Plant-Condenser Control

17 object types from idfpy.models.plant_control · EnergyPlus 26.2

Object Summary
CondenserEquipmentList List condenser equipment in order of operating priority, 1st in list will be used 1st, etc Use only condenser …
CondenserEquipmentOperationSchemes Operation schemes are listed in "priority" order.
PlantEquipmentList List plant equipment in order of operating priority, 1st in list will be used 1st, etc Use only plant …
PlantEquipmentOperation:ChillerHeaterChangeover Plant equipment operation object to control switchover between chiller and heater operation of chiller heater …
PlantEquipmentOperation:ComponentSetpoint Plant equipment operation scheme for component setpoint operation.
PlantEquipmentOperation:CoolingLoad Plant equipment operation scheme for cooling load range operation.
PlantEquipmentOperation:HeatingLoad Plant equipment operation scheme for heating load range operation.
PlantEquipmentOperation:OutdoorDewpoint Plant equipment operation scheme for outdoor dewpoint temperature range operation.
PlantEquipmentOperation:OutdoorDewpointDifference Plant equipment operation scheme for outdoor dewpoint temperature difference operation.
PlantEquipmentOperation:OutdoorDryBulb Plant equipment operation scheme for outdoor dry-bulb temperature range operation.
PlantEquipmentOperation:OutdoorDryBulbDifference Plant equipment operation scheme for outdoor dry-bulb temperature difference operation.
PlantEquipmentOperation:OutdoorRelativeHumidity Plant equipment operation scheme for outdoor relative humidity range operation.
PlantEquipmentOperation:OutdoorWetBulb Plant equipment operation scheme for outdoor wet-bulb temperature range operation.
PlantEquipmentOperation:OutdoorWetBulbDifference Plant equipment operation scheme for outdoor wet-bulb temperature difference operation.
PlantEquipmentOperation:ThermalEnergyStorage Plant equipment operation scheme for simpler input to control thermal (ice) energy storage systems.
PlantEquipmentOperation:Uncontrolled Plant equipment operation scheme for uncontrolled operation.
PlantEquipmentOperationSchemes Operation schemes are listed in "priority" order.

CondenserEquipmentList

from idfpy.models import CondenserEquipmentList extensible

List condenser equipment in order of operating priority, 1st in list will be used 1st, etc Use only condenser equipment in this list. If no equipment object types and equipment names are specified, then the corresponding PlantEquipmentOperation:* object will assume all available condenser equipment for the loop should be OFF (not operate) within the specified lower/upper limit.

Field Type Default Details
name
Name required
string
equipment list Each item: equipment_object_type, equipment_name
Referenced by 10 object types

PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled

CondenserEquipmentOperationSchemes

from idfpy.models import CondenserEquipmentOperationSchemes

Operation schemes are listed in "priority" order. Note that each scheme must address the entire load and/or condition ranges for the simulation. The actual one selected for use will be the first that is "Scheduled" on. That is, if control scheme 1 is not "on" and control scheme 2 is -- then control scheme 2 is selected. Only condenser equipment should be listed on a Control Scheme for this item.

Field Type Default Details
name
Name required
string
control_scheme_1_object_type
Control Scheme 1 Object Type required
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_1_name
Control Scheme 1 Name required
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_1_schedule_name
Control Scheme 1 Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_2_object_type
Control Scheme 2 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_2_name
Control Scheme 2 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_2_schedule_name
Control Scheme 2 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_3_object_type
Control Scheme 3 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_3_name
Control Scheme 3 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_3_schedule_name
Control Scheme 3 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_4_object_type
Control Scheme 4 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_4_name
Control Scheme 4 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_4_schedule_name
Control Scheme 4 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_5_object_type
Control Scheme 5 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_5_name
Control Scheme 5 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_5_schedule_name
Control Scheme 5 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_6_object_type
Control Scheme 6 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_6_name
Control Scheme 6 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_6_schedule_name
Control Scheme 6 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_7_object_type
Control Scheme 7 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_7_name
Control Scheme 7 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_7_schedule_name
Control Scheme 7 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_8_object_type
Control Scheme 8 Object Type
choice One of PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_8_name
Control Scheme 8 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_8_schedule_name
Control Scheme 8 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 2 object types

CondenserLoop, HVACTemplate:Plant:ChilledWaterLoop

PlantEquipmentList

from idfpy.models import PlantEquipmentList extensible

List plant equipment in order of operating priority, 1st in list will be used 1st, etc Use only plant equipment in this list. If no equipment object types and equipment names are specified, then the corresponding PlantEquipmentOperation:* object will assume all available plant equipment for the loop should be OFF (not operate) within the specified lower/upper limit.

Field Type Default Details
name
Name required
string
equipment list Each item: equipment_object_type, equipment_name
Referenced by 10 object types

PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:Uncontrolled

PlantEquipmentOperation:ChillerHeaterChangeover

from idfpy.models import PlantEquipmentOperationChillerHeaterChangeover

Plant equipment operation object to control switchover between chiller and heater operation of chiller heater heat pump serving 2 plant loops. Poll zone loads and determine if plant should be in heating, cooling or simultaneous heating and cooling and dispatch equipment accordingly.

Field Type Default Details
name
Name required
string
primary_cooling_plant_setpoint_temperature
Primary Cooling Plant Setpoint Temperature required
number
C
Range: ≥ -10, ≤ 20
secondary_distribution_cooling_plant_setpoint_temperature
Secondary Distribution Cooling Plant Setpoint Temperature
number
C
Range: ≥ 0, ≤ 20
primary_heating_plant_setpoint_at_outdoor_high_temperature
Primary Heating Plant Setpoint at Outdoor High Temperature required
number
C
Range: ≥ 20, ≤ 80
outdoor_high_temperature
Outdoor High Temperature required
number
C
Range: ≥ 0, ≤ 35
primary_heating_plant_setpoint_at_outdoor_low_temperature
Primary Heating Plant Setpoint at Outdoor Low Temperature required
number
C
Range: ≥ 20, ≤ 80
outdoor_low_temperature
Outdoor Low Temperature required
number
C
Range: ≥ -35, ≤ 35
secondary_distribution_heating_plant_setpoint_temperature
Secondary Distribution Heating Plant Setpoint Temperature
number
C
Range: ≥ 20, ≤ 80
zone_load_polling_zonelist_name
Zone Load Polling ZoneList Name
reference Names a ZoneList
cooling_only_load_plant_equipment_operation_cooling_load_name
Cooling Only Load Plant Equipment Operation Cooling Load Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
heating_only_load_plant_equipment_operation_heating_load_name
Heating Only Load Plant Equipment Operation Heating Load Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
simultaneous_cooling_and_heating_plant_equipment_operation_cooling_load_name
Simultaneous Cooling And Heating Plant Equipment Operation Cooling Load Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
simultaneous_cooling_and_heating_plant_equipment_operation_heating_load_name
Simultaneous Cooling And Heating Plant Equipment Operation Heating Load Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
dedicated_chilled_water_return_recovery_heat_pump_name
Dedicated Chilled Water Return Recovery Heat Pump Name
reference enter name of HeatPump:PlantLoop:EIR:Cooling object to control chilled water return adding heat to hot water return
Names a HeatPump:PlantLoop:EIR:Cooling
dedicated_hot_water_return_recovery_heat_pump_name
Dedicated Hot Water Return Recovery Heat Pump Name
reference enter name of HeatPump:PlantLoop:EIR:Heating object to control hot water return cooling the chilled water return
Names a HeatPump:PlantLoop:EIR:Heating
boiler_setpoint_temperature_offset
Boiler Setpoint Temperature Offset
number
deltaC
0.5
primary_heating_plant_setpoint_at_backup_outdoor_low_temperature
Primary Heating Plant Setpoint at Backup Outdoor Low Temperature
number
C
if empty or not used then set equal to Primary Heating Plant Setpoint at Outdoor Low Temperature
backup_outdoor_low_temperature
Backup Outdoor Low Temperature
number
C
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:ComponentSetpoint

from idfpy.models import PlantEquipmentOperationComponentSetpoint

Plant equipment operation scheme for component setpoint operation. Specifies one or pieces of equipment which are controlled to meet the temperature setpoint at the component outlet node.

Field Type Default Details
name
Name required
string
equipment_1_object_type
Equipment 1 Object Type required
string
equipment_1_name
Equipment 1 Name required
string
demand_calculation_1_node_name
Demand Calculation 1 Node Name required
string
setpoint_1_node_name
Setpoint 1 Node Name required
string
component_1_flow_rate
Component 1 Flow Rate required
number or Autosize
m3/s
operation_1_type
Operation 1 Type required
choice One of Cooling, Dual, Heating
equipment_2_object_type
Equipment 2 Object Type
string
equipment_2_name
Equipment 2 Name
string
demand_calculation_2_node_name
Demand Calculation 2 Node Name
string
setpoint_2_node_name
Setpoint 2 Node Name
string
component_2_flow_rate
Component 2 Flow Rate
number or Autosize
m3/s
operation_2_type
Operation 2 Type
choice One of Cooling, Dual, Heating
equipment_3_object_type
Equipment 3 Object Type
string
equipment_3_name
Equipment 3 Name
string
demand_calculation_3_node_name
Demand Calculation 3 Node Name
string
setpoint_3_node_name
Setpoint 3 Node Name
string
component_3_flow_rate
Component 3 Flow Rate
number or Autosize
m3/s
operation_3_type
Operation 3 Type
choice One of Cooling, Dual, Heating
equipment_4_object_type
Equipment 4 Object Type
string
equipment_4_name
Equipment 4 Name
string
demand_calculation_4_node_name
Demand Calculation 4 Node Name
string
setpoint_4_node_name
Setpoint 4 Node Name
string
component_4_flow_rate
Component 4 Flow Rate
number or Autosize
m3/s
operation_4_type
Operation 4 Type
choice One of Cooling, Dual, Heating
equipment_5_object_type
Equipment 5 Object Type
string
equipment_5_name
Equipment 5 Name
string
demand_calculation_5_node_name
Demand Calculation 5 Node Name
string
setpoint_5_node_name
Setpoint 5 Node Name
string
component_5_flow_rate
Component 5 Flow Rate
number or Autosize
m3/s
operation_5_type
Operation 5 Type
choice One of Cooling, Dual, Heating
equipment_6_object_type
Equipment 6 Object Type
string
equipment_6_name
Equipment 6 Name
string
demand_calculation_6_node_name
Demand Calculation 6 Node Name
string
setpoint_6_node_name
Setpoint 6 Node Name
string
component_6_flow_rate
Component 6 Flow Rate
number or Autosize
m3/s
operation_6_type
Operation 6 Type
choice One of Cooling, Dual, Heating
equipment_7_object_type
Equipment 7 Object Type
string
equipment_7_name
Equipment 7 Name
string
demand_calculation_7_node_name
Demand Calculation 7 Node Name
string
setpoint_7_node_name
Setpoint 7 Node Name
string
component_7_flow_rate
Component 7 Flow Rate
number or Autosize
m3/s
operation_7_type
Operation 7 Type
choice One of Cooling, Dual, Heating
equipment_8_object_type
Equipment 8 Object Type
string
equipment_8_name
Equipment 8 Name
string
demand_calculation_8_node_name
Demand Calculation 8 Node Name
string
setpoint_8_node_name
Setpoint 8 Node Name
string
component_8_flow_rate
Component 8 Flow Rate
number or Autosize
m3/s
operation_8_type
Operation 8 Type
choice One of Cooling, Dual, Heating
equipment_9_object_type
Equipment 9 Object Type
string
equipment_9_name
Equipment 9 Name
string
demand_calculation_9_node_name
Demand Calculation 9 Node Name
string
setpoint_9_node_name
Setpoint 9 Node Name
string
component_9_flow_rate
Component 9 Flow Rate
number or Autosize
m3/s
operation_9_type
Operation 9 Type
choice One of Cooling, Dual, Heating
equipment_10_object_type
Equipment 10 Object Type
string
equipment_10_name
Equipment 10 Name
string
demand_calculation_10_node_name
Demand Calculation 10 Node Name
string
setpoint_10_node_name
Setpoint 10 Node Name
string
component_10_flow_rate
Component 10 Flow Rate
number or Autosize
m3/s
operation_10_type
Operation 10 Type
choice One of Cooling, Dual, Heating
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:CoolingLoad

from idfpy.models import PlantEquipmentOperationCoolingLoad

Plant equipment operation scheme for cooling load range operation. Specifies one or more groups of equipment which are available to operate for successive cooling load ranges.

Field Type Default Details
name
Name required
string
load_range_1_lower_limit
Load Range 1 Lower Limit required
number
W
Range: ≥ 0
load_range_1_upper_limit
Load Range 1 Upper Limit required
number
W
Range: ≥ 0
range_1_equipment_list_name
Range 1 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_2_lower_limit
Load Range 2 Lower Limit
number
W
Range: ≥ 0
load_range_2_upper_limit
Load Range 2 Upper Limit
number
W
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_3_lower_limit
Load Range 3 Lower Limit
number
W
Range: ≥ 0
load_range_3_upper_limit
Load Range 3 Upper Limit
number
W
Range: ≥ 0
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_4_lower_limit
Load Range 4 Lower Limit
number
W
Range: ≥ 0
load_range_4_upper_limit
Load Range 4 Upper Limit
number
W
Range: ≥ 0
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_5_lower_limit
Load Range 5 Lower Limit
number
W
Range: ≥ 0
load_range_5_upper_limit
Load Range 5 Upper Limit
number
W
Range: ≥ 0
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_6_lower_limit
Load Range 6 Lower Limit
number
W
Range: ≥ 0
load_range_6_upper_limit
Load Range 6 Upper Limit
number
W
Range: ≥ 0
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_7_lower_limit
Load Range 7 Lower Limit
number
W
Range: ≥ 0
load_range_7_upper_limit
Load Range 7 Upper Limit
number
W
Range: ≥ 0
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_8_lower_limit
Load Range 8 Lower Limit
number
W
Range: ≥ 0
load_range_8_upper_limit
Load Range 8 Upper Limit
number
W
Range: ≥ 0
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_9_lower_limit
Load Range 9 Lower Limit
number
W
Range: ≥ 0
load_range_9_upper_limit
Load Range 9 Upper Limit
number
W
Range: ≥ 0
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_10_lower_limit
Load Range 10 Lower Limit
number
W
Range: ≥ 0
load_range_10_upper_limit
Load Range 10 Upper Limit
number
W
Range: ≥ 0
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:HeatingLoad

from idfpy.models import PlantEquipmentOperationHeatingLoad

Plant equipment operation scheme for heating load range operation. Specifies one or more groups of equipment which are available to operate for successive heating load ranges.

Field Type Default Details
name
Name required
string
load_range_1_lower_limit
Load Range 1 Lower Limit required
number
W
Range: ≥ 0
load_range_1_upper_limit
Load Range 1 Upper Limit required
number
W
Range: ≥ 0
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_2_lower_limit
Load Range 2 Lower Limit
number
W
Range: ≥ 0
load_range_2_upper_limit
Load Range 2 Upper Limit
number
W
Range: ≥ 0
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_3_lower_limit
Load Range 3 Lower Limit
number
W
Range: ≥ 0
load_range_3_upper_limit
Load Range 3 Upper Limit
number
W
Range: ≥ 0
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_4_lower_limit
Load Range 4 Lower Limit
number
W
Range: ≥ 0
load_range_4_upper_limit
Load Range 4 Upper Limit
number
W
Range: ≥ 0
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_5_lower_limit
Load Range 5 Lower Limit
number
W
Range: ≥ 0
load_range_5_upper_limit
Load Range 5 Upper Limit
number
W
Range: ≥ 0
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_6_lower_limit
Load Range 6 Lower Limit
number
W
Range: ≥ 0
load_range_6_upper_limit
Load Range 6 Upper Limit
number
W
Range: ≥ 0
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_7_lower_limit
Load Range 7 Lower Limit
number
W
Range: ≥ 0
load_range_7_upper_limit
Load Range 7 Upper Limit
number
W
Range: ≥ 0
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_8_lower_limit
Load Range 8 Lower Limit
number
W
Range: ≥ 0
load_range_8_upper_limit
Load Range 8 Upper Limit
number
W
Range: ≥ 0
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_9_lower_limit
Load Range 9 Lower Limit
number
W
Range: ≥ 0
load_range_9_upper_limit
Load Range 9 Upper Limit
number
W
Range: ≥ 0
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
load_range_10_lower_limit
Load Range 10 Lower Limit
number
W
Range: ≥ 0
load_range_10_upper_limit
Load Range 10 Upper Limit
number
W
Range: ≥ 0
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorDewpoint

from idfpy.models import PlantEquipmentOperationOutdoorDewpoint

Plant equipment operation scheme for outdoor dewpoint temperature range operation. Specifies one or more groups of equipment which are available to operate for successive outdoor dewpoint temperature ranges.

Field Type Default Details
name
Name required
string
dewpoint_temperature_range_1_lower_limit
Dewpoint Temperature Range 1 Lower Limit required
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_1_upper_limit
Dewpoint Temperature Range 1 Upper Limit required
number
C
Range: ≥ -70, ≤ 70
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_2_lower_limit
Dewpoint Temperature Range 2 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_2_upper_limit
Dewpoint Temperature Range 2 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_3_lower_limit
Dewpoint Temperature Range 3 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_3_upper_limit
Dewpoint Temperature Range 3 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_4_lower_limit
Dewpoint Temperature Range 4 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_4_upper_limit
Dewpoint Temperature Range 4 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_5_lower_limit
Dewpoint Temperature Range 5 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_5_upper_limit
Dewpoint Temperature Range 5 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_6_lower_limit
Dewpoint Temperature Range 6 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_6_upper_limit
Dewpoint Temperature Range 6 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_7_lower_limit
Dewpoint Temperature Range 7 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_7_upper_limit
Dewpoint Temperature Range 7 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_8_lower_limit
Dewpoint Temperature Range 8 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_8_upper_limit
Dewpoint Temperature Range 8 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_9_lower_limit
Dewpoint Temperature Range 9 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_9_upper_limit
Dewpoint Temperature Range 9 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_range_10_lower_limit
Dewpoint Temperature Range 10 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dewpoint_temperature_range_10_upper_limit
Dewpoint Temperature Range 10 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorDewpointDifference

from idfpy.models import PlantEquipmentOperationOutdoorDewpointDifference

Plant equipment operation scheme for outdoor dewpoint temperature difference operation. Specifies one or more groups of equipment which are available to operate for successive ranges based the difference between a reference node temperature and the outdoor dewpoint temperature.

Field Type Default Details
name
Name required
string
reference_temperature_node_name
Reference Temperature Node Name required
string
dewpoint_temperature_difference_range_1_lower_limit
Dewpoint Temperature Difference Range 1 Lower Limit required
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_1_upper_limit
Dewpoint Temperature Difference Range 1 Upper Limit required
number
deltaC
Range: ≥ -50, ≤ 100
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_2_lower_limit
Dewpoint Temperature Difference Range 2 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_2_upper_limit
Dewpoint Temperature Difference Range 2 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_3_lower_limit
Dewpoint Temperature Difference Range 3 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_3_upper_limit
Dewpoint Temperature Difference Range 3 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_4_lower_limit
Dewpoint Temperature Difference Range 4 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_4_upper_limit
Dewpoint Temperature Difference Range 4 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_5_lower_limit
Dewpoint Temperature Difference Range 5 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_5_upper_limit
Dewpoint Temperature Difference Range 5 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_6_lower_limit
Dewpoint Temperature Difference Range 6 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_6_upper_limit
Dewpoint Temperature Difference Range 6 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_7_lower_limit
Dewpoint Temperature Difference Range 7 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_7_upper_limit
Dewpoint Temperature Difference Range 7 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_8_lower_limit
Dewpoint Temperature Difference Range 8 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_8_upper_limit
Dewpoint Temperature Difference Range 8 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_9_lower_limit
Dewpoint Temperature Difference Range 9 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_9_upper_limit
Dewpoint Temperature Difference Range 9 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dewpoint_temperature_difference_range_10_lower_limit
Dewpoint Temperature Difference Range 10 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dewpoint_temperature_difference_range_10_upper_limit
Dewpoint Temperature Difference Range 10 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorDryBulb

from idfpy.models import PlantEquipmentOperationOutdoorDryBulb

Plant equipment operation scheme for outdoor dry-bulb temperature range operation. Specifies one or more groups of equipment which are available to operate for successive outdoor dry-bulb temperature ranges.

Field Type Default Details
name
Name required
string
dry_bulb_temperature_range_1_lower_limit
Dry-Bulb Temperature Range 1 Lower Limit required
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_1_upper_limit
Dry-Bulb Temperature Range 1 Upper Limit required
number
C
Range: ≥ -70, ≤ 70
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_2_lower_limit
Dry-Bulb Temperature Range 2 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_2_upper_limit
Dry-Bulb Temperature Range 2 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_3_lower_limit
Dry-Bulb Temperature Range 3 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_3_upper_limit
Dry-Bulb Temperature Range 3 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_4_lower_limit
Dry-Bulb Temperature Range 4 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_4_upper_limit
Dry-Bulb Temperature Range 4 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_5_lower_limit
Dry-Bulb Temperature Range 5 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_5_upper_limit
Dry-Bulb Temperature Range 5 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_6_lower_limit
Dry-Bulb Temperature Range 6 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_6_upper_limit
Dry-Bulb Temperature Range 6 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_7_lower_limit
Dry-Bulb Temperature Range 7 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_7_upper_limit
Dry-Bulb Temperature Range 7 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_8_lower_limit
Dry-Bulb Temperature Range 8 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_8_upper_limit
Dry-Bulb Temperature Range 8 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_9_lower_limit
Dry-Bulb Temperature Range 9 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_9_upper_limit
Dry-Bulb Temperature Range 9 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_range_10_lower_limit
Dry-Bulb Temperature Range 10 Lower Limit
number
C
Range: ≥ -70, ≤ 70
dry_bulb_temperature_range_10_upper_limit
Dry-Bulb Temperature Range 10 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorDryBulbDifference

from idfpy.models import PlantEquipmentOperationOutdoorDryBulbDifference

Plant equipment operation scheme for outdoor dry-bulb temperature difference operation. Specifies one or more groups of equipment which are available to operate for successive ranges based the difference between a reference node temperature and the outdoor dry-bulb temperature.

Field Type Default Details
name
Name required
string
reference_temperature_node_name
Reference Temperature Node Name required
string
dry_bulb_temperature_difference_range_1_lower_limit
Dry-Bulb Temperature Difference Range 1 Lower Limit required
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_1_upper_limit
Dry-Bulb Temperature Difference Range 1 Upper Limit required
number
deltaC
Range: ≥ -50, ≤ 100
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_2_lower_limit
Dry-Bulb Temperature Difference Range 2 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_2_upper_limit
Dry-Bulb Temperature Difference Range 2 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_3_lower_limit
Dry-Bulb Temperature Difference Range 3 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_3_upper_limit
Dry-Bulb Temperature Difference Range 3 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_4_lower_limit
Dry-Bulb Temperature Difference Range 4 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_4_upper_limit
Dry-Bulb Temperature Difference Range 4 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_5_lower_limit
Dry-Bulb Temperature Difference Range 5 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_5_upper_limit
Dry-Bulb Temperature Difference Range 5 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_6_lower_limit
Dry-Bulb Temperature Difference Range 6 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_6_upper_limit
Dry-Bulb Temperature Difference Range 6 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_7_lower_limit
Dry-Bulb Temperature Difference Range 7 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_7_upper_limit
Dry-Bulb Temperature Difference Range 7 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_8_lower_limit
Dry-Bulb Temperature Difference Range 8 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_8_upper_limit
Dry-Bulb Temperature Difference Range 8 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_9_lower_limit
Dry-Bulb Temperature Difference Range 9 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_9_upper_limit
Dry-Bulb Temperature Difference Range 9 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
dry_bulb_temperature_difference_range_10_lower_limit
Dry-Bulb Temperature Difference Range 10 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
dry_bulb_temperature_difference_range_10_upper_limit
Dry-Bulb Temperature Difference Range 10 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorRelativeHumidity

from idfpy.models import PlantEquipmentOperationOutdoorRelativeHumidity

Plant equipment operation scheme for outdoor relative humidity range operation. Specifies one or more groups of equipment which are available to operate for successive outdoor relative humidity ranges.

Field Type Default Details
name
Name required
string
relative_humidity_range_1_lower_limit
Relative Humidity Range 1 Lower Limit required
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_1_upper_limit
Relative Humidity Range 1 Upper Limit required
number
percent
Range: ≥ 0, ≤ 100
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_2_lower_limit
Relative Humidity Range 2 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_2_upper_limit
Relative Humidity Range 2 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_3_lower_limit
Relative Humidity Range 3 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_3_upper_limit
Relative Humidity Range 3 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_4_lower_limit
Relative Humidity Range 4 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_4_upper_limit
Relative Humidity Range 4 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_5_lower_limit
Relative Humidity Range 5 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_5_upper_limit
Relative Humidity Range 5 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_6_lower_limit
Relative Humidity Range 6 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_6_upper_limit
Relative Humidity Range 6 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_7_lower_limit
Relative Humidity Range 7 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_7_upper_limit
Relative Humidity Range 7 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_8_lower_limit
Relative Humidity Range 8 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_8_upper_limit
Relative Humidity Range 8 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_9_lower_limit
Relative Humidity Range 9 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_9_upper_limit
Relative Humidity Range 9 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
relative_humidity_range_10_lower_limit
Relative Humidity Range 10 Lower Limit
number
percent
Range: ≥ 0, ≤ 100
relative_humidity_range_10_upper_limit
Relative Humidity Range 10 Upper Limit
number
percent
Range: ≥ 0, ≤ 100
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorWetBulb

from idfpy.models import PlantEquipmentOperationOutdoorWetBulb

Plant equipment operation scheme for outdoor wet-bulb temperature range operation. Specifies one or more groups of equipment which are available to operate for successive outdoor wet-bulb temperature ranges.

Field Type Default Details
name
Name required
string
wet_bulb_temperature_range_1_lower_limit
Wet-Bulb Temperature Range 1 Lower Limit required
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_1_upper_limit
Wet-Bulb Temperature Range 1 Upper Limit required
number
C
Range: ≥ -70, ≤ 70
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_2_lower_limit
Wet-Bulb Temperature Range 2 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_2_upper_limit
Wet-Bulb Temperature Range 2 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_3_lower_limit
Wet-Bulb Temperature Range 3 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_3_upper_limit
Wet-Bulb Temperature Range 3 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_4_lower_limit
Wet-Bulb Temperature Range 4 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_4_upper_limit
Wet-Bulb Temperature Range 4 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_5_lower_limit
Wet-Bulb Temperature Range 5 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_5_upper_limit
Wet-Bulb Temperature Range 5 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_6_lower_limit
Wet-Bulb Temperature Range 6 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_6_upper_limit
Wet-Bulb Temperature Range 6 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_7_lower_limit
Wet-Bulb Temperature Range 7 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_7_upper_limit
Wet-Bulb Temperature Range 7 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_8_lower_limit
Wet-Bulb Temperature Range 8 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_8_upper_limit
Wet-Bulb Temperature Range 8 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_9_lower_limit
Wet-Bulb Temperature Range 9 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_9_upper_limit
Wet-Bulb Temperature Range 9 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_range_10_lower_limit
Wet-Bulb Temperature Range 10 Lower Limit
number
C
Range: ≥ -70, ≤ 70
wet_bulb_temperature_range_10_upper_limit
Wet-Bulb Temperature Range 10 Upper Limit
number
C
Range: ≥ -70, ≤ 70
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:OutdoorWetBulbDifference

from idfpy.models import PlantEquipmentOperationOutdoorWetBulbDifference

Plant equipment operation scheme for outdoor wet-bulb temperature difference operation. Specifies one or more groups of equipment which are available to operate for successive ranges based the difference between a reference node temperature and the outdoor wet-bulb temperature.

Field Type Default Details
name
Name required
string
reference_temperature_node_name
Reference Temperature Node Name required
string
wet_bulb_temperature_difference_range_1_lower_limit
Wet-Bulb Temperature Difference Range 1 Lower Limit required
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_1_upper_limit
Wet-Bulb Temperature Difference Range 1 Upper Limit required
number
deltaC
Range: ≥ -50, ≤ 100
range_1_equipment_list_name
Range 1 Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_2_lower_limit
Wet-Bulb Temperature Difference Range 2 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_2_upper_limit
Wet-Bulb Temperature Difference Range 2 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_2_equipment_list_name
Range 2 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_3_lower_limit
Wet-Bulb Temperature Difference Range 3 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_3_upper_limit
Wet-Bulb Temperature Difference Range 3 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_3_equipment_list_name
Range 3 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_4_lower_limit
Wet-Bulb Temperature Difference Range 4 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_4_upper_limit
Wet-Bulb Temperature Difference Range 4 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_4_equipment_list_name
Range 4 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_5_lower_limit
Wet-Bulb Temperature Difference Range 5 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_5_upper_limit
Wet-Bulb Temperature Difference Range 5 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_5_equipment_list_name
Range 5 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_6_lower_limit
Wet-Bulb Temperature Difference Range 6 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_6_upper_limit
Wet-Bulb Temperature Difference Range 6 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_6_equipment_list_name
Range 6 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_7_lower_limit
Wet-Bulb Temperature Difference Range 7 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_7_upper_limit
Wet-Bulb Temperature Difference Range 7 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_7_equipment_list_name
Range 7 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_8_lower_limit
Wet-Bulb Temperature Difference Range 8 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_8_upper_limit
Wet-Bulb Temperature Difference Range 8 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_8_equipment_list_name
Range 8 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_9_lower_limit
Wet-Bulb Temperature Difference Range 9 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_9_upper_limit
Wet-Bulb Temperature Difference Range 9 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_9_equipment_list_name
Range 9 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
wet_bulb_temperature_difference_range_10_lower_limit
Wet-Bulb Temperature Difference Range 10 Lower Limit
number
deltaC
Range: ≥ -50, ≤ 100
wet_bulb_temperature_difference_range_10_upper_limit
Wet-Bulb Temperature Difference Range 10 Upper Limit
number
deltaC
Range: ≥ -50, ≤ 100
range_10_equipment_list_name
Range 10 Equipment List Name
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:ThermalEnergyStorage

from idfpy.models import PlantEquipmentOperationThermalEnergyStorage

Plant equipment operation scheme for simpler input to control thermal (ice) energy storage systems. It replaces a host of setpoint managers with simple, single input values. For more complex controls, use the ComponentSetpoint scheme.

Field Type Default Details
name
Name required
string
on_peak_schedule
On-Peak Schedule required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
charging_availability_schedule
Charging Availability Schedule required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
non_charging_chilled_water_temperature
Non-Charging Chilled Water Temperature required
number
C
Single temperature for chiller outlet when not in cooling season or during on-peak cooling (discharge)
charging_chilled_water_temperature
Charging Chilled Water Temperature required
number
C
Single temperature for chiller outlet when off-peak during cooling season (charging)
component_1_object_type
Component 1 Object Type required
choice This field is the type of object and should either be a chiller or some ice storage equipment.
One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_1_name
Component 1 Name required
reference This field is the name of either the chiller or ice storage equipment on the loop.
Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_1_demand_calculation_node_name
Component 1 Demand Calculation Node Name required
string This field is the name of the inlet node for the component defined in the two previous input fields.
component_1_setpoint_node_name
Component 1 Setpoint Node Name required
string This field is the name of the outlet node for the component listed above.
component_1_flow_rate
Component 1 Flow Rate required
number or Autosize
m3/s
This field is the flow rate for the component listed above.
component_1_operation_type
Component 1 Operation Type required
choice This field is the operation type for the component listed above. For this plant equipment operation scheme, "Cooling" should be selected for chiller equipment while ice storage equipment should be defined as "Dual".
One of Cooling, Dual, Heating
component_2_object_type
Component 2 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_2_name
Component 2 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_2_demand_calculation_node_name
Component 2 Demand Calculation Node Name
string
component_2_setpoint_node_name
Component 2 Setpoint Node Name
string
component_2_flow_rate
Component 2 Flow Rate
number or Autosize
m3/s
component_2_operation_type
Component 2 Operation Type
choice One of Cooling, Dual, Heating
component_3_object_type
Component 3 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_3_name
Component 3 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_3_demand_calculation_node_name
Component 3 Demand Calculation Node Name
string
component_3_setpoint_node_name
Component 3 Setpoint Node Name
string
component_3_flow_rate
Component 3 Flow Rate
number or Autosize
m3/s
component_3_operation_type
Component 3 Operation Type
choice One of Cooling, Dual, Heating
component_4_object_type
Component 4 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_4_name
Component 4 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_4_demand_calculation_node_name
Component 4 Demand Calculation Node Name
string
component_4_setpoint_node_name
Component 4 Setpoint Node Name
string
component_4_flow_rate
Component 4 Flow Rate
number or Autosize
m3/s
component_4_operation_type
Component 4 Operation Type
choice One of Cooling, Dual, Heating
component_5_object_type
Component 5 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_5_name
Component 5 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_5_demand_calculation_node_name
Component 5 Demand Calculation Node Name
string
component_5_setpoint_node_name
Component 5 Setpoint Node Name
string
component_5_flow_rate
Component 5 Flow Rate
number or Autosize
m3/s
component_5_operation_type
Component 5 Operation Type
choice One of Cooling, Dual, Heating
component_6_object_type
Component 6 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_6_name
Component 6 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_6_demand_calculation_node_name
Component 6 Demand Calculation Node Name
string
component_6_setpoint_node_name
Component 6 Setpoint Node Name
string
component_6_flow_rate
Component 6 Flow Rate
number or Autosize
m3/s
component_6_operation_type
Component 6 Operation Type
choice One of Cooling, Dual, Heating
component_7_object_type
Component 7 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_7_name
Component 7 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_7_demand_calculation_node_name
Component 7 Demand Calculation Node Name
string
component_7_setpoint_node_name
Component 7 Setpoint Node Name
string
component_7_flow_rate
Component 7 Flow Rate
number or Autosize
m3/s
component_7_operation_type
Component 7 Operation Type
choice One of Cooling, Dual, Heating
component_8_object_type
Component 8 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_8_name
Component 8 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_8_demand_calculation_node_name
Component 8 Demand Calculation Node Name
string
component_8_setpoint_node_name
Component 8 Setpoint Node Name
string
component_8_flow_rate
Component 8 Flow Rate
number or Autosize
m3/s
component_8_operation_type
Component 8 Operation Type
choice One of Cooling, Dual, Heating
component_9_object_type
Component 9 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_9_name
Component 9 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_9_demand_calculation_node_name
Component 9 Demand Calculation Node Name
string
component_9_setpoint_node_name
Component 9 Setpoint Node Name
string
component_9_flow_rate
Component 9 Flow Rate
number or Autosize
m3/s
component_9_operation_type
Component 9 Operation Type
choice One of Cooling, Dual, Heating
component_10_object_type
Component 10 Object Type
choice One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_10_name
Component 10 Name
reference Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple
component_10_demand_calculation_node_name
Component 10 Demand Calculation Node Name
string
component_10_setpoint_node_name
Component 10 Setpoint Node Name
string
component_10_flow_rate
Component 10 Flow Rate
number or Autosize
m3/s
component_10_operation_type
Component 10 Operation Type
choice One of Cooling, Dual, Heating
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperation:Uncontrolled

from idfpy.models import PlantEquipmentOperationUncontrolled

Plant equipment operation scheme for uncontrolled operation. Specifies a group of equipment that runs if the loop is active, unless turned off by the loop flow resolver to maintain continuity in the fluid loop.

Field Type Default Details
name
Name required
string
equipment_list_name
Equipment List Name required
reference Names a CondenserEquipmentList, PlantEquipmentList
Referenced by 3 object types

CondenserEquipmentOperationSchemes, PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperationSchemes

PlantEquipmentOperationSchemes

from idfpy.models import PlantEquipmentOperationSchemes

Operation schemes are listed in "priority" order. Note that each scheme must address the entire load and/or condition ranges for the simulation. The actual one selected for use will be the first that is "Scheduled" on. That is, if control scheme 1 is not "on" and control scheme 2 is -- then control scheme 2 is selected. Only plant equipment should be listed on a Control Scheme for this item.

Field Type Default Details
name
Name required
string
control_scheme_1_object_type
Control Scheme 1 Object Type required
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_1_name
Control Scheme 1 Name required
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_1_schedule_name
Control Scheme 1 Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_2_object_type
Control Scheme 2 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_2_name
Control Scheme 2 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_2_schedule_name
Control Scheme 2 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_3_object_type
Control Scheme 3 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_3_name
Control Scheme 3 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_3_schedule_name
Control Scheme 3 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_4_object_type
Control Scheme 4 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_4_name
Control Scheme 4 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_4_schedule_name
Control Scheme 4 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_5_object_type
Control Scheme 5 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_5_name
Control Scheme 5 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_5_schedule_name
Control Scheme 5 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_6_object_type
Control Scheme 6 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_6_name
Control Scheme 6 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_6_schedule_name
Control Scheme 6 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_7_object_type
Control Scheme 7 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_7_name
Control Scheme 7 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_7_schedule_name
Control Scheme 7 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
control_scheme_8_object_type
Control Scheme 8 Object Type
choice One of PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage, PlantEquipmentOperation:Uncontrolled, PlantEquipmentOperation:UserDefined
control_scheme_8_name
Control Scheme 8 Name
reference Names a PlantEquipmentOperation:ChillerHeaterChangeover, PlantEquipmentOperation:ComponentSetpoint, PlantEquipmentOperation:CoolingLoad, PlantEquipmentOperation:HeatingLoad, PlantEquipmentOperation:OutdoorDewpoint, PlantEquipmentOperation:OutdoorDewpointDifference, PlantEquipmentOperation:OutdoorDryBulb, PlantEquipmentOperation:OutdoorDryBulbDifference, PlantEquipmentOperation:OutdoorRelativeHumidity, PlantEquipmentOperation:OutdoorWetBulb, PlantEquipmentOperation:OutdoorWetBulbDifference, PlantEquipmentOperation:ThermalEnergyStorage and 1 more
control_scheme_8_schedule_name
Control Scheme 8 Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 4 object types

HVACTemplate:Plant:ChilledWaterLoop, HVACTemplate:Plant:HotWaterLoop, HVACTemplate:Plant:MixedWaterLoop, PlantLoop