HVAC Design Objects

10 object types from idfpy.models.hvac_design · EnergyPlus 26.2

Object Summary
DesignSpecification:AirTerminal:Sizing This object is used to scale the sizing of air terminal units.
DesignSpecification:OutdoorAir This object is used to describe general outdoor air requirements which are referenced by other objects.
DesignSpecification:OutdoorAir:SpaceList Defines a list of DesignSpecification:OutdoorAir names which can be referenced as a group.
DesignSpecification:ZoneAirDistribution This object is used to describe zone air distribution in terms of air distribution effectiveness and …
DesignSpecification:ZoneHVAC:Sizing This object is used to describe general scalable zone HVAC equipment sizing which are referenced by other …
OutputControl:Sizing:Style Default style for the Sizing output files is comma -- this works well for importing into spreadsheet programs …
Sizing:Parameters Specifies global heating and cooling sizing factors/ratios.
Sizing:Plant Specifies the input needed to autosize plant loop flow rates and equipment capacities.
Sizing:System Specifies the input needed to perform sizing calculations for a central forced air system.
Sizing:Zone Specifies the data needed to perform a zone design air flow calculation.

DesignSpecification:AirTerminal:Sizing

from idfpy.models import DesignSpecificationAirTerminalSizing

This object is used to scale the sizing of air terminal units.

Field Type Default Details
name
Name required
string This name may be referenced by a ZoneHVAC:AirDistributionUnit object.
fraction_of_design_cooling_load
Fraction of Design Cooling Load
number
dimensionless
1.0 The fraction of the design sensible cooling load to be met by this terminal unit. This fraction is applied after the Zone Cooling Sizing Factor (see Sizing:Zone).
Range: ≥ 0
cooling_design_supply_air_temperature_difference_ratio
Cooling Design Supply Air Temperature Difference Ratio
number
dimensionless
1.0 This ratio adjusts the supply air temperature difference used to calculate the cooling design supply air flow rate for this terminal unit.
Range: > 0
fraction_of_design_heating_load
Fraction of Design Heating Load
number
dimensionless
1.0 The fraction of the design sensible heating load to be met by this terminal unit. This fraction is applied after the Zone Heating Sizing Factor (see Sizing:Zone).
Range: ≥ 0
heating_design_supply_air_temperature_difference_ratio
Heating Design Supply Air Temperature Difference Ratio
number
dimensionless
1.0 This ratio adjusts the supply air temperature difference used to calculate the heating design supply air flow rate for this terminal unit.
Range: > 0
fraction_of_minimum_outdoor_air_flow
Fraction of Minimum Outdoor Air Flow
number
dimensionless
1.0 The fraction of the zone minimum outdoor air requirement to be met by this terminal unit.
Range: ≥ 0
Referenced by 1 object types

ZoneHVAC:AirDistributionUnit

DesignSpecification:OutdoorAir

from idfpy.models import DesignSpecificationOutdoorAir

This object is used to describe general outdoor air requirements which are referenced by other objects.

Field Type Default Details
name
Name required
string
outdoor_air_method
Outdoor Air Method
choice Flow/Person Flow/Person => Outdoor Air Flow per Person * Occupancy = Design Flow Rate, Flow/Area => Outdoor Air Flow per Zone Floor Area * Zone Floor Area = Design Flow Rate, Flow/Zone => Outdoor Air Flow per Zone = Design Flow Rate, AirChanges/Hour => Outdoor Air Flow Air Changes per Hour * Zone Volume adjusted for m3/s = Design Flow Rate
One of AirChanges/Hour, Flow/Area, Flow/Person, Flow/Zone, IndoorAirQualityProcedure, Maximum, ProportionalControlBasedOnDesignOccupancy, ProportionalControlBasedOnOccupancySchedule, Sum
outdoor_air_flow_per_person
Outdoor Air Flow per Person
number
m3/s-person
0.00944 0.00944 m3/s is equivalent to 20 cfm per person This input is only used if the field Outdoor Air Method is Flow/Person, Sum, or Maximum For sizing, the design number of occupants is used. For outdoor air flow control, the use of design occupants or current occupants depends on the component and DCV options. AirTerminal:SingleDuct:VAV:NoReheat, AirTerminal:SingleDuct:VAV:Reheat use the DCV flag specified in Controller:MechanicalVentilation AirTerminal:DualDuct:VAV:OutdoorAir and ZoneHVAC:IdealLoadsAirSystem have their own DCV control input. ZoneHVAC:FourPipeFanCoil always uses current occupants.
Range: ≥ 0
outdoor_air_flow_per_zone_floor_area
Outdoor Air Flow per Zone Floor Area
number
m3/s-m2
0.0 This input is only used if the field Outdoor Air Method is Flow/Area, Sum, or Maximum
Range: ≥ 0
outdoor_air_flow_per_zone
Outdoor Air Flow per Zone
number
m3/s
0.0 This input is only used if the field Outdoor Air Method is Flow/Zone, Sum, or Maximum
Range: ≥ 0
outdoor_air_flow_air_changes_per_hour
Outdoor Air Flow Air Changes per Hour
number
1/hr
0.0 This input is only used if the field Outdoor Air Method is AirChanges/Hour, Sum, or Maximum
Range: ≥ 0
outdoor_air_schedule_name
Outdoor Air Schedule Name
reference Schedule values are multiplied by the Outdoor Air Flow rate calculated using the previous four inputs. Schedule values are limited to 0 to 1. If left blank, the schedule defaults to 1.0. This schedule is ignored during sizing. All other components which reference this design specification use the current schedule value to calculate the current outdoor air requirement. This includes AirTerminal:SingleDuct:VAV:NoReheat, AirTerminal:SingleDuct:VAV:Reheat, AirTerminal:DualDuct:VAV:OutdoorAir, ZoneHVAC:FourPipeFanCoil, and ZoneHVAC:IdealLoadsAirSystem. This schedule will also be applied by Controller:MechanicalVentilation for all System Outdoor Air Methods.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
proportional_control_minimum_outdoor_air_flow_rate_schedule_name
Proportional Control Minimum Outdoor Air Flow Rate Schedule Name
reference This input is only used to calculate the minimum outdoor air flow rate when the field System Outdoor Air Method = ProportionalControlBasedOnDesignOARate in Controller:MechanicalVentilation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 24 object types

AirTerminal:DualDuct:VAV, AirTerminal:DualDuct:VAV:OutdoorAir, AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:Mixer, AirTerminal:SingleDuct:VAV:NoReheat, AirTerminal:SingleDuct:VAV:Reheat, Controller:MechanicalVentilation, DesignSpecification:OutdoorAir:SpaceList, HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:ConstantVolume, HVACTemplate:Zone:DualDuct, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:IdealLoadsAirSystem, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:Unitary, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump, Sizing:Zone, ZoneHVAC:HybridUnitaryHVAC, ZoneHVAC:IdealLoadsAirSystem

DesignSpecification:OutdoorAir:SpaceList

from idfpy.models import DesignSpecificationOutdoorAirSpaceList extensible

Defines a list of DesignSpecification:OutdoorAir names which can be referenced as a group. The DesignSpecification:OutdoorAir:SpaceList name may be used in Sizing:Zone and Controller:MechanicalVentilation to specify space-by-space OA requirements and anywhere else that accepts a DesignSpecification:OutdoorAir object name.

Field Type Default Details
name
Name required
string Name of the List
space_specs list Each item: space_name, space_design_specification_outdoor_air_object_name
Referenced by 23 object types

AirTerminal:DualDuct:VAV, AirTerminal:DualDuct:VAV:OutdoorAir, AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:Mixer, AirTerminal:SingleDuct:VAV:NoReheat, AirTerminal:SingleDuct:VAV:Reheat, Controller:MechanicalVentilation, HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:ConstantVolume, HVACTemplate:Zone:DualDuct, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:IdealLoadsAirSystem, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:Unitary, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump, Sizing:Zone, ZoneHVAC:HybridUnitaryHVAC, ZoneHVAC:IdealLoadsAirSystem

DesignSpecification:ZoneAirDistribution

from idfpy.models import DesignSpecificationZoneAirDistribution

This object is used to describe zone air distribution in terms of air distribution effectiveness and secondary recirculation fraction. It is referenced by Sizing:Zone and Controller:MechanicalVentilation objects

Field Type Default Details
name
Name required
string
zone_air_distribution_effectiveness_in_cooling_mode
Zone Air Distribution Effectiveness in Cooling Mode
number
dimensionless
1.0 Range: > 0
zone_air_distribution_effectiveness_in_heating_mode
Zone Air Distribution Effectiveness in Heating Mode
number
dimensionless
1.0 Range: > 0
zone_air_distribution_effectiveness_schedule_name
Zone Air Distribution Effectiveness Schedule Name
reference optionally used to replace Zone Air Distribution Effectiveness in Cooling and Heating Mode
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_secondary_recirculation_fraction
Zone Secondary Recirculation Fraction
number
dimensionless
0.0 Range: ≥ 0
minimum_zone_ventilation_efficiency
Minimum Zone Ventilation Efficiency
number
dimensionless
0.0 Range: ≥ 0, ≤ 1
Referenced by 14 object types

Controller:MechanicalVentilation, HVACTemplate:Zone:BaseboardHeat, HVACTemplate:Zone:ConstantVolume, HVACTemplate:Zone:DualDuct, HVACTemplate:Zone:FanCoil, HVACTemplate:Zone:PTAC, HVACTemplate:Zone:PTHP, HVACTemplate:Zone:Unitary, HVACTemplate:Zone:VAV, HVACTemplate:Zone:VAV:FanPowered, HVACTemplate:Zone:VAV:HeatAndCool, HVACTemplate:Zone:VRF, HVACTemplate:Zone:WaterToAirHeatPump, Sizing:Zone

DesignSpecification:ZoneHVAC:Sizing

from idfpy.models import DesignSpecificationZoneHVACSizing

This object is used to describe general scalable zone HVAC equipment sizing which are referenced by other objects.

Field Type Default Details
name
Name required
string
cooling_supply_air_flow_rate_method
Cooling Supply Air Flow Rate Method
choice SupplyAirFlowRate Enter the method used to determine the cooling supply air volume flow rate. None is used when a cooling coil is not included in the Zone HVAC Equip or this field may be blank. SupplyAirFlowRate => selected when the magnitude of the supply air volume flow rate is specified. FlowPerFloorArea => selected when the supply air volume flow rate is determined from total floor area served by the Zone HVAC unit and Flow Per Floor Area value specified. FractionOfAutosizedCoolingAirflow => is selected when the supply air volume is determined from a user specified fraction and the autosized cooling supply air flow rate value determined by the simulation. FlowPerCoolingCapacity => is selected when the supply air volume is determined from user specified flow per Cooling Capacity and Cooling Capacity determined by the simulation.
One of FlowPerCoolingCapacity, FlowPerFloorArea, FractionOfAutosizedCoolingAirflow, None, SupplyAirFlowRate
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of supply air volume flow rate during cooling operation. Required field when Cooling Supply Air Flow Rate Method is SupplyAirFlowRate. This field may be blank if a cooling coil is not included in the Zone HVAC equipment.
cooling_supply_air_flow_rate_per_floor_area
Cooling Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the cooling supply air volume flow rate per total conditioned floor area. Required field when Cooling Supply Air Flow Rate Method is FlowPerFloorArea. This field may be blank if a cooling coil is not included in the Zone HVAC equipment.
Range: ≥ 0
cooling_fraction_of_autosized_cooling_supply_air_flow_rate
Cooling Fraction of Autosized Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when Cooling Supply Air Flow Rate Method is FractionOfAutosizedCoolingAirflow. This field may be blank if a cooling coil is not included in the Zone HVAC equipment.
Range: ≥ 0
cooling_supply_air_flow_rate_per_unit_cooling_capacity
Cooling Supply Air Flow Rate Per Unit Cooling Capacity
number
m3/s-W
Enter the cooling supply air volume flow rate unit cooling capacity. Required field when Cooling Supply Air Flow Rate Method is FlowPerCoolingCapacity. This field may be blank if a cooling coil is not included in the Zone HVAC equipment.
Range: ≥ 0
no_load_supply_air_flow_rate_method
No Load Supply Air Flow Rate Method
choice SupplyAirFlowRate Enter the method used to determine the supply air volume flow rate When No Cooling or Heating is Required. None is used when a cooling or heating coil is not included in the Zone HVAC Equipment or this field may be blank. SupplyAirFlowRate => selected when the magnitude of the supply air volume flow rate is specified. FlowPerFloorArea => selected when the supply air volume flow rate is determined from total floor area served by the Zone HVAC unit and Flow Per Floor Area is specified. FractionOfAutosizedCoolingAirflow => is selected when the supply air volume is determined from a user specified fraction and the Autosized cooling supply air flow rate value determined by the simulation. FractionOfAutosizedHeatingAirflow => is selected when the supply air volume is determined from a user specified fraction and the Autosized heating supply air flow rate value determined by the simulation.
One of FlowPerFloorArea, FractionOfAutosizedCoolingAirflow, FractionOfAutosizedHeatingAirflow, None, SupplyAirFlowRate
no_load_supply_air_flow_rate
No Load Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of the supply air volume flow rate during when no cooling or heating is required. Required field when No Load Supply Air Flow Rate Method is SupplyAirFlowRate.
no_load_supply_air_flow_rate_per_floor_area
No Load Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the supply air volume flow rate per total floor area. Required field when No Load Supply Air Flow Rate Method is FlowPerFloorArea.
Range: ≥ 0
no_load_fraction_of_cooling_supply_air_flow_rate
No Load Fraction of Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when No Load Supply Air Flow Rate Method is FractionOfAutosizedCoolingAirflow.
Range: ≥ 0
no_load_fraction_of_heating_supply_air_flow_rate
No Load Fraction of Heating Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the heating supply air flow rate. Required field when No Load Supply Air Flow Rate Method is FractionOfAutosizedHeatingAirflow.
Range: ≥ 0
heating_supply_air_flow_rate_method
Heating Supply Air Flow Rate Method
choice SupplyAirFlowRate Enter the method used to determine the heating supply air volume flow rate. None is used when a heating coil is not included in the Zone HVAC Equipment or this field may be blank. SupplyAirFlowRate => selected when the magnitude of the heating supply air volume flow rate is specified. FlowPerFloorArea => selected when the supply air volume flow rate is determined from total floor area served by a Zone HVAC unit and user specified value of Flow Per Floor Area. FractionOfAutosizedHeatingAirflow => is selected when the supply air volume is determined from a user specified fraction and the Autosized heating supply air flow rate value determined by the simulation. FlowPerHeatingCapacity => is selected when the supply air volume is determined from user specified flow per Heating Capacity and Heating Capacity determined by the simulation.
One of FlowPerFloorArea, FlowPerHeatingCapacity, FractionOfAutosizedHeatingAirflow, None, SupplyAirFlowRate
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number or Autosize
m3/s
Enter the magnitude of the supply air volume flow rate during heating operation. Required field when Heating Supply Air Flow Rate Method is SupplyAirFlowRate. This field may be blank if a heating coil is not included in the Zone HVAC equipment.
heating_supply_air_flow_rate_per_floor_area
Heating Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the heating supply air volume flow rate per total conditioned floor area. Required field when Heating Supply Air Flow Rate Method is FlowPerFloorArea. This field may be blank if a heating coil is not included in the Zone HVAC equipment.
Range: ≥ 0
heating_fraction_of_heating_supply_air_flow_rate
Heating Fraction of Heating Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the heating supply air flow rate. Required field when Heating Supply Air Flow Rate Method is FractionOfAutosizedHeatingAirflow. This field may be blank if a heating coil is not included in the Zone HVAC equipment.
Range: ≥ 0
heating_supply_air_flow_rate_per_unit_heating_capacity
Heating Supply Air Flow Rate Per Unit Heating Capacity
number
m3/s-W
Enter the supply air volume flow rate per unit heating capacity. Required field when Heating Supply Air Flow Rate Method is FlowPerHeatingCapacity. This field may be blank if a heating coil is not included in the Zone HVAC equipment.
Range: ≥ 0
cooling_design_capacity_method
Cooling Design Capacity Method
choice None Enter the method used to determine the cooling design capacity for scalable sizing. None is used when a cooling coils is not included in the Zone HVAC Equipment or this field may be blank. If this input field is left blank, then the design cooling capacity is set to zero. CoolingDesignCapacity => selected when the design cooling capacity value is specified or auto-sized. CapacityPerFloorArea => selected when the design cooling capacity is determine from user specified cooling capacity per floor area and zone floor area. FractionOfAutosizedCoolingCapacity => is selected when the design cooling capacity is determined from a user specified fraction and the auto-sized design cooling capacity.
One of CapacityPerFloorArea, CoolingDesignCapacity, FractionOfAutosizedCoolingCapacity, None
cooling_design_capacity
Cooling Design Capacity
number or Autosize
W
Enter the design cooling capacity. Required field when the cooling design capacity method CoolingDesignCapacity.
cooling_design_capacity_per_floor_area
Cooling Design Capacity Per Floor Area
number
W/m2
Enter the cooling design capacity per zone floor area. Required field when the cooling design capacity method field is CapacityPerFloorArea.
Range: ≥ 0
fraction_of_autosized_cooling_design_capacity
Fraction of Autosized Cooling Design Capacity
number Enter the fraction of auto-sized cooling design capacity. Required field when the cooling design capacity method field is FractionOfAutosizedCoolingCapacity.
Range: ≥ 0
heating_design_capacity_method
Heating Design Capacity Method
choice None Enter the method used to determine the heating design capacity for scalable sizing. None is used when a heating coil is not included in the Zone HVAC Equipment or this field may be blank. If this input field is left blank, then the design heating capacity is set to zero. HeatingDesignCapacity => selected when the design heating capacity value is specified or auto-sized. CapacityPerFloorArea => selected when the design cooling capacity is determine from user specified heating capacity per flow area and zone floor area. FractionOfAutosizedHeatingCapacity => is selected when the design heating capacity is determined from a user specified fraction and the auto-sized design heating capacity
One of CapacityPerFloorArea, FractionOfAutosizedHeatingCapacity, HeatingDesignCapacity, None
heating_design_capacity
Heating Design Capacity
number or Autosize
W
Enter the design heating capacity. Required field when the heating design capacity method HeatingDesignCapacity.
heating_design_capacity_per_floor_area
Heating Design Capacity Per Floor Area
number
W/m2
Enter the heating design capacity per zone floor area. Required field when the heating design capacity method field is CapacityPerFloorArea.
Range: ≥ 0
fraction_of_autosized_heating_design_capacity
Fraction of Autosized Heating Design Capacity
number Enter the fraction of auto-sized heating design capacity. Required field when capacity the heating design capacity method field is FractionOfAutosizedHeatingCapacity.
Range: ≥ 0
Referenced by 11 object types

ZoneHVAC:EvaporativeCoolerUnit, ZoneHVAC:FourPipeFanCoil, ZoneHVAC:IdealLoadsAirSystem, ZoneHVAC:PackagedTerminalAirConditioner, ZoneHVAC:PackagedTerminalHeatPump, ZoneHVAC:TerminalUnit:VariableRefrigerantFlow, ZoneHVAC:UnitHeater, ZoneHVAC:UnitVentilator, ZoneHVAC:VentilatedSlab, ZoneHVAC:WaterToAirHeatPump, ZoneHVAC:WindowAirConditioner

OutputControl:Sizing:Style

from idfpy.models import OutputControlSizingStyle unique

Default style for the Sizing output files is comma -- this works well for importing into spreadsheet programs such as Excel™ but not so well for word processing programs -- there tab may be a better choice. Fixed puts spaces between the "columns"

Field Type Default Details
column_separator
Column Separator required
choice One of Comma, Fixed, Tab

Sizing:Parameters

from idfpy.models import SizingParameters unique

Specifies global heating and cooling sizing factors/ratios. These ratios are applied at the zone level to all of the zone heating and cooling loads and air flow rates. Then these new loads and air flow rates are used to calculate the system level flow rates and capacities and are used in all component sizing calculations. Specifies the width (in load timesteps) of a moving average window which is used to smooth the peak load across more than one timestep.

Field Type Default Details
heating_sizing_factor
Heating Sizing Factor
number 1.0 Range: > 0
cooling_sizing_factor
Cooling Sizing Factor
number 1.0 Range: > 0
timesteps_in_averaging_window
Timesteps in Averaging Window
integer blank => set the timesteps in averaging window to Number of Timesteps per Hour resulting in a 1 hour averaging window default is number of timesteps for 1 hour averaging window If the PerformancePrecisionTradeoffs Override Mode is set to non-Normal, this field will be overwritten to 1
Range: ≥ 1

Sizing:Plant

from idfpy.models import SizingPlant

Specifies the input needed to autosize plant loop flow rates and equipment capacities. This information is initially used by components that use water for heating or cooling such as hot or chilled water coils to calculate their maximum water flow rates. These flow rates are then summed for use in calculating the Plant Loop flow rates.

Field Type Default Details
plant_or_condenser_loop_name
Plant or Condenser Loop Name required
reference Enter the name of a PlantLoop or a CondenserLoop object
Names a CondenserLoop, PlantLoop
loop_type
Loop Type required
choice One of Condenser, Cooling, Heating, Steam
design_loop_exit_temperature
Design Loop Exit Temperature required
number
C
loop_design_temperature_difference
Loop Design Temperature Difference required
number
deltaC
Range: > 0
sizing_option
Sizing Option
choice NonCoincident if Coincident is chosen, then sizing is based on HVAC Sizing Simulations and the input field called Do HVAC Sizing Simulation for Sizing Periods in SimulationControl must be set to Yes
One of Coincident, NonCoincident
zone_timesteps_in_averaging_window
Zone Timesteps in Averaging Window
integer 1 this is used in the coincident sizing algorithm to apply a running average to peak flow rates that occur during HVAC Sizing Simulations
Range: ≥ 1
coincident_sizing_factor_mode
Coincident Sizing Factor Mode
choice this is used to adjust the result for coincident sizing by applying a sizing factor
One of GlobalCoolingSizingFactor, GlobalHeatingSizingFactor, LoopComponentSizingFactor, None

Sizing:System

from idfpy.models import SizingSystem

Specifies the input needed to perform sizing calculations for a central forced air system. System design air flow, heating capacity, and cooling capacity will be calculated using this input data.

Field Type Default Details
airloop_name
AirLoop Name required
reference Names a AirLoopHVAC
type_of_load_to_size_on
Type of Load to Size On
choice Sensible Specifies the basis for sizing the system supply air flow rate Sensible and Total use the zone design air flow rates to size the system supply air flow rate The cooling coil will then be sized at either the peak Sensible or Total flow rate and conditions The heating coil is always sized at the peak sensible heating load. Latent uses the larger of the zone sensible and latent design air flow rates for system sizing. VentilationRequirement uses the system ventilation requirement
One of Latent, Sensible, Total, VentilationRequirement
design_outdoor_air_flow_rate
Design Outdoor Air Flow Rate
number or Autosize
m3/s
Autosize
central_heating_maximum_system_air_flow_ratio
Central Heating Maximum System Air Flow Ratio
number or Autosize Autosize
preheat_design_temperature
Preheat Design Temperature required
number
C
preheat_design_humidity_ratio
Preheat Design Humidity Ratio required
number
kgWater/kgDryAir
precool_design_temperature
Precool Design Temperature required
number
C
precool_design_humidity_ratio
Precool Design Humidity Ratio required
number
kgWater/kgDryAir
central_cooling_design_supply_air_temperature
Central Cooling Design Supply Air Temperature required
number
C
central_heating_design_supply_air_temperature
Central Heating Design Supply Air Temperature required
number
C
type_of_zone_sum_to_use
Type of Zone Sum to Use
choice NonCoincident One of Coincident, NonCoincident
n100_outdoor_air_in_cooling
100% Outdoor Air in Cooling
choice No One of No, Yes
n100_outdoor_air_in_heating
100% Outdoor Air in Heating
choice No One of No, Yes
central_cooling_design_supply_air_humidity_ratio
Central Cooling Design Supply Air Humidity Ratio
number
kgWater/kgDryAir
0.008
central_heating_design_supply_air_humidity_ratio
Central Heating Design Supply Air Humidity Ratio
number
kgWater/kgDryAir
0.008
cooling_supply_air_flow_rate_method
Cooling Supply Air Flow Rate Method
choice DesignDay One of DesignDay, Flow/System, FlowPerCoolingCapacity, FlowPerFloorArea, FractionOfAutosizedCoolingAirflow
cooling_supply_air_flow_rate
Cooling Supply Air Flow Rate
number
m3/s
0.0 This input is used if Cooling Supply Air Flow Rate Method is Flow/System This value will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers, this value must be large enough to serve the multiplied zones.
Range: ≥ 0
cooling_supply_air_flow_rate_per_floor_area
Cooling Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the cooling supply air volume flow rate per total conditioned floor area. Required field when Cooling Supply Air Flow Rate Method is FlowPerFloorArea.
Range: ≥ 0
cooling_fraction_of_autosized_cooling_supply_air_flow_rate
Cooling Fraction of Autosized Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when Cooling Supply Air Flow Rate Method is FractionOfAutosizedCoolingAirflow.
Range: ≥ 0
cooling_supply_air_flow_rate_per_unit_cooling_capacity
Cooling Supply Air Flow Rate Per Unit Cooling Capacity
number
m3/s-W
Enter the supply air volume flow rate per unit cooling capacity. Required field when Cooling Supply Air Flow Rate Method is FlowPerCoolingCapacity.
Range: ≥ 0
heating_supply_air_flow_rate_method
Heating Supply Air Flow Rate Method
choice DesignDay One of DesignDay, Flow/System, FlowPerFloorArea, FlowPerHeatingCapacity, FractionOfAutosizedCoolingAirflow, FractionOfAutosizedHeatingAirflow
heating_supply_air_flow_rate
Heating Supply Air Flow Rate
number
m3/s
0.0 Required field when Heating Supply Air Flow Rate Method is Flow/System This value will *not* be multiplied by any sizing factor or by zone multipliers. If using zone multipliers, this value must be large enough to serve the multiplied zones.
Range: ≥ 0
heating_supply_air_flow_rate_per_floor_area
Heating Supply Air Flow Rate Per Floor Area
number
m3/s-m2
Enter the heating supply air volume flow rate per total conditioned floor area. Required field when Heating Supply Air Flow Rate Method is FlowPerFloorArea.
Range: ≥ 0
heating_fraction_of_autosized_heating_supply_air_flow_rate
Heating Fraction of Autosized Heating Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the heating supply air flow rate. Required field when Heating Supply Air Flow Rate Method is FractionOfAutosizedHeatingAirflow.
Range: ≥ 0
heating_fraction_of_autosized_cooling_supply_air_flow_rate
Heating Fraction of Autosized Cooling Supply Air Flow Rate
number Enter the supply air volume flow rate as a fraction of the cooling supply air flow rate. Required field when Heating Supply Air Flow Rate Method is FractionOfAutosizedCoolingAirflow.
Range: ≥ 0
heating_supply_air_flow_rate_per_unit_heating_capacity
Heating Supply Air Flow Rate Per Unit Heating Capacity
number
m3/s-W
Enter the heating supply air volume flow rate per unit heating capacity. Required field when Heating Supply Air Flow Rate Method is FlowPerHeatingCapacity.
Range: ≥ 0
system_outdoor_air_method
System Outdoor Air Method
choice ZoneSum One of Standard62.1SimplifiedProcedure, Standard62.1VentilationRateProcedure, ZoneSum
zone_maximum_outdoor_air_fraction
Zone Maximum Outdoor Air Fraction
number
dimensionless
1.0 Range: > 0
cooling_design_capacity_method
Cooling Design Capacity Method
choice CoolingDesignCapacity Enter the method used to determine the system cooling design capacity for scalable sizing. None is used when a cooling coils is not included in an airloop or this field may be blank. If this input field is left blank, then the design cooling capacity is set to zero. CoolingDesignCapacity => selected when the design cooling capacity value is specified or auto-sized. CapacityPerFloorArea => selected when the design cooling capacity is determined from user specified cooling capacity per floor area and total floor area of cooled zones served by an airloop. FractionOfAutosizedCoolingCapacity => is selected when the design cooling capacity is determined from a user specified fraction and the auto-sized design cooling capacity of the system.
One of CapacityPerFloorArea, CoolingDesignCapacity, FractionOfAutosizedCoolingCapacity, None
cooling_design_capacity
Cooling Design Capacity
number or Autosize
W
Autosize Enter the design cooling capacity.
cooling_design_capacity_per_floor_area
Cooling Design Capacity Per Floor Area
number
W/m2
Enter the cooling design capacity per total floor area of cooled zones served by an airloop. Required field when the cooling design capacity method field is CapacityPerFloorArea.
Range: ≥ 0
fraction_of_autosized_cooling_design_capacity
Fraction of Autosized Cooling Design Capacity
number Enter the fraction of auto-sized cooling design capacity. Required field when the cooling design capacity method field is FractionOfAutosizedCoolingCapacity.
Range: ≥ 0
heating_design_capacity_method
Heating Design Capacity Method
choice HeatingDesignCapacity Enter the method used to determine the heating design capacity for scalable sizing. None is used when a heating coil not included in an airloop or this field may be blank. If this input field is left blank, then the design heating capacity is set to zero. HeatingDesignCapacity => selected when the design heating capacity value is specified or auto-sized. CapacityPerFloorArea => selected when the design heating capacity is determined from user specified heating capacity per flow area and total floor area of heated zones served by an airloop. FractionOfAutosizedHeatingCapacity => is selected when the design heating capacity is determined from a user specified fraction and the auto-sized design heating capacity of the system.
One of CapacityPerFloorArea, FractionOfAutosizedHeatingCapacity, HeatingDesignCapacity, None
heating_design_capacity
Heating Design Capacity
number or Autosize
W
Autosize Enter the design heating capacity.
heating_design_capacity_per_floor_area
Heating Design Capacity Per Floor Area
number
W/m2
Enter the heating design capacity per zone floor area. Required field when the heating design capacity method field is CapacityPerFloorArea.
Range: ≥ 0
fraction_of_autosized_heating_design_capacity
Fraction of Autosized Heating Design Capacity
number Enter the fraction of auto-sized heating design capacity. Required field when capacity the heating design capacity method field is FractionOfAutosizedHeatingCapacity.
Range: ≥ 0
central_cooling_capacity_control_method
Central Cooling Capacity Control Method
choice OnOff Method used to control the coil's output
One of Bypass, OnOff, VAV, VT
occupant_diversity
Occupant Diversity
number or Autosize Autosize The Occupant Diversity is used to determine a multi-zone system's outdoor air intake when the System Outdoor Air Method is Standard62.1VentilationRateProcedure or the Standard62.1SimplifiedProcedure. If set to be autosized, it will be calculated using the information in the People objects assigned to each zone attached to this system/airloop.
heating_coil_sizing_method
Heating Coil Sizing Method
choice None Size a heat pump heating coil using the Cooling, Heating or GreaterOfHeatingOrCooling capacities
One of CoolingCapacity, GreaterOfHeatingOrCooling, HeatingCapacity, None
maximum_heating_capacity_to_cooling_capacity_sizing_ratio
Maximum Heating Capacity To Cooling Capacity Sizing Ratio
number
W/W
1.0 The limit of heating coil capacity to cooling coil capacity
Range: ≥ 1

Sizing:Zone

from idfpy.models import SizingZone

Specifies the data needed to perform a zone design air flow calculation. The calculation is done for every sizing period included in the input. The maximum cooling and heating load and cooling, heating, and ventilation air flows are then saved for system level and zone component design calculations.

Field Type Default Details
zone_or_zonelist_name
Zone or ZoneList Name required
reference Names a Zone, ZoneList
zone_cooling_design_supply_air_temperature_input_method
Zone Cooling Design Supply Air Temperature Input Method
choice SupplyAirTemperature One of SupplyAirTemperature, TemperatureDifference
zone_cooling_design_supply_air_temperature
Zone Cooling Design Supply Air Temperature
number
C
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_cooling_design_supply_air_temperature_difference
Zone Cooling Design Supply Air Temperature Difference
number
deltaC
Zone Cooling Design Supply Air Temperature is only used when Zone Cooling Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be subtracted from the zone temperature at peak load to calculate the Zone Cooling Design Supply Air Temperature.
zone_heating_design_supply_air_temperature_input_method
Zone Heating Design Supply Air Temperature Input Method
choice SupplyAirTemperature One of SupplyAirTemperature, TemperatureDifference
zone_heating_design_supply_air_temperature
Zone Heating Design Supply Air Temperature
number
C
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = SupplyAirTemperature
zone_heating_design_supply_air_temperature_difference
Zone Heating Design Supply Air Temperature Difference
number
deltaC
Zone Heating Design Supply Air Temperature is only used when Zone Heating Design Supply Air Temperature Input Method = TemperatureDifference The absolute value of this field will be added to the zone temperature at peak load to calculate the Zone Heating Design Supply Air Temperature.
zone_cooling_design_supply_air_humidity_ratio
Zone Cooling Design Supply Air Humidity Ratio required
number
kgWater/kgDryAir
Range: ≥ 0
zone_heating_design_supply_air_humidity_ratio
Zone Heating Design Supply Air Humidity Ratio required
number
kgWater/kgDryAir
Range: ≥ 0
design_specification_outdoor_air_object_name
Design Specification Outdoor Air Object Name
reference Specify the name of a DesignSpecification:OutdoorAir object to specify one set of requirements for the Zone. Use a DesignSpecification:OutdoorAir:SpaceList object name to specify different requirements for Spaces within the Zone.
Names a DesignSpecification:OutdoorAir, DesignSpecification:OutdoorAir:SpaceList
zone_heating_sizing_factor
Zone Heating Sizing Factor
number if blank or zero, global heating sizing factor from Sizing:Parameters is used.
Range: ≥ 0
zone_cooling_sizing_factor
Zone Cooling Sizing Factor
number if blank or zero, global cooling sizing factor from Sizing:Parameters is used.
Range: ≥ 0
cooling_design_air_flow_method
Cooling Design Air Flow Method
choice DesignDay One of DesignDay, DesignDayWithLimit, Flow/Zone
cooling_design_air_flow_rate
Cooling Design Air Flow Rate
number
m3/s
0.0 This input is used if Cooling Design Air Flow Method is Flow/Zone This value will be multiplied by the global or zone sizing factor and by zone multipliers.
Range: ≥ 0
cooling_minimum_air_flow_per_zone_floor_area
Cooling Minimum Air Flow per Zone Floor Area
number
m3/s-m2
0.000762 default is .15 cfm/ft2 This input is used if Cooling Design Air Flow Method is DesignDayWithLimit
Range: ≥ 0
cooling_minimum_air_flow
Cooling Minimum Air Flow
number
m3/s
0.0 This input is used if Cooling Design Air Flow Method is DesignDayWithLimit
Range: ≥ 0
cooling_minimum_air_flow_fraction
Cooling Minimum Air Flow Fraction
number 0.2 fraction of the Cooling design Air Flow Rate This input is currently used in sizing the VAV air terminal unit and fan minimum flow rate It does not currently affect other component autosizing.
Range: ≥ 0
heating_design_air_flow_method
Heating Design Air Flow Method
choice DesignDay One of DesignDay, DesignDayWithLimit, Flow/Zone
heating_design_air_flow_rate
Heating Design Air Flow Rate
number
m3/s
0.0 This input is used if Heating Design Air Flow Method is Flow/Zone. This value will be multiplied by the global or zone sizing factor and by zone multipliers.
Range: ≥ 0
heating_maximum_air_flow_per_zone_floor_area
Heating Maximum Air Flow per Zone Floor Area
number
m3/s-m2
0.002032 default is .40 cfm/ft2 This field is used to size the heating design flow rate when Heating Design Air Flow Method = Flow/Zone. This input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.
Range: ≥ 0
heating_maximum_air_flow
Heating Maximum Air Flow
number
m3/s
0.1415762 default is 300 cfm This input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.
Range: ≥ 0
heating_maximum_air_flow_fraction
Heating Maximum Air Flow Fraction
number 0.3 fraction of the Heating Design Air Flow Rate This input is used for autosizing components when Heating Design Air Flow Method = DesignDayWithLimit.
Range: ≥ 0
design_specification_zone_air_distribution_object_name
Design Specification Zone Air Distribution Object Name
reference Names a DesignSpecification:ZoneAirDistribution
account_for_dedicated_outdoor_air_system
Account for Dedicated Outdoor Air System
choice No account for effect of dedicated outdoor air system supplying air directly to the zone
One of No, Yes
dedicated_outdoor_air_system_control_strategy
Dedicated Outdoor Air System Control Strategy
choice NeutralSupplyAir 1)supply neutral ventilation air; 2)supply neutral dehumidified and reheated ventilation air; 3)supply cold ventilation air
One of ColdSupplyAir, NeutralDehumidifiedSupplyAir, NeutralSupplyAir
dedicated_outdoor_air_low_setpoint_temperature_for_design
Dedicated Outdoor Air Low Setpoint Temperature for Design
number or Autosize
C
Autosize
dedicated_outdoor_air_high_setpoint_temperature_for_design
Dedicated Outdoor Air High Setpoint Temperature for Design
number or Autosize
C
Autosize
zone_load_sizing_method
Zone Load Sizing Method
choice Sensible Load Only No Latent Load Specifies the basis for sizing the zone supply air flow rate. Zone latent loads will not be used during sizing only when Zone Load Sizing Method = Sensible Load Only No Latent Load. For this case the zone humidity level will float according to the fields Cooling and Heating Design Supply Air Humidity Ratio. For all other choices the zone humidity level will be controlled. Sensible Load will use zone sensible air flow rate for zone component sizing. Latent loads will also be reported during sizing. Latent Load will use zone latent air flow rate for zone component sizing. Sensible loads will also be reported during sizing. Sensible and Latent Load will use the larger of sensible and latent load to choose air flow rate for zone component sizing. Sensible Load Only No Latent Load or leaving this field blank will disable zone latent sizing and reporting. Latent loads will not be reported during sizing (reported as 0's).
One of Latent Load, Sensible And Latent Load, Sensible Load, Sensible Load Only No Latent Load
zone_latent_cooling_design_supply_air_humidity_ratio_input_method
Zone Latent Cooling Design Supply Air Humidity Ratio Input Method
choice HumidityRatioDifference Use SupplyAirHumidityRatio to enter the humidity ratio when zone dehumidification is required. The supply air humidity ratio should be less than the zone humidity ratio at the zone thermostat and humidistat set point condition. Use HumidityRatioDifference to enter the difference in humidity ratio from the zone thermostat and humidistat set point condition.
One of HumidityRatioDifference, SupplyAirHumidityRatio
zone_dehumidification_design_supply_air_humidity_ratio
Zone Dehumidification Design Supply Air Humidity Ratio
number
kgWater/kgDryAir
Zone Dehumidification Design Supply Air Humidity Ratio is only used when Zone Latent Cooling Design Supply Air Humidity Ratio Input Method = SupplyAirHumidityRatio. This input must be less than the zone humidity ratio at the humidistat set point so that dehumidification can occur.
Range: > 0
zone_cooling_design_supply_air_humidity_ratio_difference
Zone Cooling Design Supply Air Humidity Ratio Difference
number
kgWater/kgDryAir
0.005 Zone Dehumidification Design Supply Air Humidity Ratio Difference is only used when Zone Latent Cooling Design Supply Air Humidity Ratio Input Method = HumidityRatioDifference. This input is a positive value and defines the difference between the zone humidity ratio at the thermostat and humidistat set point condition and the supply air humidity ratio entering the zone.
Range: > 0
zone_latent_heating_design_supply_air_humidity_ratio_input_method
Zone Latent Heating Design Supply Air Humidity Ratio Input Method
choice HumidityRatioDifference Use SupplyAirHumidityRatio to enter the humidity ratio when zone humidification is required. The supply air humidity ratio should be greater than the zone humidity ratio at the zone thermostat and humidistat set point condition. Use HumidityRatioDifference to enter the difference in humidity ratio from the zone thermostat and humidistat set point condition.
One of HumidityRatioDifference, SupplyAirHumidityRatio
zone_humidification_design_supply_air_humidity_ratio
Zone Humidification Design Supply Air Humidity Ratio
number
kgWater/kgDryAir
Zone Humidification Design Supply Air Humidity Ratio is only used when Zone Latent Heating Design Supply Air Humidity Ratio Input Method = SupplyAirHumidityRatio. This input must be greater than the zone humidity ratio at the humidistat set point so that humidification can occur.
Range: > 0
zone_humidification_design_supply_air_humidity_ratio_difference
Zone Humidification Design Supply Air Humidity Ratio Difference
number
kgWater/kgDryAir
0.005 Zone Humidification Design Supply Air Humidity Ratio is only used when Zone Latent Heating Design Supply Air Humidity Ratio Input Method = HumidityRatioDifference. This input is a positive value and defines the difference between the zone humidity ratio at the thermostat and humidistat set point condition and the supply air humidity ratio entering the zone.
Range: ≥ 0
zone_humidistat_dehumidification_set_point_schedule_name
Zone Humidistat Dehumidification Set Point Schedule Name
reference Enter the zone relative humidity schedule used for zone latent cooling calculations. A zone humidistat will take priority over this input. This field is not used if Zone Load Sizing Method = Sensible Load Only No Latent Load or a zone humidistat is present. A default of 50.0 will be used if no schedule is provided and no humidistat is associated with this zone.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_humidistat_humidification_set_point_schedule_name
Zone Humidistat Humidification Set Point Schedule Name
reference Enter the zone relative humidity schedule used for zone latent heating calculations. A zone humidistat will take priority over this input. This field is not used if Zone Load Sizing Method = Sensible Load Only No Latent Load or a zone humidistat is present. A default of 50.0 will be used if no schedule is provided and no humidistat is associated with this zone.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
type_of_space_sum_to_use
Type of Space Sum to Use
choice Coincident NonCoincident is available only if Do Space Heat Balance for Sizing=Yes in ZoneAirHeatBalanceAlgorithm.
One of Coincident, NonCoincident
heating_coil_sizing_method
Heating Coil Sizing Method
choice None One of CoolingCapacity, GreaterOfHeatingOrCooling, HeatingCapacity, None
maximum_heating_capacity_to_cooling_load_sizing_ratio
Maximum Heating Capacity To Cooling Load Sizing Ratio
number
W/W
1.0 Range: ≥ 1