Water Heaters and Thermal Storage

12 object types from idfpy.models.water_heaters · EnergyPlus 26.2

Object Summary
ThermalStorage:ChilledWater:Mixed Chilled water storage with a well-mixed, single-node tank.
ThermalStorage:ChilledWater:Stratified Chilled water storage with a stratified, multi-node tank.
ThermalStorage:HotWater:Stratified
ThermalStorage:Ice:Detailed This input syntax is intended to describe a thermal storage system that includes smaller containers filled …
ThermalStorage:Ice:Simple This ice storage model is a simplified model It requires a setpoint placed on the Chilled Water Side Outlet …
ThermalStorage:PCM This thermal storage model is PCM-based It requires PCM material property connection In addition to the …
ThermalStorage:Sizing Sizing information for thermal energy stoarge capacity.
WaterHeater:HeatPump:PumpedCondenser This object models an air-source heat pump for water heating where the water is pumped out of the tank, …
WaterHeater:HeatPump:WrappedCondenser This object models an air-source heat pump for water heating where the heating coil is wrapped around the …
WaterHeater:Mixed Water heater with well-mixed, single-node water tank.
WaterHeater:Sizing This input object is used with WaterHeater:Mixed or with WaterHeater:Stratified to autosize tank volume and …
WaterHeater:Stratified Water heater with stratified, multi-node water tank.

ThermalStorage:ChilledWater:Mixed

from idfpy.models import ThermalStorageChilledWaterMixed

Chilled water storage with a well-mixed, single-node tank. The chilled water is "used" by drawing from the "Use Side" of the water tank. The tank is indirectly charged by circulating cold water through the "Source Side" of the water tank.

Field Type Default Details
name
Name required
string
tank_volume
Tank Volume
number
m3
0.1 Range: > 0
setpoint_temperature_schedule_name
Setpoint Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
deadband_temperature_difference
Deadband Temperature Difference
number
deltaC
0.5 Range: > 0
minimum_temperature_limit
Minimum Temperature Limit
number
C
nominal_cooling_capacity
Nominal Cooling Capacity
number
W
ambient_temperature_indicator
Ambient Temperature Indicator required
choice One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required when field Ambient Temperature Indicator=Outdoors
heat_gain_coefficient_from_ambient_temperature
Heat Gain Coefficient from Ambient Temperature
number
W/K
Range: ≥ 0
use_side_inlet_node_name
Use Side Inlet Node Name
string
use_side_outlet_node_name
Use Side Outlet Node Name
string
use_side_heat_transfer_effectiveness
Use Side Heat Transfer Effectiveness
number 1.0 Range: ≥ 0, ≤ 1
use_side_availability_schedule_name
Use Side Availability Schedule Name
reference Availability schedule name for use side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
use_side_design_flow_rate
Use Side Design Flow Rate
number or Autosize
m3/s
Autosize
source_side_inlet_node_name
Source Side Inlet Node Name
string
source_side_outlet_node_name
Source Side Outlet Node Name
string
source_side_heat_transfer_effectiveness
Source Side Heat Transfer Effectiveness
number 1.0 Range: > 0, ≤ 1
source_side_availability_schedule_name
Source Side Availability Schedule Name
reference Availability schedule name for source side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
source_side_design_flow_rate
Source Side Design Flow Rate
number or Autosize
m3/s
Autosize
tank_recovery_time
Tank Recovery Time
number
hr
4.0 Parameter for autosizing design flow rates for indirectly cooled water tanks time required to lower temperature of entire tank from 14.4C to 9.0C
Range: > 0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList, WaterHeater:Sizing

ThermalStorage:ChilledWater:Stratified

from idfpy.models import ThermalStorageChilledWaterStratified

Chilled water storage with a stratified, multi-node tank. The chilled water is "used" by drawing from the "Use Side" of the water tank. The tank is indirectly charged by circulating cold water through the "Source Side" of the water tank.

Field Type Default Details
name
Name required
string
tank_volume
Tank Volume required
number
m3
Range: > 0
tank_height
Tank Height required
number
m
Height is measured in the axial direction for horizontal cylinders
Range: > 0
tank_shape
Tank Shape
choice VerticalCylinder One of HorizontalCylinder, Other, VerticalCylinder
tank_perimeter
Tank Perimeter
number
m
Only used if Tank Shape is Other
Range: ≥ 0
setpoint_temperature_schedule_name
Setpoint Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
deadband_temperature_difference
Deadband Temperature Difference
number
deltaC
0.0001 Range: ≥ 0.0001
temperature_sensor_height
Temperature Sensor Height
number
m
Range: ≥ 0
minimum_temperature_limit
Minimum Temperature Limit
number
C
nominal_cooling_capacity
Nominal Cooling Capacity
number or Autosize
W
Autosize
ambient_temperature_indicator
Ambient Temperature Indicator required
choice One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required for Ambient Temperature Indicator=Outdoors
uniform_skin_loss_coefficient_per_unit_area_to_ambient_temperature
Uniform Skin Loss Coefficient per Unit Area to Ambient Temperature
number
W/m2-K
Range: ≥ 0
use_side_inlet_node_name
Use Side Inlet Node Name
string
use_side_outlet_node_name
Use Side Outlet Node Name
string
use_side_heat_transfer_effectiveness
Use Side Heat Transfer Effectiveness
number 1.0 The use side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of use mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The use side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: ≥ 0, ≤ 1
use_side_availability_schedule_name
Use Side Availability Schedule Name
reference Availability schedule name for use side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
use_side_inlet_height
Use Side Inlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
use_side_outlet_height
Use Side Outlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
use_side_design_flow_rate
Use Side Design Flow Rate
number or Autosize
m3/s
Autosize
source_side_inlet_node_name
Source Side Inlet Node Name
string
source_side_outlet_node_name
Source Side Outlet Node Name
string
source_side_heat_transfer_effectiveness
Source Side Heat Transfer Effectiveness
number 1.0 The source side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of source mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The source side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: > 0, ≤ 1
source_side_availability_schedule_name
Source Side Availability Schedule Name
reference Availability schedule name for use side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
source_side_inlet_height
Source Side Inlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
source_side_outlet_height
Source Side Outlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
source_side_design_flow_rate
Source Side Design Flow Rate
number or Autosize
m3/s
Autosize
tank_recovery_time
Tank Recovery Time
number
hr
4.0 Parameter for autosizing design flow rates for indirectly cooled water tanks time required to lower temperature of entire tank from 14.4C to 9.0C
Range: > 0
inlet_mode
Inlet Mode
choice Fixed One of Fixed, Seeking
number_of_nodes
Number of Nodes
integer 1 Range: ≥ 1, ≤ 10
additional_destratification_conductivity
Additional Destratification Conductivity
number
W/m-K
0.0 Range: ≥ 0
node_1_additional_loss_coefficient
Node 1 Additional Loss Coefficient
number
W/K
0.0
node_2_additional_loss_coefficient
Node 2 Additional Loss Coefficient
number
W/K
0.0
node_3_additional_loss_coefficient
Node 3 Additional Loss Coefficient
number
W/K
0.0
node_4_additional_loss_coefficient
Node 4 Additional Loss Coefficient
number
W/K
0.0
node_5_additional_loss_coefficient
Node 5 Additional Loss Coefficient
number
W/K
0.0
node_6_additional_loss_coefficient
Node 6 Additional Loss Coefficient
number
W/K
0.0
node_7_additional_loss_coefficient
Node 7 Additional Loss Coefficient
number
W/K
0.0
node_8_additional_loss_coefficient
Node 8 Additional Loss Coefficient
number
W/K
0.0
node_9_additional_loss_coefficient
Node 9 Additional Loss Coefficient
number
W/K
0.0
node_10_additional_loss_coefficient
Node 10 Additional Loss Coefficient
number
W/K
0.0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList, WaterHeater:Sizing

ThermalStorage:HotWater:Stratified

from idfpy.models import ThermalStorageHotWaterStratified

Field Type Default Details
name
Name required
string
tank_volume
Tank Volume required
number
m3
Range: > 0
tank_height
Tank Height required
number
m
Height is measured in the axial direction for horizontal cylinders
Range: > 0
tank_shape
Tank Shape
choice VerticalCylinder One of HorizontalCylinder, Other, VerticalCylinder
tank_perimeter
Tank Perimeter
number
m
Only used if Tank Shape is Other
Range: ≥ 0
top_setpoint_temperature_schedule_name
Top Setpoint Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
bottom_setpoint_temperature_schedule_name
Bottom Setpoint Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
deadband_temperature_difference
Deadband Temperature Difference
number
deltaC
0.0001 Range: ≥ 0.0001
top_temperature_sensor_height
Top Temperature Sensor Height
number
m
Range: ≥ 0
bottom_temperature_sensor_height
Bottom Temperature Sensor Height
number
m
Range: ≥ 0
maximum_temperature_limit
Maximum Temperature Limit
number
C
nominal_heating_capacity
Nominal Heating Capacity
number or Autosize
W
Autosize
ambient_temperature_indicator
Ambient Temperature Indicator required
choice One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required for Ambient Temperature Indicator=Outdoors
uniform_skin_loss_coefficient_per_unit_area_to_ambient_temperature
Uniform Skin Loss Coefficient per Unit Area to Ambient Temperature
number
W/m2-K
Range: ≥ 0
use_side_inlet_node_name
Use Side Inlet Node Name
string
use_side_outlet_node_name
Use Side Outlet Node Name
string
use_side_flow_direction_schedule
Use Side Flow Direction Schedule
string allowed value is -1 and 1. When the value is 1, water flows in from the inlet and flows out from the outlet node. When the value is -1, water flows in from the outlet node and flows out from the inlet node (i.e. the flow direction is reversed)
use_side_heat_transfer_effectiveness
Use Side Heat Transfer Effectiveness
number 1.0 The use side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of use mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The use side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: ≥ 0, ≤ 1
use_side_availability_schedule_name
Use Side Availability Schedule Name
reference Availability schedule name for use side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
use_side_inlet_height
Use Side Inlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
use_side_outlet_height
Use Side Outlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
use_side_design_flow_rate
Use Side Design Flow Rate
number or Autosize
m3/s
Autosize
source_side_inlet_node_name
Source Side Inlet Node Name
string
source_side_outlet_node_name
Source Side Outlet Node Name
string
source_side_flow_direction_schedule
Source Side Flow Direction Schedule
string allowed value is -1 and 1. When the value is 1, water flows in from the inlet and flows out from the outlet node. When the value is -1, water flows in from the outlet node and flows out from the inlet node (i.e. the flow direction is reversed)
source_side_heat_transfer_effectiveness
Source Side Heat Transfer Effectiveness
number 1.0 The source side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of source mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The source side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: > 0, ≤ 1
source_side_availability_schedule_name
Source Side Availability Schedule Name
reference Availability schedule name for use side. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
source_side_inlet_height
Source Side Inlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
source_side_outlet_height
Source Side Outlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
source_side_design_flow_rate
Source Side Design Flow Rate
number or Autosize
m3/s
Autosize
tank_recovery_time
Tank Recovery Time
number
hr
4.0 Parameter for autosizing design flow rates for indirectly cooled water tanks time required to lower temperature of entire tank from 14.4C to 9.0C
Range: > 0
inlet_mode
Inlet Mode
choice Fixed One of Fixed, Seeking
number_of_nodes
Number of Nodes
integer 1 Range: ≥ 1, ≤ 10
additional_destratification_conductivity
Additional Destratification Conductivity
number
W/m-K
0.0 Range: ≥ 0
node_1_additional_loss_coefficient
Node 1 Additional Loss Coefficient
number
W/K
0.0
node_2_additional_loss_coefficient
Node 2 Additional Loss Coefficient
number
W/K
0.0
node_3_additional_loss_coefficient
Node 3 Additional Loss Coefficient
number
W/K
0.0
node_4_additional_loss_coefficient
Node 4 Additional Loss Coefficient
number
W/K
0.0
node_5_additional_loss_coefficient
Node 5 Additional Loss Coefficient
number
W/K
0.0
node_6_additional_loss_coefficient
Node 6 Additional Loss Coefficient
number
W/K
0.0
node_7_additional_loss_coefficient
Node 7 Additional Loss Coefficient
number
W/K
0.0
node_8_additional_loss_coefficient
Node 8 Additional Loss Coefficient
number
W/K
0.0
node_9_additional_loss_coefficient
Node 9 Additional Loss Coefficient
number
W/K
0.0
node_10_additional_loss_coefficient
Node 10 Additional Loss Coefficient
number
W/K
0.0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList, WaterHeater:Sizing

ThermalStorage:Ice:Detailed

from idfpy.models import ThermalStorageIceDetailed

This input syntax is intended to describe a thermal storage system that includes smaller containers filled with water that are placed in a larger tank or series of tanks. The model uses polynomial equations to describe the system performance.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
capacity
Capacity required
number or Autosize
GJ
This includes only the latent storage capacity
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
discharging_curve_variable_specifications
Discharging Curve Variable Specifications required
choice One of FractionChargedLMTD, FractionDischargedLMTD, LMTDFractionCharged, LMTDMassFlow
discharging_curve_name
Discharging Curve Name required
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
charging_curve_variable_specifications
Charging Curve Variable Specifications required
choice One of FractionChargedLMTD, FractionDischargedLMTD, LMTDFractionCharged, LMTDMassFlow
charging_curve_name
Charging Curve Name required
reference Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
timestep_of_the_curve_data
Timestep of the Curve Data
number
hr
parasitic_electric_load_during_discharging
Parasitic Electric Load During Discharging
number
dimensionless
parasitic_electric_load_during_charging
Parasitic Electric Load During Charging
number
dimensionless
tank_loss_coefficient
Tank Loss Coefficient
number
dimensionless
This is the fraction the total storage capacity that is lost or melts each hour
freezing_temperature_of_storage_medium
Freezing Temperature of Storage Medium
number
C
0.0 This temperature is typically 0C for water. Simply changing this temperature without adjusting the performance parameters input above is inappropriate and not advised.
thaw_process_indicator
Thaw Process Indicator
choice OutsideMelt This field determines whether the system uses internal or external melt during discharging. This will then have an impact on charging performance.
One of InsideMelt, OutsideMelt
thermal_storage_sizing_object_name
Thermal Storage Sizing Object Name
reference used only when tank capacity is autosized
Names a ThermalStorage:Sizing
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

ThermalStorage:Ice:Simple

from idfpy.models import ThermalStorageIceSimple

This ice storage model is a simplified model It requires a setpoint placed on the Chilled Water Side Outlet Node It should be placed in the chilled water supply side outlet branch followed by a pipe. Use the PlantEquipmentOperation:ComponentSetpoint plant operation scheme.

Field Type Default Details
name
Name required
string
ice_storage_type
Ice Storage Type required
choice IceOnCoilInternal = Ice-on-Coil, internal melt IceOnCoilExternal = Ice-on-Coil, external melt
One of IceOnCoilExternal, IceOnCoilInternal
capacity
Capacity required
number or Autosize
GJ
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
thermal_storage_sizing_object_name
Thermal Storage Sizing Object Name
reference used only when tank capacity is autosized
Names a ThermalStorage:Sizing
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentOperation:ThermalEnergyStorage

ThermalStorage:PCM

from idfpy.models import ThermalStoragePCM

This thermal storage model is PCM-based It requires PCM material property connection In addition to the object linking, this object needs PCM Latent heat storage capacity and Heat Loss Rate This model needs 4 nodes: 2 plant side nodes and 2 use side nodes.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
plant_side_inlet_node_name
Plant Side Inlet Node Name required
string
plant_side_outlet_node_name
Plant Side Outlet Node Name required
string
use_side_inlet_node_name
Use Side Inlet Node Name required
string
use_side_outlet_node_name
Use Side Outlet Node Name required
string
pcm_material_name
PCM Material Name required
reference Names a Material, Material:AirGap, Material:InfraredTransparent, Material:NoMass, Material:RoofVegetation, WindowMaterial:Blind, WindowMaterial:Gas, WindowMaterial:GasMixture, WindowMaterial:Glazing, WindowMaterial:Glazing:RefractionExtinctionMethod, WindowMaterial:GlazingGroup:Thermochromic, WindowMaterial:Screen and 2 more
tank_capacity
Tank Capacity required
number or Autosize
kg
heat_loss_rate
Heat Loss Rate
number
W
0.0
use_side_design_flow_rate
Use Side Design Flow Rate required
number or Autosize
m3/s
plant_side_design_flow_rate
Plant Side Design Flow Rate required
number or Autosize
m3/s
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

ThermalStorage:Sizing

from idfpy.models import ThermalStorageSizing

Sizing information for thermal energy stoarge capacity.

Field Type Default Details
name
Name required
string
on_peak_period_start_time
On Peak Period Start Time required
number
hr
Start time of on peak period in hours
on_peak_period_end_time
On Peak Period End Time required
number
hr
End time of on peak period in hours
sizing_factor
Sizing Factor
number 1.0 Range: > 0
Referenced by 2 object types

ThermalStorage:Ice:Detailed, ThermalStorage:Ice:Simple

WaterHeater:HeatPump:PumpedCondenser

from idfpy.models import WaterHeaterHeatPumpPumpedCondenser

This object models an air-source heat pump for water heating where the water is pumped out of the tank, through a heating coil and returned to the tank. For wrapped condenser HPWHs, see WaterHeater:HeatPump:WrappedCondenser. WaterHeater:HeatPump:PumpedCondenser is a compound object that references other component objects - Coil:WaterHeating:AirToWaterHeatPump:*, Fan:OnOff, WaterHeater:Mixed or WaterHeater:Stratified

Field Type Default Details
name
Name required
string Unique name for this instance of a heat pump water heater.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Schedule values of 0 denote the heat pump compressor is off and the parasitic electric energy is also off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
compressor_setpoint_temperature_schedule_name
Compressor Setpoint Temperature Schedule Name required
reference Defines the cut-out temperature where the heat pump compressor turns off. The heat pump compressor setpoint temperature should always be greater than the water tank's heater (element or burner) setpoint temperature.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dead_band_temperature_difference
Dead Band Temperature Difference
number
deltaC
5.0 Setpoint temperature minus the dead band temperature difference defines the cut-in temperature where the heat pump compressor turns on. The water tank's heater (element or burner) setpoint temperature should always be less than the heat pump compressor cut-in temperature.
Range: > 0, ≤ 20
condenser_water_inlet_node_name
Condenser Water Inlet Node Name required
string Should match the field Source Outlet Node Name in the water heater tank object. Should also match the Condenser Water Inlet Node Name in the associated DX coil object.
condenser_water_outlet_node_name
Condenser Water Outlet Node Name required
string Should match the field Source Inlet Node Name in water heater tank object. Should also match the Condenser Water Outlet Node Name in the associated DX Coil object.
condenser_water_flow_rate
Condenser Water Flow Rate
number or Autocalculate
m3/s
Actual water flow rate through the heat pump's water coil (condenser). If autocalculated, the water flow rate is set equal to 4.487E-8 m3/s/W times the rated heating capacity of the heat pump's DX coil.
evaporator_air_flow_rate
Evaporator Air Flow Rate
number or Autocalculate
m3/s
Actual air flow rate across the heat pump's air coil (evaporator). If autocalculated, the air flow rate is set equal to 5.035E-5 m3/s/W times the rated heating capacity of the heat pump's DX coil.
inlet_air_configuration
Inlet Air Configuration required
choice Defines the configuration of the airflow path through the air coil and fan section.
One of OutdoorAirOnly, Schedule, ZoneAirOnly, ZoneAndOutdoorAir
air_inlet_node_name
Air Inlet Node Name
string Zone air exhaust node name if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Simply a unique Node Name if Inlet Air Configuration is Schedule. Otherwise, leave field blank.
air_outlet_node_name
Air Outlet Node Name
string Zone Air Inlet Node Name if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Simply a unique Node Name if Inlet Air Configuration is Schedule. Otherwise, leave field blank.
outdoor_air_node_name
Outdoor Air Node Name
string Outdoor air node name if inlet air configuration is ZoneAndOutdoorAir or OutdoorAirOnly, otherwise leave field blank.
exhaust_air_node_name
Exhaust Air Node Name
string Simply a unique Node Name if Inlet Air Configuration is ZoneAndOutdoorAir or OutdoorAirOnly, otherwise leave field blank.
inlet_air_temperature_schedule_name
Inlet Air Temperature Schedule Name
reference Used only if Inlet Air Configuration is Schedule, otherwise leave blank. Schedule values should be degrees C.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
inlet_air_humidity_schedule_name
Inlet Air Humidity Schedule Name
reference Used only if Inlet Air Configuration is Schedule, otherwise leave blank. Schedule values are entered as a fraction (e.g. 0.5 is equal to 50%RH)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
inlet_air_zone_name
Inlet Air Zone Name
reference Used only if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Otherwise, leave field blank.
Names a Zone
tank_object_type
Tank Object Type
choice WaterHeater:Mixed Specify the type of water heater tank used by this heat pump water heater.
One of WaterHeater:Mixed, WaterHeater:Stratified
tank_name
Tank Name required
reference Needs to match the name used in the corresponding Water Heater object.
Names a WaterHeater:Mixed, WaterHeater:Stratified
tank_use_side_inlet_node_name
Tank Use Side Inlet Node Name
string Used only when the heat pump water heater is connected to a plant loop, otherwise leave blank. Needs to match the name used in the corresponding Water Heater object when connected to a plant loop.
tank_use_side_outlet_node_name
Tank Use Side Outlet Node Name
string Used only when the heat pump water heater is connected to a plant loop, otherwise leave blank. Needs to match the name used in the corresponding Water Heater object when connected to a plant loop.
dx_coil_object_type
DX Coil Object Type
choice Coil:WaterHeating:AirToWaterHeatPump:Pumped Specify the type of DX coil used by this heat pump water heater. The only valid choice is Coil:WaterHeating:AirToWaterHeatPump:Pumped and Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed, and CoilSystem:IntegratedHeatPump:AirSource
One of Coil:WaterHeating:AirToWaterHeatPump:Pumped, Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed, CoilSystem:IntegratedHeatPump:AirSource
dx_coil_name
DX Coil Name required
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:* object, or CoilSystem:IntegratedHeatPump:AirSource
Names a Coil:WaterHeating:AirToWaterHeatPump:Pumped, Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed, CoilSystem:IntegratedHeatPump:AirSource
minimum_inlet_air_temperature_for_compressor_operation
Minimum Inlet Air Temperature for Compressor Operation
number
C
10.0 Heat pump compressor will not operate when the inlet air dry-bulb temperature is below this value.
maximum_inlet_air_temperature_for_compressor_operation
Maximum Inlet Air Temperature for Compressor Operation
number
C
48.88888888889 Heat pump compressor will not operate when the inlet air dry-bulb temperature is above this value.
Range: ≥ 26, ≤ 94
compressor_location
Compressor Location required
choice If Zone is selected, Inlet Air Configuration must be ZoneAirOnly or ZoneAndOutdoorAir. If Schedule is selected, then you must provide a Compressor Ambient Temperature Schedule Name below.
One of Outdoors, Schedule, Zone
compressor_ambient_temperature_schedule_name
Compressor Ambient Temperature Schedule Name
reference Used only if Compressor Location is Schedule, otherwise leave field blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fan_object_type
Fan Object Type
choice Fan:OnOff Specify the type of fan used by this heat pump water heater. The only valid choices are Fan:SystemModel or Fan:OnOff.
One of Fan:OnOff, Fan:SystemModel
fan_name
Fan Name required
reference Needs to match the name used in the corresponding Fan:SystemModel or Fan:OnOff object.
Names a Fan:OnOff, Fan:SystemModel
fan_placement
Fan Placement
choice DrawThrough BlowThrough means the fan is located before the air coil (upstream). DrawThrough means the fan is located after the air coil (downstream).
One of BlowThrough, DrawThrough
on_cycle_parasitic_electric_load
On Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric power consumed when the heat pump compressor operates. Does not contribute to water heating but can impact the zone air heat balance.
Range: ≥ 0
off_cycle_parasitic_electric_load
Off Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric power consumed when the heat pump compressor is off. Does not contribute to water heating but can impact the zone air heat balance. Off-cycle parasitic power is 0 when the availability schedule is 0.
Range: ≥ 0
parasitic_heat_rejection_location
Parasitic Heat Rejection Location
choice Outdoors This field determines if the parasitic electric load impacts the zone air heat balance. If Zone is selected, Inlet Air Configuration must be ZoneAirOnly or ZoneAndOutdoorAir.
One of Outdoors, Zone
inlet_air_mixer_node_name
Inlet Air Mixer Node Name
string Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank.
outlet_air_splitter_node_name
Outlet Air Splitter Node Name
string Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank.
inlet_air_mixer_schedule_name
Inlet Air Mixer Schedule Name
reference Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank. Schedule values define whether the heat pump draws its inlet air from the zone, outdoors or a combination of zone and outdoor air. A schedule value of 0 denotes inlet air is drawn only from the zone. A schedule value of 1 denotes inlet air is drawn only from outdoors. Schedule values between 0 and 1 denote a mixture of zone and outdoor air proportional to the schedule value (i.e. 0.4 = 40% outdoor air, 60% zone air).
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
tank_element_control_logic
Tank Element Control Logic
choice Simultaneous MutuallyExclusive means that once the tank heating element is active the heat pump is shut down until setpoint is reached. Simultaneous (default) means that both the tank heating element and heat pump are used at the same time recover the tank temperature.
One of MutuallyExclusive, Simultaneous
control_sensor_1_height_in_stratified_tank
Control Sensor 1 Height In Stratified Tank
number
m
Used to indicate height of control sensor for Tank Object Type = WaterHeater:Stratified If left blank, it will default to the height of Heater1
Range: ≥ 0
control_sensor_1_weight
Control Sensor 1 Weight
number
dimensionless
1.0 Weight to give Control Sensor 1 temperature The weight of Control Sensor 2 will be 1 - (wt. of control sensor 1)
Range: ≥ 0, ≤ 1
control_sensor_2_height_in_stratified_tank
Control Sensor 2 Height In Stratified Tank
number
m
Used to indicate height of control sensor for Tank Object Type = WaterHeater:Stratified If left blank, it will default to the height of Heater2
Range: ≥ 0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList, SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList

WaterHeater:HeatPump:WrappedCondenser

from idfpy.models import WaterHeaterHeatPumpWrappedCondenser

This object models an air-source heat pump for water heating where the heating coil is wrapped around the tank, which is typical of residential HPWHs. For pumped condenser HPWHs, see WaterHeater:HeatPump:PumpedCondenser. WaterHeater:HeatPump:WrappedCondenser is a compound object that references other component objects - Coil:WaterHeating:AirToWaterHeatPump:Pumped, Fan:OnOff, WaterHeater:Mixed

Field Type Default Details
name
Name required
string Unique name for this instance of a heat pump water heater.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Schedule values of 0 denote the heat pump compressor is off and the parasitic electric energy is also off.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
compressor_setpoint_temperature_schedule_name
Compressor Setpoint Temperature Schedule Name required
reference Defines the cut-out temperature where the heat pump compressor turns off. The heat pump compressor setpoint temperature should always be greater than the water tank's heater (element or burner) setpoint temperature.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
dead_band_temperature_difference
Dead Band Temperature Difference
number
deltaC
5.0 Setpoint temperature minus the dead band temperature difference defines the cut-in temperature where the heat pump compressor turns on. The water tank's heater (element or burner) setpoint temperature should always be less than the heat pump compressor cut-in temperature.
Range: > 0, ≤ 20
condenser_bottom_location
Condenser Bottom Location
number
m
0.0 Distance from the bottom of the tank to the bottom of the wrapped condenser.
Range: ≥ 0
condenser_top_location
Condenser Top Location required
number
m
Distance from the bottom of the tank to the top of the wrapped condenser.
Range: ≥ 0
evaporator_air_flow_rate
Evaporator Air Flow Rate
number or Autocalculate
m3/s
Actual air flow rate across the heat pump's air coil (evaporator). If autocalculated, the air flow rate is set equal to 5.035E-5 m3/s/W times the rated heating capacity of the heat pump's DX coil.
inlet_air_configuration
Inlet Air Configuration required
choice Defines the configuration of the airflow path through the air coil and fan section.
One of OutdoorAirOnly, Schedule, ZoneAirOnly, ZoneAndOutdoorAir
air_inlet_node_name
Air Inlet Node Name
string Zone air exhaust node name if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Simply a unique Node Name if Inlet Air Configuration is Schedule. Otherwise, leave field blank.
air_outlet_node_name
Air Outlet Node Name
string Zone Air Inlet Node Name if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Simply a unique Node Name if Inlet Air Configuration is Schedule. Otherwise, leave field blank.
outdoor_air_node_name
Outdoor Air Node Name
string Outdoor air node name if inlet air configuration is ZoneAndOutdoorAir or OutdoorAirOnly, otherwise leave field blank.
exhaust_air_node_name
Exhaust Air Node Name
string Simply a unique Node Name if Inlet Air Configuration is ZoneAndOutdoorAir or OutdoorAirOnly, otherwise leave field blank.
inlet_air_temperature_schedule_name
Inlet Air Temperature Schedule Name
reference Used only if Inlet Air Configuration is Schedule, otherwise leave blank. Schedule values should be degrees C.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
inlet_air_humidity_schedule_name
Inlet Air Humidity Schedule Name
reference Used only if Inlet Air Configuration is Schedule, otherwise leave blank. Schedule values are entered as a fraction (e.g. 0.5 is equal to 50%RH)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
inlet_air_zone_name
Inlet Air Zone Name
reference Used only if Inlet Air Configuration is ZoneAirOnly or ZoneAndOutdoorAir. Otherwise, leave field blank.
Names a Zone
tank_object_type
Tank Object Type
choice WaterHeater:Stratified Specify the type of water heater tank used by this heat pump water heater.
One of WaterHeater:Stratified
tank_name
Tank Name required
reference Needs to match the name used in the corresponding Water Heater object. Must be a WaterHeater:Stratified tank.
Names a WaterHeater:Stratified
tank_use_side_inlet_node_name
Tank Use Side Inlet Node Name
string Used only when the heat pump water heater is connected to a plant loop, otherwise leave blank. Needs to match the name used in the corresponding Water Heater object when connected to a plant loop.
tank_use_side_outlet_node_name
Tank Use Side Outlet Node Name
string Used only when the heat pump water heater is connected to a plant loop, otherwise leave blank. Needs to match the name used in the corresponding Water Heater object when connected to a plant loop.
dx_coil_object_type
DX Coil Object Type
choice Coil:WaterHeating:AirToWaterHeatPump:Wrapped Specify the type of DX coil used by this heat pump water heater. The only valid choice is Coil:WaterHeating:AirToWaterHeatPump:Wrapped
One of Coil:WaterHeating:AirToWaterHeatPump:Wrapped
dx_coil_name
DX Coil Name required
reference Must match the name used in the corresponding Coil:WaterHeating:AirToWaterHeatPump:Wrapped object.
Names a Coil:WaterHeating:AirToWaterHeatPump:Wrapped
minimum_inlet_air_temperature_for_compressor_operation
Minimum Inlet Air Temperature for Compressor Operation
number
C
10.0 Heat pump compressor will not operate when the inlet air dry-bulb temperature is below this value.
maximum_inlet_air_temperature_for_compressor_operation
Maximum Inlet Air Temperature for Compressor Operation
number
C
48.88888888889 Heat pump compressor will not operate when the inlet air dry-bulb temperature is above this value.
Range: ≥ 26, ≤ 94
compressor_location
Compressor Location required
choice If Zone is selected, Inlet Air Configuration must be ZoneAirOnly or ZoneAndOutdoorAir. If Schedule is selected, then you must provide a Compressor Ambient Temperature Schedule Name below.
One of Outdoors, Schedule, Zone
compressor_ambient_temperature_schedule_name
Compressor Ambient Temperature Schedule Name
reference Used only if Compressor Location is Schedule, otherwise leave field blank.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fan_object_type
Fan Object Type
choice Fan:OnOff Specify the type of fan used by this heat pump water heater. The only valid choices are Fan:SystemModel or Fan:OnOff.
One of Fan:OnOff, Fan:SystemModel
fan_name
Fan Name required
reference Needs to match the name used in the corresponding Fan:SystemModel or Fan:OnOff object.
Names a Fan:OnOff, Fan:SystemModel
fan_placement
Fan Placement
choice DrawThrough BlowThrough means the fan is located before the air coil (upstream). DrawThrough means the fan is located after the air coil (downstream).
One of BlowThrough, DrawThrough
on_cycle_parasitic_electric_load
On Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric power consumed when the heat pump compressor operates. Does not contribute to water heating but can impact the zone air heat balance.
Range: ≥ 0
off_cycle_parasitic_electric_load
Off Cycle Parasitic Electric Load
number
W
0.0 Parasitic electric power consumed when the heat pump compressor is off. Does not contribute to water heating but can impact the zone air heat balance. Off-cycle parasitic power is 0 when the availability schedule is 0.
Range: ≥ 0
parasitic_heat_rejection_location
Parasitic Heat Rejection Location
choice Outdoors This field determines if the parasitic electric load impacts the zone air heat balance. If Zone is selected, Inlet Air Configuration must be ZoneAirOnly or ZoneAndOutdoorAir.
One of Outdoors, Zone
inlet_air_mixer_node_name
Inlet Air Mixer Node Name
string Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank.
outlet_air_splitter_node_name
Outlet Air Splitter Node Name
string Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank.
inlet_air_mixer_schedule_name
Inlet Air Mixer Schedule Name
reference Required only if Inlet Air Configuration is ZoneAndOutdoorAir, otherwise leave field blank. Schedule values define whether the heat pump draws its inlet air from the zone, outdoors or a combination of zone and outdoor air. A schedule value of 0 denotes inlet air is drawn only from the zone. A schedule value of 1 denotes inlet air is drawn only from outdoors. Schedule values between 0 and 1 denote a mixture of zone and outdoor air proportional to the schedule value.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
tank_element_control_logic
Tank Element Control Logic
choice Simultaneous MutuallyExclusive means that once the tank heating element is active the heat pump is shut down until setpoint is reached. Simultaneous (default) means that both the tank heating element and heat pump are used at the same time recover the tank temperature.
One of MutuallyExclusive, Simultaneous
control_sensor_1_height_in_stratified_tank
Control Sensor 1 Height In Stratified Tank
number
m
Used to indicate height of control sensor if Tank Object Type is WaterHeater:Stratified If left blank, it will default to the height of Heater1
Range: ≥ 0
control_sensor_1_weight
Control Sensor 1 Weight
number
dimensionless
1.0 Weight to give Control Sensor 1 temperature
Range: ≥ 0, ≤ 1
control_sensor_2_height_in_stratified_tank
Control Sensor 2 Height In Stratified Tank
number
m
Used to indicate height of control sensor if Tank Object Type is WaterHeater:Stratified If left blank, it will default to the height of Heater2 The weight of this control sensor will be 1 - (wt. of control sensor 1)
Range: ≥ 0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList, SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList

WaterHeater:Mixed

from idfpy.models import WaterHeaterMixed

Water heater with well-mixed, single-node water tank. May be used to model a tankless water heater (small tank volume), a hot water storage tank (zero heater capacity), or a heat pump water heater (see WaterHeater:HeatPump:PumpedCondenser.)

Field Type Default Details
name
Name required
string
tank_volume
Tank Volume
number or Autosize
m3
0.0
setpoint_temperature_schedule_name
Setpoint Temperature Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
deadband_temperature_difference
Deadband Temperature Difference
number
deltaC
0.0 Range: ≥ 0
maximum_temperature_limit
Maximum Temperature Limit
number
C
heater_control_type
Heater Control Type
choice Cycle One of Cycle, Modulate
heater_maximum_capacity
Heater Maximum Capacity
number or Autosize
W
heater_minimum_capacity
Heater Minimum Capacity
number
W
Only used when Heater Control Type is set to Modulate
Range: ≥ 0
heater_ignition_minimum_flow_rate
Heater Ignition Minimum Flow Rate
number
m3/s
0.0 Not yet implemented
Range: ≥ 0
heater_ignition_delay
Heater Ignition Delay
number
s
0.0 Not yet implemented
Range: ≥ 0
heater_fuel_type
Heater Fuel Type required
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
heater_thermal_efficiency
Heater Thermal Efficiency required
number Range: > 0
part_load_factor_curve_name
Part Load Factor Curve Name
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
off_cycle_parasitic_fuel_consumption_rate
Off Cycle Parasitic Fuel Consumption Rate
number
W
0.0 Range: ≥ 0
off_cycle_parasitic_fuel_type
Off Cycle Parasitic Fuel Type
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
off_cycle_parasitic_heat_fraction_to_tank
Off Cycle Parasitic Heat Fraction to Tank
number 0.0 Range: ≥ 0, ≤ 1
on_cycle_parasitic_fuel_consumption_rate
On Cycle Parasitic Fuel Consumption Rate
number
W
0.0 Range: ≥ 0
on_cycle_parasitic_fuel_type
On Cycle Parasitic Fuel Type
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
on_cycle_parasitic_heat_fraction_to_tank
On Cycle Parasitic Heat Fraction to Tank
number 0.0 Range: ≥ 0, ≤ 1
ambient_temperature_indicator
Ambient Temperature Indicator required
choice One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required for Ambient Temperature Indicator=Outdoors
off_cycle_loss_coefficient_to_ambient_temperature
Off Cycle Loss Coefficient to Ambient Temperature
number
W/K
Range: ≥ 0
off_cycle_loss_fraction_to_zone
Off Cycle Loss Fraction to Zone
number 1.0 Range: ≥ 0, ≤ 1
on_cycle_loss_coefficient_to_ambient_temperature
On Cycle Loss Coefficient to Ambient Temperature
number
W/K
Range: ≥ 0
on_cycle_loss_fraction_to_zone
On Cycle Loss Fraction to Zone
number 1.0 Range: ≥ 0, ≤ 1
peak_use_flow_rate
Peak Use Flow Rate
number
m3/s
Only used if Use Side Node connections are blank
Range: ≥ 0
use_flow_rate_fraction_schedule_name
Use Flow Rate Fraction Schedule Name
reference Only used if Use Side Node connections are blank
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cold_water_supply_temperature_schedule_name
Cold Water Supply Temperature Schedule Name
reference Only used if Use Side Node connections are blank Defaults to water temperatures calculated by Site:WaterMainsTemperature object
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
use_side_inlet_node_name
Use Side Inlet Node Name
string
use_side_outlet_node_name
Use Side Outlet Node Name
string
use_side_effectiveness
Use Side Effectiveness
number 1.0 Range: ≥ 0, ≤ 1
source_side_inlet_node_name
Source Side Inlet Node Name
string
source_side_outlet_node_name
Source Side Outlet Node Name
string
source_side_effectiveness
Source Side Effectiveness
number 1.0 Range: > 0, ≤ 1
use_side_design_flow_rate
Use Side Design Flow Rate
number or Autosize
m3/s
Autosize
source_side_design_flow_rate
Source Side Design Flow Rate
number or Autosize
m3/s
Autosize
indirect_water_heating_recovery_time
Indirect Water Heating Recovery Time
number
hr
1.5 Parameter for autosizing design flow rates for indirectly heated water tanks Time required to raise temperature of entire tank from 14.4C to 57.2C
Range: > 0
source_side_flow_control_mode
Source Side Flow Control Mode
choice IndirectHeatPrimarySetpoint StorageTank mode always requests flow unless tank is at its Maximum Temperature Limit IndirectHeatPrimarySetpoint mode requests flow whenever primary setpoint calls for heat IndirectHeatAlternateSetpoint mode requests flow whenever alternate indirect setpoint calls for heat
One of IndirectHeatAlternateSetpoint, IndirectHeatPrimarySetpoint, StorageTank
indirect_alternate_setpoint_temperature_schedule_name
Indirect Alternate Setpoint Temperature Schedule Name
reference This field is only used if the previous is set to IndirectHeatAlternateSetpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, Coil:WaterHeating:Desuperheater, CondenserEquipmentList, PlantEquipmentList, WaterHeater:HeatPump:PumpedCondenser, WaterHeater:Sizing

WaterHeater:Sizing

from idfpy.models import WaterHeaterSizing

This input object is used with WaterHeater:Mixed or with WaterHeater:Stratified to autosize tank volume and heater capacity This object is not needed if water heaters are not autosized.

Field Type Default Details
waterheater_name
WaterHeater Name required
reference Names a ThermalStorage:ChilledWater:Mixed, ThermalStorage:ChilledWater:Stratified, ThermalStorage:HotWater:Stratified, WaterHeater:Mixed, WaterHeater:Stratified
design_mode
Design Mode
choice One of PeakDraw, PerFloorArea, PerPerson, PerSolarCollectorArea, PerUnit, ResidentialHUD-FHAMinimum
time_storage_can_meet_peak_draw
Time Storage Can Meet Peak Draw
number
hr
Only used for Design Mode = PeakDraw
Range: ≥ 0
time_for_tank_recovery
Time for Tank Recovery
number
hr
Only used for Design Mode = PeakDraw
Range: ≥ 0
nominal_tank_volume_for_autosizing_plant_connections
Nominal Tank Volume for Autosizing Plant Connections
number
m3
Only used if Design Mode = PeakDraw and the water heater also has autosized flow rates for connections on the demand side of a plant loop
number_of_bedrooms
Number of Bedrooms
integer Only used for Design Mode = ResidentialHUD-FHAMinimum
Range: ≥ 1
number_of_bathrooms
Number of Bathrooms
integer Only used for Design Mode = ResidentialHUD-FHAMinimum
Range: ≥ 1
storage_capacity_per_person
Storage Capacity per Person
number
m3/person
Only used for Design Mode = PerPerson
Range: ≥ 0
recovery_capacity_per_person
Recovery Capacity per Person
number
m3/hr-person
Only used for Design Mode = PerPerson
Range: ≥ 0
storage_capacity_per_floor_area
Storage Capacity per Floor Area
number
m3/m2
Only used for Design Mode = PerFloorArea
Range: ≥ 0
recovery_capacity_per_floor_area
Recovery Capacity per Floor Area
number
m3/hr-m2
Only used for Design Mode = PerFloorArea
Range: ≥ 0
number_of_units
Number of Units
number Only used for Design Mode = PerUnit
storage_capacity_per_unit
Storage Capacity per Unit
number
m3
Only used for Design Mode = PerUnit
Range: ≥ 0
recovery_capacity_perunit
Recovery Capacity PerUnit
number
m3/hr
Only used for Design Mode = PerUnit
Range: ≥ 0
storage_capacity_per_collector_area
Storage Capacity per Collector Area
number
m3/m2
Only used for Design Mode = PerSolarCollectorArea
Range: ≥ 0
height_aspect_ratio
Height Aspect Ratio
number only used if for WaterHeater:Stratified
Range: ≥ 0

WaterHeater:Stratified

from idfpy.models import WaterHeaterStratified

Water heater with stratified, multi-node water tank. May be used to model a tankless water heater (small tank volume), a hot water storage tank (zero heater capacity), or a heat pump water heater (see WaterHeater:HeatPump:*.)

Field Type Default Details
name
Name required
string
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
tank_volume
Tank Volume required
number or Autosize
m3
tank_height
Tank Height required
number or Autosize
m
Height is measured in the axial direction for horizontal cylinders
tank_shape
Tank Shape
choice VerticalCylinder One of HorizontalCylinder, Other, VerticalCylinder
tank_perimeter
Tank Perimeter
number
m
Only used if Tank Shape is Other
Range: ≥ 0
maximum_temperature_limit
Maximum Temperature Limit
number
C
heater_priority_control
Heater Priority Control
choice MasterSlave One of MasterSlave, Simultaneous
heater_1_setpoint_temperature_schedule_name
Heater 1 Setpoint Temperature Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heater_1_deadband_temperature_difference
Heater 1 Deadband Temperature Difference
number
deltaC
0.0 Range: ≥ 0
heater_1_capacity
Heater 1 Capacity
number or Autosize
W
heater_1_height
Heater 1 Height
number
m
Range: ≥ 0
heater_2_setpoint_temperature_schedule_name
Heater 2 Setpoint Temperature Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heater_2_deadband_temperature_difference
Heater 2 Deadband Temperature Difference
number
deltaC
0.0 Range: ≥ 0
heater_2_capacity
Heater 2 Capacity
number
W
Range: ≥ 0
heater_2_height
Heater 2 Height
number
m
Range: ≥ 0
heater_fuel_type
Heater Fuel Type required
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
heater_thermal_efficiency
Heater Thermal Efficiency required
number Range: > 0
off_cycle_parasitic_fuel_consumption_rate
Off Cycle Parasitic Fuel Consumption Rate
number
W
0.0 Range: ≥ 0
off_cycle_parasitic_fuel_type
Off Cycle Parasitic Fuel Type
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
off_cycle_parasitic_heat_fraction_to_tank
Off Cycle Parasitic Heat Fraction to Tank
number 0.0 Range: ≥ 0, ≤ 1
off_cycle_parasitic_height
Off Cycle Parasitic Height
number
m
0.0 Range: ≥ 0
on_cycle_parasitic_fuel_consumption_rate
On Cycle Parasitic Fuel Consumption Rate
number
W
0.0 Range: ≥ 0
on_cycle_parasitic_fuel_type
On Cycle Parasitic Fuel Type
choice One of Coal, Diesel, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
on_cycle_parasitic_heat_fraction_to_tank
On Cycle Parasitic Heat Fraction to Tank
number 0.0 Range: ≥ 0, ≤ 1
on_cycle_parasitic_height
On Cycle Parasitic Height
number
m
0.0 Range: ≥ 0
ambient_temperature_indicator
Ambient Temperature Indicator required
choice One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required for Ambient Temperature Indicator=Outdoors
uniform_skin_loss_coefficient_per_unit_area_to_ambient_temperature
Uniform Skin Loss Coefficient per Unit Area to Ambient Temperature
number
W/m2-K
Range: ≥ 0
skin_loss_fraction_to_zone
Skin Loss Fraction to Zone
number 1.0 Range: ≥ 0, ≤ 1
off_cycle_flue_loss_coefficient_to_ambient_temperature
Off Cycle Flue Loss Coefficient to Ambient Temperature
number
W/K
Range: ≥ 0
off_cycle_flue_loss_fraction_to_zone
Off Cycle Flue Loss Fraction to Zone
number 1.0 Range: ≥ 0, ≤ 1
peak_use_flow_rate
Peak Use Flow Rate
number
m3/s
Only used if Use Side Node connections are blank
Range: ≥ 0
use_flow_rate_fraction_schedule_name
Use Flow Rate Fraction Schedule Name
reference If blank, defaults to 1.0 at all times Only used if use side node connections are blank
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cold_water_supply_temperature_schedule_name
Cold Water Supply Temperature Schedule Name
reference Only used if use side node connections are blank Defaults to water temperatures calculated by Site:WaterMainsTemperature object
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
use_side_inlet_node_name
Use Side Inlet Node Name
string
use_side_outlet_node_name
Use Side Outlet Node Name
string
use_side_effectiveness
Use Side Effectiveness
number 1.0 The use side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of use mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The use side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: ≥ 0, ≤ 1
use_side_inlet_height
Use Side Inlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
use_side_outlet_height
Use Side Outlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
source_side_inlet_node_name
Source Side Inlet Node Name
string
source_side_outlet_node_name
Source Side Outlet Node Name
string
source_side_effectiveness
Source Side Effectiveness
number 1.0 The source side effectiveness in the stratified tank model is a simplified analogy of a heat exchanger's effectiveness. This effectiveness is equal to the fraction of source mass flow rate that directly mixes with the tank fluid. And one minus the effectiveness is the fraction that bypasses the tank. The source side mass flow rate that bypasses the tank is mixed with the fluid or water leaving the stratified tank.
Range: > 0, ≤ 1
source_side_inlet_height
Source Side Inlet Height
number or Autocalculate
m
Autocalculate Defaults to top of tank
source_side_outlet_height
Source Side Outlet Height
number
m
0.0 Defaults to bottom of tank
Range: ≥ 0
inlet_mode
Inlet Mode
choice Fixed One of Fixed, Seeking
use_side_design_flow_rate
Use Side Design Flow Rate
number or Autosize
m3/s
Autosize
source_side_design_flow_rate
Source Side Design Flow Rate
number or Autosize
m3/s
Autosize
indirect_water_heating_recovery_time
Indirect Water Heating Recovery Time
number
hr
1.5 Parameter for autosizing design flow rates for indirectly heated water tanks time required to raise temperature of entire tank from 14.4C to 57.2C
Range: > 0
number_of_nodes
Number of Nodes
integer 1 Range: ≥ 1, ≤ 12
additional_destratification_conductivity
Additional Destratification Conductivity
number
W/m-K
0.0 Range: ≥ 0
node_1_additional_loss_coefficient
Node 1 Additional Loss Coefficient
number
W/K
0.0
node_2_additional_loss_coefficient
Node 2 Additional Loss Coefficient
number
W/K
0.0
node_3_additional_loss_coefficient
Node 3 Additional Loss Coefficient
number
W/K
0.0
node_4_additional_loss_coefficient
Node 4 Additional Loss Coefficient
number
W/K
0.0
node_5_additional_loss_coefficient
Node 5 Additional Loss Coefficient
number
W/K
0.0
node_6_additional_loss_coefficient
Node 6 Additional Loss Coefficient
number
W/K
0.0
node_7_additional_loss_coefficient
Node 7 Additional Loss Coefficient
number
W/K
0.0
node_8_additional_loss_coefficient
Node 8 Additional Loss Coefficient
number
W/K
0.0
node_9_additional_loss_coefficient
Node 9 Additional Loss Coefficient
number
W/K
0.0
node_10_additional_loss_coefficient
Node 10 Additional Loss Coefficient
number
W/K
0.0
node_11_additional_loss_coefficient
Node 11 Additional Loss Coefficient
number
W/K
0.0
node_12_additional_loss_coefficient
Node 12 Additional Loss Coefficient
number
W/K
0.0
source_side_flow_control_mode
Source Side Flow Control Mode
choice IndirectHeatPrimarySetpoint StorageTank mode always requests flow unless tank is at its Maximum Temperature Limit IndirectHeatPrimarySetpoint mode requests flow whenever primary setpoint for heater 1 calls for heat IndirectHeatAlternateSetpoint mode requests flow whenever alternate indirect setpoint calls for heat
One of IndirectHeatAlternateSetpoint, IndirectHeatPrimarySetpoint, StorageTank
indirect_alternate_setpoint_temperature_schedule_name
Indirect Alternate Setpoint Temperature Schedule Name
reference This field is only used if the previous is set to IndirectHeatAlternateSetpoint
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, Coil:WaterHeating:Desuperheater, CondenserEquipmentList, PlantEquipmentList, WaterHeater:HeatPump:PumpedCondenser, WaterHeater:HeatPump:WrappedCondenser, WaterHeater:Sizing