Simulation Parameters

16 object types from idfpy.models.simulation · EnergyPlus 26.2

Object Summary
Building Describes parameters that are used during the simulation of the building.
ConvergenceLimits Specifies limits on HVAC system simulation timesteps and iterations.
HVACSystemRootFindingAlgorithm Specifies a HVAC system solver algorithm to find a root
HeatBalanceAlgorithm Determines which Heat Balance Algorithm will be used ie.
HeatBalanceSettings:ConductionFiniteDifference Determines settings for the Conduction Finite Difference algorithm for surface heat transfer modeling.
PerformancePrecisionTradeoffs This object enables users to choose certain options that speed up EnergyPlus simulation, but may lead to …
ShadowCalculation This object is used to control details of the solar, shading, and daylighting models
SimulationControl Note that the following 3 fields are related to the Sizing:Zone, Sizing:System, and Sizing:Plant objects.
SurfaceConvectionAlgorithm:Inside Default indoor surface heat transfer convection algorithm to be used for all zones
SurfaceConvectionAlgorithm:Outside Default outside surface heat transfer convection algorithm to be used for all zones
Timestep Specifies the "basic" timestep for the simulation.
Version Specifies the EnergyPlus version of the IDF file.
ZoneAirContaminantBalance Determines which contaminant concentration will be simulates.
ZoneAirHeatBalanceAlgorithm Controls the zone/space air heat balance.
ZoneAirMassFlowConservation Enforces the zone air mass flow balance by either adjusting zone mixing object flow only, adjusting zone …
ZoneCapacitanceMultiplier:ResearchSpecial Multiplier altering the relative capacitance of the air compared to an empty zone

Building

from idfpy.models import Building unique

Describes parameters that are used during the simulation of the building. There are necessary correlations between the entries for this object and some entries in the Site:WeatherStation and Site:HeightVariation objects, specifically the Terrain field.

Field Type Default Details
name
Name
string NONE
north_axis
North Axis
number
deg
0.0 degrees from true North
terrain
Terrain
choice Suburbs Country=FlatOpenCountry | Suburbs=CountryTownsSuburbs | City=CityCenter | Ocean=body of water (5km) | Urban=Urban-Industrial-Forest
One of City, Country, Ocean, Suburbs, Urban
loads_convergence_tolerance_value
Loads Convergence Tolerance Value
number
W
0.04 Loads Convergence Tolerance Value is a change in load from one warmup day to the next
Range: > 0, ≤ 0.5
temperature_convergence_tolerance_value
Temperature Convergence Tolerance Value
number
deltaC
0.4 Range: > 0, ≤ 0.5
solar_distribution
Solar Distribution
choice FullExterior MinimalShadowing | FullExterior | FullInteriorAndExterior | FullExteriorWithReflections | FullInteriorAndExteriorWithReflections
One of FullExterior, FullExteriorWithReflections, FullInteriorAndExterior, FullInteriorAndExteriorWithReflections, MinimalShadowing
maximum_number_of_warmup_days
Maximum Number of Warmup Days
integer 25 EnergyPlus will only use as many warmup days as needed to reach convergence tolerance. This field's value should NOT be set less than 25.
Range: > 0
minimum_number_of_warmup_days
Minimum Number of Warmup Days
integer 1 The minimum number of warmup days that produce enough temperature and flux history to start EnergyPlus simulation for all reference buildings was suggested to be 6. However this can lead to excessive run times as warmup days can be repeated needlessly. For faster execution rely on the convergence criteria to detect when warmup is complete. When this field is greater than the maximum warmup days defined previous field the maximum number of warmup days will be reset to the minimum value entered here. Warmup days will be set to be the value you entered. The default is 1.
Range: > 0
construction_assignment_set_name
Construction Assignment Set Name
reference Optional. Provides inherited construction assignments for surfaces and sub-surfaces in the building. Assignments referenced by Space take precedence over assignments referenced by Building.
Names a ConstructionAssignmentSet

ConvergenceLimits

from idfpy.models import ConvergenceLimits unique

Specifies limits on HVAC system simulation timesteps and iterations. This item is an advanced feature that should be used only with caution.

Field Type Default Details
minimum_system_timestep
Minimum System Timestep
integer
minutes
0 sets the minimum to the zone timestep (ref: Timestep) 1 is normal (ratchet down to 1 minute) setting greater than zone timestep (in minutes) will effectively set to zone timestep
Range: ≥ 0, ≤ 60
maximum_hvac_iterations
Maximum HVAC Iterations
integer 20 Range: ≥ 1
minimum_plant_iterations
Minimum Plant Iterations
integer 2 Controls the minimum number of plant system solver iterations within a single HVAC iteration Larger values will increase runtime but might improve solution accuracy for complicated plant systems Complex plants include: several interconnected loops, heat recovery, thermal load following generators, etc.
Range: ≥ 1
maximum_plant_iterations
Maximum Plant Iterations
integer 8 Controls the maximum number of plant system solver iterations within a single HVAC iteration Smaller values might decrease runtime but could decrease solution accuracy for complicated plant systems
Range: ≥ 2

HVACSystemRootFindingAlgorithm

from idfpy.models import HVACSystemRootFindingAlgorithm unique

Specifies a HVAC system solver algorithm to find a root

Field Type Default Details
algorithm
Algorithm
choice RegulaFalsi One of Alternation, Bisection, BisectionThenRegulaFalsi, RegulaFalsi, RegulaFalsiThenBisection
number_of_iterations_before_algorithm_switch
Number of Iterations Before Algorithm Switch
integer 5 This field is used when RegulaFalsiThenBisection or BisectionThenRegulaFalsi is entered. When iteration number is greater than the value, algorithm switches.

HeatBalanceAlgorithm

from idfpy.models import HeatBalanceAlgorithm unique

Determines which Heat Balance Algorithm will be used ie. CTF (Conduction Transfer Functions), EMPD (Effective Moisture Penetration Depth with Conduction Transfer Functions). Advanced/Research Usage: CondFD (Conduction Finite Difference) Advanced/Research Usage: ConductionFiniteDifferenceSimplified Advanced/Research Usage: HAMT (Combined Heat And Moisture Finite Element)

Field Type Default Details
algorithm
Algorithm
choice ConductionTransferFunction One of CombinedHeatAndMoistureFiniteElement, ConductionFiniteDifference, ConductionTransferFunction, MoisturePenetrationDepthConductionTransferFunction
surface_temperature_upper_limit
Surface Temperature Upper Limit
number
C
200.0 Range: ≥ 200
minimum_surface_convection_heat_transfer_coefficient_value
Minimum Surface Convection Heat Transfer Coefficient Value
number
W/m2-K
0.1 Range: > 0
maximum_surface_convection_heat_transfer_coefficient_value
Maximum Surface Convection Heat Transfer Coefficient Value
number
W/m2-K
1000.0 Range: ≥ 1

HeatBalanceSettings:ConductionFiniteDifference

from idfpy.models import HeatBalanceSettingsConductionFiniteDifference unique

Determines settings for the Conduction Finite Difference algorithm for surface heat transfer modeling.

Field Type Default Details
difference_scheme
Difference Scheme
choice FullyImplicitFirstOrder One of CrankNicholsonSecondOrder, FullyImplicitFirstOrder
space_discretization_constant
Space Discretization Constant
number 3.0 increase or decrease number of nodes
relaxation_factor
Relaxation Factor
number 1.0 Range: ≥ 0.01, ≤ 1
inside_face_surface_temperature_convergence_criteria
Inside Face Surface Temperature Convergence Criteria
number 0.002 Range: ≥ 1e-07, ≤ 0.01

PerformancePrecisionTradeoffs

from idfpy.models import PerformancePrecisionTradeoffs unique

This object enables users to choose certain options that speed up EnergyPlus simulation, but may lead to small decreases in accuracy of results.

Field Type Default Details
use_coil_direct_solutions
Use Coil Direct Solutions
choice No If Yes, an analytical or empirical solution will be used to replace iterations in the coil performance calculations.
One of No, Yes
zone_radiant_exchange_algorithm
Zone Radiant Exchange Algorithm
choice ScriptF Determines which algorithm will be used to solve long wave radiant exchange among surfaces within a zone.
One of CarrollMRT, ScriptF
override_mode
Override Mode
choice Normal The increasing mode number roughly correspond with increased speed. A description of each mode are shown in the documentation. When Advanced is selected the N1 field value is used.
One of Advanced, Mode01, Mode02, Mode03, Mode04, Mode05, Mode06, Mode07, Mode08, Normal
maxzonetempdiff
MaxZoneTempDiff
number 0.3 Maximum zone temperature change before HVAC timestep is shortened. Only used when Override Mode is set to Advanced
Range: ≥ 0.1, ≤ 3
maxalloweddeltemp
MaxAllowedDelTemp
number 0.002 Maximum surface temperature change before HVAC timestep is shortened. Only used when Override Mode is set to Advanced
Range: ≥ 0.002, ≤ 0.1
use_representative_surfaces_for_calculations
Use Representative Surfaces for Calculations
choice No Automatically group surfaces with similar characteristics and perform relevant calculations only once for each group.
One of No, Yes

ShadowCalculation

from idfpy.models import ShadowCalculation unique extensible

This object is used to control details of the solar, shading, and daylighting models

Field Type Default Details
shading_calculation_method
Shading Calculation Method
choice PolygonClipping Select between CPU-based polygon clipping method, the GPU-based pixel counting method, or importing from external shading data. If PixelCounting is selected and GPU hardware (or GPU emulation) is not available, a warning will be displayed and EnergyPlus will revert to PolygonClipping. If Scheduled is chosen, the Sunlit Fraction Schedule Name is required in SurfaceProperty:LocalEnvironment. If Imported is chosen, the Schedule:File:Shading object is required.
One of Imported, PixelCounting, PolygonClipping, Scheduled
shading_calculation_update_frequency_method
Shading Calculation Update Frequency Method
choice Periodic choose calculation frequency method. note that Timestep is only needed for certain cases and can increase execution time significantly.
One of Periodic, Timestep
shading_calculation_update_frequency
Shading Calculation Update Frequency
integer 20 enter number of days this field is only used if the previous field is set to Periodic warning issued if >31
Range: ≥ 1
maximum_figures_in_shadow_overlap_calculations
Maximum Figures in Shadow Overlap Calculations
integer 15000 Number of allowable figures in shadow overlap in PolygonClipping calculations
Range: ≥ 200
polygon_clipping_algorithm
Polygon Clipping Algorithm
choice SutherlandHodgman Advanced Feature. Internal default is SutherlandHodgman Refer to InputOutput Reference and Engineering Reference for more information
One of ConvexWeilerAtherton, SlaterBarskyandSutherlandHodgman, SutherlandHodgman
pixel_counting_resolution
Pixel Counting Resolution
integer 512 Number of pixels in both dimensions of the surface rendering
sky_diffuse_modeling_algorithm
Sky Diffuse Modeling Algorithm
choice SimpleSkyDiffuseModeling Advanced Feature. Internal default is SimpleSkyDiffuseModeling If you have shading elements that change transmittance over the year, you may wish to choose the detailed method. Refer to InputOutput Reference and Engineering Reference for more information
One of DetailedSkyDiffuseModeling, SimpleSkyDiffuseModeling
output_external_shading_calculation_results
Output External Shading Calculation Results
choice No If Yes is chosen, the calculated external shading fraction results will be saved to an external CSV file with surface names as the column headers.
One of No, Yes
disable_self_shading_within_shading_zone_groups
Disable Self-Shading Within Shading Zone Groups
choice No If Yes, self-shading will be disabled from all exterior surfaces in a given Shading Zone Group to surfaces within the same Shading Zone Group. If both Disable Self-Shading Within Shading Zone Groups and Disable Self-Shading From Shading Zone Groups to Other Zones = Yes, then all self-shading from exterior surfaces will be disabled. If only one of these fields = Yes, then at least one Shading Zone Group must be specified, or this field will be ignored. Shading from Shading:* surfaces, overhangs, fins, and reveals will not be disabled.
One of No, Yes
disable_self_shading_from_shading_zone_groups_to_other_zones
Disable Self-Shading From Shading Zone Groups to Other Zones
choice No If Yes, self-shading will be disabled from all exterior surfaces in a given Shading Zone Group to all other zones in the model. If both Disable Self-Shading Within Shading Zone Groups and Disable Self-Shading From Shading Zone Groups to Other Zones = Yes, then all self-shading from exterior surfaces will be disabled. If only one of these fields = Yes, then at least one Shading Zone Group must be specified, or this field will be ignored. Shading from Shading:* surfaces, overhangs, fins, and reveals will not be disabled.
One of No, Yes
shading_zone_groups list Each item: shading_zone_group_zonelist_name

SimulationControl

from idfpy.models import SimulationControl unique

Note that the following 3 fields are related to the Sizing:Zone, Sizing:System, and Sizing:Plant objects. Having these fields set to Yes but no corresponding Sizing object will not cause the sizing to be done. However, having any of these fields set to No, the corresponding Sizing object is ignored. Note also, if you want to do system sizing, you must also do zone sizing in the same run or an error will result.

Field Type Default Details
do_zone_sizing_calculation
Do Zone Sizing Calculation
choice No If Yes, Zone sizing is accomplished from corresponding Sizing:Zone objects and autosize fields.
One of No, Yes
do_system_sizing_calculation
Do System Sizing Calculation
choice No If Yes, System sizing is accomplished from corresponding Sizing:System objects and autosize fields. If Yes, Zone sizing (previous field) must also be Yes.
One of No, Yes
do_plant_sizing_calculation
Do Plant Sizing Calculation
choice No If Yes, Plant sizing is accomplished from corresponding Sizing:Plant objects and autosize fields.
One of No, Yes
run_simulation_for_sizing_periods
Run Simulation for Sizing Periods
choice Yes If Yes, SizingPeriod:* objects are executed and results from those may be displayed..
One of No, Yes
run_simulation_for_weather_file_run_periods
Run Simulation for Weather File Run Periods
choice Yes If Yes, RunPeriod:* objects are executed and results from those may be displayed..
One of No, Yes
do_hvac_sizing_simulation_for_sizing_periods
Do HVAC Sizing Simulation for Sizing Periods
choice No If Yes, SizingPeriod:* objects are executed additional times for advanced sizing. Currently limited to use with coincident plant sizing, see Sizing:Plant object
One of No, Yes
maximum_number_of_hvac_sizing_simulation_passes
Maximum Number of HVAC Sizing Simulation Passes
integer 1 the entire set of SizingPeriod:* objects may be repeated to fine tune size results this input sets a limit on the number of passes that the sizing algorithms can repeat the set
Range: ≥ 1

SurfaceConvectionAlgorithm:Inside

from idfpy.models import SurfaceConvectionAlgorithmInside unique

Default indoor surface heat transfer convection algorithm to be used for all zones

Field Type Default Details
algorithm
Algorithm
choice TARP Simple = constant value natural convection (ASHRAE) TARP = variable natural convection based on temperature difference (ASHRAE, Walton) CeilingDiffuser = ACH-based forced and mixed convection correlations for ceiling diffuser configuration with simple natural convection limit AdaptiveConvectionAlgorithm = dynamic selection of convection models based on conditions ASTMC1340 = mixed convection correlations based on heat flow direction, surface tilt angle, surface characteristic length, and air speed past the surface.
One of ASTMC1340, AdaptiveConvectionAlgorithm, CeilingDiffuser, Simple, TARP

SurfaceConvectionAlgorithm:Outside

from idfpy.models import SurfaceConvectionAlgorithmOutside unique

Default outside surface heat transfer convection algorithm to be used for all zones

Field Type Default Details
algorithm
Algorithm
choice DOE-2 SimpleCombined = Combined radiation and convection coefficient using simple ASHRAE model TARP = correlation from models developed by ASHRAE, Walton, and Sparrow et. al. MoWiTT = correlation from measurements by Klems and Yazdanian for smooth surfaces DOE-2 = correlation from measurements by Klems and Yazdanian for rough surfaces AdaptiveConvectionAlgorithm = dynamic selection of correlations based on conditions
One of AdaptiveConvectionAlgorithm, DOE-2, MoWiTT, SimpleCombined, TARP

Timestep

from idfpy.models import Timestep unique

Specifies the "basic" timestep for the simulation. The value entered here is also known as the Zone Timestep. This is used in the Zone Heat Balance Model calculation as the driving timestep for heat transfer and load calculations.

Field Type Default Details
number_of_timesteps_per_hour
Number of Timesteps per Hour
integer 6 Number in hour: normal validity 4 to 60: 6 suggested Must be evenly divisible into 60 Allowable values include 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 Normal 6 is minimum as lower values may cause inaccuracies A minimum value of 20 is suggested for both ConductionFiniteDifference and CombinedHeatAndMoistureFiniteElement surface heat balance algorithms A minimum of 12 is suggested for simulations involving a Vegetated Roof (Material:RoofVegetation).
Range: ≥ 1, ≤ 60

Version

from idfpy.models import Version unique

Specifies the EnergyPlus version of the IDF file.

Field Type Default Details
version_identifier
Version Identifier
string 26.2

ZoneAirContaminantBalance

from idfpy.models import ZoneAirContaminantBalance unique

Determines which contaminant concentration will be simulates.

Field Type Default Details
carbon_dioxide_concentration
Carbon Dioxide Concentration
choice No If Yes, CO2 simulation will be performed.
One of No, Yes
outdoor_carbon_dioxide_schedule_name
Outdoor Carbon Dioxide Schedule Name
reference Schedule values should be in parts per million (ppm)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
generic_contaminant_concentration
Generic Contaminant Concentration
choice No If Yes, generic contaminant simulation will be performed.
One of No, Yes
outdoor_generic_contaminant_schedule_name
Outdoor Generic Contaminant Schedule Name
reference Schedule values should be generic contaminant concentration in parts per million (ppm)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

ZoneAirHeatBalanceAlgorithm

from idfpy.models import ZoneAirHeatBalanceAlgorithm unique

Controls the zone/space air heat balance.

Field Type Default Details
algorithm
Algorithm
choice ThirdOrderBackwardDifference Determines which algorithm will be used to solve the air heat balance.
One of AnalyticalSolution, EulerMethod, ThirdOrderBackwardDifference
do_space_heat_balance_for_sizing
Do Space Heat Balance for Sizing
choice No If yes, space heat balance will be calculated and reported during sizing.
One of No, Yes
do_space_heat_balance_for_simulation
Do Space Heat Balance for Simulation
choice No If yes, space heat balance will be calculated and reported during simulation.
One of No, Yes

ZoneAirMassFlowConservation

from idfpy.models import ZoneAirMassFlowConservation unique

Enforces the zone air mass flow balance by either adjusting zone mixing object flow only, adjusting zone total return flow only, zone mixing and the zone total return flows, or adjusting the zone total return and zone mixing object flows. Zone infiltration flow air flow is increased or decreased depending user selection in the infiltration treatment method. If either of zone mixing or zone return flow adjusting methods or infiltration is active, then the zone air mass flow balance calculation will attempt to enforce conservation of mass for each zone. If flow balancing method is "None" and infiltration is "None", then the zone air mass flow calculation defaults to assume self-balanced simple flow mixing and infiltration objects.

Field Type Default Details
adjust_zone_mixing_and_return_for_air_mass_flow_balance
Adjust Zone Mixing and Return For Air Mass Flow Balance
choice None If "AdjustMixingOnly", zone mixing object flow rates are adjusted to balance the zone air mass flow and zone infiltration air flow may be increased or decreased if required in order to balance the zone air mass flow. If "AdjustReturnOnly", zone total return flow rate is adjusted to balance the zone air mass flow and zone infiltration air flow may be increased or decreased if required in order to balance the zone air mass flow. If "AdjustMixingThenReturn", first the zone mixing objects flow rates are adjusted to balance the zone air flow, second zone total return flow rate is adjusted and zone infiltration air flow may be increased or decreased if required in order to balance the zone air mass flow. If "AdjustReturnThenMixing", first zone total return flow rate is adjusted to balance the zone air flow, second the zone mixing object flow rates are adjusted and infiltration air flow may be increased or decreased if required in order to balance the zone air mass flow.
One of AdjustMixingOnly, AdjustMixingThenReturn, AdjustReturnOnly, AdjustReturnThenMixing, None
infiltration_balancing_method
Infiltration Balancing Method
choice AddInfiltrationFlow This input field allows user to choose how zone infiltration flow is treated during the zone air mass flow balance calculation. AddInfiltrationFlow may add infiltration to the base flow specified in the infiltration object to balance the zone air mass flow. The additional infiltration air mass flow is not self-balanced. The base flow is assumed to be self-balanced. AdjustInfiltrationFlow may adjust the base flow calculated using the base flow specified in the infiltration object to balance the zone air mass flow. If it If no adjustment is required, then the base infiltration is assumed to be self-balanced. None will make no changes to the base infiltration flow.
One of AddInfiltrationFlow, AdjustInfiltrationFlow, None
infiltration_balancing_zones
Infiltration Balancing Zones
choice MixingSourceZonesOnly This input field allows user to choose which zones are included in infiltration balancing. MixingSourceZonesOnly allows infiltration balancing only in zones which as source zones for mixing which also have an infiltration object defined. AllZones allows infiltration balancing in any zone which has an infiltration object defined.
One of AllZones, MixingSourceZonesOnly

ZoneCapacitanceMultiplier:ResearchSpecial

from idfpy.models import ZoneCapacitanceMultiplierResearchSpecial

Multiplier altering the relative capacitance of the air compared to an empty zone

Field Type Default Details
name
Name required
string
zone_or_zonelist_name
Zone or ZoneList Name
reference If this field is left blank, the multipliers are applied to all the zones not specified
Names a Zone, ZoneList
temperature_capacity_multiplier
Temperature Capacity Multiplier
number 1.0 Used to alter the capacitance of zone air with respect to heat or temperature
Range: > 0
humidity_capacity_multiplier
Humidity Capacity Multiplier
number 1.0 Used to alter the capacitance of zone air with respect to moisture or humidity ratio
Range: > 0
carbon_dioxide_capacity_multiplier
Carbon Dioxide Capacity Multiplier
number 1.0 Used to alter the capacitance of zone air with respect to zone air carbon dioxide concentration
Range: > 0
generic_contaminant_capacity_multiplier
Generic Contaminant Capacity Multiplier
number 1.0 Used to alter the capacitance of zone air with respect to zone air generic contaminant concentration
Range: > 0