Refrigeration

18 object types from idfpy.models.refrigeration · EnergyPlus 26.2

Object Summary
Refrigeration:AirChiller Works in conjunction with a refrigeration chiller set, compressor rack, a refrigeration system, or a …
Refrigeration:Case The Refrigeration Case object works in conjunction with a compressor rack, a refrigeration system, or a …
Refrigeration:CaseAndWalkInList Provides a list of all the refrigerated cases, walk in coolers, or air chillers cooled by a single …
Refrigeration:Compressor Refrigeration system compressor.
Refrigeration:CompressorList List of all the compressors included within a single refrigeration system (Refrigeration:System).
Refrigeration:CompressorRack Works in conjunction with the refrigeration case and walk-in objects to simulate the performance of a …
Refrigeration:Condenser:AirCooled Air cooled condenser for a refrigeration system (Refrigeration:System).
Refrigeration:Condenser:Cascade Cascade condenser for a refrigeration system (Refrigeration:System).
Refrigeration:Condenser:EvaporativeCooled Evaporative-cooled condenser for a refrigeration system (Refrigeration:System).
Refrigeration:Condenser:WaterCooled Water cooled condenser for a refrigeration system (Refrigeration:System).
Refrigeration:GasCooler:AirCooled The transcritical refrigeration system requires a single gas cooler to reject the system heat.
Refrigeration:SecondarySystem Works in conjunction with refrigerated cases and walkins to simulate the performance of a secondary loop …
Refrigeration:Subcooler Two types of subcoolers are modeled by the detailed refrigeration system.
Refrigeration:System Simulates the performance of a supermarket refrigeration system when used along with other objects to define …
Refrigeration:TranscriticalSystem Detailed transcritical carbon dioxide (CO2) booster refrigeration systems used in supermarkets.
Refrigeration:TransferLoadList A refrigeration system may provide cooling to other, secondary, systems through either a secondary loop or a …
Refrigeration:WalkIn Works in conjunction with a compressor rack, a refrigeration system, or a refrigeration secondary system to …
ZoneHVAC:RefrigerationChillerSet Works in conjunction with one or multiple air chillers, compressor racks, refrigeration systems, or …

Refrigeration:AirChiller

from idfpy.models import RefrigerationAirChiller

Works in conjunction with a refrigeration chiller set, compressor rack, a refrigeration system, or a refrigeration secondary system to simulate the performance of an air chiller, similar to one found in a refrigerated warehouse. Energy use for fans and heaters is modeled based on inputs for nominal power, schedules, and control type. The air chiller model accounts for the sensible and latent heat exchange with the surrounding environment.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
capacity_rating_type
Capacity Rating Type required
choice In each case, select the rating option that corresponds to the expected service conditions. For example, U.S. manufacturers quote a separate Unit Load Factor for wet or frosted coils. If the evaporating temperature is less than 0C, input the frosted coil value. Within the European convention, select SC1, 2, 3, 4, or 5 depending upon the expected evaporating temperature.
One of CapacityTotalSpecificConditions, EuropeanSC1NominalWet, EuropeanSC1Standard, EuropeanSC2NominalWet, EuropeanSC2Standard, EuropeanSC3NominalWet, EuropeanSC3Standard, EuropeanSC4NominalWet, EuropeanSC4Standard, EuropeanSC5NominalWet, EuropeanSC5Standard, FixedLinear, UnitLoadFactorSensibleOnly
rated_unit_load_factor
Rated Unit Load Factor
number
W/K
The sensible cooling capacity in watts (W/C) at rated conditions. The value entered for this field must be greater than zero, with no default value. This value is only used if the Capacity Rating Type is UnitLoadFactorSensibleOnly. The value given must be based upon the difference between the chiller inlet and outlet air temperatures, not on the difference between the zone mean temperature and the outlet air temperature
rated_capacity
Rated Capacity
number
W
This value is only used if the Capacity Rating Type is NOT UnitLoadFactorSensibleOnly. For CapacityTotalSpecificConditions, this capacity includes both sensible and latent at the conditions given in the next two fields. Note that the European Standard ratings are sensible only and the European Nominal ratings include latent capacity as well. The value given here must correspond to the capacity rating type given previously
rated_relative_humidity
Rated Relative Humidity
number
percent
85.0 This field is ONLY used if the Capacity Rating Type is CapacityTotalSpecificConditions and represents the relative humidity at rated conditions. The default is 85.
Range: ≤ 100
rated_cooling_source_temperature
Rated Cooling Source Temperature required
number
C
If DXEvaporator, use evaporating temperature (saturated suction temperature) If BrineCoil, use Brine entering temperature used to set minimum suction pressure for DX systems and minimum brine temp for secondary systems
Range: ≥ -70, ≤ 40
rated_temperature_difference_dt1
Rated Temperature Difference DT1 required
number
deltaC
The rated difference between the air entering the refrigeration chiller and the cooling source temperature in degC.
Range: ≥ 0, ≤ 20
maximum_temperature_difference_between_inlet_air_and_evaporating_temperature
Maximum Temperature Difference Between Inlet Air and Evaporating Temperature
number
deltaC
The maximum difference between the air entering the refrigeration chiller and the cooling source temperature in degC used to limit capacity during pull-down. defaults to 1.3 times the Rated Temperature Difference DT1
Range: ≥ 0, ≤ 25
coil_material_correction_factor
Coil Material Correction Factor
number
dimensionless
1.0 This is the manufacturer's correction factor for coil material corresponding to rating
refrigerant_correction_factor
Refrigerant Correction Factor
number
dimensionless
1.0 This is the manufacturer's correction factor for refrigerant corresponding to rating
capacity_correction_curve_type
Capacity Correction Curve Type
choice In each case, select the correction curve type that corresponds to the rating type. default LinearSHR60 unless Capacity Rating Type = CapacityTotalSpecificConditions
One of European, LinearSHR60, QuadraticSHR, TabularRHxDT1xTRoom
capacity_correction_curve_name
Capacity Correction Curve Name
reference Should be blank for LinearSHR60 correction curve type
Names a Curve:ChillerPartLoadWithLift, Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2 and 3 more
shr60_correction_factor
SHR60 Correction Factor
number
dimensionless
1.48 only used when the capacity correction curve type is LinearSHR60
Range: ≤ 1.67
rated_total_heating_power
Rated Total Heating Power required
number
W
Include total for all heater power Do not include defrost heater power
heating_power_schedule_name
Heating Power Schedule Name
reference Values will be used to multiply the total heating power Values in the schedule should be between 0.0 and 1.0 Defaults to always on if schedule name left blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fan_speed_control_type
Fan Speed Control Type
choice Fixed One of Fixed, FixedLinear, TwoSpeed, VariableSpeed
rated_fan_power
Rated Fan Power
number
W
375.0 Range: ≥ 0
rated_air_flow
Rated Air Flow required
number
m3/s
minimum_fan_air_flow_ratio
Minimum Fan Air Flow Ratio
number
dimensionless
0.2 Minimum air flow fraction through fan
Range: ≥ 0
defrost_type
Defrost Type
choice Electric HotFluid includes either hot gas defrost for a DX system or Hot Brine defrost if this walk in is cooled by brine from a secondary chiller
One of Electric, HotFluid, None, OffCycle
defrost_control_type
Defrost Control Type
choice TimeSchedule One of TemperatureTermination, TimeSchedule
defrost_schedule_name
Defrost Schedule Name required
reference The schedule values should be 0 (off) or 1 (on)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_drip_down_schedule_name
Defrost Drip-Down Schedule Name
reference The schedule values should be 0 (off) or 1 (on) The start time for each defrost period in this drip-down schedule should coincide with the start time for each defrost period in the defrost schedule (previous input field). The length of each defrost drip-down period must be greater than or equal to the corresponding defrost period specified in the defrost schedule. This extra time allows the melted frost to drip from the coil before refrigeration is restarted.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_power
Defrost Power
number
W
needed for all defrost types except none and offcycle
Range: ≥ 0
temperature_termination_defrost_fraction_to_ice
Temperature Termination Defrost Fraction to Ice
number
dimensionless
This is the portion of the defrost energy that is available to melt frost Needed only for defrost control type TemperatureTermination defaults to 0.7 for electric defrost and to 0.3 for hot fluid defrost
Range: > 0, ≤ 1
vertical_location
Vertical Location
choice Middle One of Ceiling, Floor, Middle
average_refrigerant_charge_inventory
Average Refrigerant Charge Inventory
number
kg
0.0 This value is only used if the Cooling Source Type is DXEvaporator
Referenced by 6 object types

Refrigeration:CaseAndWalkInList, Refrigeration:CompressorRack, Refrigeration:SecondarySystem, Refrigeration:System, Refrigeration:TranscriticalSystem, ZoneHVAC:RefrigerationChillerSet

Refrigeration:Case

from idfpy.models import RefrigerationCase

The Refrigeration Case object works in conjunction with a compressor rack, a refrigeration system, or a secondary loop to simulate the performance of a refrigerated case system. The object calculates the energy use for lights, fans and anti-sweat heaters and accounts for the sensible and latent heat exchange with the surrounding environment (termed "case credits") which impacts the temperature and humidity in the zone where the case is located.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_name
Zone Name required
reference This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object.
Names a Zone
rated_ambient_temperature
Rated Ambient Temperature
number
C
23.9 Range: > 0
rated_ambient_relative_humidity
Rated Ambient Relative Humidity
number
percent
55.0 Range: > 0, < 100
rated_total_cooling_capacity_per_unit_length
Rated Total Cooling Capacity per Unit Length
number
W/m
1900.0 Range: > 0
rated_latent_heat_ratio
Rated Latent Heat Ratio
number 0.3 Range: ≥ 0, ≤ 1
rated_runtime_fraction
Rated Runtime Fraction
number 0.85 Range: > 0, ≤ 1
case_length
Case Length
number
m
3.0 Range: > 0
case_operating_temperature
Case Operating Temperature
number
C
1.1 Range: < 20
latent_case_credit_curve_type
Latent Case Credit Curve Type
choice CaseTemperatureMethod One of CaseTemperatureMethod, DewpointMethod, RelativeHumidityMethod
latent_case_credit_curve_name
Latent Case Credit Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
standard_case_fan_power_per_unit_length
Standard Case Fan Power per Unit Length
number
W/m
75.0 Range: ≥ 0
operating_case_fan_power_per_unit_length
Operating Case Fan Power per Unit Length
number
W/m
75.0 Range: ≥ 0
standard_case_lighting_power_per_unit_length
Standard Case Lighting Power per Unit Length
number
W/m
90.0
installed_case_lighting_power_per_unit_length
Installed Case Lighting Power per Unit Length
number
W/m
default set equal to Standard Case Lighting Power per Unit Length
case_lighting_schedule_name
Case Lighting Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fraction_of_lighting_energy_to_case
Fraction of Lighting Energy to Case
number 1.0 Range: ≥ 0, ≤ 1
case_anti_sweat_heater_power_per_unit_length
Case Anti-Sweat Heater Power per Unit Length
number
W/m
0.0 Range: ≥ 0
minimum_anti_sweat_heater_power_per_unit_length
Minimum Anti-Sweat Heater Power per Unit Length
number
W/m
0.0 This field is only applicable to the Linear, Dewpoint Method, and Heat Balance Method anti-sweat heater control types
Range: ≥ 0
anti_sweat_heater_control_type
Anti-Sweat Heater Control Type
choice None One of Constant, DewpointMethod, HeatBalanceMethod, Linear, None
humidity_at_zero_anti_sweat_heater_energy
Humidity at Zero Anti-Sweat Heater Energy
number
percent
-10.0 This field is only applicable to Linear AS heater control type Zone relative humidity (%) where anti-sweat heater energy is zero
case_height
Case Height
number
m
1.5 This field only applicable to Heat Balance Method AS heater control type Height must be greater than zero if Heat Balance Method AS heater control is selected
Range: ≥ 0
fraction_of_anti_sweat_heater_energy_to_case
Fraction of Anti-Sweat Heater Energy to Case
number 1.0 Range: ≥ 0, ≤ 1
case_defrost_power_per_unit_length
Case Defrost Power per Unit Length
number
W/m
0.0 Used to evaluate load on case as well as power or heat consumption
Range: ≥ 0
case_defrost_type
Case Defrost Type
choice OffCycle One of Electric, ElectricWithTemperatureTermination, HotFluid, HotFluidWithTemperatureTermination, HotGas, HotGasWithTemperatureTermination, None, OffCycle
case_defrost_schedule_name
Case Defrost Schedule Name
reference A case defrost schedule name is required unless case defrost type = None
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
case_defrost_drip_down_schedule_name
Case Defrost Drip-Down Schedule Name
reference If left blank, the defrost schedule will be used The start time for each defrost period in this drip-down schedule should coincide with the start time for each defrost period in the case defrost schedule (previous input field). The length of each defrost drip-down period must be greater than or equal to the corresponding defrost period specified in the case defrost schedule. This extra time allows the melted frost to drip from the coil before refrigeration is restarted.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_energy_correction_curve_type
Defrost Energy Correction Curve Type
choice None Case Temperature, Relative Humidity, and Dewpoint Method are applicable to case defrost types with temperature termination only.
One of CaseTemperatureMethod, DewpointMethod, None, RelativeHumidityMethod
defrost_energy_correction_curve_name
Defrost Energy Correction Curve Name
reference Defrost Energy Correction Curve Name is applicable to case defrost types with temperature termination only.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
under_case_hvac_return_air_fraction
Under Case HVAC Return Air Fraction
number 0.0 Range: ≥ 0, ≤ 1
refrigerated_case_restocking_schedule_name
Refrigerated Case Restocking Schedule Name
reference Schedule values should be in units of Watts per unit case length (W/m) Leave this field blank if no restocking is to be modeled
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
case_credit_fraction_schedule_name
Case Credit Fraction Schedule Name
reference Schedule values should be from 0 to 1 Leave this field blank if no case credit fraction is to be applied
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_evaporator_temperature_or_brine_inlet_temperature
Design Evaporator Temperature or Brine Inlet Temperature
number
C
Required for detailed refrigeration system, not for compressor rack For a DX system, enter the saturated temperature for refrigerant pressure leaving case For a brine-cooled cooled (secondary system) case, enter the brine inlet temperature Default is 5 C less than case operating temperature
Range: ≥ -70, ≤ 40
average_refrigerant_charge_inventory
Average Refrigerant Charge Inventory
number
kg/m
0.0
under_case_hvac_return_air_node_name
Under Case HVAC Return Air Node Name
string Name of the return air node for this case. If left blank, defaults to the first return air node for this zone.
Referenced by 5 object types

Refrigeration:CaseAndWalkInList, Refrigeration:CompressorRack, Refrigeration:SecondarySystem, Refrigeration:System, Refrigeration:TranscriticalSystem

Refrigeration:CaseAndWalkInList

from idfpy.models import RefrigerationCaseAndWalkInList extensible

Provides a list of all the refrigerated cases, walk in coolers, or air chillers cooled by a single refrigeration system. Note that the names of all cases, walk-ins ,air chillers, and CaseAndWalkInLists must be unique. That is, you cannot give a list the same name as one of list items. This list may contain a combination of case and walk-in names OR a list of air chiller names. Air chillers may not be included in any list that also includes cases or walk-ins.

Field Type Default Details
name
Name required
string
cases_and_walkins list Each item: case_or_walkin_name
Referenced by 4 object types

Refrigeration:CompressorRack, Refrigeration:SecondarySystem, Refrigeration:System, Refrigeration:TranscriticalSystem

Refrigeration:Compressor

from idfpy.models import RefrigerationCompressor

Refrigeration system compressor. Data is available for many compressors in the RefrigerationCompressor.idf dataset

Field Type Default Details
name
Name required
string
refrigeration_compressor_power_curve_name
Refrigeration Compressor Power Curve Name required
reference the input order for the Curve:Bicubic does not match the ARI 540-2004 Eq. 1 coefficient order N1 is ARI_C1, N2 is ARI_C2, N3 is ARI_C4, N4 is ARI_C3, N5 is ARI_C6, N6 is ARI_C5, N7 is ARI_C7, N8 is ARI_C10, N9 is ARI_C8, N10 is ARI_C9, N11 is Minimum Suction dewpoint temperature, N12 is Maximum Suction dewpoint temperature, N13 is Minimum Discharge dewpoint temperature, N14 is Maximum Discharge dewpoint temperature
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
refrigeration_compressor_capacity_curve_name
Refrigeration Compressor Capacity Curve Name required
reference the input order for the Curve:Bicubic does not match the ARI 540-2004 Eq. 1 coefficient order N1 is ARI_C1, N2 is ARI_C2, N3 is ARI_C4, N4 is ARI_C3, N5 is ARI_C6, N6 is ARI_C5, N7 is ARI_C7, N8 is ARI_C10, N9 is ARI_C8, N10 is ARI_C9, N11 is Minimum Suction dewpoint temperature, N12 is Maximum Suction dewpoint temperature, N13 is Minimum Discharge dewpoint temperature, N14 is Maximum Discharge dewpoint temperature
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
rated_superheat
Rated Superheat
number
deltaC
Use this input field OR the next, not both This is used if the compressor rating is based upon degrees of superheat
rated_return_gas_temperature
Rated Return Gas Temperature
number
C
Use this input field OR the previous, not both This is used if the compressor rating is based upon rated return gas temperature (Rated Suction Temperature)
rated_liquid_temperature
Rated Liquid Temperature
number
C
Use this input field OR the next, not both This is used if the compressor rating is based upon rated liquid temperature at the expansion valve
rated_subcooling
Rated Subcooling
number
deltaC
Use this input field OR the previous, not both This is used if the compressor rating is based upon degrees of subcooling
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
mode_of_operation
Mode of Operation
choice Subcritical One of Subcritical, Transcritical
transcritical_compressor_power_curve_name
Transcritical Compressor Power Curve Name
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
transcritical_compressor_capacity_curve_name
Transcritical Compressor Capacity Curve Name
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
Referenced by 3 object types

Refrigeration:CompressorList, Refrigeration:System, Refrigeration:TranscriticalSystem

Refrigeration:CompressorList

from idfpy.models import RefrigerationCompressorList extensible

List of all the compressors included within a single refrigeration system (Refrigeration:System). Each list must contain at least one compressor. The order in which the individual compressors are listed here will be the order in which the compressors are dispatched to meet the system load. IMPORTANT: List compressor names in the order in which the compressors will be loaded Data is available for many compressors in the RefrigerationCompressor.idf dataset

Field Type Default Details
name
Name required
string
compressors list Each item: refrigeration_compressor_name
Referenced by 2 object types

Refrigeration:System, Refrigeration:TranscriticalSystem

Refrigeration:CompressorRack

from idfpy.models import RefrigerationCompressorRack

Works in conjunction with the refrigeration case and walk-in objects to simulate the performance of a refrigerated case system. This object models the electric consumption of the rack compressors and the condenser fans. Heat can be rejected either outdoors or to a zone. Compressor rack waste heat can also be reclaimed for use by an optional air- or water-heating coil (Coil:Heating:Desuperheater and Coil:WaterHeating:Desuperheater).

Field Type Default Details
name
Name required
string
heat_rejection_location
Heat Rejection Location
choice Outdoors One of Outdoors, Zone
design_compressor_rack_cop
Design Compressor Rack COP
number
W/W
2.0 It is important that this COP correspond to the lowest saturated suction temperature needed to serve all refrigeration loads
Range: > 0
compressor_rack_cop_function_of_temperature_curve_name
Compressor Rack COP Function of Temperature Curve Name required
reference It is important that this COP curve correspond to the lowest saturated suction temperature needed to serve all refrigeration loads
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
design_condenser_fan_power
Design Condenser Fan Power
number
W
250.0 Design power for condenser fan(s).
Range: ≥ 0
condenser_fan_power_function_of_temperature_curve_name
Condenser Fan Power Function of Temperature Curve Name
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
condenser_type
Condenser Type
choice AirCooled Applicable only when Heat Rejection Location is Outdoors.
One of AirCooled, EvaporativelyCooled, WaterCooled
water_cooled_condenser_inlet_node_name
Water-Cooled Condenser Inlet Node Name
string
water_cooled_condenser_outlet_node_name
Water-Cooled Condenser Outlet Node Name
string
water_cooled_loop_flow_type
Water-Cooled Loop Flow Type
choice VariableFlow Applicable only when Condenser Type is WaterCooled.
One of ConstantFlow, VariableFlow
water_cooled_condenser_outlet_temperature_schedule_name
Water-Cooled Condenser Outlet Temperature Schedule Name
reference Applicable only when loop Flow type is VariableFlow.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_cooled_condenser_design_flow_rate
Water-Cooled Condenser Design Flow Rate
number
m3/s
Applicable only when loop flow type is ConstantFlow.
Range: > 0
water_cooled_condenser_maximum_flow_rate
Water-Cooled Condenser Maximum Flow Rate
number
m3/s
Range: > 0
water_cooled_condenser_maximum_water_outlet_temperature
Water-Cooled Condenser Maximum Water Outlet Temperature
number
C
55.0 Range: ≥ 10, ≤ 60
water_cooled_condenser_minimum_water_inlet_temperature
Water-Cooled Condenser Minimum Water Inlet Temperature
number
C
10.0 Range: ≥ 10, ≤ 30
evaporative_condenser_availability_schedule_name
Evaporative Condenser Availability Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 indicate that evaporative cooling of the condenser is available. This schedule allows the user to define seasonal shutdown/draining of the water cooling system in cold climate applications. For periods with schedule values of 0, the condenser operates as AirCooled.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Applicable only for Condenser Type = EvaporativlyCooled.
Range: ≥ 0, ≤ 1
evaporative_condenser_air_flow_rate
Evaporative Condenser Air Flow Rate
number or Autocalculate
m3/s
Autocalculate Applicable only for Condenser Type = EvaporativelyCooled. Used to calculate evaporative condenser water use.
basin_heater_capacity
Basin Heater Capacity
number
W/K
200.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the evaporatively cooled condenser is available (field Evaporative Condenser Availability Schedule Name). For this situation, the heater heats the basin water when the outdoor air dry-bulb temperature falls below the setpoint temperature, but only when the condenser fans are off (i.e., no refrigerated case load).
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature at which the basin heater turns on.
Range: ≥ 2
design_evaporative_condenser_water_pump_power
Design Evaporative Condenser Water Pump Power
number or Autocalculate
W
1000.0 Design recirc water pump power for Condenser Type = EvaporativelyCooled. Applicable only for Condenser Type = EvaporativelyCooled.
evaporative_water_supply_tank_name
Evaporative Water Supply Tank Name
reference If blank, water supply is from Mains. Applicable only for Condenser Type = EvaporativelyCooled.
Names a WaterUse:Storage
condenser_air_inlet_node_name
Condenser Air Inlet Node Name
string Applicable only when Heat Rejection Location is Outdoors and Condenser Type is not WaterCooled; otherwise, leave field blank. If field is left blank with Heat Rejection Location = Outdoors, then the model assumes that the Inlet Air conditions are the outdoor air conditions for the current timestep (e.g., no adjustment for height above ground).
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
refrigeration_case_name_or_walkin_name_or_caseandwalkinlist_name
Refrigeration Case Name or WalkIn Name or CaseAndWalkInList Name
reference Enter the name of a Refrigeration:Case or Refrigeration:Walkin or Refrigeration:CaseAndWalkinList object.
Names a Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:CaseAndWalkInList, Refrigeration:WalkIn
heat_rejection_zone_name
Heat Rejection Zone Name
reference This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object. Required only if walk-in[s] are connected to this rack AND the heat rejection location is "Zone"
Names a Zone
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater

Refrigeration:Condenser:AirCooled

from idfpy.models import RefrigerationCondenserAirCooled

Air cooled condenser for a refrigeration system (Refrigeration:System).

Field Type Default Details
name
Name required
string
rated_effective_total_heat_rejection_rate_curve_name
Rated Effective Total Heat Rejection Rate Curve Name
reference Rating as per ARI 460 Be sure the rating corresponds to the correct refrigerant HeatRejection(W)=C1 +C2(Condensing Temp - Entering Air Temp, deg C) Will be adjusted for elevation automatically
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_subcooling_temperature_difference
Rated Subcooling Temperature Difference
number
deltaC
0.0 must correspond to rating given for total heat rejection effect
Range: ≥ 0
condenser_fan_speed_control_type
Condenser Fan Speed Control Type
choice Fixed One of Fixed, FixedLinear, TwoSpeed, VariableSpeed
rated_fan_power
Rated Fan Power
number
W
250.0 Power for condenser fan(s) corresponding to rated total heat rejection effect.
Range: ≥ 0
minimum_fan_air_flow_ratio
Minimum Fan Air Flow Ratio
number
dimensionless
0.2 Minimum air flow fraction through condenser fan
Range: ≥ 0
air_inlet_node_name_or_zone_name
Air Inlet Node Name or Zone Name
string If field is left blank, then the model assumes that the inlet air conditions are the outdoor air conditions for the current timestep (e.g., no adjustment for height above ground). If the condenser rejects heat to a conditioned zone, enter the zone name here.
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
condenser_refrigerant_operating_charge_inventory
Condenser Refrigerant Operating Charge Inventory
number
kg
0.0 optional input
condensate_receiver_refrigerant_inventory
Condensate Receiver Refrigerant Inventory
number
kg
0.0 optional input
condensate_piping_refrigerant_inventory
Condensate Piping Refrigerant Inventory
number
kg
0.0 optional input
Referenced by 3 object types

Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, Refrigeration:System

Refrigeration:Condenser:Cascade

from idfpy.models import RefrigerationCondenserCascade

Cascade condenser for a refrigeration system (Refrigeration:System). The cascade condenser is unlike the other condenser options because it rejects heat to another, higher-temperature, refrigeration system. That is, the cascade condenser acts as a heat rejection object for one system, but acts as a refrigeration load for another system.

Field Type Default Details
name
Name required
string
rated_condensing_temperature
Rated Condensing Temperature required
number
C
This is the condensing temperature for the lower temperature secondary loop
rated_approach_temperature_difference
Rated Approach Temperature Difference
number
deltaC
3.0 This is the difference between the condensing and evaporating temperatures
Range: > 0
rated_effective_total_heat_rejection_rate
Rated Effective Total Heat Rejection Rate required
number
W
used for identification and rough system size error checking
Range: > 0
condensing_temperature_control_type
Condensing Temperature Control Type
choice Fixed Fixed keeps condensing temperature constant Float sets the condensing temperature according to the other loads on the higher temperature system
One of Fixed, Float
condenser_refrigerant_operating_charge_inventory
Condenser Refrigerant Operating Charge Inventory
number
kg
optional input
condensate_receiver_refrigerant_inventory
Condensate Receiver Refrigerant Inventory
number
kg
optional input
condensate_piping_refrigerant_inventory
Condensate Piping Refrigerant Inventory
number
kg
optional input
Referenced by 2 object types

Refrigeration:System, Refrigeration:TransferLoadList

Refrigeration:Condenser:EvaporativeCooled

from idfpy.models import RefrigerationCondenserEvaporativeCooled

Evaporative-cooled condenser for a refrigeration system (Refrigeration:System).

Field Type Default Details
name
Name required
string
rated_effective_total_heat_rejection_rate
Rated Effective Total Heat Rejection Rate required
number
W
Rating as per ARI 490 Be sure the rating corresponds to the correct refrigerant
Range: ≥ 0
rated_subcooling_temperature_difference
Rated Subcooling Temperature Difference
number
deltaC
0.0 must correspond to rating given for total heat rejection effect
Range: ≥ 0
fan_speed_control_type
Fan Speed Control Type
choice Fixed One of Fixed, FixedLinear, TwoSpeed, VariableSpeed
rated_fan_power
Rated Fan Power required
number
W
Power for condenser fan(s) corresponding to rated total heat rejection effect.
Range: ≥ 0
minimum_fan_air_flow_ratio
Minimum Fan Air Flow Ratio
number
dimensionless
0.2 Minimum air flow fraction through condenser fan
Range: ≥ 0
approach_temperature_constant_term
Approach Temperature Constant Term
number
C
6.63 A1 in delta T = A1 + A2(hrcf) + A3/(hrcf) + A4(Twb)
Range: ≥ 0, ≤ 20
approach_temperature_coefficient_2
Approach Temperature Coefficient 2
number
C
0.468 A2 in delta T = A1 + A2(hrcf) +A3/(hrcf) +A4(Twb)
Range: ≥ 0, ≤ 20
approach_temperature_coefficient_3
Approach Temperature Coefficient 3
number
C
17.93 A3 in delta T = A1 + A2(hrcf) +A3/(hrcf) +A4(Twb)
Range: ≥ 0, ≤ 30
approach_temperature_coefficient_4
Approach Temperature Coefficient 4
number
dimensionless
-0.322 A4 in deltaT=A1 + A2(hrcf) +A3/(hrcf) +A4(Twb)
Range: ≥ -20, ≤ 20
minimum_capacity_factor
Minimum Capacity Factor
number
dimensionless
0.5 taken from manufacturer's Heat Rejection Capacity Factor Table
maximum_capacity_factor
Maximum Capacity Factor
number
dimensionless
5.0 taken from manufacturer's Heat Rejection Capacity Factor Table
air_inlet_node_name
Air Inlet Node Name
string If field is left blank, then the model assumes that the inlet air conditions are the outdoor air conditions for the current timestep (e.g., no adjustment for height above ground).
rated_air_flow_rate
Rated Air Flow Rate
number or Autocalculate
m3/s
Autocalculate Used to calculate evaporative condenser water use and fan energy use.
basin_heater_capacity
Basin Heater Capacity
number
W/K
200.0 This field is only used for periods when the evap condenser is available (field Evaporative Condenser Availability Schedule). For this situation, the heater heats the basin water when the outdoor air dry-bulb temperature falls below the set point temperature, but only when the condenser fans are off (i.e., no refrigerated case load).
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 Enter the outdoor dry-bulb temperature at which the basin heater turns on.
Range: ≥ 2
rated_water_pump_power
Rated Water Pump Power
number or Autocalculate
W
1000.0 Design recirculating water pump power.
evaporative_water_supply_tank_name
Evaporative Water Supply Tank Name
reference If blank, water supply is from Mains.
Names a WaterUse:Storage
evaporative_condenser_availability_schedule_name
Evaporative Condenser Availability Schedule Name
reference Schedule values greater than 0 indicate that evaporative cooling of the condenser is available. This schedule allows the user to define seasonal shutdown/draining of the water cooling system in cold climate applications. For periods with schedule values of 0, the condenser operates as Air Cooled.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
condenser_refrigerant_operating_charge_inventory
Condenser Refrigerant Operating Charge Inventory
number
kg
0.0 optional input
condensate_receiver_refrigerant_inventory
Condensate Receiver Refrigerant Inventory
number
kg
0.0 optional input
condensate_piping_refrigerant_inventory
Condensate Piping Refrigerant Inventory
number
kg
0.0 optional input
Referenced by 3 object types

Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, Refrigeration:System

Refrigeration:Condenser:WaterCooled

from idfpy.models import RefrigerationCondenserWaterCooled

Water cooled condenser for a refrigeration system (Refrigeration:System).

Field Type Default Details
name
Name required
string
rated_effective_total_heat_rejection_rate
Rated Effective Total Heat Rejection Rate
number
W
Rating as per ARI 450 Be sure the rating corresponds to the correct refrigerant not used in calculations, only for identification and output
Range: > 0
rated_condensing_temperature
Rated Condensing Temperature required
number
C
must correspond to rating given for total heat rejection effect
Range: > 0
rated_subcooling_temperature_difference
Rated Subcooling Temperature Difference
number
deltaC
0.0 must correspond to rating given for total heat rejection effect
Range: ≥ 0
rated_water_inlet_temperature
Rated Water Inlet Temperature required
number
C
must correspond to rating given for total heat rejection effect
Range: > 0
water_inlet_node_name
Water Inlet Node Name
string
water_outlet_node_name
Water Outlet Node Name
string
water_cooled_loop_flow_type
Water-Cooled Loop Flow Type
choice VariableFlow One of ConstantFlow, VariableFlow
water_outlet_temperature_schedule_name
Water Outlet Temperature Schedule Name
reference Applicable only when loop flow type is Variable Flow.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
water_design_flow_rate
Water Design Flow Rate
number
m3/s
note required units must be converted from L/s as specified in ARI 450-2007 Applicable only when loop flow type is Constant Flow.
Range: > 0
water_maximum_flow_rate
Water Maximum Flow Rate
number
m3/s
Range: > 0
water_maximum_water_outlet_temperature
Water Maximum Water Outlet Temperature
number
C
55.0 Range: ≥ 10, ≤ 60
water_minimum_water_inlet_temperature
Water Minimum Water Inlet Temperature
number
C
10.0 related to the minimum allowed refrigeration system condensing temperature
Range: ≥ 10, ≤ 30
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
condenser_refrigerant_operating_charge_inventory
Condenser Refrigerant Operating Charge Inventory
number
kg
optional input
condensate_receiver_refrigerant_inventory
Condensate Receiver Refrigerant Inventory
number
kg
optional input
condensate_piping_refrigerant_inventory
Condensate Piping Refrigerant Inventory
number
kg
optional input
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, Coil:Heating:Desuperheater, Coil:WaterHeating:Desuperheater, Refrigeration:System

Refrigeration:GasCooler:AirCooled

from idfpy.models import RefrigerationGasCoolerAirCooled

The transcritical refrigeration system requires a single gas cooler to reject the system heat.

Field Type Default Details
name
Name required
string
rated_total_heat_rejection_rate_curve_name
Rated Total Heat Rejection Rate Curve Name required
reference Be sure the rating corresponds to the correct refrigerant (R744) HeatRejection(W)=C1 +C2(Gas Cooler Outlet Temp - Entering Air Temp, deg C) Will be adjusted for elevation automatically
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
gas_cooler_fan_speed_control_type
Gas Cooler Fan Speed Control Type
choice Fixed One of Fixed, FixedLinear, TwoSpeed, VariableSpeed
rated_fan_power
Rated Fan Power
number
W
5000.0 Power for gas cooler fan(s) corresponding to rated total heat rejection effect.
Range: ≥ 0
minimum_fan_air_flow_ratio
Minimum Fan Air Flow Ratio
number
dimensionless
0.2 Minimum air flow fraction through gas cooler fan
Range: ≥ 0
transition_temperature
Transition Temperature
number
C
27.0 Temperature at which system transitions between subcritical and transcritical operation.
transcritical_approach_temperature
Transcritical Approach Temperature
number
deltaC
3.0 Temperature difference between the CO2 exiting the gas cooler and the air entering the gas cooler during transcritical operation.
subcritical_temperature_difference
Subcritical Temperature Difference
number
deltaC
10.0 Temperature difference between the saturated condensing temperature and the air temperature during subcritical operation.
minimum_condensing_temperature
Minimum Condensing Temperature
number
C
10.0 Minimum saturated condensing temperature during subcritical operation.
air_inlet_node_name
Air Inlet Node Name
string If field is left blank, then the model assumes that the inlet air conditions are the outdoor air conditions for the current timestep (e.g., no adjustment for height above ground).
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
gas_cooler_refrigerant_operating_charge_inventory
Gas Cooler Refrigerant Operating Charge Inventory
number
kg
0.0 optional input
gas_cooler_receiver_refrigerant_inventory
Gas Cooler Receiver Refrigerant Inventory
number
kg
0.0 optional input
gas_cooler_outlet_piping_refrigerant_inventory
Gas Cooler Outlet Piping Refrigerant Inventory
number
kg
0.0 optional input
Referenced by 1 object types

Refrigeration:TranscriticalSystem

Refrigeration:SecondarySystem

from idfpy.models import RefrigerationSecondarySystem

Works in conjunction with refrigerated cases and walkins to simulate the performance of a secondary loop supermarket refrigeration system. Heat from the refrigeration loads served by the secondary loop is absorbed by a primary refrigeration system (Refrigeration:System). The SecondarySystem object simulates a heat exchanger that is an evaporator, or refrigeration load, on the primary refrigeration system.

Field Type Default Details
name
Name required
string
refrigerated_case_or_walkin_or_caseandwalkinlist_name
Refrigerated Case or Walkin or CaseAndWalkInList Name required
reference Enter the name of a Refrigeration:Case or Refrigeration:WalkIn object. If there is more than one refrigerated case or walk-in served by this secondary system, enter the name of a Refrigeration:CaseAndWalkInList object.
Names a Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:CaseAndWalkInList, Refrigeration:WalkIn
circulating_fluid_type
Circulating Fluid Type required
choice If "FluidAlwaysLiquid" is selected, the fluid properties must be input using the objects: FluidProperties:Name, FluidProperties:GlycolConcentration, and, if user defined fluid type, FluidProperties:Temperatures and FluidProperties:Concentration. Many sets of fluid properties can be found in GlycolPropertiesRefData.idf. If "FluidPhaseChange" is selected, the refrigerant properties must be input using the objects: (if user defined fluid type): FluidProperties:Name, FluidProperties:Temperatures, FluidProperties:Saturated, and FluidProperties:Superheated. Many sets of refrigerant data can be found in FluidPropertiesRefData.idf.
One of FluidAlwaysLiquid, FluidPhaseChange
circulating_fluid_name
Circulating Fluid Name required
reference This must correspond to a name in the FluidProperties:Name object.
Names a FluidProperties:GlycolConcentration, FluidProperties:Name
evaporator_capacity
Evaporator Capacity
number
W
For "FluidAlwaysLiquid", at least one of the two, Evaporator Capacity OR Evaporator Flow Rate for Secondary Fluid, is required. For "FluidPhaseChange", the default capacity is the sum of the rated capacities of the Cases and Walk-ins served by the secondary loop.
Range: ≥ 0
evaporator_flow_rate_for_secondary_fluid
Evaporator Flow Rate for Secondary Fluid
number
m3/s
For "FluidAlwaysLiquid", at least one of the two, Evaporator Capacity OR Evaporator Flow Rate for Secondary Fluid, is required. For "FluidPhaseChange" loops, this input is not used. (see PhaseChange Circulating Rate)
Range: ≥ 0
evaporator_evaporating_temperature
Evaporator Evaporating Temperature required
number
C
This is the evaporating temperature in the heat exchanger used to chill or condense the secondary loop circulating fluid. It is NOT the temperature in any cases or walk-ins served by the secondary loop.
evaporator_approach_temperature_difference
Evaporator Approach Temperature Difference required
number
deltaC
For "FluidAlwaysLiquid", this is the rated difference between the temperature of the circulating fluid leaving the heat exchanger and the heat exchanger's rated evaporating temperature. For "FluidPhaseChange", this is the difference between the temperature of the evaporating and condensing temperatures in the heat exchanger.
evaporator_range_temperature_difference
Evaporator Range Temperature Difference
number
deltaC
For "FluidAlwaysLiquid", this is the rated difference between the temperature of the circulating fluid entering the heat exchanger and the temperature of the circulating fluid leaving the heat exchanger, and is Required. For "FluidPhaseChange", this input is not used.
number_of_pumps_in_loop
Number of Pumps in Loop
integer 1
total_pump_flow_rate
Total Pump Flow Rate
number
m3/s
For "FluidAlwaysLiquid",if not input, Evaporator Flow Rate for Secondary Fluid will be used. For "FluidPhaseChange", if not input, this will be calculated using the PhaseChange Circulating Rate.
Range: ≥ 0
total_pump_power
Total Pump Power
number
W
Either the Total Pump Power or the Total Pump Head is required.
Range: ≥ 0
total_pump_head
Total Pump Head
number
Pa
Either the Total Pump Power or the Total Pump Head is required.
Range: ≥ 0
phasechange_circulating_rate
PhaseChange Circulating Rate
number
dimensionless
2.5 This is the total mass flow at the pump divided by the gaseous mass flow leaving the refrigeration load.
Range: ≥ 1
pump_drive_type
Pump Drive Type
choice Constant One of Constant, Variable
variable_speed_pump_cubic_curve_name
Variable Speed Pump Cubic Curve Name
reference Variable Speed Pump Curve Name is applicable to variable speed pumps only.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
pump_motor_heat_to_fluid
Pump Motor Heat to Fluid
number
dimensionless
0.85 This is the portion of the pump motor heat added to secondary circulating fluid and is equal to the motor efficiency for non-hermetic motor. Enter 1.0 for a semi-hermetic motor.
Range: ≥ 0.5, ≤ 1
sum_ua_distribution_piping
Sum UA Distribution Piping
number
W/K
0.0 Use only if you want to include distribution piping heat gain in refrigeration load.
distribution_piping_zone_name
Distribution Piping Zone Name
reference This will be used to determine the temperature used for distribution piping heat gain. The pipe heat gains are also counted as cooling credit for the zone. Required only if Sum UA Distribution Piping >0.0
Names a Zone
sum_ua_receiver_separator_shell
Sum UA Receiver/Separator Shell
number
W/K
0.0 Use only if you want to include Receiver/Separator Shell heat gain in refrigeration load.
receiver_separator_zone_name
Receiver/Separator Zone Name
reference This will be used to determine the temperature used for Receiver/Separator Shell heat gain. The shell heat gains are also counted as cooling credit for the zone. Required only if Sum UA Receiver/Separator Shell >0.0
Names a Zone
evaporator_refrigerant_inventory
Evaporator Refrigerant Inventory
number
kg
0.0 This value refers to the refrigerant circulating within the primary system providing cooling to the chiller for the secondary loop, not to the fluid circulating within the secondary loop itself.
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 2 object types

Refrigeration:System, Refrigeration:TransferLoadList

Refrigeration:Subcooler

from idfpy.models import RefrigerationSubcooler

Two types of subcoolers are modeled by the detailed refrigeration system. The liquid suction heat exchanger uses cool suction gas to subcool the hot condensate after it leaves the condenser and before it reaches the thermal expansion valve. A mechanical subcooler is used to transfer cooling capacity from one refrigeration system to another.

Field Type Default Details
name
Name required
string
subcooler_type
Subcooler Type
choice LiquidSuction plan to add ambient subcoolers at future time
One of LiquidSuction, Mechanical
liquid_suction_design_subcooling_temperature_difference
Liquid Suction Design Subcooling Temperature Difference
number
deltaC
Applicable only and required for liquid suction heat exchangers design liquid suction subcooling
design_liquid_inlet_temperature
Design Liquid Inlet Temperature
number
C
design inlet temperature on liquid side Applicable only and required for liquid suction heat exchangers (LSHX)
design_vapor_inlet_temperature
Design Vapor Inlet Temperature
number
C
design inlet temperature on vapor side Applicable only and required for liquid suction heat exchangers (LSHX) Design vapor inlet temperature must be less than or equal to the Liquid inlet design temp
capacity_providing_system
Capacity-Providing System
reference Name of the Detailed Refrigeration System providing cooling capacity Applicable only and required for mechanical subcoolers
Names a Refrigeration:System, Refrigeration:TranscriticalSystem
outlet_control_temperature
Outlet Control Temperature
number
C
Control Temperature Out for subcooled liquid Applicable only and required for mechanical subcoolers
Referenced by 1 object types

Refrigeration:System

Refrigeration:System

from idfpy.models import RefrigerationSystem

Simulates the performance of a supermarket refrigeration system when used along with other objects to define the refrigeration load(s), the compressor(s), and the condenser.

Field Type Default Details
name
Name required
string
refrigerated_case_or_walkin_or_caseandwalkinlist_name
Refrigerated Case or Walkin or CaseAndWalkInList Name
reference Enter the name of a Refrigeration:Case or Refrigeration:WalkIn object. If there is more than one refrigerated case or walk-in served by this system, enter the name of a Refrigeration:CaseAndWalkInList object. Only cases and walkins served directly by the system should be included in this list. Any cases served indirectly via a secondary chiller should NOT be included in this list
Names a Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:CaseAndWalkInList, Refrigeration:WalkIn
refrigeration_transfer_load_or_transferload_list_name
Refrigeration Transfer Load or TransferLoad List Name
reference Enter the name of a Refrigeration:SecondarySystem object OR a Refrigeration:Condenser:Cascade object OR, a Refrigeration:TransferLoadList object. A transfer load is identified as one which moves the load from one system to another. So if you have more than one such load (including cascade condensers and secondary loops) served by the same system, use a TransferLoadList object.
Names a Refrigeration:Condenser:Cascade, Refrigeration:SecondarySystem, Refrigeration:TransferLoadList
refrigeration_condenser_name
Refrigeration Condenser Name required
reference Names a Refrigeration:Condenser:AirCooled, Refrigeration:Condenser:Cascade, Refrigeration:Condenser:EvaporativeCooled, Refrigeration:Condenser:WaterCooled
compressor_or_compressorlist_name
Compressor or CompressorList Name required
reference Names a Refrigeration:Compressor, Refrigeration:CompressorList
minimum_condensing_temperature
Minimum Condensing Temperature required
number
C
related to the proper operation of the thermal expansion valves and compressors
refrigeration_system_working_fluid_type
Refrigeration System Working Fluid Type required
reference Fluid property data for the refrigerant must be entered. The fluid property data, including the objects: FluidProperties:Name, FluidProperties:Temperatures, FluidProperties:Saturated and FluidProperties:Superheated can be copied from the FluidPropertiesRefData.idf dataset
Names a FluidProperties:Name
suction_temperature_control_type
Suction Temperature Control Type
choice ConstantSuctionTemperature One of ConstantSuctionTemperature, FloatSuctionTemperature
mechanical_subcooler_name
Mechanical Subcooler Name
reference Optional Field Recipient of refrigeration capacity, that is receives cool liquid from another refrigeration system to help meet aggregate case loads
Names a Refrigeration:Subcooler
liquid_suction_heat_exchanger_subcooler_name
Liquid Suction Heat Exchanger Subcooler Name
reference Optional Field Liquid Suction Heat Exchanger Name, or leave blank
Names a Refrigeration:Subcooler
sum_ua_suction_piping
Sum UA Suction Piping
number
W/K
0.0 Use only if you want to include suction piping heat gain in refrigeration load
suction_piping_zone_name
Suction Piping Zone Name
reference This will be used to determine the temperature used for distribution piping heat gain and the pipe heat gains as cooling credit for the zone. Required only if Sum UA Distribution Piping >0.0
Names a Zone
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
number_of_compressor_stages
Number of Compressor Stages
1 or 2 1.0
intercooler_type
Intercooler Type
choice None One of Flash Intercooler, None, Shell-and-Coil Intercooler
shell_and_coil_intercooler_effectiveness
Shell-and-Coil Intercooler Effectiveness
number 0.8
high_stage_compressor_or_compressorlist_name
High-Stage Compressor or CompressorList Name
reference Names a Refrigeration:Compressor, Refrigeration:CompressorList
Referenced by 1 object types

Refrigeration:Subcooler

Refrigeration:TranscriticalSystem

from idfpy.models import RefrigerationTranscriticalSystem

Detailed transcritical carbon dioxide (CO2) booster refrigeration systems used in supermarkets. The object allows for modeling either a single stage system with medium-temperature loads or a two stage system with both medium- and low-temperature loads.

Field Type Default Details
name
Name required
string
system_type
System Type required
choice One of SingleStage, TwoStage
medium_temperature_refrigerated_case_or_walkin_or_caseandwalkinlist_name
Medium Temperature Refrigerated Case or Walkin or CaseAndWalkInList Name required
reference Enter the name of a Refrigeration:Case or Refrigeration:WalkIn object. If there is more than one refrigerated case or walk-in served by this system, enter the name of a Refrigeration:CaseAndWalkInList object. Only medium temperature cases and walk-ins served directly by the system should be included in this list.
Names a Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:CaseAndWalkInList, Refrigeration:WalkIn
low_temperature_refrigerated_case_or_walkin_or_caseandwalkinlist_name
Low Temperature Refrigerated Case or Walkin or CaseAndWalkInList Name
reference Enter the name of a Refrigeration:Case or Refrigeration:WalkIn object. If there is more than one refrigerated case or walk-in served by this system, enter the name of a Refrigeration:CaseAndWalkInList object. Only low temperature cases and walkins served directly by the system should be included in this list.
Names a Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:CaseAndWalkInList, Refrigeration:WalkIn
refrigeration_gas_cooler_name
Refrigeration Gas Cooler Name required
reference Names a Refrigeration:GasCooler:AirCooled
high_pressure_compressor_or_compressorlist_name
High Pressure Compressor or CompressorList Name required
reference Names a Refrigeration:Compressor, Refrigeration:CompressorList
low_pressure_compressor_or_compressorlist_name
Low Pressure Compressor or CompressorList Name
reference Names a Refrigeration:Compressor, Refrigeration:CompressorList
receiver_pressure
Receiver Pressure
number
Pa
4000000.0
subcooler_effectiveness
Subcooler Effectiveness
number 0.4
refrigeration_system_working_fluid_type
Refrigeration System Working Fluid Type required
reference Fluid property data for the refrigerant must be entered. The fluid property data, including the objects: FluidProperties:Name, FluidProperties:Temperatures, FluidProperties:Saturated and FluidProperties:Superheated can be copied from the FluidPropertiesRefData.idf dataset
Names a FluidProperties:Name
sum_ua_suction_piping_for_medium_temperature_loads
Sum UA Suction Piping for Medium Temperature Loads
number
W/K
0.0 Use only if you want to include suction piping heat gain in refrigeration load
medium_temperature_suction_piping_zone_name
Medium Temperature Suction Piping Zone Name
reference This will be used to determine the temperature used for distribution piping heat gain and the pipe heat gains as cooling credit for the zone. Required only if Sum UA Distribution Piping for Medium Temperature Loads > 0.0
Names a Zone
sum_ua_suction_piping_for_low_temperature_loads
Sum UA Suction Piping for Low Temperature Loads
number
W/K
0.0 Use only if you want to include suction piping heat gain in refrigeration load
low_temperature_suction_piping_zone_name
Low Temperature Suction Piping Zone Name
reference This will be used to determine the temperature used for distribution piping heat gain and the pipe heat gains as cooling credit for the zone. Required only if Sum UA Distribution Piping for Low Temperature Loads > 0.0
Names a Zone
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 1 object types

Refrigeration:Subcooler

Refrigeration:TransferLoadList

from idfpy.models import RefrigerationTransferLoadList extensible

A refrigeration system may provide cooling to other, secondary, systems through either a secondary loop or a cascade condenser. If multiple transfer loads are served by a single primary system, use this list to group them together for reference by the primary system (see the field "Refrigeration Transfer Load or TransferLoad List Name" in the Refrigeration:System object).

Field Type Default Details
name
Name required
string
transfer_loads list Each item: cascade_condenser_name_or_secondary_system_name
Referenced by 1 object types

Refrigeration:System

Refrigeration:WalkIn

from idfpy.models import RefrigerationWalkIn extensible

Works in conjunction with a compressor rack, a refrigeration system, or a refrigeration secondary system to simulate the performance of a walk-in cooler. The walk-in cooler model uses information at rated conditions along with input descriptions for heat transfer surfaces facing multiple zones to determine performance.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_coil_cooling_capacity
Rated Coil Cooling Capacity required
number
W
operating_temperature
Operating Temperature required
number
C
Range: < 20
rated_cooling_source_temperature
Rated Cooling Source Temperature required
number
C
If DXEvaporator, use evaporating temperature (saturated suction temperature) If BrineCoil, use Brine entering temperature used to set minimum suction pressure for DX systems and minimum brine temp for secondary systems
Range: ≥ -70, ≤ 40
rated_total_heating_power
Rated Total Heating Power required
number
W
Include total for all anti-sweat, door, drip-pan, and floor heater power Do not include defrost heater power
heating_power_schedule_name
Heating Power Schedule Name
reference Values will be used to multiply the total heating power Values in the schedule should be between 0.0 and 1.0 For example, this could be used if display door antisweat heaters are turned off at night Defaults to always on if schedule name left blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_cooling_coil_fan_power
Rated Cooling Coil Fan Power
number
W
375.0 Range: ≥ 0
rated_circulation_fan_power
Rated Circulation Fan Power
number
W
0.0 Range: ≥ 0
rated_total_lighting_power
Rated Total Lighting Power required
number
W
Enter the total (display + task) installed lighting power.
lighting_schedule_name
Lighting Schedule Name
reference The schedule should contain values between 0 and 1 Defaults to always on if schedule name left blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_type
Defrost Type
choice Electric HotFluid includes either hot gas defrost for a DX system or Hot Brine defrost if this walk in is cooled by brine from a secondary chiller
One of Electric, HotFluid, None, OffCycle
defrost_control_type
Defrost Control Type
choice TimeSchedule One of TemperatureTermination, TimeSchedule
defrost_schedule_name
Defrost Schedule Name required
reference The schedule values should be 0 (off) or 1 (on)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_drip_down_schedule_name
Defrost Drip-Down Schedule Name
reference The schedule values should be 0 (off) or 1 (on) The start time for each defrost period in this drip-down schedule should coincide with the start time for each defrost period in the defrost schedule (previous input field). The length of each defrost drip-down period must be greater than or equal to the corresponding defrost period specified in the defrost schedule. This extra time allows the melted frost to drip from the coil before refrigeration is restarted.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
defrost_power
Defrost Power
number
W
needed for all defrost types except none and offcycle
Range: ≥ 0
temperature_termination_defrost_fraction_to_ice
Temperature Termination Defrost Fraction to Ice
number
dimensionless
This is the portion of the defrost energy that is available to melt frost Needed only for defrost control type TemperatureTermination defaults to 0.7 for electric defrost and to 0.3 for hot fluid defrost
Range: > 0, ≤ 1
restocking_schedule_name
Restocking Schedule Name
reference Schedule values should be in units of Watts Leave this field blank if no restocking is to be modeled
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
average_refrigerant_charge_inventory
Average Refrigerant Charge Inventory
number
kg
0.0 This value is only used if the Cooling Source Type is DXEvaporator
insulated_floor_surface_area
Insulated Floor Surface Area required
number
m2
floor area of walk-in cooler
Range: > 0
insulated_floor_u_value
Insulated Floor U-Value
number
W/m2-K
0.3154 The default value corresponds to R18 [ft2-F-hr/Btu] To convert other IP R-values to U, divide 5.678 by the R-value Some examples: R15 is U 0.3785 W/m2-K R5 is U 1.136 W/m2-K
Range: > 0
zone_data list Each item: zone_name, total_insulated_surface_area_facing_zone (m2), insulated_surface_u_value_facing_zone (W/m2-K), area_of_glass_reach_in_doors_facing_zone (m2), height_of_glass_reach_in_doors_facing_zone (m), glass_reach_in_door_u_value_facing_zone (W/m2-K), glass_reach_in_door_opening_schedule_name_facing_zone, area_of_stocking_doors_facing_zone (m2), height_of_stocking_doors_facing_zone (m), stocking_door_u_value_facing_zone (W/m2-K), stocking_door_opening_schedule_name_facing_zone, stocking_door_opening_protection_type_facing_zone
Referenced by 5 object types

Refrigeration:CaseAndWalkInList, Refrigeration:CompressorRack, Refrigeration:SecondarySystem, Refrigeration:System, Refrigeration:TranscriticalSystem

ZoneHVAC:RefrigerationChillerSet

from idfpy.models import ZoneHVACRefrigerationChillerSet extensible

Works in conjunction with one or multiple air chillers, compressor racks, refrigeration systems, or refrigeration secondary system objects to simulate the performance of a group of air chillers cooling a single zone. The chiller set model passes information about the zone conditions to determine the performance of individual chiller coils within the set, thus providing the sensible and latent heat exchange with the zone environment.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_name
Zone Name
reference This must be a controlled zone and appear in a ZoneHVAC:EquipmentConnections object.
Names a Zone
air_inlet_node_name
Air Inlet Node Name
string Not used - reserved for future use Name of the zone exhaust node (see Node) from which the refrigeration chiller draws its indoor air. This should be one of the zone exhaust nodes for the zone cooled by the chiller set.
air_outlet_node_name
Air Outlet Node Name
string Not used - reserved for future use The name of the node where the chiller coil sends its outlet air, which must be one of the inlet air nodes for the zone which is being cooled.
chillers list Each item: air_chiller_name
Referenced by 2 object types

SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList