Operational Faults¶
16 object types from idfpy.models.faults · EnergyPlus 26.2
| Object | Summary |
|---|---|
| FaultModel:EnthalpySensorOffset:OutdoorAir | This object describes outdoor air enthalpy sensor offset |
| FaultModel:EnthalpySensorOffset:ReturnAir | This object describes return air enthalpy sensor offset |
| FaultModel:Fouling:AirFilter | This object describes fault of dirty air filters |
| FaultModel:Fouling:Boiler | This object describes the fouling fault of boilers with water-based heat exchangers |
| FaultModel:Fouling:Chiller | This object describes the fouling fault of chillers with water-cooled condensers |
| FaultModel:Fouling:Coil | This object describes fouling water heating or cooling coils |
| FaultModel:Fouling:CoolingTower | This object describes the fault of fouling cooling towers |
| FaultModel:Fouling:EvaporativeCooler | This object describes the fouling fault of the wetted coil evaporative cooler |
| FaultModel:HumidistatOffset | This object describes fault of humidistat offset |
| FaultModel:HumiditySensorOffset:OutdoorAir | This object describes outdoor air humidity sensor offset |
| FaultModel:TemperatureSensorOffset:ChillerSupplyWater | This object describes fault of chiller supply water temperature sensor offset |
| FaultModel:TemperatureSensorOffset:CoilSupplyAir | This object describes fault of coil supply air temperature sensor offset |
| FaultModel:TemperatureSensorOffset:CondenserSupplyWater | This object describes fault of condenser supply water temperature sensor offset |
| FaultModel:TemperatureSensorOffset:OutdoorAir | This object describes outdoor air temperature sensor offset |
| FaultModel:TemperatureSensorOffset:ReturnAir | This object describes return air temperature sensor offset |
| FaultModel:ThermostatOffset | This object describes fault of thermostat offset |
FaultModel:EnthalpySensorOffset:OutdoorAir¶
from idfpy.models import FaultModelEnthalpySensorOffsetOutdoorAir
This object describes outdoor air enthalpy sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
controller_Controller Object Type required |
choice | One of Controller:OutdoorAir |
|
controller_Controller Object Name required |
reference | Names a Controller:OutdoorAir | |
enthalpy_Enthalpy Sensor Offset |
number J/kg |
0.0 |
Range: > -20000, < 20000 |
FaultModel:EnthalpySensorOffset:ReturnAir¶
from idfpy.models import FaultModelEnthalpySensorOffsetReturnAir
This object describes return air enthalpy sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
controller_Controller Object Type required |
choice | One of Controller:OutdoorAir |
|
controller_Controller Object Name required |
reference | Names a Controller:OutdoorAir | |
enthalpy_Enthalpy Sensor Offset |
number J/kg |
0.0 |
Range: > -20000, < 20000 |
FaultModel:Fouling:AirFilter¶
from idfpy.models import FaultModelFoulingAirFilter
This object describes fault of dirty air filters
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
fan_Fan Object Type required |
choice | Choose the type of the fan Support for Fan:SystemModel is pending One of Fan:ConstantVolume, Fan:OnOff, Fan:VariableVolume |
|
fan_Fan Name required |
reference | Enter the name of a fan object Names a Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel, Fan:VariableVolume |
|
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
pressure_Pressure Fraction Schedule Name required |
reference | Enter the name of a schedule describing the variations of the fan pressure rise in terms of multipliers to the fan design pressure rise Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
fan_Fan Curve Name required |
reference | The curve describes the relationship between the fan pressure rise and air flow rate Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more |
FaultModel:Fouling:Boiler¶
from idfpy.models import FaultModelFoulingBoiler
This object describes the fouling fault of boilers with water-based heat exchangers
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
boiler_Boiler Object Type required |
choice | Enter the type of a boiler object The fault applies to the hot-water boilers One of Boiler:HotWater |
|
boiler_Boiler Object Name required |
reference | Enter the name of a Boiler object Names a Boiler:HotWater |
|
fouling_Fouling Factor |
number dimensionless |
1.0 |
The factor indicates the decrease of the nominal capacity of the boiler It is the ratio between the nominal capacity at fouling case and that at fault free case Range: > 0, ≤ 1 |
FaultModel:Fouling:Chiller¶
from idfpy.models import FaultModelFoulingChiller
This object describes the fouling fault of chillers with water-cooled condensers
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
chiller_Chiller Object Type required |
choice | Enter the type of a chiller object The fault applies to the chillers with water-cooled condensers One of Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
chiller_Chiller Object Name required |
reference | Enter the name of a chiller object Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
fouling_Fouling Factor |
number dimensionless |
1.0 |
The factor indicates the decrease of the nominal capacity of the chiller It is the ratio between the nominal capacity at fouling case and that at fault free case Range: > 0, ≤ 1 |
FaultModel:Fouling:Coil¶
from idfpy.models import FaultModelFoulingCoil
This object describes fouling water heating or cooling coils
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | ||
coil_Coil Name required |
reference | Names a Coil:Cooling:Water, Coil:Heating:Water | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
fouling_Fouling Input Method |
choice | FouledUARated |
One of FouledUARated, FoulingFactor |
uafouledUAFouled |
number W/K |
Fouling coil UA value under rating conditions For Fouling Input Method: FouledUARated Range: > 0 |
|
water_Water Side Fouling Factor |
number m2-K/W |
0.0 |
For Fouling Input Method: FoulingFactor Range: ≥ 0 |
air_Air Side Fouling Factor |
number m2-K/W |
0.0 |
For Fouling Input Method: FoulingFactor Range: ≥ 0 |
outside_Outside Coil Surface Area |
number m2 |
For Fouling Input Method: FoulingFactor Range: > 0 |
|
inside_Inside to Outside Coil Surface Area Ratio |
number dimensionless |
0.07 |
For Fouling Input Method: FoulingFactor Range: > 0 |
FaultModel:Fouling:CoolingTower¶
from idfpy.models import FaultModelFoulingCoolingTower
This object describes the fault of fouling cooling towers
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
cooling_Cooling Tower Object Type required |
choice | Enter the type of the cooling tower affected One of CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed:MERKEL |
|
cooling_Cooling Tower Object Name required |
reference | Enter the name of the cooling tower affected Names a CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed:Merkel |
|
reference_Reference UA Reduction Factor |
number dimensionless |
Factor describing the tower UA reduction due to fouling It is the ratio between the UA value at fouling case and that at fault free case It is applicable to both the Design UA and Free Convection UA of the tower Range: > 0 |
FaultModel:Fouling:EvaporativeCooler¶
from idfpy.models import FaultModelFoulingEvaporativeCooler
This object describes the fouling fault of the wetted coil evaporative cooler
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
evaporative_Evaporative Cooler Object Type required |
choice | Enter the type of a Evaporative Cooler object The fault applies to the wetted coil evaporative cooler The fault does not apply to direct evaporative coolers or the dry coil indirect evaporative coolers One of EvaporativeCooler:Indirect:WetCoil |
|
evaporative_Evaporative Cooler Object Name required |
reference | Enter the name of aN Evaporative Cooler object Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
fouling_Fouling Factor |
number dimensionless |
1.0 |
The factor indicates the decrease of the indirect stage efficiency It is the ratio between the indirect stage efficiency at fouling case and that at fault free case Range: > 0, ≤ 1 |
FaultModel:HumidistatOffset¶
from idfpy.models import FaultModelHumidistatOffset
This object describes fault of humidistat offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
humidistat_Humidistat Name required |
reference | Enter the name of a ZoneControl:Humidistat object. Names a ZoneControl:Humidistat |
|
humidistat_Humidistat Offset Type |
choice | ThermostatOffsetIndependent |
Two types are available: Type ThermostatOffsetIndependent Type ThermostatOffsetDependent One of ThermostatOffsetDependent, ThermostatOffsetIndependent |
availability_Availability Schedule Name |
reference | This field is applicable for Type ThermostatOffsetIndependent Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
severity_Severity Schedule Name |
reference | This field is applicable for Type ThermostatOffsetIndependent Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules |
|
reference_Reference Humidistat Offset |
number percent |
5.0 |
Required field for Type ThermostatOffsetIndependent Range: > -20, < 20 |
related_Related Thermostat Offset Fault Name |
reference | Enter the name of a FaultModel:ThermostatOffset object Required field for Type ThermostatOffsetDependent Names a FaultModel:ThermostatOffset |
FaultModel:HumiditySensorOffset:OutdoorAir¶
from idfpy.models import FaultModelHumiditySensorOffsetOutdoorAir
This object describes outdoor air humidity sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
controller_Controller Object Type required |
choice | One of Controller:OutdoorAir |
|
controller_Controller Object Name required |
reference | Names a Controller:OutdoorAir | |
humidity_Humidity Sensor Offset |
number kgWater/kgDryAir |
0.0 |
Range: > -0.02, < 0.02 |
FaultModel:TemperatureSensorOffset:ChillerSupplyWater¶
from idfpy.models import FaultModelTemperatureSensorOffsetChillerSupplyWater
This object describes fault of chiller supply water temperature sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
chiller_Chiller Object Type required |
choice | Enter the type of a chiller object One of Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
chiller_Chiller Object Name required |
reference | Enter the name of a chiller object Names a Chiller:Absorption, Chiller:Absorption:Indirect, Chiller:CombustionTurbine, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:ASHRAE205, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven |
|
reference_Reference Sensor Offset |
number deltaC |
0.0 |
Range: > -10, < 10 |
FaultModel:TemperatureSensorOffset:CoilSupplyAir¶
from idfpy.models import FaultModelTemperatureSensorOffsetCoilSupplyAir
This object describes fault of coil supply air temperature sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
coil_Coil Object Type required |
choice | Enter the type of the coil affected One of AirLoopHVAC:UnitarySystem, Coil:Cooling:Water, Coil:Cooling:Water:Detailedgeometry, Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Gas, Coil:Heating:Steam, Coil:Heating:Water, CoilSystem:Cooling:DX, CoilSystem:Heating:DX |
|
coil_Coil Object Name required |
reference | Enter the name of the coil affected Names a AirLoopHVAC:UnitarySystem, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:MultiStage, Coil:Heating:Fuel, Coil:Heating:Gas:MultiStage, Coil:Heating:Steam, Coil:Heating:Water, CoilSystem:Cooling:DX, CoilSystem:Heating:DX and 6 more |
|
water_Water Coil Controller Name |
reference | Enter the name of controller for the water coil affected Required for water coils Names a Controller:WaterCoil |
|
reference_Reference Sensor Offset |
number deltaC |
0.0 |
Range: > -10, < 10 |
FaultModel:TemperatureSensorOffset:CondenserSupplyWater¶
from idfpy.models import FaultModelTemperatureSensorOffsetCondenserSupplyWater
This object describes fault of condenser supply water temperature sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
cooling_Cooling Tower Object Type required |
choice | Enter the type of the cooling tower affected One of CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed, CoolingTower:VariableSpeed:MERKEL |
|
cooling_Cooling Tower Object Name required |
reference | Enter the name of the cooling tower affected Names a CoolingTower:SingleSpeed, CoolingTower:TwoSpeed, CoolingTower:VariableSpeed, CoolingTower:VariableSpeed:Merkel |
|
reference_Reference Sensor Offset |
number deltaC |
0.0 |
Range: > -10, < 10 |
FaultModel:TemperatureSensorOffset:OutdoorAir¶
from idfpy.models import FaultModelTemperatureSensorOffsetOutdoorAir
This object describes outdoor air temperature sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
controller_Controller Object Type required |
choice | One of Controller:OutdoorAir |
|
controller_Controller Object Name required |
reference | Names a Controller:OutdoorAir | |
temperature_Temperature Sensor Offset |
number deltaC |
0.0 |
Range: > -10, < 10 |
FaultModel:TemperatureSensorOffset:ReturnAir¶
from idfpy.models import FaultModelTemperatureSensorOffsetReturnAir
This object describes return air temperature sensor offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
controller_Controller Object Type required |
choice | One of Controller:OutdoorAir |
|
controller_Controller Object Name required |
reference | Names a Controller:OutdoorAir | |
temperature_Temperature Sensor Offset |
number deltaC |
0.0 |
Range: > -10, < 10 |
FaultModel:ThermostatOffset¶
from idfpy.models import FaultModelThermostatOffset
This object describes fault of thermostat offset
| Field | Type | Default | Details |
|---|---|---|---|
nameName required |
string | Enter the name of the fault | |
thermostat_Thermostat Name required |
reference | Enter the name of a ZoneControl:Thermostat object. Names a ZoneControl:Thermostat, ZoneControl:Thermostat:StagedDualSetpoint |
|
availability_Availability Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
severity_Severity Schedule Name |
reference | Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules | |
reference_Reference Thermostat Offset |
number deltaC |
2.0 |
Range: > -10, < 10 |