Range: > 0
design_entering_air_temperature
Design Entering Air Temperature required
number
C
Design Entering Air Temperature must be specified for both the performance input methods and its value must be greater than Design Entering Air Wet-bulb Temperature.
Range: > 0
design_entering_air_wetbulb_temperature
Design Entering Air Wetbulb Temperature required
number
C
Design Entering Air Wet-bulb Temperature must be specified for both the performance input methods and its value must be less than Design Entering Air Temperature.
Range: > 0
design_water_flow_rate
Design Water Flow Rate required
number or Autosize
m3/s
design_air_flow_rate
Design Air Flow Rate required
number or Autosize
m3/s
design_air_flow_rate_fan_power
Design Air Flow Rate Fan Power required
number or Autosize
W
This is the fan motor electric input power
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string Enter the name of an outdoor air node
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

FluidCooler:TwoSpeed

from idfpy.models import FluidCoolerTwoSpeed

The fluid cooler is modeled as a cross flow heat exchanger (both streams unmixed) with two-speed fans (induced draft configuration).

Field Type Default Details
name
Name required
string fluid cooler name
water_inlet_node_name
Water Inlet Node Name required
string Name of fluid cooler water inlet node
water_outlet_node_name
Water Outlet Node Name required
string Name of fluid cooler water outlet node
performance_input_method
Performance Input Method
choice NominalCapacity User can define fluid cooler thermal performance by specifying the fluid cooler UA and the Design Water Flow Rate, or by specifying the fluid cooler nominal capacity
One of NominalCapacity, UFactorTimesAreaAndDesignWaterFlowRate
high_fan_speed_u_factor_times_area_value
High Fan Speed U-factor Times Area Value
number or Autosize
W/K
Leave field blank if fluid cooler Performance Input Method is NominalCapacity
low_fan_speed_u_factor_times_area_value
Low Fan Speed U-factor Times Area Value
number or Autocalculate
W/K
Leave field blank if fluid cooler Performance Input Method is NominalCapacity Low speed fluid cooler UA must be less than high speed fluid cooler UA Low speed fluid cooler UA must be greater than free convection fluid cooler UA
low_fan_speed_u_factor_times_area_sizing_factor
Low Fan Speed U-Factor Times Area Sizing Factor
number 0.6 This field is only used if the previous field is set to autocalculate and the Performance Input Method is UFactorTimesAreaAndDesignWaterFlowRate
high_speed_nominal_capacity
High Speed Nominal Capacity
number
W
Nominal fluid cooler capacity at high fan speed
Range: > 0
low_speed_nominal_capacity
Low Speed Nominal Capacity
number or Autocalculate
W
Nominal fluid cooler capacity at low fan speed
low_speed_nominal_capacity_sizing_factor
Low Speed Nominal Capacity Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate and the Performance Input Method is NominalCapacity
design_entering_water_temperature
Design Entering Water Temperature required
number
C
Design Entering Water Temperature must be specified for both the performance input methods and its value must be greater than Design Entering Air Temperature.
Range: > 0
design_entering_air_temperature
Design Entering Air Temperature required
number
C
Design Entering Air Temperature must be specified for both the performance input methods and its value must be greater than Design Entering Air Wet-bulb Temperature.
Range: > 0
design_entering_air_wet_bulb_temperature
Design Entering Air Wet-bulb Temperature required
number
C
Design Entering Air Wet-bulb Temperature must be specified for both the performance input methods and its value must be less than Design Entering Air Temperature.
Range: > 0
design_water_flow_rate
Design Water Flow Rate required
number or Autosize
m3/s
high_fan_speed_air_flow_rate
High Fan Speed Air Flow Rate required
number or Autosize
m3/s
Air Flow Rate at High Fan Speed must be greater than Air Flow Rate at Low Fan Speed
high_fan_speed_fan_power
High Fan Speed Fan Power required
number or Autosize
W
This is the fan motor electric input power at high speed
low_fan_speed_air_flow_rate
Low Fan Speed Air Flow Rate required
number or Autocalculate
m3/s
Air Flow Rate at Low Fan Speed must be less than Air Flow Rate at High Fan Speed
low_fan_speed_air_flow_rate_sizing_factor
Low Fan Speed Air Flow Rate Sizing Factor
number 0.5 This field is only used if the previous field is set to autocalculate.
low_fan_speed_fan_power
Low Fan Speed Fan Power required
number or Autocalculate
W
This is the fan motor electric input power at low speed
low_fan_speed_fan_power_sizing_factor
Low Fan Speed Fan Power Sizing Factor
number 0.16 This field is only used if the previous field is set to autocalculate.
outdoor_air_inlet_node_name
Outdoor Air Inlet Node Name
string
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:HorizontalTrench

from idfpy.models import GroundHeatExchangerHorizontalTrench

This models a horizontal heat exchanger placed in a series of trenches The model uses the PipingSystem:Underground underlying algorithms, but provides a more usable input interface.

Field Type Default Details
name
Name required
string
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
design_flow_rate
Design Flow Rate required
number
m3/s
Range: > 0
trench_length_in_pipe_axial_direction
Trench Length in Pipe Axial Direction
number
m
50.0 This is the total pipe axial length of the heat exchanger If all pipe trenches are parallel, this is the length of a single trench. If a single, long run of pipe is used with one trench, this is the full length of the pipe run.
Range: > 0
number_of_trenches
Number of Trenches
integer 1 This is the number of horizontal legs that will be used in the entire heat exchanger, one pipe per trench
Range: ≥ 1
horizontal_spacing_between_pipes
Horizontal Spacing Between Pipes
number
m
1.0 This represents the average horizontal spacing between any two trenches for heat exchangers that have multiple trenches
Range: > 0
pipe_inner_diameter
Pipe Inner Diameter
number
m
0.016 Range: > 0
pipe_outer_diameter
Pipe Outer Diameter
number
m
0.026 Range: > 0
burial_depth
Burial Depth
number
m
1.5 This is the burial depth of the pipes, or the trenches containing the pipes
Range: > 0
soil_thermal_conductivity
Soil Thermal Conductivity
number
W/m-K
1.08 Range: > 0
soil_density
Soil Density
number
kg/m3
962.0 Range: > 0
soil_specific_heat
Soil Specific Heat
number
J/kg-K
2576.0 Range: > 0
pipe_thermal_conductivity
Pipe Thermal Conductivity
number
W/m-K
0.3895 Range: > 0
pipe_density
Pipe Density
number
kg/m3
641.0 Range: > 0
pipe_specific_heat
Pipe Specific Heat
number
J/kg-K
2405.0 Range: > 0
soil_moisture_content_percent
Soil Moisture Content Percent
number
percent
30.0 Range: ≥ 0, ≤ 100
soil_moisture_content_percent_at_saturation
Soil Moisture Content Percent at Saturation
number
percent
50.0 Range: ≥ 0, ≤ 100
undisturbed_ground_temperature_model_type
Undisturbed Ground Temperature Model Type required
choice One of Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
undisturbed_ground_temperature_model_name
Undisturbed Ground Temperature Model Name required
reference Names a Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
evapotranspiration_ground_cover_parameter
Evapotranspiration Ground Cover Parameter
number 0.4 This specifies the ground cover effects during evapotranspiration calculations. The value roughly represents the following cases: = 0 : concrete or other solid, non-permeable ground surface material = 0.5 : short grass, much like a manicured lawn = 1 : standard reference state (12 cm grass) = 1.5 : wild growth
Range: ≥ 0, ≤ 1.5
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:Pond

from idfpy.models import GroundHeatExchangerPond

A model of a shallow pond with immersed pipe loops. Typically used in hybrid geothermal systems and included in the condenser loop. This component may also be used as a simple solar collector.

Field Type Default Details
name
Name required
string
fluid_inlet_node_name
Fluid Inlet Node Name required
string
fluid_outlet_node_name
Fluid Outlet Node Name required
string
pond_depth
Pond Depth required
number
m
Range: > 0
pond_area
Pond Area required
number
m2
Range: > 0
hydronic_tubing_inside_diameter
Hydronic Tubing Inside Diameter required
number
m
Range: > 0
hydronic_tubing_outside_diameter
Hydronic Tubing Outside Diameter required
number
m
Range: > 0
hydronic_tubing_thermal_conductivity
Hydronic Tubing Thermal Conductivity required
number
W/m-K
Range: > 0
ground_thermal_conductivity
Ground Thermal Conductivity required
number
W/m2-K
Range: > 0
number_of_tubing_circuits
Number of Tubing Circuits required
integer Range: ≥ 1
length_of_each_tubing_circuit
Length of Each Tubing Circuit required
number
m
Range: ≥ 0
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:ResponseFactors

from idfpy.models import GroundHeatExchangerResponseFactors extensible

Response factor definitions from third-party tool, commonly referred to a "g-functions"

Field Type Default Details
name
Name required
string
ghe_vertical_properties_object_name
GHE:Vertical:Properties Object Name required
reference Names a GroundHeatExchanger:Vertical:Properties
number_of_boreholes
Number of Boreholes required
integer
g_function_reference_ratio
G-Function Reference Ratio
number
dimensionless
0.0005 Range: > 0
g_functions list Each item: g_function_ln_t_ts_value, g_function_g_value
Referenced by 1 object types

GroundHeatExchanger:System

GroundHeatExchanger:Slinky

from idfpy.models import GroundHeatExchangerSlinky

This models a slinky horizontal heat exchanger placed in a series of trenches The model uses the model developed by: Xiong, Z., D.E. Fisher, and J.D. Spitler. 2015. Development and Validation of a Slinky Ground Heat Exchanger Model. Applied Energy 141: 57-69.

Field Type Default Details
name
Name required
string
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
design_flow_rate
Design Flow Rate
number
m3/s
0.002 Range: > 0
soil_thermal_conductivity
Soil Thermal Conductivity
number
W/m-K
1.08 Range: > 0
soil_density
Soil Density
number
kg/m3
962.0 Range: > 0
soil_specific_heat
Soil Specific Heat
number
J/kg-K
2576.0 Range: > 0
pipe_thermal_conductivity
Pipe Thermal Conductivity
number
W/m-K
0.4 Range: > 0
pipe_density
Pipe Density
number
kg/m3
641.0 Range: > 0
pipe_specific_heat
Pipe Specific Heat
number
J/kg-K
2405.0 Range: > 0
pipe_outer_diameter
Pipe Outer Diameter
number
m
0.02667 Range: > 0
pipe_thickness
Pipe Thickness
number
m
0.002413 Range: > 0
heat_exchanger_configuration
Heat Exchanger Configuration
choice This is the orientation of the heat exchanger
One of Horizontal, Vertical
coil_diameter
Coil Diameter
number
m
1.0 This is the diameter of the heat exchanger coil
Range: > 0
coil_pitch
Coil Pitch
number
m
0.2 This is the center-to-center distance between coils
Range: > 0
trench_depth
Trench Depth
number
m
1.8 This is the distance from the ground surface to the trench bottom
Range: > 0
trench_length
Trench Length
number
m
10.0 This is the total length of a single trench This assumes the heat exchanger runs the full length of the trench
Range: > 0
number_of_trenches
Number of Trenches
integer 1 This is the number of parallel trenches that has a heat exchanger, one per trench
Range: ≥ 1
horizontal_spacing_between_pipes
Horizontal Spacing Between Pipes
number
m
2.0 This represents the average horizontal spacing between any two trenches for heat exchangers that have multiple trenches
Range: > 0
undisturbed_ground_temperature_model_type
Undisturbed Ground Temperature Model Type required
choice One of Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
undisturbed_ground_temperature_model_name
Undisturbed Ground Temperature Model Name required
reference Names a Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
maximum_length_of_simulation
Maximum Length of Simulation
number
years
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:Surface

from idfpy.models import GroundHeatExchangerSurface

A hydronic surface/panel consisting of a multi-layer construction with embedded rows of tubes. Typically used in hybrid geothermal systems and included in the condenser loop. This component may also be used as a simple solar collector. The bottom surface may be defined as ground-coupled or exposed to wind (eg. bridge deck).

Field Type Default Details
name
Name required
string
construction_name
Construction Name required
reference Names a Construction, Construction:AirBoundary, Construction:CfactorUndergroundWall, Construction:FfactorGroundFloor, Construction:WindowDataFile, Construction:WindowEquivalentLayer
fluid_inlet_node_name
Fluid Inlet Node Name required
string
fluid_outlet_node_name
Fluid Outlet Node Name required
string
hydronic_tubing_inside_diameter
Hydronic Tubing Inside Diameter
number
m
Range: > 0
number_of_tubing_circuits
Number of Tubing Circuits
integer Range: ≥ 1
hydronic_tube_spacing
Hydronic Tube Spacing
number
m
Range: > 0
surface_length
Surface Length
number
m
Range: > 0
surface_width
Surface Width
number
m
Range: > 0
lower_surface_environment
Lower Surface Environment
choice Ground One of Exposed, Ground
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:System

from idfpy.models import GroundHeatExchangerSystem extensible

Models vertical ground heat exchangers systems using the response factor approach developed by Eskilson. Response factors are calculated using a finite line source model assuming uniform heat flux at the borehole wall if UHFcalc is specified, or uniform borehole wall temperature if UBHWTcalc is specified.

Field Type Default Details
name
Name required
string
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
design_flow_rate
Design Flow Rate required
number
m3/s
Range: > 0
undisturbed_ground_temperature_model_type
Undisturbed Ground Temperature Model Type required
choice One of Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
undisturbed_ground_temperature_model_name
Undisturbed Ground Temperature Model Name required
reference Names a Site:GroundTemperature:Undisturbed:FiniteDifference, Site:GroundTemperature:Undisturbed:KusudaAchenbach, Site:GroundTemperature:Undisturbed:Xing
ground_thermal_conductivity
Ground Thermal Conductivity required
number
W/m-K
Range: > 0
ground_thermal_heat_capacity
Ground Thermal Heat Capacity required
number
J/m3-K
Range: > 0
ghe_vertical_responsefactors_object_name
GHE:Vertical:ResponseFactors Object Name
reference Names a GroundHeatExchanger:ResponseFactors
g_function_calculation_method
g-Function Calculation Method
choice UHFcalc One of FullDesign, UBHWTcalc, UHFcalc
ghe_vertical_sizing_object_type
GHE:Vertical:Sizing Object Type
choice One of GroundHeatExchanger:Vertical:Sizing:Rectangle
ghe_vertical_sizing_object_name
GHE:Vertical:Sizing Object Name
reference Only needed when g-function calculation method is FullDesign
Names a GroundHeatExchanger:Vertical:Sizing:Rectangle
ghe_vertical_array_object_name
GHE:Vertical:Array Object Name
reference Names a GroundHeatExchanger:Vertical:Array
vertical_well_locations list Each item: ghe_vertical_single_object_name
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

GroundHeatExchanger:Vertical:Array

from idfpy.models import GroundHeatExchangerVerticalArray

Field Type Default Details
name
Name required
string
ghe_vertical_properties_object_name
GHE:Vertical:Properties Object Name required
reference Names a GroundHeatExchanger:Vertical:Properties
number_of_boreholes_in_x_direction
Number of Boreholes in X-Direction required
integer Range: ≥ 1
number_of_boreholes_in_y_direction
Number of Boreholes in Y-Direction required
integer Range: ≥ 1
borehole_spacing
Borehole Spacing required
number
m
Range: > 0
Referenced by 1 object types

GroundHeatExchanger:System

GroundHeatExchanger:Vertical:Properties

from idfpy.models import GroundHeatExchangerVerticalProperties

Properties for vertical ground heat exchanger systems

Field Type Default Details
name
Name required
string
depth_of_top_of_borehole
Depth of Top of Borehole required
number
m
Range: ≥ 0
borehole_length
Borehole Length required
number
m
Range: > 0
borehole_diameter
Borehole Diameter required
number
m
Range: > 0
grout_thermal_conductivity
Grout Thermal Conductivity required
number
W/m-K
Range: > 0
grout_thermal_heat_capacity
Grout Thermal Heat Capacity required
number
J/m3-K
Range: > 0
pipe_thermal_conductivity
Pipe Thermal Conductivity required
number
W/m-K
Range: > 0
pipe_thermal_heat_capacity
Pipe Thermal Heat Capacity required
number
J/m3-K
Range: > 0
pipe_outer_diameter
Pipe Outer Diameter required
number
m
Range: > 0
pipe_thickness
Pipe Thickness required
number
m
Range: > 0
u_tube_distance
U-Tube Distance required
number
m
Range: > 0
Referenced by 3 object types

GroundHeatExchanger:ResponseFactors, GroundHeatExchanger:Vertical:Array, GroundHeatExchanger:Vertical:Single

GroundHeatExchanger:Vertical:Single

from idfpy.models import GroundHeatExchangerVerticalSingle

Field Type Default Details
name
Name required
string
ghe_vertical_properties_object_name
GHE:Vertical:Properties Object Name required
reference Names a GroundHeatExchanger:Vertical:Properties
x_location
X-Location required
number
m
y_location
Y-Location required
number
m
Referenced by 1 object types

GroundHeatExchanger:System

GroundHeatExchanger:Vertical:Sizing:Rectangle

from idfpy.models import GroundHeatExchangerVerticalSizingRectangle

Specifies parameters to be used for Ground Heat Exchanger borehole field design and sizing.

Field Type Default Details
name
Name required
string
sizingperiod_weatherfiledays_name
SizingPeriod:WeatherFileDays Name required
reference Specifies the SizingPeriod:WeatherFileDays required to perform GHE sizing
Names a SizingPeriod:WeatherFileDays
design_flow_rate_per_borehole
Design Flow Rate Per Borehole
number
m3/s
0.0005 Design flow rate per borehole used to size borehole field
Range: > 0
available_borehole_field_length
Available Borehole Field Length required
number
m
Available length of the area available for designing the borehole field
Range: > 0
available_borehole_field_width
Available Borehole Field Width required
number
m
Available width of the area available for designing the borehole field
Range: > 0
maximum_number_of_boreholes
Maximum Number of Boreholes required
number User specified maximum number of boreholes
Range: > 0
minimum_borehole_spacing
Minimum Borehole Spacing
number
m
4.0 Minimum borehole-to-borehole spacing
Range: > 0
maximum_borehole_spacing
Maximum Borehole Spacing
number
m
6.0 Maximum borehole-to-borehole spacing
Range: > 0
minimum_borehole_vertical_length
Minimum Borehole Vertical Length
number
m
60.0 Minimum drilled depth of the vertical borehole
Range: > 0
maximum_borehole_vertical_length
Maximum Borehole Vertical Length
number
m
135.0 Maximum drilled depth of the vertical borehole
Range: > 0
minimum_exiting_fluid_temperature_for_sizing
Minimum Exiting Fluid Temperature for Sizing
number
C
5.0 Minimum ground heat exchanger exiting fluid temperature used when designing the borehole field
Range: > 0
maximum_exiting_fluid_temperature_for_sizing
Maximum Exiting Fluid Temperature for Sizing
number
C
35.0 Maximum ground heat exchanger exiting fluid temperature used when designing the borehole field
Range: > 0
Referenced by 1 object types

GroundHeatExchanger:System

HeatExchanger:FluidToFluid

from idfpy.models import HeatExchangerFluidToFluid

A fluid/fluid heat exchanger designed to couple the supply side of one loop to the demand side of another loop Loops can be either plant or condenser loops but no air side connections are allowed

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. default is that heat exchanger is on
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
loop_demand_side_inlet_node_name
Loop Demand Side Inlet Node Name required
string This connection is to the demand side of a loop and is the inlet to the heat exchanger
loop_demand_side_outlet_node_name
Loop Demand Side Outlet Node Name required
string This connection is to the demand side of a loop
loop_demand_side_design_flow_rate
Loop Demand Side Design Flow Rate required
number or Autosize
m3/s
loop_supply_side_inlet_node_name
Loop Supply Side Inlet Node Name required
string
loop_supply_side_outlet_node_name
Loop Supply Side Outlet Node Name required
string
loop_supply_side_design_flow_rate
Loop Supply Side Design Flow Rate required
number or Autosize
m3/s
heat_exchange_model_type
Heat Exchange Model Type
choice Ideal One of CounterFlow, CrossFlowBothMixed, CrossFlowBothUnMixed, CrossFlowSupplyMixedDemandUnMixed, CrossFlowSupplyUnMixedDemandMixed, Ideal, ParallelFlow
heat_exchanger_u_factor_times_area_value
Heat Exchanger U-Factor Times Area Value required
number or Autosize
W/K
control_type
Control Type
choice UncontrolledOn One of CoolingDifferentialOnOff, CoolingSetpointModulated, CoolingSetpointOnOff, CoolingSetpointOnOffWithComponentOverride, DualDeadbandSetpointModulated, DualDeadbandSetpointOnOff, HeatingSetpointModulated, HeatingSetpointOnOff, OperationSchemeModulated, OperationSchemeOnOff, UncontrolledOn
heat_exchanger_setpoint_node_name
Heat Exchanger Setpoint Node Name
string Setpoint node is needed with any Control Type that is "*Setpoint*"
minimum_temperature_difference_to_activate_heat_exchanger
Minimum Temperature Difference to Activate Heat Exchanger
number
deltaC
0.01 Tolerance between control temperatures used to determine if heat exchanger should run.
Range: ≥ 0, ≤ 50
heat_transfer_metering_end_use_type
Heat Transfer Metering End Use Type
choice LoopToLoop This field controls end use reporting for heat transfer meters
One of FreeCooling, HeatRecoveryForCooling, HeatRecoveryForHeating, HeatRejection, LoopToLoop
component_override_loop_supply_side_inlet_node_name
Component Override Loop Supply Side Inlet Node Name
string This field is only used if Control Type is set to CoolingSetpointOnOffWithComponentOverride
component_override_loop_demand_side_inlet_node_name
Component Override Loop Demand Side Inlet Node Name
string This field is only used if Control Type is set to CoolingSetpointOnOffWithComponentOverride
component_override_cooling_control_temperature_mode
Component Override Cooling Control Temperature Mode
choice Loop This field is only used if Control Type is set to CoolingSetpointOnOffWithComponentOverride
One of DryBulbTemperature, Loop, WetBulbTemperature
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized flow rates for this device
Range: > 0
operation_minimum_temperature_limit
Operation Minimum Temperature Limit
number
C
Lower limit on inlet temperatures, heat exchanger will not operate if either inlet is below this limit
operation_maximum_temperature_limit
Operation Maximum Temperature Limit
number
C
Upper limit on inlet temperatures, heat exchanger will not operate if either inlet is above this limit
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList