Miscellaneous

94 object types from idfpy.models.misc · EnergyPlus 26.2 · groups: AirflowNetwork, Compliance Objects, Controllers, Detailed Ground Heat Transfer, Exterior Equipment, General Data Entry, Heat Recovery, Humidifiers and Dehumidifiers, Hybrid Model, Non-Zone Equipment, Parametrics, Performance Tables, Plant-Condenser Flow Control, Plant-Condenser Loops, Variable Refrigerant Flow Equipment

Object Summary
AirConditioner:VariableRefrigerantFlow Variable refrigerant flow (VRF) air-to-air heat pump condensing unit (includes one or more electric …
AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl This is a key object in the new physics based VRF model applicable for Fluid Temperature Control It describes …
AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR This is a key object in the new physics based VRF Heat Recovery (HR) model applicable for Fluid Temperature …
AirLoopHVAC:ControllerList List controllers in order of control sequence
AirflowNetwork:Distribution:Component:Coil This object defines the name of a coil used in an air loop.
AirflowNetwork:Distribution:Component:ConstantPressureDrop This object defines the characteristics of a constant pressure drop component (e.g.
AirflowNetwork:Distribution:Component:Duct This object defines the relationship between pressure and air flow through the duct.
AirflowNetwork:Distribution:Component:Fan This object defines the name of the supply Air Fan used in an Air loop.
AirflowNetwork:Distribution:Component:HeatExchanger This object defines the name of an air-to-air heat exchanger used in an air loop.
AirflowNetwork:Distribution:Component:Leak This object defines the characteristics of a supply or return air leak.
AirflowNetwork:Distribution:Component:LeakageRatio This object is used to define supply and return air leaks with respect to the fan's maximum air flow rate.
AirflowNetwork:Distribution:Component:OutdoorAirFlow This object includes the outdoor air flow rate set by the Controller:OutdoorAir object in the airflow network.
AirflowNetwork:Distribution:Component:ReliefAirFlow This object allows variation of air flow rate to perform pressure.
AirflowNetwork:Distribution:Component:TerminalUnit This object defines the name of a terminal unit in an air loop.
AirflowNetwork:Distribution:DuctSizing This object defines required parameters for duct sizing in an Airflow Network simulation.
AirflowNetwork:Distribution:DuctViewFactors This object is used to allow user-defined view factors to be used for duct-surface radiation calculations.
AirflowNetwork:Distribution:Linkage This object defines the connection between two nodes and a component.
AirflowNetwork:Distribution:Node This object represents an air distribution node in the AirflowNetwork model.
AirflowNetwork:IntraZone:Linkage This object defines the connection between two nodes and a component used in the combination of RoomAir and …
AirflowNetwork:IntraZone:Node This object represents a node in a zone in the combination of RoomAir and AirflowNetwork model.
AirflowNetwork:MultiZone:Component:DetailedOpening This object specifies the properties of airflow through windows and doors (window, door and glass door heat …
AirflowNetwork:MultiZone:Component:HorizontalOpening This object specifies the properties of air flow through a horizontal opening
AirflowNetwork:MultiZone:Component:SimpleOpening This object specifies the properties of air flow through windows and doors (window, door and glass door heat …
AirflowNetwork:MultiZone:Component:ZoneExhaustFan This object specifies the additional properties for a zone exhaust fan to perform multizone airflow …
AirflowNetwork:MultiZone:ExternalNode This object defines outdoor environmental conditions outside of the building.
AirflowNetwork:MultiZone:ReferenceCrackConditions This object specifies the conditions under which the air mass flow coefficient was measured.
AirflowNetwork:MultiZone:SpecifiedFlowRate This object is used to define specified flow through a linkage.
AirflowNetwork:MultiZone:Surface This object specifies the properties of a surface linkage through which air flows.
AirflowNetwork:MultiZone:Surface:Crack This object specifies the properties of airflow through a crack.
AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea This object is used to define surface air leakage.
AirflowNetwork:MultiZone:WindPressureCoefficientArray Used only if Wind Pressure Coefficient (WPC) Type = Input in the AirflowNetwork:SimulationControl object.
AirflowNetwork:MultiZone:WindPressureCoefficientValues Used only if Wind Pressure Coefficient (WPC) Type = INPUT in the AirflowNetwork:SimulationControl object.
AirflowNetwork:MultiZone:Zone This object is used to simultaneously control a thermal zone's window and door openings, both exterior and …
AirflowNetwork:OccupantVentilationControl This object is used to provide advanced thermal comfort control of window opening and closing for both …
AirflowNetwork:SimulationControl This object defines the global parameters used in an Airflow Network simulation.
AirflowNetwork:ZoneControl:PressureController This object is used to control a zone to a specified indoor pressure using the AirflowNetwork model.
Compliance:Building Building level inputs related to compliance to building standards, building codes, and beyond energy code …
CondenserLoop Defines a central plant condenser loop.
Controller:MechanicalVentilation This object is used in conjunction with Controller:OutdoorAir to specify outdoor ventilation air based on …
Controller:OutdoorAir Controller to set the outdoor air flow rate for an air loop.
Controller:WaterCoil Controller for a water coil which is located directly in an air loop branch or outdoor air equipment list.
Dehumidifier:Desiccant:NoFans This object models a solid desiccant dehumidifier.
Dehumidifier:Desiccant:System This compound object models a desiccant heat exchanger, an optional heater, and associated fans.
Duct:Loss:Conduction
Duct:Loss:Leakage
Duct:Loss:MakeupAir
Exterior:FuelEquipment only used for Meter type reporting, does not affect building loads
Exterior:Lights only used for Meter type reporting, does not affect building loads
Exterior:WaterEquipment only used for Meter type reporting, does not affect building loads
GroundHeatTransfer:Basement:AutoGrid AutoGrid only necessary when EquivSizing is false If the modeled building is not a rectangle or square, …
GroundHeatTransfer:Basement:BldgData Specifies the surface and gravel thicknesses used for the Basement preprocessor ground heat transfer …
GroundHeatTransfer:Basement:ComBldg ComBldg contains the monthly average temperatures (C) and possibility of daily variation amplitude
GroundHeatTransfer:Basement:EquivAutoGrid EquivAutoGrid necessary when EquivSizing=TRUE, TRUE is is the normal case.
GroundHeatTransfer:Basement:EquivSlab Using an equivalent slab allows non-rectangular shapes to be modeled accurately.
GroundHeatTransfer:Basement:Insulation Describes the insulation used on an exterior basement wall for the Basement preprocessor ground heat transfer …
GroundHeatTransfer:Basement:Interior Provides the information needed to simulate the inside boundary conditions for the Basement preprocessor …
GroundHeatTransfer:Basement:ManualGrid Manual Grid only necessary using manual gridding (not recommended)
GroundHeatTransfer:Basement:MatlProps Specifies the material properties for the Basement preprocessor ground heat transfer simulation.
GroundHeatTransfer:Basement:SimParameters Specifies certain parameters that control the Basement preprocessor ground heat transfer simulation.
GroundHeatTransfer:Basement:SurfaceProps Specifies the soil surface properties for the Basement preprocessor ground heat transfer simulation.
GroundHeatTransfer:Basement:XFACE This is only needed when using manual gridding (not recommended) XFACE: X Direction cell face coordinates: m
GroundHeatTransfer:Basement:YFACE This is only needed when using manual gridding (not recommended) YFACE: Y Direction cell face coordinates: m
GroundHeatTransfer:Basement:ZFACE This is only needed when using manual gridding (not recommended) ZFACE: Z Direction cell face coordinates: m
GroundHeatTransfer:Control Object determines if the Slab and Basement preprocessors are going to be executed.
GroundHeatTransfer:Slab:AutoGrid AutoGrid only necessary when EquivalentSlab option not chosen.
GroundHeatTransfer:Slab:BldgProps Object provides information about the building and its operating conditions Monthly Average Temperature …
GroundHeatTransfer:Slab:BoundConds Supplies some of the boundary conditions used in the ground heat transfer calculations.
GroundHeatTransfer:Slab:EquivalentSlab Using an equivalent slab allows non-rectangular shapes to be modeled accurately.
GroundHeatTransfer:Slab:Insulation This object supplies the information about insulation used around the slab.
GroundHeatTransfer:Slab:ManualGrid Manual Grid only necessary when using manual gridding (not recommended) Used only in special cases when …
GroundHeatTransfer:Slab:Materials Object gives an overall description of the slab ground heat transfer model.
GroundHeatTransfer:Slab:MatlProps This object contains the material properties for the materials used in the model.
GroundHeatTransfer:Slab:XFACE This is only needed when using manual gridding (not recommended) XFACE: X Direction cell face coordinates: m
GroundHeatTransfer:Slab:YFACE This is only needed when using manual gridding (not recommended) YFACE: Y Direction cell face coordinates: m,
GroundHeatTransfer:Slab:ZFACE This is only needed when using manual gridding (not recommended) ZFACE: Z Direction cell face coordinates: m
HeatExchanger:AirToAir:FlatPlate Flat plate air-to-air heat exchanger, typically used for exhaust or relief air heat recovery.
HeatExchanger:AirToAir:SensibleAndLatent This object models an air-to-air heat exchanger using effectiveness relationships.
HeatExchanger:Desiccant:BalancedFlow This object models a balanced desiccant heat exchanger.
HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1 RTO = B1 + B2*RWI + B3*RTI + B4*(RWI/RTI) + B5*PWI + B6*PTI + B7*(PWI/PTI) + B8*RFV RWO = C1 + C2*RWI + …
Humidifier:Steam:Electric Electrically heated steam humidifier with fan.
Humidifier:Steam:Gas Natural gas fired steam humidifier with optional blower fan.
HybridModel:Zone Zones with measured air temperature data and a range of dates.
LoadProfile:Plant Used to simulate a scheduled plant loop demand profile.
Matrix:TwoDimension matrix data in row-major order list each row keeping the columns in order number of values must equal N1 x N2
Parametric:FileNameSuffix Defines the suffixes to be appended to the idf and output file names for each parametric run.
Parametric:Logic This object allows some types of objects to be included for some parametric cases and not for others.
Parametric:RunControl Controls which parametric runs are simulated.
Parametric:SetValueForRun Parametric objects allow a set of multiple simulations to be defined in a single idf file.
PlantLoop Defines a central plant loop.
Table:IndependentVariable An independent variable representing a single dimension of a Table:Lookup object.
Table:IndependentVariableList A sorted list of independent variables used by one or more Table:Lookup objects.
Table:Lookup Lookup tables are used in place of curves and can represent any number of independent variables (defined as …
TemperingValve Temperature-controlled diversion valve used to divert flow around one or more plant components such as a hot …
ZoneTerminalUnitList List of variable refrigerant flow (VRF) terminal units served by a given VRF condensing unit.

AirConditioner:VariableRefrigerantFlow

from idfpy.models import AirConditionerVariableRefrigerantFlow

Variable refrigerant flow (VRF) air-to-air heat pump condensing unit (includes one or more electric compressors and outdoor fan). Serves one or more VRF zone terminal units. See ZoneHVAC:TerminalUnit:VariableRefrigerantFlow and ZoneTerminalUnitList.

Field Type Default Details
name
Heat Pump Name
string Enter a unique name for this variable refrigerant flow heat pump.
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available. Enter the name of a schedule that defines the availability of the unit. Schedule values of 0 denote the unit is off. All other values denote the unit is available. If this field is left blank, the unit is available the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
gross_rated_total_cooling_capacity
Gross Rated Total Cooling Capacity
number or Autosize
W
Enter the total cooling capacity in watts at rated conditions or set to autosize. Total cooling capacity not accounting for the effect of supply air fan heat
gross_rated_cooling_cop
Gross Rated Cooling COP
number
W/W
3.3 Enter the coefficient of performance at rated conditions or leave blank to use default. COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electric power input
Range: > 0
minimum_condenser_inlet_node_temperature_in_cooling_mode
Minimum Condenser Inlet Node Temperature in Cooling Mode
number
C
-6.0 For cooling mode operation, enter the minimum inlet outdoor air dry-bulb temperature for air-cooled units or minimum inlet water temperature for water-cooled units. Cooling is disabled below this temperature.
maximum_condenser_inlet_node_temperature_in_cooling_mode
Maximum Condenser Inlet Node Temperature in Cooling Mode
number
C
43.0 For cooling mode operation, enter the maximum inlet outdoor air dry-bulb temperature for air-cooled units or maximum inlet water temperature for water-cooled units. Cooling is disabled above this temperature.
cooling_capacity_ratio_modifier_function_of_low_temperature_curve_name
Cooling Capacity Ratio Modifier Function of Low Temperature Curve Name
reference Enter a curve name that represents full load cooling capacity ratio as a function of outdoor dry-bulb temperature and indoor wet-bulb temperature. Up to two curves are allowed if the performance cannot be represented by a single curve. The following two fields are used if two curves are required.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_capacity_ratio_boundary_curve_name
Cooling Capacity Ratio Boundary Curve Name
reference This curve object is used to allow separate low and high cooling capacity ratio performance curves. This curve represents a line passing through the points where performance changes. The curve calculates outdoor dry-bulb temperature given weighted average indoor wet-bulb temperature. If a single performance curve is used, leave this field blank.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_capacity_ratio_modifier_function_of_high_temperature_curve_name
Cooling Capacity Ratio Modifier Function of High Temperature Curve Name
reference This curve object is used to describe the high outdoor temperature performance curve used to describe cooling capacity ratio. This curve is used when a single performance curve does not accurately describe cooling capacity ratio as a function of temperature. If a single performance curve is used, leave this field blank.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_modifier_function_of_low_temperature_curve_name
Cooling Energy Input Ratio Modifier Function of Low Temperature Curve Name
reference Enter a curve name that represents cooling energy ratio as a function of outdoor dry-bulb temperature and indoor wet-bulb temperature
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_boundary_curve_name
Cooling Energy Input Ratio Boundary Curve Name
reference This curve object is used to allow separate low and high cooling energy input ratio performance curves. This curve represents a line passing through the points where performance changes. The curve calculates outdoor dry-bulb temperature given weighted average indoor wet-bulb temperature. If a single performance curve is used, leave this field blank.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_energy_input_ratio_modifier_function_of_high_temperature_curve_name
Cooling Energy Input Ratio Modifier Function of High Temperature Curve Name
reference This curve object is used to describe the high outdoor temperature performance curve used to describe cooling energy ratio. This curve is used when a single performance curve does not accurately describe cooling energy ratio as a function of temperature
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_modifier_function_of_low_part_load_ratio_curve_name
Cooling Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name
reference Enter a curve name that represents cooling energy ratio as a function of part-load ratio for part-load ratios less than or equal to 1. If this field is left blank, the model assumes energy is proportional to part-load ratio.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_energy_input_ratio_modifier_function_of_high_part_load_ratio_curve_name
Cooling Energy Input Ratio Modifier Function of High Part-Load Ratio Curve Name
reference Enter a curve name that represents cooling energy ratio as a function of part-load ratio for part-load ratios greater than 1. Part-load ratios can exceed 1 in variable speed compression systems. If this field is left blank, the model assumes energy is proportional to part-load ratio.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_combination_ratio_correction_factor_curve_name
Cooling Combination Ratio Correction Factor Curve Name
reference This curve defines how rated capacity changes when the total indoor terminal unit cooling capacity is greater than the Gross Rated Total Cooling Capacity defined in this object. If this field is left blank, the model assumes total indoor terminal unit cooling capacity is equal to the Gross Rated Total Cooling Capacity defined above.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
cooling_part_load_fraction_correlation_curve_name
Cooling Part-Load Fraction Correlation Curve Name
reference This curve defines the cycling losses when the heat pump compressor cycles on and off below the Minimum Heat Pump Part-Load Ratio specified in the field below.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
gross_rated_heating_capacity
Gross Rated Heating Capacity
number or Autosize
W
Enter the heating capacity in watts at rated conditions or set to autosize. Heating capacity not accounting for the effect of supply air fan heat
rated_heating_capacity_sizing_ratio
Rated Heating Capacity Sizing Ratio
number
W/W
1.0 If the Gross Rated Heating Capacity is autosized, the heating capacity is sized to be equal to the cooling capacity multiplied by this sizing ratio. The zone terminal unit heating coils are also sized using this ratio unless the sizing ratio input in the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object is entered.
Range: ≥ 1
gross_rated_heating_cop
Gross Rated Heating COP
number
W/W
3.4 COP includes compressor and condenser fan electrical energy input COP does not include supply fan heat or supply fan electrical energy input
Range: > 0
minimum_condenser_inlet_node_temperature_in_heating_mode
Minimum Condenser Inlet Node Temperature in Heating Mode
number
C
-20.0 For heating mode operation, enter the minimum inlet outdoor air dry-bulb temperature for air-cooled units or minimum inlet water temperature for water-cooled units. Heating is disabled below this temperature.
maximum_condenser_inlet_node_temperature_in_heating_mode
Maximum Condenser Inlet Node Temperature in Heating Mode
number
C
16.0 For heating mode operation, enter the maximum inlet outdoor air dry-bulb temperature for air-cooled units or maximum inlet water temperature for water-cooled units. Heating is disabled below this temperature.
heating_capacity_ratio_modifier_function_of_low_temperature_curve_name
Heating Capacity Ratio Modifier Function of Low Temperature Curve Name
reference Enter a curve name that represents full load heating capacity ratio as a function of outdoor wet-bulb temperature and indoor dry-bulb temperature. Outdoor dry-bulb temperature may be used if wet-bulb temperature data is unavailable. See Heating Performance Curve Outdoor Temperature Type input below to determine which outdoor temperature type to use. Up to two curves are allowed if the performance cannot be represented by a single curve. The following two fields are used if two curves are required.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_capacity_ratio_boundary_curve_name
Heating Capacity Ratio Boundary Curve Name
reference This curve object is used to allow separate low and high heating capacity ratio performance curves. This curve represents a line passing through the points where performance changes. The curve calculates outdoor dry-bulb or wet-bulb temperature given weighted average indoor dry-bulb temperature. See Heating Performance Curve Outdoor Temperature Type input below to determine which outdoor temperature type to use. If a single performance curve is used, leave this field blank.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_capacity_ratio_modifier_function_of_high_temperature_curve_name
Heating Capacity Ratio Modifier Function of High Temperature Curve Name
reference This curve object is used to describe the high outdoor temperature performance curve used to describe heating capacity ratio. This curve is used when a single performance curve does not accurately describe heating capacity ratio as a function of temperature. If a single performance curve is used, leave this field blank.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_modifier_function_of_low_temperature_curve_name
Heating Energy Input Ratio Modifier Function of Low Temperature Curve Name
reference Enter a curve name that represents heating energy ratio as a function of outdoor wet-bulb temperature and indoor dry-bulb temperature Outdoor dry-bulb temperature may be used if wet-bulb temperature data is unavailable. See Heating Performance Curve Outdoor Temperature Type input below to determine which outdoor temperature type to use.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_boundary_curve_name
Heating Energy Input Ratio Boundary Curve Name
reference This curve object is used to allow separate low and high heating energy input ratio performance curves. This curve represents a line passing through the points where performance changes. The curve calculates outdoor dry-bulb or wet-bulb temperature given weighted average indoor dry-bulb temperature. See Heating Performance Curve Outdoor Temperature Type input below to determine which outdoor temperature type to use. If a single performance curve is used, leave this field blank.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_energy_input_ratio_modifier_function_of_high_temperature_curve_name
Heating Energy Input Ratio Modifier Function of High Temperature Curve Name
reference This curve object is used to allow separate performance curves for heating energy. If a single performance curve is used, leave this field blank.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_performance_curve_outdoor_temperature_type
Heating Performance Curve Outdoor Temperature Type
choice WetBulbTemperature Determines temperature type for heating capacity curves and heating energy curves. This input determines whether the outdoor air dry-bulb or wet-bulb temperature is used to evaluate these curves.
One of DryBulbTemperature, WetBulbTemperature
heating_energy_input_ratio_modifier_function_of_low_part_load_ratio_curve_name
Heating Energy Input Ratio Modifier Function of Low Part-Load Ratio Curve Name
reference This curve represents the heating energy input ratio for part-load ratios less than 1.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_energy_input_ratio_modifier_function_of_high_part_load_ratio_curve_name
Heating Energy Input Ratio Modifier Function of High Part-Load Ratio Curve Name
reference This curve represents the heating energy input ratio for part-load ratios greater than 1.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_combination_ratio_correction_factor_curve_name
Heating Combination Ratio Correction Factor Curve Name
reference This curve defines how rated capacity changes when the total indoor terminal unit heating capacity is greater than the Gross Rated Heating Capacity defined in this object. If this field is left blank, the model assumes total indoor terminal unit heating capacity is equal to the Gross Rated Heating Capacity defined above.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_part_load_fraction_correlation_curve_name
Heating Part-Load Fraction Correlation Curve Name
reference This curve defines the cycling losses when the heat pump compressor cycles on and off below the Minimum Heat Pump Part-Load Ratio specified in the following field.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_heat_pump_part_load_ratio
Minimum Heat Pump Part-Load Ratio
number
dimensionless
0.15 Enter the minimum heat pump part-load ratio (PLR). When the cooling or heating PLR is below this value, the heat pump compressor will cycle to meet the cooling or heating demand.
zone_name_for_master_thermostat_location
Zone Name for Master Thermostat Location
reference Enter the name of the zone where the master thermostat is located.
Names a Zone
master_thermostat_priority_control_type
Master Thermostat Priority Control Type
choice MasterThermostatPriority Choose a thermostat control logic scheme. If these control types fail to control zone temperature within a reasonable limit, consider using multiple VRF systems. This field is not used when all terminal units are set point controlled.
One of LoadPriority, MasterThermostatPriority, Scheduled, ThermostatOffsetPriority, ZonePriority
thermostat_priority_schedule_name
Thermostat Priority Schedule Name
reference this field is required if Master Thermostat Priority Control Type is Scheduled. Schedule values of 0 denote cooling, 1 for heating, and all other values disable the system.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_terminal_unit_list_name
Zone Terminal Unit List Name required
reference Enter the name of a ZoneTerminalUnitList. This list connects zone terminal units to this heat pump.
Names a ZoneTerminalUnitList
heat_pump_waste_heat_recovery
Heat Pump Waste Heat Recovery
choice No This field enables heat recovery operation within this VRF outdoor unit.
One of No, Yes
equivalent_piping_length_used_for_piping_correction_factor_in_cooling_mode
Equivalent Piping Length used for Piping Correction Factor in Cooling Mode
number
m
Enter the equivalent length of the farthest terminal unit from the condenser
vertical_height_used_for_piping_correction_factor
Vertical Height used for Piping Correction Factor
number
m
Enter the height difference between the highest and lowest terminal unit
piping_correction_factor_for_length_in_cooling_mode_curve_name
Piping Correction Factor for Length in Cooling Mode Curve Name
reference PCF = a0 + a1*L + a2*L^2 + a3*L^3 + a4*H PCF = a0 + a1*L + a2*L^2 + a3*CR + a4*CR^2 + a5*(L)(CR) where L = length and CR = combination ratio specifies coefficients for a0, a1, a2, and a3 in the PCF equation
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
piping_correction_factor_for_height_in_cooling_mode_coefficient
Piping Correction Factor for Height in Cooling Mode Coefficient
number
1/m
0.0 PCF = a0 + a1*L + a2*L^2 + a3*L^3 + a4*H PCF = a0 + a1*L + a2*L^2 + a3*CR + a4*CR^2 + a5*(L)(CR) + a6*H where L = length, H = height, and CR = combination ratio specifies coefficient a4 (or a6 for biquadratic) in the PCF equation
equivalent_piping_length_used_for_piping_correction_factor_in_heating_mode
Equivalent Piping Length used for Piping Correction Factor in Heating Mode
number
m
Enter the equivalent length of the farthest terminal unit from the condenser
piping_correction_factor_for_length_in_heating_mode_curve_name
Piping Correction Factor for Length in Heating Mode Curve Name
reference PCF = a0 + a1*L + a2*L^2 + a3*L^3 + a4*H PCF = a0 + a1*L + a2*L^2 + a3*CR + a4*CR^2 + a5*(L)(CR) + a6*H where L = length and CR = combination ratio specifies coefficients for a0, a1, a2, and a3 (or a0-a5 for biquadratic) in the PCF equation
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
piping_correction_factor_for_height_in_heating_mode_coefficient
Piping Correction Factor for Height in Heating Mode Coefficient
number
1/m
0.0 PCF = a0 + a1*L + a2*L^2 + a3*L^3 + a4*H PCF = a0 + a1*L + a2*L^2 + a3*CR + a4*CR^2 + a5*(L)(CR) + a6*H where L = length, H = height, and CR = combination ratio specifies coefficient a4 (or a6 for biquadratic) in the PCF equation
crankcase_heater_power_per_compressor
Crankcase Heater Power per Compressor
number
W
33.0 Enter the value of the resistive heater located in the compressor(s). This heater is used to warm the refrigerant and oil when the compressor is off.
number_of_compressors
Number of Compressors
integer
dimensionless
2 Enter the total number of compressor. This input is used only for crankcase heater calculations.
ratio_of_compressor_size_to_total_compressor_capacity
Ratio of Compressor Size to Total Compressor Capacity
number
W/W
0.5 Enter the ratio of the first stage compressor to total compressor capacity. All other compressors are assumed to be equally sized. This inputs is used only for crankcase heater calculations.
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater
number
C
5.0 Enter the maximum outdoor temperature above which the crankcase heaters are disabled.
defrost_strategy
Defrost Strategy
choice Resistive Select a defrost strategy. Reverse cycle reverses the operating mode from heating to cooling to melt frost formation on the condenser coil. The resistive strategy uses a resistive heater to melt the frost.
One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed Choose a defrost control type. Either use a fixed Timed defrost period or select OnDemand to defrost only when necessary.
One of OnDemand, Timed
defrost_energy_input_ratio_modifier_function_of_temperature_curve_name
Defrost Energy Input Ratio Modifier Function of Temperature Curve Name
reference A valid performance curve must be used if reversecycle defrost strategy is selected.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
defrost_time_period_fraction
Defrost Time Period Fraction
number
dimensionless
0.058333 Fraction of time in defrost mode. Only applicable if timed defrost control is specified.
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 Enter the size of the resistive defrost heating element. Only applicable if resistive defrost strategy is specified
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-bulb Temperature for Defrost Operation
number
C
5.0 Enter the maximum outdoor temperature above which defrost operation is disabled.
condenser_type
Condenser Type
choice AirCooled Select either an air-cooled, evaporatively-cooled or water-cooled condenser.
One of AirCooled, EvaporativelyCooled, WaterCooled
condenser_inlet_node_name
Condenser Inlet Node Name
string Choose an outside air node name or leave this field blank to use weather data. If this field is blank, the Condenser Type is assumed to be AirCooled. This input must be specified if Condenser Type = WaterCooled.
condenser_outlet_node_name
Condenser Outlet Node Name
string Enter a water outlet node name if Condenser Type = WaterCooled. Leave this field blank if Condenser Type = Air or EvaporativelyCooled.
water_condenser_volume_flow_rate
Water Condenser Volume Flow Rate
number or Autosize
m3/s
Only used when Condenser Type = WaterCooled.
evaporative_condenser_effectiveness
Evaporative Condenser Effectiveness
number
dimensionless
0.9 Enter the effectiveness of the evaporatively cooled condenser. This field is only used when the Condenser Type = EvaporativelyCooled.
Range: ≥ 0, ≤ 1
evaporative_condenser_air_flow_rate
Evaporative Condenser Air Flow Rate
number or Autosize
m3/s
Used to calculate evaporative condenser water use. This field is only used when the Condenser Type = EvaporativelyCooled.
evaporative_condenser_pump_rated_power_consumption
Evaporative Condenser Pump Rated Power Consumption
number or Autosize
W
0.0 Rated power consumed by the evaporative condenser's water pump. This field is only used when the Condenser Type = EvaporativelyCooled.
supply_water_storage_tank_name
Supply Water Storage Tank Name
reference A separate storage tank may be used to supply an evaporatively cooled condenser.
Names a WaterUse:Storage
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the DX coil is off.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fuel_type
Fuel Type
choice Electricity One of Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
minimum_condenser_inlet_node_temperature_in_heat_recovery_mode
Minimum Condenser Inlet Node Temperature in Heat Recovery Mode
number
C
For heat recovery mode operation, enter the minimum inlet outdoor air dry-bulb temperature for air-cooled units or minimum inlet water temperature for water-cooled units. Heat recovery is disabled below this temperature.
maximum_condenser_inlet_node_temperature_in_heat_recovery_mode
Maximum Condenser Inlet Node Temperature in Heat Recovery Mode
number
C
For heat recovery mode operation, enter the maximum inlet outdoor air dry-bulb temperature for air-cooled units or maximum inlet water temperature for water-cooled units. Heat recovery is disabled above this temperature.
heat_recovery_cooling_capacity_modifier_curve_name
Heat Recovery Cooling Capacity Modifier Curve Name
reference Enter the name of a performance curve which represents the change in cooling capacity when heat recovery is active A default constant of 0.9 is used if this input is blank
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
initial_heat_recovery_cooling_capacity_fraction
Initial Heat Recovery Cooling Capacity Fraction
number
W/W
0.5 Enter the fractional capacity available at the start of heat recovery mode. The capacity exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Capacity Modifier and Heat Recovery Cooling Capacity Time Constant
heat_recovery_cooling_capacity_time_constant
Heat Recovery Cooling Capacity Time Constant
number
hr
0.15 Enter the time constant used to model the transition from cooling only mode to heat recovery mode
heat_recovery_cooling_energy_modifier_curve_name
Heat Recovery Cooling Energy Modifier Curve Name
reference Enter the name of a performance curve which represents the change in cooling energy when heat recovery is active A default constant of 1.1 is used if this input is blank
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
initial_heat_recovery_cooling_energy_fraction
Initial Heat Recovery Cooling Energy Fraction
number
W/W
1.0 Enter the fractional electric consumption rate at the start of heat recovery mode. The electric consumption rate exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Energy Modifier and Heat Recovery Cooling Energy Time Constant
heat_recovery_cooling_energy_time_constant
Heat Recovery Cooling Energy Time Constant
number
hr
0.0 Enter the time constant used to model the transition from cooling only mode to heat recovery mode
heat_recovery_heating_capacity_modifier_curve_name
Heat Recovery Heating Capacity Modifier Curve Name
reference Enter the name of a performance curve which represents the change in heating capacity when heat recovery is active A default constant of 1.1 is used if this input is blank
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
initial_heat_recovery_heating_capacity_fraction
Initial Heat Recovery Heating Capacity Fraction
number
W/W
1.0 Enter the fractional capacity available at the start of heat recovery mode. The capacity exponentially approaches the steady-state value according to the inputs for Heat Recovery Heating Capacity Modifier and Heat Recovery Heating Capacity Time Constant
heat_recovery_heating_capacity_time_constant
Heat Recovery Heating Capacity Time Constant
number
hr
0.15 Enter the time constant used to model the transition from cooling only mode to heat recovery mode
heat_recovery_heating_energy_modifier_curve_name
Heat Recovery Heating Energy Modifier Curve Name
reference Enter the name of a performance curve which represents the change in heating electric consumption rate when heat recovery is active A default constant of 1.1 is used if this input is blank
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
initial_heat_recovery_heating_energy_fraction
Initial Heat Recovery Heating Energy Fraction
number
W/W
1.0 Enter the fractional electric consumption rate at the start of heat recovery mode. The electric consumption rate exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Energy Modifier and Heat Recovery Cooling Energy Time Constant
heat_recovery_heating_energy_time_constant
Heat Recovery Heating Energy Time Constant
number
hr
0.0 Enter the time constant used to model the transition from cooling only mode to heat recovery mode
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl

from idfpy.models import AirConditionerVariableRefrigerantFlowFluidTemperatureControl extensible

This is a key object in the new physics based VRF model applicable for Fluid Temperature Control It describes the Variable Refrigerant Flow system excluding the performance of indoor units Indoor units are modeled separately, see ZoneHVAC:TerminalUnit:VariableRefrigerantFlow

Field Type Default Details
heat_pump_name
Heat Pump Name required
string Enter a unique name for this variable refrigerant flow heat pump
availability_schedule_name
Availability Schedule Name
reference Enter the name of a schedule that defines the availability of the unit Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_terminal_unit_list_name
Zone Terminal Unit List Name required
reference Enter the name of a ZoneTerminalUnitList. This list connects zone terminal units to this heat pump
Names a ZoneTerminalUnitList
refrigerant_type
Refrigerant Type
reference R410A Names a FluidProperties:Name
rated_evaporative_capacity
Rated Evaporative Capacity
number or Autosize
W
40000.0 Enter the total evaporative capacity in watts at rated conditions This is the capacity corresponding to the max compressor speed at rated conditions The actual evaporative capacity is obtained by multiplying the rated capacity with the modification factor calculated by Evaporative Capacity Multiplier Function of Temperature Curve
rated_compressor_power_per_unit_of_rated_evaporative_capacity
Rated Compressor Power Per Unit of Rated Evaporative Capacity
number
dimensionless
0.35 Enter the rated compressor power per Watt of rated evaporative capacity [W/W] Rated compressor power corresponds to the max compressor speed at rated conditions The actual compressor power is obtained by multiplying the rated power with the modification factor calculated by Compressor Power Multiplier Function of Temperature Curve
Range: > 0
minimum_outdoor_air_temperature_in_cooling_mode
Minimum Outdoor Air Temperature in Cooling Mode
number
C
-6.0 Enter the minimum outdoor temperature allowed for cooling operation Cooling is disabled below this temperature
maximum_outdoor_air_temperature_in_cooling_mode
Maximum Outdoor Air Temperature in Cooling Mode
number
C
43.0 Enter the maximum outdoor temperature allowed for cooling operation Cooling is disabled above this temperature
minimum_outdoor_air_temperature_in_heating_mode
Minimum Outdoor Air Temperature in Heating Mode
number
C
-20.0 Enter the minimum outdoor temperature allowed for heating operation Heating is disabled below this temperature
maximum_outdoor_air_temperature_in_heating_mode
Maximum Outdoor Air Temperature in Heating Mode
number
C
16.0 Enter the maximum outdoor temperature allowed for heating operation Heating is disabled below this temperature
reference_outdoor_unit_superheating
Reference Outdoor Unit Superheating
number
deltaC
3.0
reference_outdoor_unit_subcooling
Reference Outdoor Unit Subcooling
number
deltaC
5.0
refrigerant_temperature_control_algorithm_for_indoor_unit
Refrigerant Temperature Control Algorithm for Indoor Unit
choice VariableTemp One of ConstantTemp, VariableTemp
reference_evaporating_temperature_for_indoor_unit
Reference Evaporating Temperature for Indoor Unit
number
C
6.0 This field is used if Refrigerant Temperature Control Algorithm is ConstantTemp Evaporating temperature is the refrigerant temperature, not air temperature
reference_condensing_temperature_for_indoor_unit
Reference Condensing Temperature for Indoor Unit
number
C
44.0 This field is used if Refrigerant Temperature Control Algorithm is ConstantTemp Condensing temperature is the refrigerant temperature, not air temperature
variable_evaporating_temperature_minimum_for_indoor_unit
Variable Evaporating Temperature Minimum for Indoor Unit
number
C
4.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Evaporating temperature is the refrigerant temperature, not air temperature
variable_evaporating_temperature_maximum_for_indoor_unit
Variable Evaporating Temperature Maximum for Indoor Unit
number
C
13.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Evaporating temperature is the refrigerant temperature, not air temperature
variable_condensing_temperature_minimum_for_indoor_unit
Variable Condensing Temperature Minimum for Indoor Unit
number
C
42.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Condensing temperature is the refrigerant temperature, not air temperature
variable_condensing_temperature_maximum_for_indoor_unit
Variable Condensing Temperature Maximum for Indoor Unit
number
C
46.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Condensing temperature is the refrigerant temperature, not air temperature
outdoor_unit_fan_power_per_unit_of_rated_evaporative_capacity
Outdoor Unit Fan Power Per Unit of Rated Evaporative Capacity
number
dimensionless
0.00425 Enter the outdoor unit fan power per Watt of rated evaporative capacity [W/W]
Range: > 0
outdoor_unit_fan_flow_rate_per_unit_of_rated_evaporative_capacity
Outdoor Unit Fan Flow Rate Per Unit of Rated Evaporative Capacity
number
m3/s-W
7.5e-05 This field is only used if the previous is set to autocalculate and performance input method is NominalCapacity
Range: > 0
outdoor_unit_evaporating_temperature_function_of_superheating_curve_name
Outdoor Unit Evaporating Temperature Function of Superheating Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
outdoor_unit_condensing_temperature_function_of_subcooling_curve_name
Outdoor Unit Condensing Temperature Function of Subcooling Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
diameter_of_main_pipe_connecting_outdoor_unit_to_the_first_branch_joint
Diameter of Main Pipe Connecting Outdoor Unit to the First Branch Joint
number
m
0.0762 used to calculate the piping loss
Range: ≥ 0
length_of_main_pipe_connecting_outdoor_unit_to_the_first_branch_joint
Length of Main Pipe Connecting Outdoor Unit to the First Branch Joint
number
m
30.0 used to calculate the heat loss of the main pipe
Range: ≥ 0
equivalent_length_of_main_pipe_connecting_outdoor_unit_to_the_first_branch_joint
Equivalent Length of Main Pipe Connecting Outdoor Unit to the First Branch Joint
number
m
36.0 used to calculate the refrigerant pressure drop of the main pipe
Range: ≥ 0
height_difference_between_outdoor_unit_and_indoor_units
Height Difference Between Outdoor Unit and Indoor Units
number
m
5.0 Difference between outdoor unit height and indoor unit height Positive means outdoor unit is higher than indoor unit Negative means outdoor unit is lower than indoor unit
main_pipe_insulation_thickness
Main Pipe Insulation Thickness
number
m
0.02 Range: ≥ 0
main_pipe_insulation_thermal_conductivity
Main Pipe Insulation Thermal Conductivity
number
W/m-K
0.032 Range: ≥ 0
crankcase_heater_power_per_compressor
Crankcase Heater Power per Compressor
number
W
33.0 Enter the value of the resistive heater located in the compressor(s). This heater is used to warm the refrigerant and oil when the compressor is off
number_of_compressors
Number of Compressors
integer
dimensionless
2 Enter the total number of compressor. This input is used only for crankcase heater calculations.
ratio_of_compressor_size_to_total_compressor_capacity
Ratio of Compressor Size to Total Compressor Capacity
number
W/W
0.5 Enter the ratio of the first stage compressor to total compressor capacity All other compressors are assumed to be equally sized. This inputs is used only for crankcase heater calculations
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater
number
C
5.0 Enter the maximum outdoor temperature above which the crankcase heaters are disabled
defrost_strategy
Defrost Strategy
choice Resistive Select a defrost strategy. Reverse cycle reverses the operating mode from heating to cooling to melt frost formation on the condenser coil The resistive strategy uses a resistive heater to melt the frost.
One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed Choose a defrost control type Either use a fixed Timed defrost period or select OnDemand to defrost only when necessary
One of OnDemand, Timed
defrost_energy_input_ratio_modifier_function_of_temperature_curve_name
Defrost Energy Input Ratio Modifier Function of Temperature Curve Name
reference A valid performance curve must be used if ReverseCycle defrost strategy is selected
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
defrost_time_period_fraction
Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode Only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 Enter the size of the resistive defrost heating element Only applicable if resistive defrost strategy is specified
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-bulb Temperature for Defrost Operation
number
C
5.0 Enter the maximum outdoor temperature above which the defrost operation is disabled
compressor_maximum_delta_pressure
Compressor maximum delta Pressure
number
Pa
4500000.0 Range: ≥ 0, ≤ 5e+07
number_of_compressor_loading_index_entries
Number of Compressor Loading Index Entries
integer 2 First index represents minimal capacity operation Last index represents full capacity operation
Range: ≥ 2, ≤ 9
loading_indices list Each item: compressor_speed_at_loading_index (rev/min), loading_index_evaporative_capacity_multiplier_function_of_temperature_curve_name, loading_index_compressor_power_multiplier_function_of_temperature_curve_name

AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR

from idfpy.models import AirConditionerVariableRefrigerantFlowFluidTemperatureControlHR extensible

This is a key object in the new physics based VRF Heat Recovery (HR) model applicable for Fluid Temperature Control. It describes the VRF HR system excluding the performance of indoor units. Indoor units are modeled separately in the ZoneHVAC:TerminalUnit:VariableRefrigerantFlow object

Field Type Default Details
name
Name required
string Enter a unique name for this variable refrigerant flow heat pump
availability_schedule_name
Availability Schedule Name
reference Enter the name of a schedule that defines the availability of the unit Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_terminal_unit_list_name
Zone Terminal Unit List Name required
reference Enter the name of a ZoneTerminalUnitList. This list connects zone terminal units to this heat pump
Names a ZoneTerminalUnitList
refrigerant_type
Refrigerant Type
reference R410A Names a FluidProperties:Name
rated_evaporative_capacity
Rated Evaporative Capacity
number or Autosize
W
40000.0 Enter the total evaporative capacity in watts at rated conditions This is the capacity corresponding to the max compressor speed at rated conditions The actual evaporative capacity is obtained by multiplying the rated capacity with the modification factor calculated by Evaporative Capacity Multiplier Function of Temperature Curve
rated_compressor_power_per_unit_of_rated_evaporative_capacity
Rated Compressor Power Per Unit of Rated Evaporative Capacity
number
dimensionless
0.35 Enter the rated compressor power per Watt of rated evaporative capacity [W/W] Rated compressor power corresponds to the max compressor speed at rated conditions The actual compressor power is obtained by multiplying the rated power with the modification factor calculated by Compressor Power Multiplier Function of Temperature Curve
Range: > 0
minimum_outdoor_air_temperature_in_cooling_only_mode
Minimum Outdoor Air Temperature in Cooling Only Mode
number
C
-6.0 Enter the minimum outdoor temperature allowed for cooling operation Cooling is disabled below this temperature
maximum_outdoor_air_temperature_in_cooling_only_mode
Maximum Outdoor Air Temperature in Cooling Only Mode
number
C
43.0 Enter the maximum outdoor temperature allowed for cooling operation Cooling is disabled above this temperature
minimum_outdoor_air_temperature_in_heating_only_mode
Minimum Outdoor Air Temperature in Heating Only Mode
number
C
-20.0 Enter the minimum outdoor temperature allowed for heating operation Heating is disabled below this temperature
maximum_outdoor_air_temperature_in_heating_only_mode
Maximum Outdoor Air Temperature in Heating Only Mode
number
C
16.0 Enter the maximum outdoor temperature allowed for heating operation Heating is disabled below this temperature
minimum_outdoor_temperature_in_heat_recovery_mode
Minimum Outdoor Temperature in Heat Recovery Mode
number
C
-20.0 The minimum outdoor temperature below which heat recovery mode will not operate.
maximum_outdoor_temperature_in_heat_recovery_mode
Maximum Outdoor Temperature in Heat Recovery Mode
number
C
43.0 The maximum outdoor temperature above which heat recovery mode will not operate.
refrigerant_temperature_control_algorithm_for_indoor_unit
Refrigerant Temperature Control Algorithm for Indoor Unit
choice VariableTemp One of ConstantTemp, VariableTemp
reference_evaporating_temperature_for_indoor_unit
Reference Evaporating Temperature for Indoor Unit
number
C
6.0 This field is used if Refrigerant Temperature Control Algorithm is ConstantTemp Evaporating temperature is the refrigerant temperature, not air temperature
reference_condensing_temperature_for_indoor_unit
Reference Condensing Temperature for Indoor Unit
number
C
44.0 This field is used if Refrigerant Temperature Control Algorithm is ConstantTemp Condensing temperature is the refrigerant temperature, not air temperature
variable_evaporating_temperature_minimum_for_indoor_unit
Variable Evaporating Temperature Minimum for Indoor Unit
number
C
4.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Evaporating temperature is the refrigerant temperature, not air temperature
variable_evaporating_temperature_maximum_for_indoor_unit
Variable Evaporating Temperature Maximum for Indoor Unit
number
C
13.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Evaporating temperature is the refrigerant temperature, not air temperature
variable_condensing_temperature_minimum_for_indoor_unit
Variable Condensing Temperature Minimum for Indoor Unit
number
C
42.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Condensing temperature is the refrigerant temperature, not air temperature
variable_condensing_temperature_maximum_for_indoor_unit
Variable Condensing Temperature Maximum for Indoor Unit
number
C
46.0 This field is used if Refrigerant Temperature Control Algorithm is VariableTemp Condensing temperature is the refrigerant temperature, not air temperature
outdoor_unit_evaporator_reference_superheating
Outdoor Unit Evaporator Reference Superheating
number
deltaC
3.0
outdoor_unit_condenser_reference_subcooling
Outdoor Unit Condenser Reference Subcooling
number
deltaC
5.0
outdoor_unit_evaporator_rated_bypass_factor
Outdoor Unit Evaporator Rated Bypass Factor
number
dimensionless
0.4 Range: > 0
outdoor_unit_condenser_rated_bypass_factor
Outdoor Unit Condenser Rated Bypass Factor
number
dimensionless
0.2 Range: > 0
difference_between_outdoor_unit_evaporating_temperature_and_outdoor_air_temperature_in_heat_recovery_mode
Difference between Outdoor Unit Evaporating Temperature and Outdoor Air Temperature in Heat Recovery Mode
number
deltaC
5.0
outdoor_unit_heat_exchanger_capacity_ratio
Outdoor Unit Heat Exchanger Capacity Ratio
number
dimensionless
0.3 Enter the rated capacity ratio between the main and supplementary outdoor unit heat exchangers [W/W]
Range: > 0
outdoor_unit_fan_power_per_unit_of_rated_evaporative_capacity
Outdoor Unit Fan Power Per Unit of Rated Evaporative Capacity
number
dimensionless
0.00425 Enter the outdoor unit fan power per Watt of rated evaporative capacity [W/W]
Range: > 0
outdoor_unit_fan_flow_rate_per_unit_of_rated_evaporative_capacity
Outdoor Unit Fan Flow Rate Per Unit of Rated Evaporative Capacity
number
m3/s-W
7.5e-05 Enter the outdoor unit fan flow rate per Watt of rated evaporative capacity [W/W]
Range: > 0
outdoor_unit_evaporating_temperature_function_of_superheating_curve_name
Outdoor Unit Evaporating Temperature Function of Superheating Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
outdoor_unit_condensing_temperature_function_of_subcooling_curve_name
Outdoor Unit Condensing Temperature Function of Subcooling Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
diameter_of_main_pipe_for_suction_gas
Diameter of Main Pipe for Suction Gas
number
m
0.0762 used to calculate the piping loss
Range: ≥ 0
diameter_of_main_pipe_for_discharge_gas
Diameter of Main Pipe for Discharge Gas
number
m
0.0762 used to calculate the piping loss
Range: ≥ 0
length_of_main_pipe_connecting_outdoor_unit_to_the_first_branch_joint
Length of Main Pipe Connecting Outdoor Unit to the First Branch Joint
number
m
30.0 used to calculate the heat loss of the main pipe
Range: ≥ 0
equivalent_length_of_main_pipe_connecting_outdoor_unit_to_the_first_branch_joint
Equivalent Length of Main Pipe Connecting Outdoor Unit to the First Branch Joint
number
m
36.0 used to calculate the refrigerant pressure drop of the main pipe
Range: ≥ 0
height_difference_between_outdoor_unit_and_indoor_units
Height Difference Between Outdoor Unit and Indoor Units
number
m
5.0 Difference between outdoor unit height and indoor unit height Positive means outdoor unit is higher than indoor unit Negative means outdoor unit is lower than indoor unit
main_pipe_insulation_thickness
Main Pipe Insulation Thickness
number
m
0.02 Range: ≥ 0
main_pipe_insulation_thermal_conductivity
Main Pipe Insulation Thermal Conductivity
number
W/m-K
0.032 Range: ≥ 0
crankcase_heater_power_per_compressor
Crankcase Heater Power per Compressor
number
W
33.0 Enter the value of the resistive heater located in the compressor(s). This heater is used to warm the refrigerant and oil when the compressor is off
number_of_compressors
Number of Compressors
integer
dimensionless
2 Enter the total number of compressor. This input is used only for crankcase heater calculations.
ratio_of_compressor_size_to_total_compressor_capacity
Ratio of Compressor Size to Total Compressor Capacity
number
W/W
0.5 Enter the ratio of the first stage compressor to total compressor capacity All other compressors are assumed to be equally sized. This inputs is used only for crankcase heater calculations
maximum_outdoor_dry_bulb_temperature_for_crankcase_heater
Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater
number
C
5.0 Enter the maximum outdoor temperature above which the crankcase heaters are disabled
defrost_strategy
Defrost Strategy
choice Resistive Select a defrost strategy. Reverse cycle reverses the operating mode from heating to cooling to melt frost formation on the condenser coil The resistive strategy uses a resistive heater to melt the frost.
One of Resistive, ReverseCycle
defrost_control
Defrost Control
choice Timed Choose a defrost control type Either use a fixed Timed defrost period or select OnDemand to defrost only when necessary
One of OnDemand, Timed
defrost_energy_input_ratio_modifier_function_of_temperature_curve_name
Defrost Energy Input Ratio Modifier Function of Temperature Curve Name
reference A valid performance curve must be used if ReverseCycle defrost strategy is selected
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
defrost_time_period_fraction
Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode Only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number or Autosize
W
0.0 Enter the size of the resistive defrost heating element Only applicable if resistive defrost strategy is specified
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-bulb Temperature for Defrost Operation
number
C
5.0 Enter the maximum outdoor temperature above which the defrost operation is disabled
initial_heat_recovery_cooling_capacity_fraction
Initial Heat Recovery Cooling Capacity Fraction
number
W/W
1.0 This is used to describe the transition from Cooling Only mode to Heat Recovery mode Enter the fractional capacity available at the start of heat recovery mode. The capacity exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Capacity Modifier and Heat Recovery Cooling Capacity Time Constant
heat_recovery_cooling_capacity_time_constant
Heat Recovery Cooling Capacity Time Constant
number
hr
0.0 This is used to describe the transition from Cooling Only mode to Heat Recovery mode Enter the time constant used to model the transition from cooling only mode to heat recovery mode
initial_heat_recovery_cooling_energy_fraction
Initial Heat Recovery Cooling Energy Fraction
number
W/W
1.0 This is used to describe the transition from Cooling Only mode to Heat Recovery mode Enter the fractional electric consumption rate at the start of heat recovery mode. The electric consumption rate exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Energy Modifier and Heat Recovery Cooling Energy Time Constant
heat_recovery_cooling_energy_time_constant
Heat Recovery Cooling Energy Time Constant
number
hr
0.0 This is used to describe the transition from Cooling Only mode to Heat Recovery mode Enter the time constant used to model the transition from cooling only mode to heat recovery mode
initial_heat_recovery_heating_capacity_fraction
Initial Heat Recovery Heating Capacity Fraction
number
W/W
1.0 This is used to describe the transition from Heating Only mode to Heat Recovery mode Enter the fractional capacity available at the start of heat recovery mode. The capacity exponentially approaches the steady-state value according to the inputs for Heat Recovery Heating Capacity Modifier and Heat Recovery Heating Capacity Time Constant
heat_recovery_heating_capacity_time_constant
Heat Recovery Heating Capacity Time Constant
number
hr
0.0 This is used to describe the transition from Heating Only mode to Heat Recovery mode Enter the time constant used to model the transition from cooling only mode to heat recovery mode
initial_heat_recovery_heating_energy_fraction
Initial Heat Recovery Heating Energy Fraction
number
W/W
1.0 This is used to describe the transition from Heating Only mode to Heat Recovery mode Enter the fractional electric consumption rate at the start of heat recovery mode. The electric consumption rate exponentially approaches the steady-state value according to the inputs for Heat Recovery Cooling Energy Modifier and Heat Recovery Cooling Energy Time Constant
heat_recovery_heating_energy_time_constant
Heat Recovery Heating Energy Time Constant
number
hr
0.0 This is used to describe the transition from Heating Only mode to Heat Recovery mode Enter the time constant used to model the transition from cooling only mode to heat recovery mode
compressor_maximum_delta_pressure
Compressor maximum delta Pressure
number
Pa
4500000.0 Range: ≥ 0, ≤ 5e+07
compressor_inverter_efficiency
Compressor Inverter Efficiency
number
dimensionless
0.95 Efficiency of the compressor inverter
Range: > 0, ≤ 1
compressor_evaporative_capacity_correction_factor
Compressor Evaporative Capacity Correction Factor
number
dimensionless
1.0 Describe the evaporative capacity difference because of system configuration difference between test bed and real system.
Range: > 0
number_of_compressor_loading_index_entries
Number of Compressor Loading Index Entries
integer 2 Load index describe the compressor operational state, either a single compressor or multiple compressors, at different load levels. First index represents minimal capacity operation Last index represents full capacity operation
Range: ≥ 2
loading_indices list Each item: compressor_speed_at_loading_index (rev/min), loading_index_evaporative_capacity_multiplier_function_of_temperature_curve_name, loading_index_compressor_power_multiplier_function_of_temperature_curve_name

AirLoopHVAC:ControllerList

from idfpy.models import AirLoopHVACControllerList

List controllers in order of control sequence

Field Type Default Details
name
Name required
string
controller_1_object_type
Controller 1 Object Type required
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_1_name
Controller 1 Name required
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_2_object_type
Controller 2 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_2_name
Controller 2 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_3_object_type
Controller 3 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_3_name
Controller 3 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_4_object_type
Controller 4 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_4_name
Controller 4 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_5_object_type
Controller 5 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_5_name
Controller 5 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_6_object_type
Controller 6 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_6_name
Controller 6 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_7_object_type
Controller 7 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_7_name
Controller 7 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
controller_8_object_type
Controller 8 Object Type
choice One of Controller:OutdoorAir, Controller:WaterCoil
controller_8_name
Controller 8 Name
reference Names a Controller:OutdoorAir, Controller:WaterCoil
Referenced by 2 object types

AirLoopHVAC, AirLoopHVAC:OutdoorAirSystem

AirflowNetwork:Distribution:Component:Coil

from idfpy.models import AirflowNetworkDistributionComponentCoil

This object defines the name of a coil used in an air loop.

Field Type Default Details
coil_name
Coil Name required
reference Enter the name of a cooling or heating coil in the primary Air loop.
Names a Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:Heating:DX:MultiSpeed and 8 more
coil_object_type
Coil Object Type required
choice Select the type of coil corresponding to the name entered in the field above.
One of Coil:Cooling:DX, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:Heating:DX:MultiSpeed, Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableSpeed, Coil:Heating:Desuperheater, Coil:Heating:Electric, Coil:Heating:Electric:MultiStage, Coil:Heating:Fuel, Coil:Heating:Gas:MultiStage, Coil:Heating:Water, Coil:Heating:WaterToAirHeatPump:EquationFit, Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit
air_path_length
Air Path Length required
number
m
Enter the air path length (depth) for the coil.
Range: > 0
air_path_hydraulic_diameter
Air Path Hydraulic Diameter required
number
m
Enter the hydraulic diameter of this coil. The hydraulic diameter is defined as 4 multiplied by the cross section area divided by perimeter.
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:ConstantPressureDrop

from idfpy.models import AirflowNetworkDistributionComponentConstantPressureDrop

This object defines the characteristics of a constant pressure drop component (e.g. filter). Each node connected to this object can not be a node of mixer, splitter, a node of air primary loop, or zone equipment loop. It is recommended to connect to a duct component at both ends.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
pressure_difference_across_the_component
Pressure Difference Across the Component required
number
Pa
Enter the pressure drop across this component.
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:Duct

from idfpy.models import AirflowNetworkDistributionComponentDuct

This object defines the relationship between pressure and air flow through the duct.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
duct_length
Duct Length required
number
m
Enter the length of the duct.
Range: > 0
hydraulic_diameter
Hydraulic Diameter required
number
m
Enter the hydraulic diameter of the duct. Hydraulic diameter is defined as 4 multiplied by cross section area divided by perimeter
Range: > 0
cross_section_area
Cross Section Area required
number
m2
Enter the cross section area of the duct.
Range: > 0
surface_roughness
Surface Roughness
number
m
0.0009 Enter the inside surface roughness of the duct.
Range: > 0
coefficient_for_local_dynamic_loss_due_to_fitting
Coefficient for Local Dynamic Loss Due to Fitting
number
dimensionless
0.0 Enter the coefficient used to calculate dynamic losses of fittings (e.g. elbows).
Range: ≥ 0
heat_transmittance_coefficient_u_factor_for_duct_wall_construction
Heat Transmittance Coefficient (U-Factor) for Duct Wall Construction
number
W/m2-K
0.943 conduction only Default value of 0.943 is equivalent to 1.06 m2-K/W (R6) duct insulation.
Range: > 0
overall_moisture_transmittance_coefficient_from_air_to_air
Overall Moisture Transmittance Coefficient from Air to Air
number
kg/m2
0.001 Enter the overall moisture transmittance coefficient including moisture film coefficients at both surfaces.
Range: > 0
outside_convection_coefficient
Outside Convection Coefficient
number
W/m2-K
optional. convection coefficient calculated automatically, unless specified
Range: > 0
inside_convection_coefficient
Inside Convection Coefficient
number
W/m2-K
optional. convection coefficient calculated automatically, unless specified
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:Fan

from idfpy.models import AirflowNetworkDistributionComponentFan

This object defines the name of the supply Air Fan used in an Air loop.

Field Type Default Details
fan_name
Fan Name required
reference Enter the name of the fan in the primary air loop.
Names a Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel, Fan:VariableVolume
supply_fan_object_type
Supply Fan Object Type
choice Fan:ConstantVolume One of Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel, Fan:VariableVolume
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:HeatExchanger

from idfpy.models import AirflowNetworkDistributionComponentHeatExchanger

This object defines the name of an air-to-air heat exchanger used in an air loop.

Field Type Default Details
heatexchanger_name
HeatExchanger Name required
reference Enter the name of an air-to-air heat exchanger in the primary Air loop.
Names a HeatExchanger:AirToAir:FlatPlate, HeatExchanger:AirToAir:SensibleAndLatent, HeatExchanger:Desiccant:BalancedFlow
heatexchanger_object_type
HeatExchanger Object Type required
choice Select the type of heat exchanger corresponding to the name entered in the field above.
One of HeatExchanger:AirToAir:FlatPlate, HeatExchanger:AirToAir:SensibleAndLatent, HeatExchanger:Desiccant:BalancedFlow
air_path_length
Air Path Length required
number
m
Enter the air path length (depth) for the heat exchanger.
Range: > 0
air_path_hydraulic_diameter
Air Path Hydraulic Diameter required
number
m
Enter the hydraulic diameter of this heat exchanger. The hydraulic diameter is defined as 4 multiplied by the cross section area divided by perimeter.
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:Leak

from idfpy.models import AirflowNetworkDistributionComponentLeak

This object defines the characteristics of a supply or return air leak.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_mass_flow_coefficient
Air Mass Flow Coefficient required
number
kg/s
Defined at 1 Pa pressure difference across this component. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent
Range: > 0
air_mass_flow_exponent
Air Mass Flow Exponent
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent
Range: ≥ 0.5, ≤ 1
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:LeakageRatio

from idfpy.models import AirflowNetworkDistributionComponentLeakageRatio

This object is used to define supply and return air leaks with respect to the fan's maximum air flow rate.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
effective_leakage_ratio
Effective Leakage Ratio
number
dimensionless
Defined as a ratio of leak flow rate to the maximum flow rate.
Range: > 0, ≤ 1
maximum_flow_rate
Maximum Flow Rate required
number
m3/s
Enter the maximum air flow rate in this air loop.
Range: > 0
reference_pressure_difference
Reference Pressure Difference required
number
Pa
Enter the pressure corresponding to the Effective leakage ratio entered above.
Range: > 0
air_mass_flow_exponent
Air Mass Flow Exponent
number
dimensionless
0.65 Enter the exponent used in the air mass flow equation.
Range: ≥ 0.5, ≤ 1
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:OutdoorAirFlow

from idfpy.models import AirflowNetworkDistributionComponentOutdoorAirFlow

This object includes the outdoor air flow rate set by the Controller:OutdoorAir object in the airflow network.

Field Type Default Details
name
Name required
string
outdoor_air_mixer_name
Outdoor Air Mixer Name required
reference Names a OutdoorAir:Mixer
air_mass_flow_coefficient_when_no_outdoor_air_flow_at_reference_conditions
Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions required
number
kg/s
Enter the air mass flow coefficient at the conditions defined in the Reference Crack Conditions object. Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Range: > 0
air_mass_flow_exponent_when_no_outdoor_air_flow
Air Mass Flow Exponent When No Outdoor Air Flow
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Range: ≥ 0.5, ≤ 1
reference_crack_conditions
Reference Crack Conditions
reference Select a AirflowNetwork:MultiZone:ReferenceCrackConditions name associated with the air mass flow coefficient entered above.
Names a AirflowNetwork:MultiZone:ReferenceCrackConditions
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:Component:ReliefAirFlow

from idfpy.models import AirflowNetworkDistributionComponentReliefAirFlow

This object allows variation of air flow rate to perform pressure.

Field Type Default Details
name
Name required
string
outdoor_air_mixer_name
Outdoor Air Mixer Name required
reference Names a OutdoorAir:Mixer
air_mass_flow_coefficient_when_no_outdoor_air_flow_at_reference_conditions
Air Mass Flow Coefficient When No Outdoor Air Flow at Reference Conditions required
number
kg/s
Enter the air mass flow coefficient at the conditions defined in the Reference Crack Conditions object. Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Range: > 0
air_mass_flow_exponent_when_no_outdoor_air_flow
Air Mass Flow Exponent When No Outdoor Air Flow
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when no outdoor air flow rate.
Range: ≥ 0.5, ≤ 1
reference_crack_conditions
Reference Crack Conditions
reference Select a AirflowNetwork:MultiZone:ReferenceCrackConditions name associated with the air mass flow coefficient entered above.
Names a AirflowNetwork:MultiZone:ReferenceCrackConditions
Referenced by 4 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage, AirflowNetwork:ZoneControl:PressureController

AirflowNetwork:Distribution:Component:TerminalUnit

from idfpy.models import AirflowNetworkDistributionComponentTerminalUnit

This object defines the name of a terminal unit in an air loop.

Field Type Default Details
terminal_unit_name
Terminal Unit Name required
reference Enter the name of a terminal unit in the AirLoopHVAC.
Names a AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:VAV:Reheat
terminal_unit_object_type
Terminal Unit Object Type required
choice Select the type of terminal unit corresponding to the name entered in the field above.
One of AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:VAV:Reheat
air_path_length
Air Path Length required
number
m
Enter the air path length (depth) for the terminal unit.
Range: > 0
air_path_hydraulic_diameter
Air Path Hydraulic Diameter required
number
m
Enter the hydraulic diameter of this terminal unit. The hydraulic diameter is defined as 4 multiplied by the cross section area divided by perimeter.
Range: > 0
Referenced by 3 object types

AirflowNetwork:Distribution:DuctViewFactors, AirflowNetwork:Distribution:Linkage, AirflowNetwork:IntraZone:Linkage

AirflowNetwork:Distribution:DuctSizing

from idfpy.models import AirflowNetworkDistributionDuctSizing unique

This object defines required parameters for duct sizing in an Airflow Network simulation. To activate duct sizing, see AirflowNetwork:SimulationControl Do Distribution Duct Sizing Calculation.

Field Type Default Details
name
Name required
string
duct_sizing_method
Duct Sizing Method
choice MaximumVelocity One of MaximumVelocity, PressureLoss, PressureLossWithMaximumVelocity
duct_sizing_factor
Duct Sizing Factor
number 1.0 Range: > 0
maximum_airflow_velocity
Maximum Airflow Velocity
number
m/s
5.0 Used only if Duct Sizing Type = MaximumVelocity or PressureLossWithMaximumVelocity. When MaximumVelocity is entered, duct diameter is calculated at D = flow rate / cross section area. When PressureLossWithMaximumVelocity is entered, duct diameter is calculated based on PressureLoss. The value is used to check to ensure the final velocity is less than the maximum value. If greater, final value will be obtained from MaximumVelocity. This field is apply for trunk size, while branch size is based on total pressure drop.
Range: > 0, ≤ 25
total_pressure_loss_across_supply_trunk
Total Pressure Loss Across Supply Trunk
number
Pa
Used only if Duct Sizing Type = PressureLoss or PressureLossWithMaximumVelocity. When PressureLoss is entered, duct diameter is calculated using Colebrook's equation When PressureLossWithMaximumVelocity is entered, duct diameter is calculated based on PressureLoss. The value is used to check to ensure the final velocity is less than the maximum value. If greater, final value will be obtained from MaximumVelocity. This field is apply for trunk size, while branch size is based on total pressure drop.
Range: > 0
total_pressure_loss_across_supply_branch
Total Pressure Loss Across Supply Branch
number
Pa
Duct diameter is calculated using Colebrook's equation. When there is no solution, velocity = 5 m/s is used to calculate duct diameter.
Range: > 0
total_pressure_loss_across_return_trunk
Total Pressure Loss Across Return Trunk
number
Pa
Duct diameter is calculated using Colebrook's equation. When there is no solution, velocity = 5 m/s is used to calculate duct diameter.
Range: > 0
total_pressure_loss_across_return_branch
Total Pressure Loss Across Return Branch
number
Pa
Duct diameter is calculated using Colebrook's equation. When there is no solution, velocity = 5 m/s is used to calculate duct diameter.
Range: > 0

AirflowNetwork:Distribution:DuctViewFactors

from idfpy.models import AirflowNetworkDistributionDuctViewFactors extensible

This object is used to allow user-defined view factors to be used for duct-surface radiation calculations. All surfaces must be in the same enclosure.

Field Type Default Details
linkage_name
Linkage Name required
reference Names a AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Component:ConstantPressureDrop, AirflowNetwork:Distribution:Component:Duct, AirflowNetwork:Distribution:Component:Fan, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Component:Leak, AirflowNetwork:Distribution:Component:LeakageRatio, AirflowNetwork:Distribution:Component:OutdoorAirFlow, AirflowNetwork:Distribution:Component:ReliefAirFlow, AirflowNetwork:Distribution:Component:TerminalUnit
duct_surface_exposure_fraction
Duct Surface Exposure Fraction
number 0.0 Range: ≥ 0, ≤ 1
duct_surface_emittance
Duct Surface Emittance
number 0.9 Range: ≥ 0, ≤ 1
surfaces list Each item: surface_name, surface_view_factor

AirflowNetwork:Distribution:Linkage

from idfpy.models import AirflowNetworkDistributionLinkage

This object defines the connection between two nodes and a component.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
node_1_name
Node 1 Name required
reference Enter the name of zone or AirflowNetwork Node.
Names a AirflowNetwork:Distribution:Node, Zone
node_2_name
Node 2 Name required
reference Enter the name of zone or AirflowNetwork Node.
Names a AirflowNetwork:Distribution:Node, Zone
component_name
Component Name required
reference Enter the name of an AirflowNetwork component. A component is one of the following AirflowNetwork:Distribution:Component objects: Leak, LeakageRatio, Duct, ConstantVolumeFan, Coil, TerminalUnit, ConstantPressureDrop, or HeatExchanger.
Names a AirTerminal:SingleDuct:ConstantVolume:NoReheat, AirTerminal:SingleDuct:ConstantVolume:Reheat, AirTerminal:SingleDuct:VAV:Reheat, AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Component:ConstantPressureDrop, AirflowNetwork:Distribution:Component:Duct, AirflowNetwork:Distribution:Component:Fan, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Component:Leak, AirflowNetwork:Distribution:Component:LeakageRatio, AirflowNetwork:Distribution:Component:OutdoorAirFlow, AirflowNetwork:Distribution:Component:ReliefAirFlow and 27 more
thermal_zone_name
Thermal Zone Name
reference Only used if component = AirflowNetwork:Distribution:Component:Duct The zone name is where AirflowNetwork:Distribution:Component:Duct is exposed. Leave this field blank if the duct conduction loss is ignored.
Names a Zone
Referenced by 3 object types

Duct:Loss:Conduction, Duct:Loss:Leakage, Duct:Loss:MakeupAir

AirflowNetwork:Distribution:Node

from idfpy.models import AirflowNetworkDistributionNode

This object represents an air distribution node in the AirflowNetwork model.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
component_name_or_node_name
Component Name or Node Name
string Designates node names defined in another object. The node name may occur in air branches. Enter a node name to represent a node already defined in an air loop. Leave this field blank if the Node or Object Type field below is entered as AirLoopHVAC:ZoneMixer, AirLoopHVAC:ZoneSplitter, AirLoopHVAC:OutdoorAirSystem, or Other.
component_object_type_or_node_type
Component Object Type or Node Type
choice Other Designates Node type for the Node or Component Name defined in the field above. AirLoopHVAC:ZoneMixer -- Represents a AirLoopHVAC:ZoneMixer object. AirLoopHVAC:ZoneSplitter -- Represents a AirLoopHVAC:ZoneSplitter object. AirLoopHVAC:OutdoorAirSystem -- Represents an AirLoopHVAC:OutdoorAirSystem object. OAMixerOutdoorAirStreamNode -- Represents an external node used in the OutdoorAir:Mixer OutdoorAir:NodeList -- Represents an external node when a heat exchanger is used before the OutdoorAir:Mixer OutdoorAir:Node -- Represents an external node when a heat exchanger is used before the OutdoorAir:Mixer Other -- none of the above, the Node name already defined in the previous field is part of an air loop. Zone -- Enter a zone name for duct simple model to calculate duct loss without using AFN model.
One of AirLoopHVAC:OutdoorAirSystem, AirLoopHVAC:ZoneMixer, AirLoopHVAC:ZoneSplitter, OAMixerOutdoorAirStreamNode, Other, OutdoorAir:Node, OutdoorAir:NodeList, Zone
node_height
Node Height
number
m
0.0 Enter the reference height used to calculate the relative pressure.
Referenced by 1 object types

AirflowNetwork:Distribution:Linkage

AirflowNetwork:IntraZone:Linkage

from idfpy.models import AirflowNetworkIntraZoneLinkage

This object defines the connection between two nodes and a component used in the combination of RoomAir and AirflowNetwork model.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
node_1_name
Node 1 Name required
reference Enter the name of zone or AirflowNetwork Node.
Names a AirflowNetwork:IntraZone:Node, Zone
node_2_name
Node 2 Name required
reference Enter the name of zone or AirflowNetwork Node.
Names a AirflowNetwork:IntraZone:Node, Zone
component_name
Component Name
reference Enter the name of an AirflowNetwork component. A component is one of the following AirflowNetwork:Multizone:Component objects: AirflowNetwork:MultiZone:Surface:Crack, AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea, If the next field is specified, this field can be either blank or ignored.
Names a AirflowNetwork:Distribution:Component:Coil, AirflowNetwork:Distribution:Component:ConstantPressureDrop, AirflowNetwork:Distribution:Component:Duct, AirflowNetwork:Distribution:Component:Fan, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Component:Leak, AirflowNetwork:Distribution:Component:LeakageRatio, AirflowNetwork:Distribution:Component:OutdoorAirFlow, AirflowNetwork:Distribution:Component:ReliefAirFlow, AirflowNetwork:Distribution:Component:TerminalUnit
airflownetwork_multizone_surface_name
AirflowNetwork:MultiZone:Surface Name
reference Only used when one of two nodes defined above are not located in the same zone, and the input of the Component Name field in this object is ignored
Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Door, Door:Interzone, FenestrationSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, GlazedDoor, GlazedDoor:Interzone and 9 more

AirflowNetwork:IntraZone:Node

from idfpy.models import AirflowNetworkIntraZoneNode

This object represents a node in a zone in the combination of RoomAir and AirflowNetwork model.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
roomair_node_airflownetwork_name
RoomAir:Node:AirflowNetwork Name required
reference Enter the name of a RoomAir:Node object defined in a RoomAirSettings:AirflowNetwork object.
Names a RoomAir:Node:AirflowNetwork
zone_name
Zone Name required
reference Enter the name of a zone object defined in a AirflowNetwork:MultiZone:Zone object.
Names a AirflowNetwork:MultiZone:Zone
node_height
Node Height
number
m
0.0 Enter the reference height used to calculate the relative pressure
Referenced by 1 object types

AirflowNetwork:IntraZone:Linkage

AirflowNetwork:MultiZone:Component:DetailedOpening

from idfpy.models import AirflowNetworkMultiZoneComponentDetailedOpening

This object specifies the properties of airflow through windows and doors (window, door and glass door heat transfer subsurfaces) when they are closed or open.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_mass_flow_coefficient_when_opening_is_closed
Air Mass Flow Coefficient When Opening is Closed required
number
kg/s-m
Defined at 1 Pa per meter of crack length. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening (window or door) is closed.
Range: > 0
air_mass_flow_exponent_when_opening_is_closed
Air Mass Flow Exponent When Opening is Closed
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening (window or door) is closed.
Range: ≥ 0.5, ≤ 1
type_of_rectangular_large_vertical_opening_lvo
Type of Rectangular Large Vertical Opening (LVO)
choice NonPivoted Select the type of vertical opening: Non-pivoted opening or Horizontally pivoted opening.
One of HorizontallyPivoted, NonPivoted
extra_crack_length_or_height_of_pivoting_axis
Extra Crack Length or Height of Pivoting Axis
number
m
0.0 Extra crack length is used for LVO Non-pivoted type with multiple openable parts. Height of pivoting axis is used for LVO Horizontally pivoted type. Specifies window or door characteristics that depend on the LVO type. For Non-pivoted Type (rectangular windows and doors), this field is the extra crack length in meters due to multiple openable parts, if present. Extra here means in addition to the length of the cracks on the top, bottom and sides of the window/door. For Horizontally pivoted Type, this field gives the height of the pivoting axis measured from the bottom of the glazed part of the window (m).
Range: ≥ 0
number_of_sets_of_opening_factor_data
Number of Sets of Opening Factor Data required
integer Enter the number of the following sets of data for opening factor, discharge coefficient, width factor, height factor, and start height factor.
Range: ≥ 2, ≤ 4
opening_factor_1
Opening Factor 1
number
dimensionless
0.0 This value must be specified as 0.
Range: ≥ 0, ≤ 0
discharge_coefficient_for_opening_factor_1
Discharge Coefficient for Opening Factor 1
number
dimensionless
0.001 The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Range: > 0, ≤ 1
width_factor_for_opening_factor_1
Width Factor for Opening Factor 1
number
dimensionless
0.0 The Width Factor is the opening width divided by the window or door width.
Range: ≥ 0, ≤ 1
height_factor_for_opening_factor_1
Height Factor for Opening Factor 1
number
dimensionless
0.0 The Height Factor is the opening height divided by the window or door height.
Range: ≥ 0, ≤ 1
start_height_factor_for_opening_factor_1
Start Height Factor for Opening Factor 1
number
dimensionless
0.0 The Start Height Factor is the Start Height divided by the window or door height. Start Height is the distance between the bottom of the window or door and the bottom of the window or door opening. The sum of the Height Factor and the Start Height Factor must be less than 1.0 in order to have the opening within the window or door dimensions.
Range: ≥ 0, ≤ 1
opening_factor_2
Opening Factor 2 required
number
dimensionless
If Number of Sets of Opening Factor Data = 2, this value must be 1.0. If Number of Sets of Opening Factor Data = 3, this value must be less than 1.0. If Number of Sets of Opening Factor Data = 4, this value must be less than the value entered for Opening factor 3 and greater than the value entered for Opening factor 1.
Range: > 0, ≤ 1
discharge_coefficient_for_opening_factor_2
Discharge Coefficient for Opening Factor 2
number
dimensionless
1.0 The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Range: > 0, ≤ 1
width_factor_for_opening_factor_2
Width Factor for Opening Factor 2
number
dimensionless
1.0 The Width Factor is the opening width divided by the window or door width.
Range: > 0, ≤ 1
height_factor_for_opening_factor_2
Height Factor for Opening Factor 2
number
dimensionless
1.0 The Height Factor is the opening height divided by the window or door height.
Range: > 0, ≤ 1
start_height_factor_for_opening_factor_2
Start Height Factor for Opening Factor 2
number
dimensionless
0.0 The Start Height Factor is the Start Height divided by the window or door height. Start Height is the distance between the bottom of the window or door and the bottom of the window or door opening. The sum of the Height Factor and the Start Height Factor must be less than 1.0 in order to have the opening within the window or door dimensions.
Range: ≥ 0, < 1
opening_factor_3
Opening Factor 3
number
dimensionless
If Number of Sets of Opening Factor Data = 3, this value must be 1.0. If Number of Sets of Opening Factor Data = 4, this value must be less than 1.0, and greater than value entered for Opening factor 2.
Range: ≥ 0, ≤ 1
discharge_coefficient_for_opening_factor_3
Discharge Coefficient for Opening Factor 3
number
dimensionless
0.0 The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Range: ≥ 0, ≤ 1
width_factor_for_opening_factor_3
Width Factor for Opening Factor 3
number
dimensionless
0.0 The Width Factor is the opening width divided by the window or door width.
Range: ≥ 0, ≤ 1
height_factor_for_opening_factor_3
Height Factor for Opening Factor 3
number
dimensionless
0.0 The Height Factor is the opening height divided by the window or door height.
Range: ≥ 0, ≤ 1
start_height_factor_for_opening_factor_3
Start Height Factor for Opening Factor 3
number
dimensionless
0.0 The Start Height Factor is the Start Height divided by the window or door height. Start Height is the distance between the bottom of the window or door and the bottom of the window or door opening. The sum of the Height Factor and the Start Height Factor must be less than 1.0 in order to have the opening within the window or door dimensions.
Range: ≥ 0, ≤ 1
opening_factor_4
Opening Factor 4
number
dimensionless
If Number of Sets of Opening Factor Data = 4, this value must be 1.0
Range: ≥ 0, ≤ 1
discharge_coefficient_for_opening_factor_4
Discharge Coefficient for Opening Factor 4
number
dimensionless
0.0 The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Range: ≥ 0, ≤ 1
width_factor_for_opening_factor_4
Width Factor for Opening Factor 4
number
dimensionless
0.0 The Width Factor is the opening width divided by the window or door width.
Range: ≥ 0, ≤ 1
height_factor_for_opening_factor_4
Height Factor for Opening Factor 4
number
dimensionless
0.0 The Height Factor is the opening height divided by the window or door height.
Range: ≥ 0, ≤ 1
start_height_factor_for_opening_factor_4
Start Height Factor for Opening Factor 4
number
dimensionless
0.0 The Start Height Factor is the Start Height divided by the window or door height. Start Height is the distance between the bottom of the window or door and the bottom of the window or door opening. The sum of the Height Factor and the Start Height Factor must be less than 1.0 in order to have the opening within the window or door dimensions.
Range: ≥ 0, ≤ 1
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:Component:HorizontalOpening

from idfpy.models import AirflowNetworkMultiZoneComponentHorizontalOpening

This object specifies the properties of air flow through a horizontal opening

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_mass_flow_coefficient_when_opening_is_closed
Air Mass Flow Coefficient When Opening is Closed required
number
kg/s-m
Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass flow rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening is closed.
Range: > 0
air_mass_flow_exponent_when_opening_is_closed
Air Mass Flow Exponent When Opening is Closed
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass flow rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening is closed.
Range: ≥ 0.5, ≤ 1
sloping_plane_angle
Sloping Plane Angle
number
deg
90.0 Sloping plane angle = 90 is equivalent to fully open.
Range: > 0, ≤ 90
discharge_coefficient
Discharge Coefficient required
number
dimensionless
The Discharge Coefficient indicates the fractional effectiveness for air flow through the opening at that Opening Factor.
Range: > 0
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:Component:SimpleOpening

from idfpy.models import AirflowNetworkMultiZoneComponentSimpleOpening

This object specifies the properties of air flow through windows and doors (window, door and glass door heat transfer subsurfaces) when they are closed or open.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_mass_flow_coefficient_when_opening_is_closed
Air Mass Flow Coefficient When Opening is Closed required
number
kg/s-m
Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening (window or door) is closed.
Range: > 0
air_mass_flow_exponent_when_opening_is_closed
Air Mass Flow Exponent When Opening is Closed
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when opening (window or door) is closed.
Range: ≥ 0.5, ≤ 1
minimum_density_difference_for_two_way_flow
Minimum Density Difference for Two-Way Flow required
number
kg/m3
Enter the minimum density difference above which two-way flow may occur due to stack effect.
Range: > 0
discharge_coefficient
Discharge Coefficient required
number
dimensionless
The Discharge Coefficient indicates the fractional effectiveness for air flow through a window or door at that Opening Factor.
Range: > 0
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:Component:ZoneExhaustFan

from idfpy.models import AirflowNetworkMultiZoneComponentZoneExhaustFan

This object specifies the additional properties for a zone exhaust fan to perform multizone airflow calculations.

Field Type Default Details
name
Name required
reference Enter the name of a Fan:ZoneExhaust object.
Names a Fan:ZoneExhaust
air_mass_flow_coefficient_when_the_zone_exhaust_fan_is_off_at_reference_conditions
Air Mass Flow Coefficient When the Zone Exhaust Fan is Off at Reference Conditions required
number
kg/s
Enter the air mass flow coefficient at the conditions defined in the Reference Crack Conditions object. Defined at 1 Pa pressure difference. Enter the coefficient used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when the fan is off.
Range: > 0
air_mass_flow_exponent_when_the_zone_exhaust_fan_is_off
Air Mass Flow Exponent When the Zone Exhaust Fan is Off
number
dimensionless
0.65 Enter the exponent used in the following equation: Mass Flow Rate = Air Mass Flow Coefficient * (dP)^Air Mass Flow Exponent. Used only when the fan is off.
Range: ≥ 0.5, ≤ 1
reference_crack_conditions
Reference Crack Conditions
reference Select a AirflowNetwork:MultiZone:ReferenceCrackConditions name associated with the air mass flow coefficient entered above.
Names a AirflowNetwork:MultiZone:ReferenceCrackConditions
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:ExternalNode

from idfpy.models import AirflowNetworkMultiZoneExternalNode

This object defines outdoor environmental conditions outside of the building.

Field Type Default Details
name
Name required
string Enter a unique name for this object. This node name will be referenced by a particular building facade.
external_node_height
External Node Height
number
m
0.0 Designates the reference height used to calculate relative pressure.
wind_pressure_coefficient_curve_name
Wind Pressure Coefficient Curve Name required
reference The name of the AirflowNetwork:MultiZone:WindPressureCoefficientValues, curve, or table object specifying the wind pressure coefficient.
Names a AirflowNetwork:MultiZone:WindPressureCoefficientValues, Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2 and 2 more
symmetric_wind_pressure_coefficient_curve
Symmetric Wind Pressure Coefficient Curve
choice No Specify whether the pressure curve is symmetric or not. Specify Yes for curves that should be evaluated from 0 to 180 degrees Specify No for curves that should be evaluated from 0 to 360 degrees
One of No, Yes
wind_angle_type
Wind Angle Type
choice Absolute Specify whether the angle used to compute the wind pressure coefficient is absolute or relative Specify Relative to compute the angle between the wind direction and the surface azimuth Specify Absolute to use the wind direction angle directly
One of Absolute, Relative
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:ReferenceCrackConditions

from idfpy.models import AirflowNetworkMultiZoneReferenceCrackConditions

This object specifies the conditions under which the air mass flow coefficient was measured.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
reference_temperature
Reference Temperature required
number
C
Enter the reference temperature under which the surface crack data were obtained. Suggested value 20C.
reference_barometric_pressure
Reference Barometric Pressure
number
Pa
101325.0 Enter the reference barometric pressure under which the surface crack data were obtained.
Range: ≥ 31000, ≤ 120000
reference_humidity_ratio
Reference Humidity Ratio
number
kgWater/kgDryAir
0.0 Enter the reference humidity ratio under which the surface crack data were obtained.
Referenced by 4 object types

AirflowNetwork:Distribution:Component:OutdoorAirFlow, AirflowNetwork:Distribution:Component:ReliefAirFlow, AirflowNetwork:MultiZone:Component:ZoneExhaustFan, AirflowNetwork:MultiZone:Surface:Crack

AirflowNetwork:MultiZone:SpecifiedFlowRate

from idfpy.models import AirflowNetworkMultiZoneSpecifiedFlowRate

This object is used to define specified flow through a linkage.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_flow_value
Air Flow Value required
number Enter the specified flow rate.
air_flow_units
Air Flow Units
choice MassFlow Enter the units of the air flow value. VolumetricFlow (m3/s) MassFlow (kg/s)
One of MassFlow, VolumetricFlow
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:Surface

from idfpy.models import AirflowNetworkMultiZoneSurface

This object specifies the properties of a surface linkage through which air flows. Airflow Report: Node 1 as an inside face zone; Node 2 as an outside face zone or external node.

Field Type Default Details
surface_name
Surface Name required
reference Enter the name of a heat transfer surface.
Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Door, Door:Interzone, FenestrationSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, GlazedDoor, GlazedDoor:Interzone and 9 more
leakage_component_name
Leakage Component Name required
reference Enter the name of an Airflow Network leakage component. A leakage component is one of the following AirflowNetwork:Multizone objects: AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, AirflowNetwork:MultiZone:Surface:Crack, AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea, AirflowNetwork:MultiZone:Component:HorizontalOpening, or AirflowNetwork:MultiZone:Component:ZoneExhaustFan. When the zone exhaust fan name is entered, any surface control fields below A3 are ignored when the zone exhaust fan turns on.
Names a AirflowNetwork:MultiZone:Component:DetailedOpening, AirflowNetwork:MultiZone:Component:HorizontalOpening, AirflowNetwork:MultiZone:Component:SimpleOpening, AirflowNetwork:MultiZone:Component:ZoneExhaustFan, AirflowNetwork:MultiZone:SpecifiedFlowRate, AirflowNetwork:MultiZone:Surface:Crack, AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea
external_node_name
External Node Name
reference Used if Wind Pressure Coefficient Type = Input in the AirflowNetwork:SimulationControl object, otherwise this field may be left blank.
Names a AirflowNetwork:MultiZone:ExternalNode, OutdoorAir:Node
window_door_opening_factor_or_crack_factor
Window/Door Opening Factor, or Crack Factor
number
dimensionless
1.0 This field specifies a multiplier for a crack, window, or door.
Range: > 0, ≤ 1
ventilation_control_mode
Ventilation Control Mode
choice ZoneLevel When Ventilation Control Mode = Temperature or Enthalpy, the following fields are used to modulate the Ventilation Open Factor for a window or door opening according to the parent zone's indoor-outdoor temperature or enthalpy difference. When Ventilation Control Mode = AdjacentTemperature or AdjacentEnthalpy, the following fields are used to modulate the Ventilation Open Factor for an interior window or door opening according to temperature or enthalpy difference between the parent zone and the adjacent zone. Constant: controlled by field Venting Schedule Name. NoVent: control will not open window or door during simulation (Ventilation Open Factor = 0). ZoneLevel: control will be controlled by AirflowNetwork:MultiZone:Zone Mode.
One of ASHRAE55Adaptive, AdjacentEnthalpy, AdjacentTemperature, CEN15251Adaptive, Constant, Enthalpy, NoVent, Temperature, ZoneLevel
ventilation_control_zone_temperature_setpoint_schedule_name
Ventilation Control Zone Temperature Setpoint Schedule Name
reference Used only if Ventilation Control Mode = Temperature or Enthalpy.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
minimum_venting_open_factor
Minimum Venting Open Factor
number
dimensionless
0.0 Used only if Ventilation Control Mode = Temperature or Enthalpy.
Range: ≥ 0, ≤ 1
indoor_and_outdoor_temperature_difference_lower_limit_for_maximum_venting_open_factor
Indoor and Outdoor Temperature Difference Lower Limit For Maximum Venting Open Factor
number
deltaC
0.0 Applicable only if Ventilation Control Mode = Temperature
Range: ≥ 0, < 100
indoor_and_outdoor_temperature_difference_upper_limit_for_minimum_venting_open_factor
Indoor and Outdoor Temperature Difference Upper Limit for Minimum Venting Open Factor
number
deltaC
100.0 Applicable only if Ventilation Control Mode = Temperature. This value must be greater than the corresponding lower value (previous field).
Range: > 0
indoor_and_outdoor_enthalpy_difference_lower_limit_for_maximum_venting_open_factor
Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum Venting Open Factor
number
deltaJ/kg
0.0 Applicable only if Ventilation Control Mode = Enthalpy. This value must be less than the corresponding upper value (next field).
Range: ≥ 0, < 300000
indoor_and_outdoor_enthalpy_difference_upper_limit_for_minimum_venting_open_factor
Indoor and Outdoor Enthalpy Difference Upper Limit for Minimum Venting Open Factor
number
deltaJ/kg
300000.0 Applicable only if Ventilation Control Mode = Enthalpy. This value must be greater than the corresponding lower value (previous field).
Range: > 0
venting_availability_schedule_name
Venting Availability Schedule Name
reference Non-zero schedule value means venting is allowed if other venting control conditions are satisfied. A zero (or negative) schedule value means venting is not allowed under any circumstances. The schedule values should be greater than or equal to 0 and less than or equal to 1. If this schedule is not specified then venting is allowed if other venting control conditions are satisfied. Not used if Ventilation Control Mode = NoVent or ZoneLevel.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
occupant_ventilation_control_name
Occupant Ventilation Control Name
reference Enter the name where Occupancy Ventilation Control is required.
Names a AirflowNetwork:OccupantVentilationControl
equivalent_rectangle_method
Equivalent Rectangle Method
choice PolygonHeight This field is applied to a non-rectangular window or door. The equivalent shape has the same area as a polygonal window or door.
One of BaseSurfaceAspectRatio, PolygonHeight, UserDefinedAspectRatio
equivalent_rectangle_aspect_ratio
Equivalent Rectangle Aspect Ratio
number
dimensionless
1.0 This field is used when UserDefinedAspectRatio is entered in the Equivalent Rectangle Method field.
Range: > 0

AirflowNetwork:MultiZone:Surface:Crack

from idfpy.models import AirflowNetworkMultiZoneSurfaceCrack

This object specifies the properties of airflow through a crack.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
air_mass_flow_coefficient_at_reference_conditions
Air Mass Flow Coefficient at Reference Conditions required
number
kg/s
Enter the air mass flow coefficient at the conditions defined in the Reference Crack Conditions object. Defined at 1 Pa pressure difference across this crack.
Range: > 0
air_mass_flow_exponent
Air Mass Flow Exponent
number
dimensionless
0.65 Enter the air mass flow exponent for the surface crack.
Range: ≥ 0.5, ≤ 1
reference_crack_conditions
Reference Crack Conditions
reference Select a AirflowNetwork:MultiZone:ReferenceCrackConditions name associated with the air mass flow coefficient entered above.
Names a AirflowNetwork:MultiZone:ReferenceCrackConditions
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:Surface:EffectiveLeakageArea

from idfpy.models import AirflowNetworkMultiZoneSurfaceEffectiveLeakageArea

This object is used to define surface air leakage.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
effective_leakage_area
Effective Leakage Area required
number
m2
Enter the effective leakage area.
Range: > 0
discharge_coefficient
Discharge Coefficient
number
dimensionless
1.0 Enter the coefficient used in the air mass flow equation.
Range: > 0
reference_pressure_difference
Reference Pressure Difference
number
Pa
4.0 Enter the pressure difference used to define the air mass flow coefficient and exponent.
Range: > 0
air_mass_flow_exponent
Air Mass Flow Exponent
number
dimensionless
0.65 Enter the exponent used in the air mass flow equation.
Range: ≥ 0.5, ≤ 1
Referenced by 1 object types

AirflowNetwork:MultiZone:Surface

AirflowNetwork:MultiZone:WindPressureCoefficientArray

from idfpy.models import AirflowNetworkMultiZoneWindPressureCoefficientArray

Used only if Wind Pressure Coefficient (WPC) Type = Input in the AirflowNetwork:SimulationControl object. Number of WPC Values in the corresponding AirflowNetwork:MultiZone:WindPressureCoefficientValues object must be the same as the number of wind directions specified for this AirflowNetwork:MultiZone:WindPressureCoefficientArray object.

Field Type Default Details
name
Name required
string Enter a unique name for the object.
wind_direction_1
Wind Direction 1 required
number
deg
Enter the wind direction corresponding to the 1st WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_2
Wind Direction 2 required
number
deg
Enter the wind direction corresponding to the 2nd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_3
Wind Direction 3
number
deg
Enter the wind direction corresponding to the 3rd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_4
Wind Direction 4
number
deg
Enter the wind direction corresponding to the 4th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_5
Wind Direction 5
number
deg
Enter the wind direction corresponding to the 5th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_6
Wind Direction 6
number
deg
Enter the wind direction corresponding to the 6th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_7
Wind Direction 7
number
deg
Enter the wind direction corresponding to the 7th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_8
Wind Direction 8
number
deg
Enter the wind direction corresponding to the 8th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_9
Wind Direction 9
number
deg
Enter the wind direction corresponding to the 9th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_10
Wind Direction 10
number
deg
Enter the wind direction corresponding to the 10th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_11
Wind Direction 11
number
deg
Enter the wind direction corresponding to the 11th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_12
Wind Direction 12
number
deg
Enter the wind direction corresponding to the 12th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_13
Wind Direction 13
number
deg
Enter the wind direction corresponding to the 13th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_14
Wind Direction 14
number
deg
Enter the wind direction corresponding to the 14th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_15
Wind Direction 15
number
deg
Enter the wind direction corresponding to the 15th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_16
Wind Direction 16
number
deg
Enter the wind direction corresponding to the 16th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_17
Wind Direction 17
number
deg
Enter the wind direction corresponding to the 17th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_18
Wind Direction 18
number
deg
Enter the wind direction corresponding to the 18th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_19
Wind Direction 19
number
deg
Enter the wind direction corresponding to the 19th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_20
Wind Direction 20
number
deg
Enter the wind direction corresponding to the 20th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_21
Wind Direction 21
number
deg
Enter the wind direction corresponding to the 21st WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_22
Wind Direction 22
number
deg
Enter the wind direction corresponding to the 22nd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_23
Wind Direction 23
number
deg
Enter the wind direction corresponding to the 23rd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_24
Wind Direction 24
number
deg
Enter the wind direction corresponding to the 24th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_25
Wind Direction 25
number
deg
Enter the wind direction corresponding to the 25th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_26
Wind Direction 26
number
deg
Enter the wind direction corresponding to the 26th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_27
Wind Direction 27
number
deg
Enter the wind direction corresponding to the 27th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_28
Wind Direction 28
number
deg
Enter the wind direction corresponding to the 28th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_29
Wind Direction 29
number
deg
Enter the wind direction corresponding to the 29th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_30
Wind Direction 30
number
deg
Enter the wind direction corresponding to the 30th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_31
Wind Direction 31
number
deg
Enter the wind direction corresponding to the 31st WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_32
Wind Direction 32
number
deg
Enter the wind direction corresponding to the 32nd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_33
Wind Direction 33
number
deg
Enter the wind direction corresponding to the 33rd WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_34
Wind Direction 34
number
deg
Enter the wind direction corresponding to the 34th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_35
Wind Direction 35
number
deg
Enter the wind direction corresponding to the 35th WPC Array value.
Range: ≥ 0, ≤ 360
wind_direction_36
Wind Direction 36
number
deg
Enter the wind direction corresponding to the 36th WPC Array value.
Range: ≥ 0, ≤ 360
Referenced by 1 object types

AirflowNetwork:MultiZone:WindPressureCoefficientValues

AirflowNetwork:MultiZone:WindPressureCoefficientValues

from idfpy.models import AirflowNetworkMultiZoneWindPressureCoefficientValues

Used only if Wind Pressure Coefficient (WPC) Type = INPUT in the AirflowNetwork:SimulationControl object. The number of WPC numeric inputs must correspond to the number of wind direction inputs in the AirflowNetwork:Multizone:WindPressureCoefficientArray object.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
airflownetwork_multizone_windpressurecoefficientarray_name
AirflowNetwork:MultiZone:WindPressureCoefficientArray Name required
reference Enter the name of the AirflowNetwork:Multizone:WindPressureCoefficientArray object.
Names a AirflowNetwork:MultiZone:WindPressureCoefficientArray
wind_pressure_coefficient_value_1
Wind Pressure Coefficient Value 1 required
number
dimensionless
Enter the WPC Value corresponding to the 1st wind direction.
wind_pressure_coefficient_value_2
Wind Pressure Coefficient Value 2 required
number
dimensionless
Enter the WPC Value corresponding to the 2nd wind direction.
wind_pressure_coefficient_value_3
Wind Pressure Coefficient Value 3
number
dimensionless
Enter the WPC Value corresponding to the 3rd wind direction.
wind_pressure_coefficient_value_4
Wind Pressure Coefficient Value 4
number
dimensionless
Enter the WPC Value corresponding to the 4th wind direction.
wind_pressure_coefficient_value_5
Wind Pressure Coefficient Value 5
number
dimensionless
Enter the WPC Value corresponding to the 5th wind direction.
wind_pressure_coefficient_value_6
Wind Pressure Coefficient Value 6
number
dimensionless
Enter the WPC Value corresponding to the 6th wind direction.
wind_pressure_coefficient_value_7
Wind Pressure Coefficient Value 7
number
dimensionless
Enter the WPC Value corresponding to the 7th wind direction.
wind_pressure_coefficient_value_8
Wind Pressure Coefficient Value 8
number
dimensionless
Enter the WPC Value corresponding to the 8th wind direction.
wind_pressure_coefficient_value_9
Wind Pressure Coefficient Value 9
number
dimensionless
Enter the WPC Value corresponding to the 9th wind direction.
wind_pressure_coefficient_value_10
Wind Pressure Coefficient Value 10
number
dimensionless
Enter the WPC Value corresponding to the 10th wind direction.
wind_pressure_coefficient_value_11
Wind Pressure Coefficient Value 11
number
dimensionless
Enter the WPC Value corresponding to the 11th wind direction.
wind_pressure_coefficient_value_12
Wind Pressure Coefficient Value 12
number
dimensionless
Enter the WPC Value corresponding to the 12th wind direction.
wind_pressure_coefficient_value_13
Wind Pressure Coefficient Value 13
number
dimensionless
Enter the WPC Value corresponding to the 13th wind direction.
wind_pressure_coefficient_value_14
Wind Pressure Coefficient Value 14
number
dimensionless
Enter the WPC Value corresponding to the 14th wind direction.
wind_pressure_coefficient_value_15
Wind Pressure Coefficient Value 15
number
dimensionless
Enter the WPC Value corresponding to the 15th wind direction.
wind_pressure_coefficient_value_16
Wind Pressure Coefficient Value 16
number
dimensionless
Enter the WPC Value corresponding to the 16th wind direction.
wind_pressure_coefficient_value_17
Wind Pressure Coefficient Value 17
number
dimensionless
Enter the WPC Value corresponding to the 17th wind direction.
wind_pressure_coefficient_value_18
Wind Pressure Coefficient Value 18
number
dimensionless
Enter the WPC Value corresponding to the 18th wind direction.
wind_pressure_coefficient_value_19
Wind Pressure Coefficient Value 19
number
dimensionless
Enter the WPC Value corresponding to the 19th wind direction.
wind_pressure_coefficient_value_20
Wind Pressure Coefficient Value 20
number
dimensionless
Enter the WPC Value corresponding to the 20th wind direction.
wind_pressure_coefficient_value_21
Wind Pressure Coefficient Value 21
number
dimensionless
Enter the WPC Value corresponding to the 21st wind direction.
wind_pressure_coefficient_value_22
Wind Pressure Coefficient Value 22
number
dimensionless
Enter the WPC Value corresponding to the 22nd wind direction.
wind_pressure_coefficient_value_23
Wind Pressure Coefficient Value 23
number
dimensionless
Enter the WPC Value corresponding to the 23rd wind direction.
wind_pressure_coefficient_value_24
Wind Pressure Coefficient Value 24
number
dimensionless
Enter the WPC Value corresponding to the 24th wind direction.
wind_pressure_coefficient_value_25
Wind Pressure Coefficient Value 25
number
dimensionless
Enter the WPC Value corresponding to the 25th wind direction.
wind_pressure_coefficient_value_26
Wind Pressure Coefficient Value 26
number
dimensionless
Enter the WPC Value corresponding to the 26th wind direction.
wind_pressure_coefficient_value_27
Wind Pressure Coefficient Value 27
number
dimensionless
Enter the WPC Value corresponding to the 27th wind direction.
wind_pressure_coefficient_value_28
Wind Pressure Coefficient Value 28
number
dimensionless
Enter the WPC Value corresponding to the 28th wind direction.
wind_pressure_coefficient_value_29
Wind Pressure Coefficient Value 29
number
dimensionless
Enter the WPC Value corresponding to the 29th wind direction.
wind_pressure_coefficient_value_30
Wind Pressure Coefficient Value 30
number
dimensionless
Enter the WPC Value corresponding to the 30th wind direction.
wind_pressure_coefficient_value_31
Wind Pressure Coefficient Value 31
number
dimensionless
Enter the WPC Value corresponding to the 31st wind direction.
wind_pressure_coefficient_value_32
Wind Pressure Coefficient Value 32
number
dimensionless
Enter the WPC Value corresponding to the 32nd wind direction.
wind_pressure_coefficient_value_33
Wind Pressure Coefficient Value 33
number
dimensionless
Enter the WPC Value corresponding to the 33rd wind direction.
wind_pressure_coefficient_value_34
Wind Pressure Coefficient Value 34
number
dimensionless
Enter the WPC Value corresponding to the 34th wind direction.
wind_pressure_coefficient_value_35
Wind Pressure Coefficient Value 35
number
dimensionless
Enter the WPC Value corresponding to the 35th wind direction.
wind_pressure_coefficient_value_36
Wind Pressure Coefficient Value 36
number
dimensionless
Enter the WPC Value corresponding to the 36th wind direction.
Referenced by 2 object types

AirflowNetwork:MultiZone:ExternalNode, OutdoorAir:Node

AirflowNetwork:MultiZone:Zone

from idfpy.models import AirflowNetworkMultiZoneZone

This object is used to simultaneously control a thermal zone's window and door openings, both exterior and interior.

Field Type Default Details
zone_name
Zone Name required
reference Enter the zone name where ventilation control is required.
Names a Zone
ventilation_control_mode
Ventilation Control Mode
choice NoVent When Ventilation Control Mode = Temperature or Enthalpy, the following fields are used to modulate the Ventilation Open Factor for all window and door openings in the zone according to the zone's indoor-outdoor temperature or enthalpy difference. Constant: controlled by field Venting Schedule Name. NoVent: control will not open window or door during simulation (Ventilation Open Factor = 0).
One of ASHRAE55Adaptive, CEN15251Adaptive, Constant, Enthalpy, NoVent, Temperature
ventilation_control_zone_temperature_setpoint_schedule_name
Ventilation Control Zone Temperature Setpoint Schedule Name
reference Used only if Ventilation Control Mode = Temperature or Enthalpy.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
minimum_venting_open_factor
Minimum Venting Open Factor
number
dimensionless
0.0 Used only if Ventilation Control Mode = Temperature or Enthalpy.
Range: ≥ 0, ≤ 1
indoor_and_outdoor_temperature_difference_lower_limit_for_maximum_venting_open_factor
Indoor and Outdoor Temperature Difference Lower Limit For Maximum Venting Open Factor
number
deltaC
0.0 Applicable only if Ventilation Control Mode = Temperature. This value must be less than the corresponding upper value (next field).
Range: ≥ 0, < 100
indoor_and_outdoor_temperature_difference_upper_limit_for_minimum_venting_open_factor
Indoor and Outdoor Temperature Difference Upper Limit for Minimum Venting Open Factor
number
deltaC
100.0 Applicable only if Ventilation Control Mode = Temperature. This value must be greater than the corresponding lower value (previous field).
Range: > 0
indoor_and_outdoor_enthalpy_difference_lower_limit_for_maximum_venting_open_factor
Indoor and Outdoor Enthalpy Difference Lower Limit For Maximum Venting Open Factor
number
deltaJ/kg
0.0 Applicable only if Ventilation Control Mode = Enthalpy. This value must be less than the corresponding upper value (next field).
Range: ≥ 0, < 300000
indoor_and_outdoor_enthalpy_difference_upper_limit_for_minimum_venting_open_factor
Indoor and Outdoor Enthalpy Difference Upper Limit for Minimum Venting Open Factor
number
deltaJ/kg
300000.0 Applicable only if Ventilation Control Mode = Enthalpy. This value must be greater than the corresponding lower value (previous field).
Range: > 0
venting_availability_schedule_name
Venting Availability Schedule Name
reference Non-zero Schedule value means venting is allowed if other venting control conditions are satisfied. A zero (or negative) Schedule value means venting is not allowed under any The Schedule values should be greater than or equal to 0 and less than or equal to 1. circumstances. If this Schedule is not specified then venting is allowed if other venting control conditions are satisfied. Not used if Ventilation Control Mode = NoVent.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
single_sided_wind_pressure_coefficient_algorithm
Single Sided Wind Pressure Coefficient Algorithm
choice Standard Selecting Advanced results in EnergyPlus calculating modified Wind Pressure Coefficients to account for wind direction and turbulence effects on single sided ventilation rates. Model is only valid for zones with 2 openings, both of which are on a single facade.
One of Advanced, Standard
facade_width
Facade Width
number
m
10.0 This is the whole building width along the direction of the facade of this zone.
Range: ≥ 0
occupant_ventilation_control_name
Occupant Ventilation Control Name
reference Enter the name where Occupancy Ventilation Control is required.
Names a AirflowNetwork:OccupantVentilationControl
Referenced by 1 object types

AirflowNetwork:IntraZone:Node

AirflowNetwork:OccupantVentilationControl

from idfpy.models import AirflowNetworkOccupantVentilationControl

This object is used to provide advanced thermal comfort control of window opening and closing for both exterior and interior windows.

Field Type Default Details
name
Name required
string Enter the name where the advanced thermal comfort control is required.
minimum_opening_time
Minimum Opening Time
number
minutes
0.0 Range: ≥ 0
minimum_closing_time
Minimum Closing Time
number
minutes
0.0 Range: ≥ 0
thermal_comfort_low_temperature_curve_name
Thermal Comfort Low Temperature Curve Name
reference Enter a curve name that represents thermal comfort temperature as a function of outdoor dry-bulb temperature. Up to two curves are allowed if the performance cannot be represented by a single curve. The following two fields are used if two curves are required.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermal_comfort_temperature_boundary_point
Thermal Comfort Temperature Boundary Point
number
C
10.0 This point is used to allow separate low and high thermal comfort temperature curves. If a single performance curve is used, leave this field blank.
Range: ≥ 0
thermal_comfort_high_temperature_curve_name
Thermal Comfort High Temperature Curve Name
reference Enter a curve name that represents thermal comfort temperature as a function of outdoor dry-bulb temperature. Up to two curves are allowed if the performance cannot be represented by a single curve. If a single performance curve is used, leave this field blank.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_threshold_for_persons_dissatisfied_ppd
Maximum Threshold for Persons Dissatisfied PPD
number
percent
10.0 Range: ≥ 0, ≤ 100
occupancy_check
Occupancy Check
choice No If Yes, occupancy check will be performed as part of the opening probability check.
One of No, Yes
opening_probability_schedule_name
Opening Probability Schedule Name
reference If this field is blank, the opening probability check is bypassed and opening is true.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
closing_probability_schedule_name
Closing Probability Schedule Name
reference If this field is blank, the closing probability check is bypassed and closing is true.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 2 object types

AirflowNetwork:MultiZone:Surface, AirflowNetwork:MultiZone:Zone

AirflowNetwork:SimulationControl

from idfpy.models import AirflowNetworkSimulationControl unique

This object defines the global parameters used in an Airflow Network simulation.

Field Type Default Details
name
Name required
string Enter a unique name for this object.
airflownetwork_control
AirflowNetwork Control
choice NoMultizoneOrDistribution NoMultizoneOrDistribution: Only perform Simple calculations (objects ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing, ZoneCrossMixing, ZoneRefrigerationDoorMixing, ZoneAirBalance:OutdoorAir, ZoneEarthtube, ZoneThermalChimney, and ZoneCoolTower:Shower); MultizoneWithoutDistribution: Use AirflowNetwork objects to simulate multizone Airflows driven by wind during simulation time, and objects of ZoneInfiltration:*, ZoneVentilation:*, ZoneMixing, ZoneCrossMixing ZoneRefrigerationDoorMixing, ZoneAirBalance:OutdoorAir, ZoneEarthtube, ZoneThermalChimney, and ZoneCoolTower:Shower are ignored; MultizoneWithDistributionOnlyDuringFanOperation: Perform distribution system calculations during system fan on time and Simple calculations during system Fan off time; MultizoneWithDistribution: Perform distribution system calculations during system fan on time and multizone Airflow driven by wind during system fan off time.
One of MultizoneWithDistribution, MultizoneWithDistributionOnlyDuringFanOperation, MultizoneWithoutDistribution, NoMultizoneOrDistribution
wind_pressure_coefficient_type
Wind Pressure Coefficient Type
choice SurfaceAverageCalculation Input: User must enter AirflowNetwork:MultiZone:WindPressureCoefficientArray, AirflowNetwork:MultiZone:ExternalNode, and AirflowNetwork:MultiZone:WindPressureCoefficientValues objects. SurfaceAverageCalculation: used only for rectangular buildings. If SurfaceAverageCalculation is selected, AirflowNetwork:MultiZone:WindPressureCoefficientArray, AirflowNetwork:MultiZone:ExternalNode, and AirflowNetwork:MultiZone:WindPressureCoefficientValues objects are not used.
One of Input, SurfaceAverageCalculation
height_selection_for_local_wind_pressure_calculation
Height Selection for Local Wind Pressure Calculation
choice OpeningHeight If ExternalNode is selected, the height given in the AirflowNetwork:MultiZone:ExternalNode object will be used. If OpeningHeight is selected, the surface opening height (centroid) will be used to calculate local wind pressure This field is ignored when the choice of the Wind Pressure Coefficient Type field is SurfaceAverageCalculation.
One of ExternalNode, OpeningHeight
building_type
Building Type
choice LowRise Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation, otherwise this field may be left blank.
One of HighRise, LowRise
maximum_number_of_iterations
Maximum Number of Iterations
integer
dimensionless
500 Determines the maximum number of iterations used to converge on a solution. If this limit is exceeded, the program terminates.
Range: > 10, ≤ 30000
initialization_type
Initialization Type
choice ZeroNodePressures One of LinearInitializationMethod, ZeroNodePressures
relative_airflow_convergence_tolerance
Relative Airflow Convergence Tolerance
number
dimensionless
0.0001 This tolerance is defined as the absolute value of the sum of the mass Flow Rates divided by the sum of the absolute value of the mass Flow Rates. The mass Flow Rates described here refer to the mass Flow Rates at all Nodes in the AirflowNetwork model. The solution converges when both this tolerance and the tolerance in the next field (Absolute Airflow Convergence Tolerance) are satisfied.
Range: > 0
absolute_airflow_convergence_tolerance
Absolute Airflow Convergence Tolerance
number
kg/s
1e-06 This tolerance is defined as the absolute value of the sum of the mass flow rates. The mass flow rates described here refer to the mass flow rates at all nodes in the AirflowNetwork model. The solution converges when both this tolerance and the tolerance in the previous field (Relative Airflow Convergence Tolerance) are satisfied.
Range: > 0
convergence_acceleration_limit
Convergence Acceleration Limit
number
dimensionless
-0.5 Used only for AirflowNetwork:SimulationControl
Range: ≥ -1, ≤ 1
azimuth_angle_of_long_axis_of_building
Azimuth Angle of Long Axis of Building
number
deg
0.0 Degrees clockwise from true North. Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation.
Range: ≥ 0, ≤ 180
ratio_of_building_width_along_short_axis_to_width_along_long_axis
Ratio of Building Width Along Short Axis to Width Along Long Axis
number 1.0 Used only if Wind Pressure Coefficient Type = SurfaceAverageCalculation.
Range: > 0, ≤ 1
height_dependence_of_external_node_temperature
Height Dependence of External Node Temperature
choice No If Yes, external node temperature is height dependent. If No, external node temperature is based on zero height.
One of No, Yes
solver
Solver
choice SkylineLU Select the solver to use for the pressure network solution
One of ConjugateGradient, SkylineLU
allow_unsupported_zone_equipment
Allow Unsupported Zone Equipment
choice No Set this input to Yes to have zone equipment that are currently unsupported in the AirflowNetwork model allowed in the simulation if present. Setting this field to Yes, allows the following equipment to be modeled along an AirflowNetwork model: ZoneHVAC:Dehumidifier, ZoneHVAC:EnergyRecoveryVentilator, WaterHeater:HeatPump:*.
One of No, Yes
do_distribution_duct_sizing_calculation
Do Distribution Duct Sizing Calculation
choice No Controls duct sizing. See AirflowNetwork:Distribution:DuctSizing for sizing options.
One of No, Yes

AirflowNetwork:ZoneControl:PressureController

from idfpy.models import AirflowNetworkZoneControlPressureController unique

This object is used to control a zone to a specified indoor pressure using the AirflowNetwork model. The specified pressure setpoint is used to control the zone exhaust fan flow rate in a controlled zone or the relief air flow rate in an air loop.

Field Type Default Details
name
Name required
string
control_zone_name
Control Zone Name required
reference Names a Zone
control_object_type
Control Object Type required
choice The current selection is AirflowNetwork:MultiZone:Component:ZoneExhaustFan or AirflowNetwork:Distribution:Component:ReliefAirFlow.
One of AirflowNetwork:Distribution:Component:ReliefAirFlow, AirflowNetwork:MultiZone:Component:ZoneExhaustFan
control_object_name
Control Object Name required
reference Control names are names of individual control objects
Names a AirflowNetwork:Distribution:Component:ReliefAirFlow, Fan:ZoneExhaust
pressure_control_availability_schedule_name
Pressure Control Availability Schedule Name
reference Availability schedule name for pressure controller. Schedule value > 0 means the pressure controller is enabled. If this field is blank, then pressure controller is always enabled.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
pressure_setpoint_schedule_name
Pressure Setpoint Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

Compliance:Building

from idfpy.models import ComplianceBuilding unique

Building level inputs related to compliance to building standards, building codes, and beyond energy code programs.

Field Type Default Details
building_rotation_for_appendix_g
Building Rotation for Appendix G
number
deg
0.0 Additional degrees of rotation to be used with the requirement in ASHRAE Standard 90.1 Appendix G that states that the baseline building should be rotated in four directions.

CondenserLoop

from idfpy.models import CondenserLoop

Defines a central plant condenser loop. CondenserLoop and PlantLoop are nearly identical except some components and operation schemes are applicable to only one loop type or the other.

Field Type Default Details
name
Name required
string
fluid_type
Fluid Type
choice Water One of UserDefinedFluidType, Water
user_defined_fluid_type
User Defined Fluid Type
reference This field is only required when Fluid Type is UserDefinedFluidType
Names a FluidProperties:GlycolConcentration, FluidProperties:Name
condenser_equipment_operation_scheme_name
Condenser Equipment Operation Scheme Name required
reference Names a CondenserEquipmentOperationSchemes
condenser_loop_temperature_setpoint_node_name
Condenser Loop Temperature Setpoint Node Name required
string
maximum_loop_temperature
Maximum Loop Temperature required
number
C
minimum_loop_temperature
Minimum Loop Temperature required
number
C
maximum_loop_flow_rate
Maximum Loop Flow Rate required
number or Autosize
m3/s
minimum_loop_flow_rate
Minimum Loop Flow Rate
number
m3/s
0.0
condenser_loop_volume
Condenser Loop Volume
number or Autocalculate
m3
Autocalculate
condenser_side_inlet_node_name
Condenser Side Inlet Node Name required
string
condenser_side_outlet_node_name
Condenser Side Outlet Node Name required
string
condenser_side_branch_list_name
Condenser Side Branch List Name required
reference Names a BranchList
condenser_side_connector_list_name
Condenser Side Connector List Name required
reference Names a ConnectorList
demand_side_inlet_node_name
Demand Side Inlet Node Name required
string
demand_side_outlet_node_name
Demand Side Outlet Node Name required
string
condenser_demand_side_branch_list_name
Condenser Demand Side Branch List Name required
reference Names a BranchList
condenser_demand_side_connector_list_name
Condenser Demand Side Connector List Name required
reference Names a ConnectorList
load_distribution_scheme
Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR
pressure_simulation_type
Pressure Simulation Type
choice None One of LoopFlowCorrection, None, PumpPowerCorrection
loop_circulation_time
Loop Circulation Time
number
minutes
2.0 This field is only used to autocalculate the Condenser Loop Volume. Loop Volume = Loop Circulation Time * Maximum Loop Flow Rate
Range: ≥ 0
Referenced by 1 object types

Sizing:Plant

Controller:MechanicalVentilation

from idfpy.models import ControllerMechanicalVentilation extensible

This object is used in conjunction with Controller:OutdoorAir to specify outdoor ventilation air based on outdoor air specified in the DesignSpecification:OutdoorAir object The Controller:OutdoorAir object is associated with a specific air loop, so the outdoor air flow rates specified in Controller:MechanicalVentilation correspond to the zones attached to that specific air loop. Duplicate groups of Zone name, Design Specification Outdoor Air Object Name, and Design Specification Zone Air Distribution Object Name to increase allowable number of entries

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference If this field is blank, the controller uses the values from the associated Controller:OutdoorAir. Schedule values greater than 0 indicate mechanical ventilation is enabled
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
demand_controlled_ventilation
Demand Controlled Ventilation
choice No One of No, Yes
system_outdoor_air_method
System Outdoor Air Method
choice Standard62.1VentilationRateProcedure One of IndoorAirQualityProcedure, IndoorAirQualityProcedureCombined, IndoorAirQualityProcedureGenericContaminant, ProportionalControlBasedOnDesignOARate, ProportionalControlBasedOnDesignOccupancy, ProportionalControlBasedOnOccupancySchedule, Standard62.1VentilationRateProcedure, Standard62.1VentilationRateProcedureWithLimit, ZoneSum
zone_maximum_outdoor_air_fraction
Zone Maximum Outdoor Air Fraction
number
dimensionless
1.0 Range: > 0
zone_specifications list Each item: zone_or_zonelist_name, design_specification_outdoor_air_object_name, design_specification_zone_air_distribution_object_name
Referenced by 1 object types

Controller:OutdoorAir

Controller:OutdoorAir

from idfpy.models import ControllerOutdoorAir

Controller to set the outdoor air flow rate for an air loop. Control options include fixed, proportional, scheduled, economizer, and demand-controlled ventilation.

Field Type Default Details
name
Name required
string
relief_air_outlet_node_name
Relief Air Outlet Node Name required
string
return_air_node_name
Return Air Node Name required
string
mixed_air_node_name
Mixed Air Node Name required
string
actuator_node_name
Actuator Node Name required
string Outdoor air inlet node entering the first pre-treat component if any
minimum_outdoor_air_flow_rate
Minimum Outdoor Air Flow Rate required
number or Autosize
m3/s
If there is a Mechanical Ventilation Controller (Controller:MechanicalVentilation), note that this value times the Minimum Outdoor Air Schedule is a hard minimum that may override DCV or other advanced OA controls.
maximum_outdoor_air_flow_rate
Maximum Outdoor Air Flow Rate required
number or Autosize
m3/s
economizer_control_type
Economizer Control Type
choice NoEconomizer One of DifferentialDryBulb, DifferentialDryBulbAndEnthalpy, DifferentialEnthalpy, ElectronicEnthalpy, FixedDewPointAndDryBulb, FixedDryBulb, FixedEnthalpy, NoEconomizer
economizer_control_action_type
Economizer Control Action Type
choice ModulateFlow One of MinimumFlowWithBypass, ModulateFlow
economizer_maximum_limit_dry_bulb_temperature
Economizer Maximum Limit Dry-Bulb Temperature
number
C
Enter the maximum outdoor dry-bulb temperature limit for FixedDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
economizer_maximum_limit_enthalpy
Economizer Maximum Limit Enthalpy
number
J/kg
Enter the maximum outdoor enthalpy limit for FixedEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
economizer_maximum_limit_dewpoint_temperature
Economizer Maximum Limit Dewpoint Temperature
number
C
Enter the maximum outdoor dewpoint temperature limit for FixedDewPointAndDryBulb economizer control type. No input or blank input means this limit is not operative. Limit is applied regardless of economizer control type.
electronic_enthalpy_limit_curve_name
Electronic Enthalpy Limit Curve Name
reference Enter the name of a quadratic or cubic curve which defines the maximum outdoor humidity ratio (function of outdoor dry-bulb temperature) for ElectronicEnthalpy economizer control type. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
economizer_minimum_limit_dry_bulb_temperature
Economizer Minimum Limit Dry-Bulb Temperature
number
C
Enter the minimum outdoor dry-bulb temperature limit for economizer control. No input or blank input means this limit is not operative Limit is applied regardless of economizer control type.
lockout_type
Lockout Type
choice NoLockout One of LockoutWithCompressor, LockoutWithHeating, NoLockout
minimum_limit_type
Minimum Limit Type
choice ProportionalMinimum One of FixedMinimum, ProportionalMinimum
minimum_outdoor_air_schedule_name
Minimum Outdoor Air Schedule Name
reference Schedule values multiply the minimum outdoor air flow rate
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
minimum_fraction_of_outdoor_air_schedule_name
Minimum Fraction of Outdoor Air Schedule Name
reference schedule values multiply the design/mixed air flow rate
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_fraction_of_outdoor_air_schedule_name
Maximum Fraction of Outdoor Air Schedule Name
reference schedule values multiply the design/mixed air flow rate
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
mechanical_ventilation_controller_name
Mechanical Ventilation Controller Name
reference Enter the name of a Controller:MechanicalVentilation object. Optional field for defining outdoor ventilation air based on flow rate per unit floor area and flow rate per person. Simplified method of demand-controlled ventilation.
Names a Controller:MechanicalVentilation
time_of_day_economizer_control_schedule_name
Time of Day Economizer Control Schedule Name
reference Optional schedule to simulate "push-button" type economizer control. Schedule values greater than 0 indicate time-of-day economizer control is enabled. Economizer control may be used with or without the high humidity control option. When used together, high humidity control has priority over economizer control. If the field Economizer Control Type = NoEconomizer, then this option is disabled.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
high_humidity_control
High Humidity Control
choice No Optional field to enable modified outdoor air flow rates based on zone relative humidity. Select Yes to modify outdoor air flow rate based on a zone humidistat. Select No to disable this feature. If the field Economizer Control Type = NoEconomizer, then this option is disabled.
One of No, Yes
humidistat_control_zone_name
Humidistat Control Zone Name
reference Enter the name of the zone where the humidistat is located. This field is only used when the field High Humidity Control = Yes.
Names a Zone
high_humidity_outdoor_air_flow_ratio
High Humidity Outdoor Air Flow Ratio
number 1.0 Enter the ratio of outdoor air to the maximum outdoor air flow rate when modified air flow rates are active based on high indoor humidity. The minimum value must be greater than 0. This field is only used when the field High Humidity Control = Yes.
Range: > 0
control_high_indoor_humidity_based_on_outdoor_humidity_ratio
Control High Indoor Humidity Based on Outdoor Humidity Ratio
choice Yes If No is selected, the outdoor air flow rate is modified any time indoor relative humidity is above the humidistat setpoint. If Yes is selected, the outdoor air flow rate is modified any time the indoor relative humidity is above the humidistat setpoint and the outdoor humidity ratio is less than the indoor humidity ratio. This field is only used when the field High Humidity Control = Yes.
One of No, Yes
heat_recovery_bypass_control_type
Heat Recovery Bypass Control Type
choice BypassWhenWithinEconomizerLimits BypassWhenWithinEconomizerLimits specifies that heat recovery is active only when the economizer is off because conditions are outside the economizer control limits BypassWhenOAFlowGreaterThanMinimum specifies enhanced economizer controls to allow heat recovery when economizer is active (within limits) but the outdoor air flow rate is at the minimum.
One of BypassWhenOAFlowGreaterThanMinimum, BypassWhenWithinEconomizerLimits
economizer_operation_staging
Economizer Operation Staging
choice InterlockedWithMechanicalCooling This input is only used when the Controller:OutdoorAir is used in conjunction with an AirLoopHVAC:UnitarySystem with multiple cooling speeds. When modeling an AirLoopHVAC:UnitarySystem with multiple cooling speeds (as specified in a UnitarySystemPerformance:Multispeed), EconomizerFirst runs the economizer at all speeds, all the way to the highest cooling speed before mechanical cooling is used to meet the load. InterlockedWithMechanicalCooling runs the economizer at the cooling speed chosen by the AirLoopHVAC:UnitarySystem. Use EconomizerFirst to model typical economizer staging for multi-speed packaged single-zone equipment with sensible load control (Control Type input of the AirLoopHVAC:UnitarySystem should be set to Load).
One of EconomizerFirst, InterlockedWithMechanicalCooling
Referenced by 7 object types

AirLoopHVAC:ControllerList, DemandManager:Ventilation, FaultModel:EnthalpySensorOffset:OutdoorAir, FaultModel:EnthalpySensorOffset:ReturnAir, FaultModel:HumiditySensorOffset:OutdoorAir, FaultModel:TemperatureSensorOffset:OutdoorAir, FaultModel:TemperatureSensorOffset:ReturnAir

Controller:WaterCoil

from idfpy.models import ControllerWaterCoil

Controller for a water coil which is located directly in an air loop branch or outdoor air equipment list. Controls the coil water flow to meet the specified leaving air setpoint(s). Used with Coil:Heating:Water, Coil:Cooling:Water, Coil:Cooling:Water:DetailedGeometry, and CoilSystem:Cooling:Water:HeatexchangerAssisted.

Field Type Default Details
name
Name required
string
control_variable
Control Variable required
choice keys HumidityRatio or TemperatureAndHumidityRatio requires a ZoneControl:Humidistat object along with SetpointManager:SingleZone:Humidity:Maximum, SetpointManager:MultiZone:MaximumHumidity:Average, or SetpointManager:Multizone:Humidity:Maximum object
One of HumidityRatio, Temperature, TemperatureAndHumidityRatio
action
Action
choice Leave blank to have this automatically selected from coil type. Chilled water coils should be reverse action Hot water coils should be normal action
One of Normal, Reverse
actuator_variable
Actuator Variable required
choice One of Flow
sensor_node_name
Sensor Node Name required
string
actuator_node_name
Actuator Node Name required
string
controller_convergence_tolerance
Controller Convergence Tolerance
number or Autosize
deltaC
Autosize
maximum_actuated_flow
Maximum Actuated Flow
number or Autosize
m3/s
Autosize
minimum_actuated_flow
Minimum Actuated Flow
number
m3/s
0.0 Range: ≥ 0
Referenced by 2 object types

AirLoopHVAC:ControllerList, FaultModel:TemperatureSensorOffset:CoilSupplyAir

Dehumidifier:Desiccant:NoFans

from idfpy.models import DehumidifierDesiccantNoFans

This object models a solid desiccant dehumidifier. The process air stream is the air which is dehumidified. The regeneration air stream is the air which is heated to regenerate the desiccant. This object determines the process air outlet conditions, the load on the regeneration heating coil, the electric power consumption for the wheel rotor motor, and the regeneration air fan mass flow rate. All other heat exchangers are modeled as separate objects connected to the inlet and outlet nodes of the dehumidifier. The solid desiccant dehumidifier is typically used in an AirLoopHVAC:OutdoorAirSystem, but can also be specified in any AirLoopHVAC.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
process_air_inlet_node_name
Process Air Inlet Node Name
string This is the node entering the process side of the desiccant wheel.
process_air_outlet_node_name
Process Air Outlet Node Name
string This is the node leaving the process side of the desiccant wheel.
regeneration_air_inlet_node_name
Regeneration Air Inlet Node Name
string This is the node entering the regeneration side of the desiccant wheel after the regeneration coil.
regeneration_fan_inlet_node_name
Regeneration Fan Inlet Node Name
string Node for air entering the regeneration fan, mass flow is set by the desiccant dehumidifier module.
control_type
Control Type
choice Type of setpoint control: LeavingMaximumHumidityRatioSetpoint means that the unit is controlled to deliver air at the Leaving Max Humidity Ratio Setpoint (see below), SystemNodeMaximumHumidityRatioSetpoint means that the leaving humidity ratio setpoint is the System Node Humidity Ratio Max property of the Process Air Outlet Node. A Setpoint object must be used to control this setpoint. Both control types use bypass dampers to prevent over drying.
One of LeavingMaximumHumidityRatioSetpoint, SystemNodeMaximumHumidityRatioSetpoint
leaving_maximum_humidity_ratio_setpoint
Leaving Maximum Humidity Ratio Setpoint
number
kgWater/kgDryAir
Fixed setpoint for maximum process air leaving humidity ratio Applicable only when Control Type = LeavingMaximumHumidityRatioSetpoint.
nominal_process_air_flow_rate
Nominal Process Air Flow Rate
number
m3/s
Process air flow rate at nominal conditions
Range: > 0
nominal_process_air_velocity
Nominal Process Air Velocity
number
m/s
Process air velocity at nominal flow When using Performance Model Type of Default, must be 2.032 to 4.064 m/s (400 to 800 fpm)
Range: > 0, ≤ 6
rotor_power
Rotor Power
number
W
Power input to wheel rotor motor
Range: ≥ 0
regeneration_coil_object_type
Regeneration Coil Object Type
choice heating coil type works with gas, electric, hot water and steam heating coils
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
regeneration_coil_name
Regeneration Coil Name
reference Name of heating coil object for regeneration air
Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
regeneration_fan_object_type
Regeneration Fan Object Type
choice Type of fan object for regeneration air. When using the Default Performance Model Type (see below), only Fan:VariableVolume or Fan:SystemModel are valid.
One of Fan:ConstantVolume, Fan:SystemModel, Fan:VariableVolume
regeneration_fan_name
Regeneration Fan Name
reference Name of fan object for regeneration air
Names a Fan:ConstantVolume, Fan:SystemModel, Fan:VariableVolume
performance_model_type
Performance Model Type
choice Specifies whether the default performance model or user-specified curves should be used to model the performance. The default model is a generic solid desiccant wheel using performance curves of the form: curve = C1 + C2*edb + C3*edb**2 + C4*ew + C5*ew**2 + C6*vel + C7*vel**2 + C8*edb*ew + C9*edb**2*ew**2 + C10*edb*vel + C11*edb**2*vel**2 + C12*ew*vel + C13*ew**2*vel**2 + C14*ALOG(edb) + C15*ALOG(ew) + C16*ALOG(vel) edb = process entering dry-bulb temperature [C] ew = process entering humidity ratio [kgWater/kgDryAir] vel = process air velocity [m/s] If UserCurves are specified, then performance is calculated as follows: Leaving Dry-Bulb = (Leaving Dry-Bulb fTW Curve) * (Leaving Dry-Bulb fV Curve) Leaving Humidity Ratio = (Leaving Humidity Ratio fTW Curve) * (Leaving Humidity Ratio fV Curve) Regen Energy = (Regen Energy fTW Curve) * (Regen Energy fV Curve) Regen Velocity = (Regen Velocity fTW Curve) * (Regen Velocity fV Curve)
One of Default, UserCurves
leaving_dry_bulb_function_of_entering_dry_bulb_and_humidity_ratio_curve_name
Leaving Dry-Bulb Function of Entering Dry-Bulb and Humidity Ratio Curve Name
reference Leaving dry-bulb of process air as a function of entering dry-bulb and entering humidity ratio, biquadratic curve curve = C1 + C2*edb + C3*edb**2 + C4*ew + C5*ew**2 + C6*edb*ew edb = process entering dry-bulb temperature [C] ew = process entering humidity ratio [kgWater/kgDryAir]
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
leaving_dry_bulb_function_of_air_velocity_curve_name
Leaving Dry-Bulb Function of Air Velocity Curve Name
reference Leaving dry-bulb of process air as a function of air velocity, quadratic curve. curve = C1 + C2*v + C3*v**2 v = process air velocity [m/s]
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
leaving_humidity_ratio_function_of_entering_dry_bulb_and_humidity_ratio_curve_name
Leaving Humidity Ratio Function of Entering Dry-Bulb and Humidity Ratio Curve Name
reference Leaving humidity ratio of process air as a function of entering dry-bulb and entering humidity ratio, biquadratic curve curve = C1 + C2*edb + C3*edb**2 + C4*ew + C5*ew**2 + C6*edb*ew edb = process entering dry-bulb temperature [C] ew = process entering humidity ratio [kgWater/kgDryAir]
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
leaving_humidity_ratio_function_of_air_velocity_curve_name
Leaving Humidity Ratio Function of Air Velocity Curve Name
reference Leaving humidity ratio of process air as a function of process air velocity, quadratic curve. curve = C1 + C2*v + C3*v**2 v = process air velocity [m/s]
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
regeneration_energy_function_of_entering_dry_bulb_and_humidity_ratio_curve_name
Regeneration Energy Function of Entering Dry-Bulb and Humidity Ratio Curve Name
reference Regeneration energy [J/kg of water removed] as a function of entering dry-bulb and entering humidity ratio, biquadratic curve curve = C1 + C2*edb + C3*edb**2 + C4*ew + C5*ew**2 + C6*edb*ew edb = process entering dry-bulb temperature [C] ew = process entering humidity ratio [kgWater/kgDryAir]
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
regeneration_energy_function_of_air_velocity_curve_name
Regeneration Energy Function of Air Velocity Curve Name
reference Regeneration energy [J/kg of water removed] as a function of process air velocity, quadratic curve. curve = C1 + C2*v + C3*v**2 v = process air velocity [m/s]
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
regeneration_velocity_function_of_entering_dry_bulb_and_humidity_ratio_curve_name
Regeneration Velocity Function of Entering Dry-Bulb and Humidity Ratio Curve Name
reference Regeneration velocity [m/s] as a function of entering dry-bulb and entering humidity ratio, biquadratic curve curve = C1 + C2*edb + C3*edb**2 + C4*ew + C5*ew**2 + C6*edb*ew edb = process entering dry-bulb temperature [C] ew = process entering humidity ratio [kgWater/kgDryAir]
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
regeneration_velocity_function_of_air_velocity_curve_name
Regeneration Velocity Function of Air Velocity Curve Name
reference Regeneration velocity [m/s] as a function of process air velocity, quadratic curve. curve = C1 + C2*v + C3*v**2 v = process air velocity [m/s]
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
nominal_regeneration_temperature
Nominal Regeneration Temperature
number
C
Nominal regen temperature upon which the regen energy modifier curve is based. Not used if Default if chosen for the field Performance Mode Type. 121 C is a commonly used value.
Range: ≥ 40, ≤ 250
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch

Dehumidifier:Desiccant:System

from idfpy.models import DehumidifierDesiccantSystem

This compound object models a desiccant heat exchanger, an optional heater, and associated fans. The process air stream is the air which is dehumidified. The regeneration air stream is the air which is heated to regenerate the desiccant. The desiccant heat exchanger transfers both sensible and latent energy between the process and regeneration air streams. The desiccant dehumidifier is typically used in an AirLoopHVAC:OutdoorAirSystem, but can also be specified in any AirLoopHVAC.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
desiccant_heat_exchanger_object_type
Desiccant Heat Exchanger Object Type required
choice One of HeatExchanger:Desiccant:BalancedFlow
desiccant_heat_exchanger_name
Desiccant Heat Exchanger Name required
reference Names a HeatExchanger:Desiccant:BalancedFlow
sensor_node_name
Sensor Node Name required
string
regeneration_air_fan_object_type
Regeneration Air Fan Object Type required
choice One of Fan:ConstantVolume, Fan:OnOff, Fan:SystemModel
regeneration_air_fan_name
Regeneration Air Fan Name required
reference Names a Fan:OnOff, Fan:SystemModel, Fan:VariableVolume
regeneration_air_fan_placement
Regeneration Air Fan Placement
choice DrawThrough One of BlowThrough, DrawThrough
regeneration_air_heater_object_type
Regeneration Air Heater Object Type
choice works with gas, electric, hot water and steam heating coils. For autosizing the regeneration air heating coil the Design Coil Inlet Air Condition used is the outdoor air condition if the desiccant system is on the primary air loop, or else if the desiccant system is on outdoor air system then it is the return air condition. The Design Coil Outlet Air Temperature is the Regeneration Inlet Air Setpoint Temperature specified in the input field below.
One of Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
regeneration_air_heater_name
Regeneration Air Heater Name
reference Names a Coil:Heating:Electric, Coil:Heating:Fuel, Coil:Heating:Steam, Coil:Heating:Water
regeneration_inlet_air_setpoint_temperature
Regeneration Inlet Air Setpoint Temperature
number
C
46.0 This value is also used as regeneration air heater design coil air outlet temperature for autosizing calculation of the heater.
companion_cooling_coil_object_type
Companion Cooling Coil Object Type
choice One of Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed
companion_cooling_coil_name
Companion Cooling Coil Name
reference Names a Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableSpeed, CoilSystem:Cooling:DX:HeatExchangerAssisted
companion_cooling_coil_upstream_of_dehumidifier_process_inlet
Companion Cooling Coil Upstream of Dehumidifier Process Inlet
choice No Select Yes if the companion cooling coil is located directly upstream of the desiccant heat exchanger's process air inlet node.
One of No, Yes
companion_coil_regeneration_air_heating
Companion Coil Regeneration Air Heating
choice No One of No, Yes
exhaust_fan_maximum_flow_rate
Exhaust Fan Maximum Flow Rate
number
m3/s
exhaust_fan_maximum_power
Exhaust Fan Maximum Power
number
W
exhaust_fan_power_curve_name
Exhaust Fan Power Curve Name
reference Curve object type must be Curve:Quadratic or Curve:Cubic
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch

Duct:Loss:Conduction

from idfpy.models import DuctLossConduction

Field Type Default Details
name
Name required
string
airloophvac_name
AirLoopHVAC Name required
reference Names a AirLoopHVAC
airflownetwork_distribution_linkage_name
AirflowNetwork:Distribution:Linkage Name required
reference Names a AirflowNetwork:Distribution:Linkage
environment_type
Environment Type
choice Zone One of Schedule, Zone
ambient_zone_name
Ambient Zone Name
reference Names a Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_humidity_ratio_schedule_name
Ambient Humidity Ratio Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

Duct:Loss:Leakage

from idfpy.models import DuctLossLeakage

Field Type Default Details
name
Name required
string
airloophvac_name
AirLoopHVAC Name required
reference Names a AirLoopHVAC
airflownetwork_distribution_linkage_name
AirflowNetwork:Distribution:Linkage Name required
reference Names a AirflowNetwork:Distribution:Linkage

Duct:Loss:MakeupAir

from idfpy.models import DuctLossMakeupAir

Field Type Default Details
name
Name required
string
airloophvac_name
AirLoopHVAC Name required
reference Names a AirLoopHVAC
airflownetwork_distribution_linkage_name
AirflowNetwork:Distribution:Linkage Name required
reference Names a AirflowNetwork:Distribution:Linkage

Exterior:FuelEquipment

from idfpy.models import ExteriorFuelEquipment

only used for Meter type reporting, does not affect building loads

Field Type Default Details
name
Name required
string
fuel_use_type
Fuel Use Type required
choice One of Coal, Diesel, DistrictCooling, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane, Water
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to capacity of the exterior fuel equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level
Design Level required
number
W
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

Exterior:Lights

from idfpy.models import ExteriorLights

only used for Meter type reporting, does not affect building loads

Field Type Default Details
name
Name required
string
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to capacity of the exterior lights equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level
Design Level required
number
W
Range: ≥ 0
control_option
Control Option
choice Astronomical Clock option overrides schedule to turn lights off when sun is up
One of AstronomicalClock, ScheduleNameOnly
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 1 object types

DemandManager:ExteriorLights

Exterior:WaterEquipment

from idfpy.models import ExteriorWaterEquipment

only used for Meter type reporting, does not affect building loads

Field Type Default Details
name
Name required
string
fuel_use_type
Fuel Use Type
choice Water One of Water
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to capacity of the exterior water equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level
Design Level required
number
m3/s
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

GroundHeatTransfer:Basement:AutoGrid

from idfpy.models import GroundHeatTransferBasementAutoGrid

AutoGrid only necessary when EquivSizing is false If the modeled building is not a rectangle or square, Equivalent sizing MUST be used to get accurate results

Field Type Default Details
clearance_distance_from_outside_of_wall_to_edge
CLEARANCE: Distance from outside of wall to edge,
number
m
15.0 Range: ≥ 0
slabx_x_dimension_of_the_building_slab
SLABX: X dimension of the building slab required
number
m
Range: ≥ 0, ≤ 60
slaby_y_dimension_of_the_building_slab
SLABY: Y dimension of the building slab required
number
m
Range: ≥ 0, ≤ 60
concagheight_height_of_the_foundation_wall_above_grade
ConcAGHeight: Height of the foundation wall above grade
number
m
0.0 Range: ≥ 0
slabdepth_thickness_of_the_floor_slab
SlabDepth: Thickness of the floor slab
number
m
0.1
basedepth_depth_of_the_basement_wall_below_grade
BaseDepth: Depth of the basement wall below grade
number
m
2.0 Range: ≥ 0

GroundHeatTransfer:Basement:BldgData

from idfpy.models import GroundHeatTransferBasementBldgData

Specifies the surface and gravel thicknesses used for the Basement preprocessor ground heat transfer simulation.

Field Type Default Details
dwall_wall_thickness
DWALL: Wall thickness
number
m
0.2 Range: ≥ 0.2
dslab_floor_slab_thickness
DSLAB: Floor slab thickness
number
m
0.1 Range: > 0, ≤ 0.25
dgravxy_width_of_gravel_pit_beside_basement_wall
DGRAVXY: Width of gravel pit beside basement wall
number
m
0.3 Range: > 0
dgravzn_gravel_depth_extending_above_the_floor_slab
DGRAVZN: Gravel depth extending above the floor slab
number
m
0.2 Range: > 0
dgravzp_gravel_depth_below_the_floor_slab
DGRAVZP: Gravel depth below the floor slab
number
m
0.1 Range: > 0

GroundHeatTransfer:Basement:ComBldg

from idfpy.models import GroundHeatTransferBasementComBldg

ComBldg contains the monthly average temperatures (C) and possibility of daily variation amplitude

Field Type Default Details
january_average_temperature
January average temperature
number
C
22.0
february_average_temperature
February average temperature
number
C
22.0
march_average_temperature
March average temperature
number
C
22.0
april_average_temperature
April average temperature
number
C
22.0
may_average_temperature
May average temperature
number
C
22.0
june_average_temperature
June average temperature
number
C
22.0
july_average_temperature
July average temperature
number
C
22.0
august_average_temperature
August average temperature
number
C
22.0
september_average_temperature
September average temperature
number
C
22.0
october_average_temperature
October average temperature
number
C
22.0
november_average_temperature
November average temperature
number
C
22.0
december_average_temperature
December average temperature
number
C
22.0
daily_variation_sine_wave_amplitude
Daily variation sine wave amplitude
number
deltaC
0.0 (Normally zero, just for checking)

GroundHeatTransfer:Basement:EquivAutoGrid

from idfpy.models import GroundHeatTransferBasementEquivAutoGrid

EquivAutoGrid necessary when EquivSizing=TRUE, TRUE is is the normal case.

Field Type Default Details
clearance_distance_from_outside_of_wall_to_edge_of_3_d_ground_domain
CLEARANCE: Distance from outside of wall to edge of 3-D ground domain
number
m
15.0 Range: ≥ 0
slabdepth_thickness_of_the_floor_slab
SlabDepth: Thickness of the floor slab
number
m
0.1 Range: ≥ 0
basedepth_depth_of_the_basement_wall_below_grade
BaseDepth: Depth of the basement wall below grade
number
m
2.0 Range: ≥ 0

GroundHeatTransfer:Basement:EquivSlab

from idfpy.models import GroundHeatTransferBasementEquivSlab

Using an equivalent slab allows non-rectangular shapes to be modeled accurately. The simulation default should be EquivSizing=True

Field Type Default Details
apratio_the_area_to_perimeter_ratio_for_this_slab
APRatio: The area to perimeter ratio for this slab required
number
m
Range: > 0
equivsizing_flag
EquivSizing: Flag required
choice Will the dimensions of an equivalent slab be calculated (TRUE) or will the dimensions be input directly? (FALSE)] Only advanced special simulations should use FALSE.
One of FALSE, TRUE

GroundHeatTransfer:Basement:Insulation

from idfpy.models import GroundHeatTransferBasementInsulation

Describes the insulation used on an exterior basement wall for the Basement preprocessor ground heat transfer simulation.

Field Type Default Details
rext_r_value_of_any_exterior_insulation
REXT: R Value of any exterior insulation
number
m2-K/W
Range: > 0
insfull_flag_is_the_wall_fully_insulated
INSFULL: Flag: Is the wall fully insulated? required
choice True for full insulation False for insulation half way down side wall from grade line
One of FALSE, TRUE

GroundHeatTransfer:Basement:Interior

from idfpy.models import GroundHeatTransferBasementInterior

Provides the information needed to simulate the inside boundary conditions for the Basement preprocessor ground heat transfer simulation.

Field Type Default Details
cond_flag_is_the_basement_conditioned
COND: Flag: Is the basement conditioned?
choice TRUE for EnergyPlus this should be TRUE
One of FALSE, TRUE
hin_downward_convection_only_heat_transfer_coefficient
HIN: Downward convection only heat transfer coefficient
number
W/m2-K
0.92 Range: > 0
hin_upward_convection_only_heat_transfer_coefficient
HIN: Upward convection only heat transfer coefficient
number
W/m2-K
4.04 Range: > 0
hin_horizontal_convection_only_heat_transfer_coefficient
HIN: Horizontal convection only heat transfer coefficient
number
W/m2-K
3.08 Range: > 0
hin_downward_combined_convection_and_radiation_heat_transfer_coefficient
HIN: Downward combined (convection and radiation) heat transfer coefficient
number
W/m2-K
6.13 Range: > 0
hin_upward_combined_convection_and_radiation_heat_transfer_coefficient
HIN: Upward combined (convection and radiation) heat transfer coefficient
number
W/m2-K
9.26 Range: > 0
hin_horizontal_combined_convection_and_radiation_heat_transfer_coefficient
HIN: Horizontal combined (convection and radiation) heat transfer coefficient
number
W/m2-K
8.29 Range: > 0

GroundHeatTransfer:Basement:ManualGrid

from idfpy.models import GroundHeatTransferBasementManualGrid

Manual Grid only necessary using manual gridding (not recommended)

Field Type Default Details
nx_number_of_cells_in_the_x_direction_20
NX: Number of cells in the X direction: 20] required
number Range: ≥ 1
ny_number_of_cells_in_the_y_direction_20
NY: Number of cells in the Y direction: 20] required
number Range: ≥ 1
nzag_number_of_cells_in_the_z_direction_above_grade_4_always
NZAG: Number of cells in the Z direction. above grade: 4 Always] required
number Range: ≥ 1
nzbg_number_of_cells_in_z_direction_below_grade_10_35
NZBG: Number of cells in Z direction. below grade: 10-35] required
number Range: ≥ 1
ibase_x_direction_cell_indicator_of_slab_edge_5_20
IBASE: X direction cell indicator of slab edge: 5-20] required
number
jbase_y_direction_cell_indicator_of_slab_edge_5_20
JBASE: Y direction cell indicator of slab edge: 5-20] required
number
kbase_z_direction_cell_indicator_of_the_top_of_the_floor_slab_5_20
KBASE: Z direction cell indicator of the top of the floor slab: 5-20] required
number

GroundHeatTransfer:Basement:MatlProps

from idfpy.models import GroundHeatTransferBasementMatlProps

Specifies the material properties for the Basement preprocessor ground heat transfer simulation. Only the Foundation Wall, Floor Slab, Soil, and Gravel properties are currently used.

Field Type Default Details
nmat_number_of_materials_in_this_domain
NMAT: Number of materials in this domain required
number Range: ≤ 6
density_for_foundation_wall
Density for Foundation Wall
number
kg/m3
2243.0 Range: > 0
density_for_floor_slab
density for Floor Slab
number
kg/m3
2243.0 Range: > 0
density_for_ceiling
density for Ceiling
number
kg/m3
311.0 Range: > 0
density_for_soil
density for Soil
number
kg/m3
1500.0 Range: > 0
density_for_gravel
density for Gravel
number
kg/m3
2000.0 Range: > 0
density_for_wood
density for Wood
number
kg/m3
449.0 Range: > 0
specific_heat_for_foundation_wall
Specific heat for foundation wall
number
J/kg-K
880.0 Range: > 0
specific_heat_for_floor_slab
Specific heat for floor slab
number
J/kg-K
880.0 Range: > 0
specific_heat_for_ceiling
Specific heat for ceiling
number
J/kg-K
1530.0 Range: > 0
specific_heat_for_soil
Specific heat for soil
number
J/kg-K
840.0 Range: > 0
specific_heat_for_gravel
Specific heat for gravel
number
J/kg-K
720.0 Range: > 0
specific_heat_for_wood
Specific heat for wood
number
J/kg-K
1530.0 Range: > 0
thermal_conductivity_for_foundation_wall
Thermal conductivity for foundation wall
number
W/m-K
1.4 Range: > 0
thermal_conductivity_for_floor_slab
Thermal conductivity for floor slab
number
W/m-K
1.4 Range: > 0
thermal_conductivity_for_ceiling
Thermal conductivity for ceiling
number
W/m-K
0.09 Range: > 0
thermal_conductivity_for_soil
thermal conductivity for soil
number
W/m-K
1.1 Range: > 0
thermal_conductivity_for_gravel
thermal conductivity for gravel
number
W/m-K
1.9 Range: > 0
thermal_conductivity_for_wood
thermal conductivity for wood
number
W/m-K
0.12 Range: > 0

GroundHeatTransfer:Basement:SimParameters

from idfpy.models import GroundHeatTransferBasementSimParameters

Specifies certain parameters that control the Basement preprocessor ground heat transfer simulation.

Field Type Default Details
f_multiplier_for_the_adi_solution
F: Multiplier for the ADI solution
number 0<F<1.0, typically 0.1 (0.3 for high k soil - saturated sand is about 2.6 w/m-K)
Range: > 0, ≤ 1
iyrs_maximum_number_of_yearly_iterations
IYRS: Maximum number of yearly iterations:
number 15.0 typically 15-30]
Range: ≥ 0

GroundHeatTransfer:Basement:SurfaceProps

from idfpy.models import GroundHeatTransferBasementSurfaceProps

Specifies the soil surface properties for the Basement preprocessor ground heat transfer simulation.

Field Type Default Details
albedo_surface_albedo_for_no_snow_conditions
ALBEDO: Surface albedo for No snow conditions
number 0.16 Range: ≥ 0, ≤ 1
albedo_surface_albedo_for_snow_conditions
ALBEDO: Surface albedo for snow conditions
number 0.4 Range: ≥ 0, ≤ 1
epsln_surface_emissivity_no_snow
EPSLN: Surface emissivity No Snow
number 0.94 Range: ≥ 0, ≤ 1
epsln_surface_emissivity_with_snow
EPSLN: Surface emissivity with Snow
number 0.86 Range: ≥ 0, ≤ 1
veght_surface_roughness_no_snow_conditions
VEGHT: Surface roughness No snow conditions
number
cm
6.0 Range: ≥ 0
veght_surface_roughness_snow_conditions
VEGHT: Surface roughness Snow conditions
number
cm
0.25 Range: ≥ 0
pet_flag_potential_evapotranspiration_on
PET: Flag, Potential evapotranspiration on?
choice FALSE Typically, PET is False
One of FALSE, TRUE

GroundHeatTransfer:Basement:XFACE

from idfpy.models import GroundHeatTransferBasementXFACE

This is only needed when using manual gridding (not recommended) XFACE: X Direction cell face coordinates: m

Field Type Default Details

GroundHeatTransfer:Basement:YFACE

from idfpy.models import GroundHeatTransferBasementYFACE

This is only needed when using manual gridding (not recommended) YFACE: Y Direction cell face coordinates: m

Field Type Default Details

GroundHeatTransfer:Basement:ZFACE

from idfpy.models import GroundHeatTransferBasementZFACE

This is only needed when using manual gridding (not recommended) ZFACE: Z Direction cell face coordinates: m

Field Type Default Details

GroundHeatTransfer:Control

from idfpy.models import GroundHeatTransferControl

Object determines if the Slab and Basement preprocessors are going to be executed.

Field Type Default Details
name
Name
string This field is included for consistency.11
run_basement_preprocessor
Run Basement Preprocessor
choice No One of No, Yes
run_slab_preprocessor
Run Slab Preprocessor
choice No One of No, Yes

GroundHeatTransfer:Slab:AutoGrid

from idfpy.models import GroundHeatTransferSlabAutoGrid

AutoGrid only necessary when EquivalentSlab option not chosen. Not normally needed by EnergyPlus users. This object permits user selection of rectangular slab dimensions. NO SLAB DIMENSIONS LESS THAN 6 m.

Field Type Default Details
slabx_x_dimension_of_the_building_slab
SLABX: X dimension of the building slab required
number
m
typical values= 6 to 60.0
Range: ≥ 6
slaby_y_dimension_of_the_building_slab
SLABY: Y dimension of the building slab required
number
m
typical values= 6 to 60.0
Range: ≥ 6
slabdepth_thickness_of_slab_on_grade
SLABDEPTH: Thickness of slab on grade
number
m
0.1
clearance_distance_from_edge_of_slab_to_domain_edge
CLEARANCE: Distance from edge of slab to domain edge
number
m
15.0
zclearance_distance_from_bottom_of_slab_to_domain_bottom
ZCLEARANCE: Distance from bottom of slab to domain bottom
number
m
15.0

GroundHeatTransfer:Slab:BldgProps

from idfpy.models import GroundHeatTransferSlabBldgProps

Object provides information about the building and its operating conditions Monthly Average Temperature SetPoint fields specify the average indoor building set point temperatures for each month of the year. These fields are useful for simulating a building that is not temperature controlled for some of the year. In such a case, the average indoor set point temperatures can be obtained by first running the model in EnergyPlus with an insulated floor boundary condition, and then using the resulting monthly average zone temperatures in these fields.

Field Type Default Details
iyrs_number_of_years_to_iterate
IYRS: Number of years to iterate
number 10.0 This field specifies the number of years to iterate. Either the ground heat transfer calculations come to an an annual steady periodic condition by converging to a tolerance (see ConvTol field) or it runs for this number of years. A ten year maximum is usually sufficient.
Range: ≥ 1
shape_slab_shape
Shape: Slab shape
number Use only the value 0 here. Only a rectangular shape is implemented.
Range: ≥ 0, ≤ 0
hbldg_building_height
HBLDG: Building height
number
m
This field supplies the building height. This is used to calculate the building shadowing on the ground. typical value= 0-20
Range: ≥ 0
tin1_january_indoor_average_temperature_setpoint
TIN1: January Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin2_february_indoor_average_temperature_setpoint
TIN2: February Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin3_march_indoor_average_temperature_setpoint
TIN3: March Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin4_april_indoor_average_temperature_setpoint
TIN4: April Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin5_may_indoor_average_temperature_setpoint
TIN5: May Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin6_june_indoor_average_temperature_setpoint
TIN6: June Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin7_july_indoor_average_temperature_setpoint
TIN7: July Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin8_august_indoor_average_temperature_setpoint
TIN8: August Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin9_september_indoor_average_temperature_setpoint
TIN9: September Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin10_october_indoor_average_temperature_setpoint
TIN10: October Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin11_november_indoor_average_temperature_setpoint
TIN11: November Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tin12_december_indoor_average_temperature_setpoint
TIN12: December Indoor Average Temperature Setpoint
number
C
22.0 see memo on object for more information
tinamp_daily_indoor_sine_wave_variation_amplitude
TINAmp: Daily Indoor sine wave variation amplitude
number
deltaC
0.0 This field permits imposing a daily sinusoidal variation in the indoor setpoint temperature to simulate the effect of a setback profile. The value specified is the amplitude of the sine wave.
convtol_convergence_tolerance
ConvTol: Convergence Tolerance
number 0.1 This field specifies the convergence tolerance used to control the iteration. When the temperature change of all nodes is less than the convergence value, iteration ceases.

GroundHeatTransfer:Slab:BoundConds

from idfpy.models import GroundHeatTransferSlabBoundConds

Supplies some of the boundary conditions used in the ground heat transfer calculations.

Field Type Default Details
evtr_is_surface_evapotranspiration_modeled
EVTR: Is surface evapotranspiration modeled required
choice This field specifies whether or not to use the evapotranspiration model. The inclusion of evapotranspiration in the calculation has the greatest effect in warm dry climates, primarily on the ground surface temperature. This field can be used to turn the evapotranspiration off and on to check sensitivity to it.
One of FALSE, TRUE
fixbc_is_the_lower_boundary_at_a_fixed_temperature
FIXBC: is the lower boundary at a fixed temperature required
choice This field permits using a fixed temperature at the lower surface of the model instead of a zero heat flux condition. This change normally has a very small effect on the results. FALSE selects the zero flux lower boundary condition
One of FALSE, TRUE
tdeepin
TDEEPin
number
C
User input lower boundary temperature if FIXBC is TRUE Blank for FIXBC FALSE or to use the calculated 1-D deep ground temperature.
usrhflag_is_the_ground_surface_h_specified_by_the_user
USRHflag: Is the ground surface h specified by the user? required
choice This field flags the use of a user specified heat transfer coefficient on the ground surface. This condition is used primarily for testing. For normal runs (USPHflag is FALSE) and the program calculates the heat transfer coefficient using the weather conditions.
One of FALSE, TRUE
userh_user_specified_ground_surface_heat_transfer_coefficient
USERH: User specified ground surface heat transfer coefficient
number
W/m2-K
Used only if USRHflag is TRUE and the heat transfer coefficient value is specified in this field.

GroundHeatTransfer:Slab:EquivalentSlab

from idfpy.models import GroundHeatTransferSlabEquivalentSlab

Using an equivalent slab allows non-rectangular shapes to be modeled accurately. Object uses the area - perimeter (area/perimeter) ratio to determine the size of an equivalent rectangular slab. EnergyPlus users normally use this option.

Field Type Default Details
apratio_the_area_to_perimeter_ratio_for_this_slab
APRatio: The area to perimeter ratio for this slab required
number
m
Equivalent square slab is simulated, side is 4*APRatio.
Range: ≥ 1.5, ≤ 22
slabdepth_thickness_of_slab_on_grade
SLABDEPTH: Thickness of slab on grade
number
m
0.1 This field specifies the thickness of the slab. The slab top surface is level with the ground surface, so this is the depth into the ground. The slab depth has a significant effect on the temperature calculation, and it is also important for the auto-grid process. The finite difference grids are set in such a way that they use the slab thickness to determine the vertical grid spacing. Autogridding will fail if the slab thickness is specified larger than 0.25 meters.
clearance_distance_from_edge_of_slab_to_domain_edge
CLEARANCE: Distance from edge of slab to domain edge
number
m
15.0 This field specifies the distance from the slab to the edge of the area that will be modeled with the grid system. It is the basic size dimension that is used to set the horizontal extent of the domain. 15 meters is a reasonable value.
zclearance_distance_from_bottom_of_slab_to_domain_bottom
ZCLEARANCE: Distance from bottom of slab to domain bottom
number
m
15.0 This field specifies the vertical distance from the slab to the bottom edge of the area that will be modeled with the grid system. 15 meters is a reasonable value.

GroundHeatTransfer:Slab:Insulation

from idfpy.models import GroundHeatTransferSlabInsulation

This object supplies the information about insulation used around the slab. There are two possible configurations: under the slab or vertical insulation around the slab.

Field Type Default Details
rins_r_value_of_under_slab_insulation
RINS: R value of under slab insulation
number
m2-K/W
0.0 This field provides the thermal resistance value of the under slab insulation. It should be zero if the vertical insulation configuration is selected. typical value= 0-2.0
dins_width_of_strip_of_under_slab_insulation
DINS: Width of strip of under slab insulation
number
m
0.0 This specifies the width of the perimeter strip of insulation under the slab. It should be zero if for the vertical insulation configuration is selected. typical value= 0-2.0
rvins_r_value_of_vertical_insulation
RVINS: R value of vertical insulation
number
m2-K/W
0.0 This field specifies the thermal resistance of the vertical insulation. It should be zero if the under slab insulation configuration is selected. typical value= 0-3.0
zvins_depth_of_vertical_insulation
ZVINS: Depth of vertical insulation
number
m
0.0 This field specifies the depth of the vertical insulation into the ground in meters. It starts at the slab upper surface and extends into the ground. It should be zero if the under slab insulation configuration is selected. only use values= .2 .4 .6 .8 1.0 1.5 2.0 2.5 3.0
ivins_flag_is_there_vertical_insulation
IVINS: Flag: Is there vertical insulation
0 or 1 0.0 Specifies if the vertical insulation configuration is being used. values: 1=yes vertical insulation 0=no under-slab insulation

GroundHeatTransfer:Slab:ManualGrid

from idfpy.models import GroundHeatTransferSlabManualGrid

Manual Grid only necessary when using manual gridding (not recommended) Used only in special cases when previous two objects are not used. User must input complete gridding information.

Field Type Default Details
nx_number_of_cells_in_the_x_direction
NX: Number of cells in the X direction required
number Range: ≥ 1
ny_number_of_cells_in_the_y_direction
NY: Number of cells in the Y direction required
number Range: ≥ 1
nz_number_of_cells_in_the_z_direction
NZ: Number of cells in the Z direction required
number Range: ≥ 1
ibox_x_direction_cell_indicator_of_slab_edge
IBOX: X direction cell indicator of slab edge required
number typical values= 1-10
jbox_y_direction_cell_indicator_of_slab_edge
JBOX: Y direction cell indicator of slab edge required
number typical values= 1-10

GroundHeatTransfer:Slab:Materials

from idfpy.models import GroundHeatTransferSlabMaterials

Object gives an overall description of the slab ground heat transfer model.

Field Type Default Details
nmat_number_of_materials
NMAT: Number of materials required
number This field specifies the number of different materials that will be used in the model. Typically only a ground material and a slab material are used. (2 materials)
Range: > 0
albedo_surface_albedo_no_snow
ALBEDO: Surface Albedo: No Snow
number 0.16 Two fields specify the albedo value of the surface: first for no snow coverage days; second for days with snow coverage. The albedo is the solar reflectivity of the surface, and can vary from 0.05 for blacktop to 0.95 for fresh snow. Typical values for North America reported by Bahnfleth range from 0.16 to 0.4.
Range: ≥ 0, ≤ 1
albedo_surface_albedo_snow
ALBEDO: Surface Albedo: Snow
number 0.4 Range: ≥ 0, ≤ 1
epslw_surface_emissivity_no_snow
EPSLW: Surface Emissivity: No Snow
number 0.94 EPSLW (No Snow and Snow) specifies the long wavelength (thermal) emissivity of the ground surface. primarily important for nighttime radiation to sky. typical value .95
Range: > 0
epslw_surface_emissivity_snow
EPSLW: Surface Emissivity: Snow
number 0.86 Range: > 0
z0_surface_roughness_no_snow
Z0: Surface Roughness: No Snow
number
cm
0.75 fields Z0 (No Snow and Snow) describe the height at which an experimentally velocity profile goes to zero. typical value= .75 cm
Range: > 0
z0_surface_roughness_snow
Z0: Surface Roughness: Snow
number
cm
0.25 typical value= .05 cm
Range: > 0
hin_indoor_hconv_downward_flow
HIN: Indoor HConv: Downward Flow
number
W/m2-K
6.13 These fields specify the combined convective and radiative heat transfer coefficient between the slab top inside surface and the room air for the cases where heat is flowing downward, and upward. The program toggles between the two if the direction of the heat flux changes. Typical values can be found in the ASHRAE Handbook of Fundamentals, but should be about 6 W/(m2-K) for downward heat flow and 9 W/(m2-K) for upward heat flow. typical value= 4-10
Range: > 0
hin_indoor_hconv_upward
HIN: Indoor HConv: Upward
number
W/m2-K
9.26 typical value= 4-10
Range: > 0

GroundHeatTransfer:Slab:MatlProps

from idfpy.models import GroundHeatTransferSlabMatlProps

This object contains the material properties for the materials used in the model. The fields are mostly self explanatory.

Field Type Default Details
rho_slab_material_density
RHO: Slab Material density
number
kg/m3
2300.0 Density of Slab Material typical value= 2300.0
Range: > 0
rho_soil_density
RHO: Soil Density
number
kg/m3
1200.0 Density of Soil Material typical value= 1200.0
Range: > 0
cp_slab_cp
CP: Slab CP
number
J/kg-K
650.0 Specific Heat of Slab Material typical value=650.0
Range: > 0
cp_soil_cp
CP: Soil CP
number
J/kg-K
1200.0 Specific Heat of Soil Material typical value= 1200.0
Range: > 0
tcon_slab_k
TCON: Slab k
number
W/m-K
0.9 Conductivity of Slab Material typical value= .9
Range: > 0
tcon_soil_k
TCON: Soil k
number
W/m-K
1.0 Conductivity of Soil Material typical value= 1.0
Range: > 0

GroundHeatTransfer:Slab:XFACE

from idfpy.models import GroundHeatTransferSlabXFACE

This is only needed when using manual gridding (not recommended) XFACE: X Direction cell face coordinates: m

Field Type Default Details

GroundHeatTransfer:Slab:YFACE

from idfpy.models import GroundHeatTransferSlabYFACE

This is only needed when using manual gridding (not recommended) YFACE: Y Direction cell face coordinates: m,

Field Type Default Details

GroundHeatTransfer:Slab:ZFACE

from idfpy.models import GroundHeatTransferSlabZFACE

This is only needed when using manual gridding (not recommended) ZFACE: Z Direction cell face coordinates: m

Field Type Default Details

HeatExchanger:AirToAir:FlatPlate

from idfpy.models import HeatExchangerAirToAirFlatPlate

Flat plate air-to-air heat exchanger, typically used for exhaust or relief air heat recovery.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
flow_arrangement_type
Flow Arrangement Type
choice One of CounterFlow, CrossFlowBothUnmixed, ParallelFlow
economizer_lockout
Economizer Lockout
choice Yes Yes means that the heat exchanger will be locked out (off) when the economizer is operating or high humidity control is active
One of No, Yes
ratio_of_supply_to_secondary_ha_values
Ratio of Supply to Secondary hA Values
number Ratio of h*A for supply side to h*A for exhaust side
Range: ≥ 0
nominal_supply_air_flow_rate
Nominal Supply Air Flow Rate
number or Autosize
m3/s
Autosize
nominal_supply_air_inlet_temperature
Nominal Supply Air Inlet Temperature required
number
C
nominal_supply_air_outlet_temperature
Nominal Supply Air Outlet Temperature required
number
C
nominal_secondary_air_flow_rate
Nominal Secondary Air Flow Rate required
number or Autosize
m3/s
nominal_secondary_air_inlet_temperature
Nominal Secondary Air Inlet Temperature required
number
C
nominal_electric_power
Nominal Electric Power
number
W
supply_air_inlet_node_name
Supply Air Inlet Node Name required
string
supply_air_outlet_node_name
Supply Air Outlet Node Name required
string
secondary_air_inlet_node_name
Secondary Air Inlet Node Name required
string
secondary_air_outlet_node_name
Secondary Air Outlet Node Name required
string
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:DX:HeatExchangerAssisted, SpaceHVAC:ZoneEquipmentSplitter, ZoneHVAC:EquipmentList

HeatExchanger:AirToAir:SensibleAndLatent

from idfpy.models import HeatExchangerAirToAirSensibleAndLatent

This object models an air-to-air heat exchanger using effectiveness relationships. The heat exchanger can transfer sensible energy, latent energy, or both between the supply (primary) and exhaust (secondary) air streams.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
nominal_supply_air_flow_rate
Nominal Supply Air Flow Rate required
number or Autosize
m3/s
sensible_effectiveness_at_100_heating_air_flow
Sensible Effectiveness at 100% Heating Air Flow
number
dimensionless
0.0 Range: ≥ 0, ≤ 1
latent_effectiveness_at_100_heating_air_flow
Latent Effectiveness at 100% Heating Air Flow
number
dimensionless
0.0 Range: ≥ 0, ≤ 1
sensible_effectiveness_at_100_cooling_air_flow
Sensible Effectiveness at 100% Cooling Air Flow
number
dimensionless
0.0 Range: ≥ 0, ≤ 1
latent_effectiveness_at_100_cooling_air_flow
Latent Effectiveness at 100% Cooling Air Flow
number
dimensionless
0.0 Range: ≥ 0, ≤ 1
supply_air_inlet_node_name
Supply Air Inlet Node Name required
string
supply_air_outlet_node_name
Supply Air Outlet Node Name required
string
exhaust_air_inlet_node_name
Exhaust Air Inlet Node Name required
string
exhaust_air_outlet_node_name
Exhaust Air Outlet Node Name required
string
nominal_electric_power
Nominal Electric Power
number
W
0.0 Range: ≥ 0
supply_air_outlet_temperature_control
Supply Air Outlet Temperature Control
choice No One of No, Yes
heat_exchanger_type
Heat Exchanger Type
choice Plate One of Plate, Rotary
frost_control_type
Frost Control Type
choice None One of ExhaustAirRecirculation, ExhaustOnly, MinimumExhaustTemperature, None
threshold_temperature
Threshold Temperature
number
C
1.7 Supply (outdoor) air inlet temp threshold for exhaust air recirculation and exhaust only frost control types. Exhaust air outlet threshold Temperature for minimum exhaust temperature frost control type.
initial_defrost_time_fraction
Initial Defrost Time Fraction
number
dimensionless
0.083 Fraction of the time when frost control will be invoked at the threshold temperature. This field only used for exhaust air recirc and exhaust-only frost control types.
Range: ≥ 0, ≤ 1
rate_of_defrost_time_fraction_increase
Rate of Defrost Time Fraction Increase
number
1/K
0.012 Rate of increase in defrost time fraction as actual temp falls below threshold temperature. This field only used for exhaust air recirc and exhaust-only frost control types.
Range: ≥ 0
economizer_lockout
Economizer Lockout
choice Yes Yes means that the heat exchanger will be locked out (off) when the economizer is operating or high humidity control is active
One of No, Yes
sensible_effectiveness_of_heating_air_flow_curve_name
Sensible Effectiveness of Heating Air Flow Curve Name
reference optional if this field has value, then the sensible effectiveness for heating will be the value in N2 multiplied by this curve value
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
latent_effectiveness_of_heating_air_flow_curve_name
Latent Effectiveness of Heating Air Flow Curve Name
reference optional if this field has value, then the latent effectiveness for heating will be the value in N3 multiplied by this curve value
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
sensible_effectiveness_of_cooling_air_flow_curve_name
Sensible Effectiveness of Cooling Air Flow Curve Name
reference optional if this field has value, then the sensible effectiveness for cooling will be the value in N4 multiplied by this curve value
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
latent_effectiveness_of_cooling_air_flow_curve_name
Latent Effectiveness of Cooling Air Flow Curve Name
reference optional if this field has value, then the latent effectiveness for cooling will be the value in N5 multiplied by this curve value
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:DX:HeatExchangerAssisted, ZoneHVAC:EnergyRecoveryVentilator

HeatExchanger:Desiccant:BalancedFlow

from idfpy.models import HeatExchangerDesiccantBalancedFlow

This object models a balanced desiccant heat exchanger. The heat exchanger transfers both sensible and latent energy between the process and regeneration air streams. The air flow rate and face velocity are assumed to be the same on both the process and regeneration sides of the heat exchanger.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
regeneration_air_inlet_node_name
Regeneration Air Inlet Node Name required
string
regeneration_air_outlet_node_name
Regeneration Air Outlet Node Name required
string
process_air_inlet_node_name
Process Air Inlet Node Name required
string
process_air_outlet_node_name
Process Air Outlet Node Name required
string
heat_exchanger_performance_object_type
Heat Exchanger Performance Object Type
choice HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1 One of HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1
heat_exchanger_performance_name
Heat Exchanger Performance Name required
reference Names a HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1
economizer_lockout
Economizer Lockout
choice Yes Yes means that the heat exchanger will be locked out (off) when the economizer is operating or high humidity control is active
One of No, Yes
Referenced by 7 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, AirflowNetwork:Distribution:Component:HeatExchanger, AirflowNetwork:Distribution:Linkage, Branch, CoilSystem:Cooling:DX:HeatExchangerAssisted, Dehumidifier:Desiccant:System

HeatExchanger:Desiccant:BalancedFlow:PerformanceDataType1

from idfpy.models import HeatExchangerDesiccantBalancedFlowPerformanceDataType1

RTO = B1 + B2*RWI + B3*RTI + B4*(RWI/RTI) + B5*PWI + B6*PTI + B7*(PWI/PTI) + B8*RFV RWO = C1 + C2*RWI + C3*RTI + C4*(RWI/RTI) + C5*PWI + C6*PTI + C7*(PWI/PTI) + C8*RFV where, RTO = Dry-bulb temperature of the regeneration outlet air (C) RWO = Humidity ratio of the regeneration outlet air (kgWater/kgDryAir) RWI = Humidity ratio of the regeneration inlet air (kgWater/kgDryAir) RTI = Dry-bulb temperature of the regeneration inlet air (C) PWI = Humidity ratio of the process inlet air (kgWater/kgDryAir) PTI = Dry-bulb temperature of the process inlet air (C) RFV = Regeneration Face Velocity (m/s)

Field Type Default Details
name
Name required
string
nominal_air_flow_rate
Nominal Air Flow Rate
number or Autosize
m3/s
Air flow rate at nominal conditions (assumed to be the same for both sides of the heat exchanger).
nominal_air_face_velocity
Nominal Air Face Velocity required
number or Autosize
m/s
nominal_electric_power
Nominal Electric Power
number
W
0.0 Parasitic electric power (e.g., desiccant wheel motor)
Range: ≥ 0
temperature_equation_coefficient_1
Temperature Equation Coefficient 1 required
number
temperature_equation_coefficient_2
Temperature Equation Coefficient 2 required
number
temperature_equation_coefficient_3
Temperature Equation Coefficient 3 required
number
temperature_equation_coefficient_4
Temperature Equation Coefficient 4 required
number
temperature_equation_coefficient_5
Temperature Equation Coefficient 5 required
number
temperature_equation_coefficient_6
Temperature Equation Coefficient 6 required
number
temperature_equation_coefficient_7
Temperature Equation Coefficient 7 required
number
temperature_equation_coefficient_8
Temperature Equation Coefficient 8 required
number
minimum_regeneration_inlet_air_humidity_ratio_for_temperature_equation
Minimum Regeneration Inlet Air Humidity Ratio for Temperature Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
maximum_regeneration_inlet_air_humidity_ratio_for_temperature_equation
Maximum Regeneration Inlet Air Humidity Ratio for Temperature Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
minimum_regeneration_inlet_air_temperature_for_temperature_equation
Minimum Regeneration Inlet Air Temperature for Temperature Equation required
number
C
maximum_regeneration_inlet_air_temperature_for_temperature_equation
Maximum Regeneration Inlet Air Temperature for Temperature Equation required
number
C
minimum_process_inlet_air_humidity_ratio_for_temperature_equation
Minimum Process Inlet Air Humidity Ratio for Temperature Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
maximum_process_inlet_air_humidity_ratio_for_temperature_equation
Maximum Process Inlet Air Humidity Ratio for Temperature Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
minimum_process_inlet_air_temperature_for_temperature_equation
Minimum Process Inlet Air Temperature for Temperature Equation required
number
C
maximum_process_inlet_air_temperature_for_temperature_equation
Maximum Process Inlet Air Temperature for Temperature Equation required
number
C
minimum_regeneration_air_velocity_for_temperature_equation
Minimum Regeneration Air Velocity for Temperature Equation required
number
m/s
Range: > 0
maximum_regeneration_air_velocity_for_temperature_equation
Maximum Regeneration Air Velocity for Temperature Equation required
number
m/s
Range: > 0
minimum_regeneration_outlet_air_temperature_for_temperature_equation
Minimum Regeneration Outlet Air Temperature for Temperature Equation required
number
C
maximum_regeneration_outlet_air_temperature_for_temperature_equation
Maximum Regeneration Outlet Air Temperature for Temperature Equation required
number
C
minimum_regeneration_inlet_air_relative_humidity_for_temperature_equation
Minimum Regeneration Inlet Air Relative Humidity for Temperature Equation required
number
percent
Range: ≥ 0, ≤ 100
maximum_regeneration_inlet_air_relative_humidity_for_temperature_equation
Maximum Regeneration Inlet Air Relative Humidity for Temperature Equation required
number
percent
Range: ≥ 0, ≤ 100
minimum_process_inlet_air_relative_humidity_for_temperature_equation
Minimum Process Inlet Air Relative Humidity for Temperature Equation required
number
percent
Range: ≥ 0, ≤ 100
maximum_process_inlet_air_relative_humidity_for_temperature_equation
Maximum Process Inlet Air Relative Humidity for Temperature Equation required
number
percent
Range: ≥ 0, ≤ 100
humidity_ratio_equation_coefficient_1
Humidity Ratio Equation Coefficient 1 required
number
humidity_ratio_equation_coefficient_2
Humidity Ratio Equation Coefficient 2 required
number
humidity_ratio_equation_coefficient_3
Humidity Ratio Equation Coefficient 3 required
number
humidity_ratio_equation_coefficient_4
Humidity Ratio Equation Coefficient 4 required
number
humidity_ratio_equation_coefficient_5
Humidity Ratio Equation Coefficient 5 required
number
humidity_ratio_equation_coefficient_6
Humidity Ratio Equation Coefficient 6 required
number
humidity_ratio_equation_coefficient_7
Humidity Ratio Equation Coefficient 7 required
number
humidity_ratio_equation_coefficient_8
Humidity Ratio Equation Coefficient 8 required
number
minimum_regeneration_inlet_air_humidity_ratio_for_humidity_ratio_equation
Minimum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
maximum_regeneration_inlet_air_humidity_ratio_for_humidity_ratio_equation
Maximum Regeneration Inlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
minimum_regeneration_inlet_air_temperature_for_humidity_ratio_equation
Minimum Regeneration Inlet Air Temperature for Humidity Ratio Equation required
number
C
maximum_regeneration_inlet_air_temperature_for_humidity_ratio_equation
Maximum Regeneration Inlet Air Temperature for Humidity Ratio Equation required
number
C
minimum_process_inlet_air_humidity_ratio_for_humidity_ratio_equation
Minimum Process Inlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
maximum_process_inlet_air_humidity_ratio_for_humidity_ratio_equation
Maximum Process Inlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
minimum_process_inlet_air_temperature_for_humidity_ratio_equation
Minimum Process Inlet Air Temperature for Humidity Ratio Equation required
number
C
maximum_process_inlet_air_temperature_for_humidity_ratio_equation
Maximum Process Inlet Air Temperature for Humidity Ratio Equation required
number
C
minimum_regeneration_air_velocity_for_humidity_ratio_equation
Minimum Regeneration Air Velocity for Humidity Ratio Equation required
number
m/s
Range: > 0
maximum_regeneration_air_velocity_for_humidity_ratio_equation
Maximum Regeneration Air Velocity for Humidity Ratio Equation required
number
m/s
Range: > 0
minimum_regeneration_outlet_air_humidity_ratio_for_humidity_ratio_equation
Minimum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
maximum_regeneration_outlet_air_humidity_ratio_for_humidity_ratio_equation
Maximum Regeneration Outlet Air Humidity Ratio for Humidity Ratio Equation required
number
kgWater/kgDryAir
Range: ≥ 0, ≤ 1
minimum_regeneration_inlet_air_relative_humidity_for_humidity_ratio_equation
Minimum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation required
number
percent
Range: ≥ 0, ≤ 100
maximum_regeneration_inlet_air_relative_humidity_for_humidity_ratio_equation
Maximum Regeneration Inlet Air Relative Humidity for Humidity Ratio Equation required
number
percent
Range: ≥ 0, ≤ 100
minimum_process_inlet_air_relative_humidity_for_humidity_ratio_equation
Minimum Process Inlet Air Relative Humidity for Humidity Ratio Equation required
number
percent
Range: ≥ 0, ≤ 100
maximum_process_inlet_air_relative_humidity_for_humidity_ratio_equation
Maximum Process Inlet Air Relative Humidity for Humidity Ratio Equation required
number
percent
Range: ≥ 0, ≤ 100
Referenced by 1 object types

HeatExchanger:Desiccant:BalancedFlow

Humidifier:Steam:Electric

from idfpy.models import HumidifierSteamElectric

Electrically heated steam humidifier with fan.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_capacity
Rated Capacity
number or Autosize
m3/s
Capacity is m3/s of water at 5.05 C
rated_power
Rated Power
number or Autosize
W
if autosized the rated power is calculated from the rated capacity and enthalpy rise of water from 20.0C to 100.0C steam and assumes electric to thermal energy conversion efficiency of 100.0%
rated_fan_power
Rated Fan Power
number
W
Range: ≥ 0
standby_power
Standby Power
number
W
Range: ≥ 0
air_inlet_node_name
Air Inlet Node Name
string
air_outlet_node_name
Air Outlet Node Name
string
water_storage_tank_name
Water Storage Tank Name
reference Names a WaterUse:Storage
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch

Humidifier:Steam:Gas

from idfpy.models import HumidifierSteamGas

Natural gas fired steam humidifier with optional blower fan.

Field Type Default Details
name
Name required
string
availability_schedule_name
Availability Schedule Name
reference Availability schedule name for this system. Schedule value > 0 means the system is available. If this field is blank, the system is always available.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
rated_capacity
Rated Capacity
number or Autosize
m3/s
Capacity is m3/s of water at 5.05 C The nominal full capacity water addition rate in m3/s of water at 5.05 C
rated_gas_use_rate
Rated Gas Use Rate
number or Autosize
W
if auto-sized, the rated gas use rate is calculated from the rated capacity and enthalpy rise of water from 20.0C to 100.0C steam and user input thermal efficiency value specified in the next input field. If this input field is hard-sized and Inlet Water Temperature Option input field is selected as FixedInletWaterTemperature, then the thermal efficiency input field will not be used or else if the Inlet Water Temperature Option input field is selected as VariableInletWaterTemperature, then the thermal efficiency input value is overridden by a value calculated from the capacity, rated gas use rate and design condition.
thermal_efficiency
Thermal Efficiency
number
dimensionless
0.8 Based on the higher heating value of fuel. If "Rated Gas Use Rate" in the field above is not auto-sized and the Inlet Water Temperature Option input field is specified as FixedInletWaterTemperature, then the thermal efficiency specified will not be used in the calculation, or else if the Inlet Water Temperature Option input field is selected as VariableInletWaterTemperature, then the thermal efficiency value is overridden by a value calculated from the capacity, rated gas use rate and design condition.
Range: > 0, ≤ 1
thermal_efficiency_modifier_curve_name
Thermal Efficiency Modifier Curve Name
reference Linear, Quadratic and Cubic efficiency curves are solely a function of PLR. Linear = C1 + C2*PLR Quadratic = C1 + C2*PLR + C3*PLR^2 Cubic = C1 + C2*PLR + C3*PLR^2 + C4*PLR^3 This is thermal efficiency modifier curve name of gas fired steam humidifier. This curve is normalized, i.e., curve output value at rated condition is 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_fan_power
Rated Fan Power
number
W
The nominal full capacity electric power input to the blower fan in Watts. If no blower fan is required to inject the dry steam to the supply air stream, then this input field is set to zero.
Range: ≥ 0
auxiliary_electric_power
Auxiliary Electric Power
number
W
0.0 The auxiliary electric power input in watts. This amount of power will be consumed whenever the unit is available (as defined by the availability schedule). This electric power is used for control purpose only.
Range: ≥ 0
air_inlet_node_name
Air Inlet Node Name
string
air_outlet_node_name
Air Outlet Node Name
string
water_storage_tank_name
Water Storage Tank Name
reference Names a WaterUse:Storage
inlet_water_temperature_option
Inlet Water Temperature Option
choice FixedInletWaterTemperature The inlet water temperature can be fixed at 20C as it is done for electric steam humidifier or it can be allowed to vary with temperature of the water source. Currently allowed water sources are main water or water storage tank in water use objects. if FixedInletWaterTemperature is specified, then a fixed 20C water temperature will be used, or else if VariableInletWaterTemperature is specified, then inlet water will vary depending the source water temperature. If this input field is left blank, then fixed inlet water temperature of 20C will be assumed.
One of FixedInletWaterTemperature, VariableInletWaterTemperature
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, AirLoopHVAC:OutdoorAirSystem:EquipmentList, Branch

HybridModel:Zone

from idfpy.models import HybridModelZone

Zones with measured air temperature data and a range of dates. If the range of temperature measurement dates includes a leap day, the weather data should include a leap day.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
calculate_zone_internal_thermal_mass
Calculate Zone Internal Thermal Mass
choice No Use measured zone air temperature to calculate zone internal thermal mass. If set to Yes, the measured zone air temperature should be provided to calculate the thermal mass. If set to No, the inverse calculation of thermal mass will not be activated.
One of No, Yes
calculate_zone_air_infiltration_rate
Calculate Zone Air Infiltration Rate
choice No Use measured temperature data (temperature, humidity ratio, or CO2 concentration) to calculate zone air infiltration air flow rate. Only one of field Calculate Zone Internal Thermal Mass, Calculate Zone Air Infiltration Rate, and Calculate Zone People Count can be set to YES at a time. By default, this field is set to NO. When set to NO, the inverse calculation of the zone air infiltration rate will not be activated. If this field is set to YES, one of the following fields (combinations) should be provided: 1. Measurements were conducted when HVAC is free-floating: 1.1 Zone Measured Air Temperature Schedule Name 1.2 Zone Measured Air Humidity Ratio Schedule Name 1.3 Zone Measured Air CO2 Concentration Schedule Name 2. Measurements were conducted when HVAC is on: 2.1 Zone Measured Air Temperature Schedule Name, Zone Input Supply Air Temperature Schedule Name, and Zone Input Supply Air Mass Flow Rate Schedule Name 2.2 Zone Measured Air Humidity Ratio Schedule Name, Zone Input Supply Air Temperature Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Humidity Ratio Schedule Name 2.3 Zone Measured Air CO2 Concentration Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air CO2 Concentration Schedule Name
One of No, Yes
calculate_zone_people_count
Calculate Zone People Count
choice No Use measured humidity ratio data (temperature, humidity ratio, or CO2 concentration) to calculate zone people count. Only one of field Calculate Zone Internal Thermal Mass, Calculate Zone Air Infiltration Rate, and Calculate Zone People Count can be set to YES at a time. By default, this field is set to NO. When set to NO, the inverse calculation of the zone people count will not be activated. If this field is set to YES, one of the following fields (combinations) should be provided: 1. Measurements were conducted when HVAC is free-floating: 1.1 Zone Measured Air Temperature Schedule Name 1.2 Zone Measured Air Humidity Ratio Schedule Name 1.3 Zone Measured Air CO2 Concentration Schedule Name 2. Measurements were conducted when HVAC is on: 2.1 Zone Measured Air Temperature Schedule Name, Zone Input Supply Air Temperature Schedule Name, and Zone Input Supply Air Mass Flow Rate Schedule Name 2.2 Zone Measured Air Humidity Ratio Schedule Name, Zone Input Supply Air Temperature Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air Humidity Ratio Schedule Name 2.3 Zone Measured Air CO2 Concentration Schedule Name, Zone Input Supply Air Mass Flow Rate Schedule Name, and Zone Input Supply Air CO2 Concentration Schedule Name Field Zone Input People Activity Schedule Name, Zone Input People Sensible Heat Fraction Schedule Name, Zone Input People Radiant Heat Fraction Schedule Name, Zone Input People CO2 Generation Rate Schedule Name are optional. If provided, the default people activity level (130W), sensible heat generation rate (78W), latent heat generation (52W) rate, and CO2 generation rate (0.0000000382 [m3/(s*W)]) will be overwritten correspondingly.
One of No, Yes
zone_measured_air_temperature_schedule_name
Zone Measured Air Temperature Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_measured_air_humidity_ratio_schedule_name
Zone Measured Air Humidity Ratio Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_measured_air_co2_concentration_schedule_name
Zone Measured Air CO2 Concentration Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_people_activity_schedule_name
Zone Input People Activity Schedule Name
reference When this field is provided and valid, the default people activity level (used to calculate people count) will be overwritten. from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_people_sensible_heat_fraction_schedule_name
Zone Input People Sensible Heat Fraction Schedule Name
reference When this field is provided and valid, the default sensible heat fraction from people (used to calculate people count) will be overwritten. from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_people_radiant_heat_fraction_schedule_name
Zone Input People Radiant Heat Fraction Schedule Name
reference When this field is provided and valid, the default radiant heat portion of the sensible heat from people (used to calculate people count) will be overwritten. from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_people_co2_generation_rate_schedule_name
Zone Input People CO2 Generation Rate Schedule Name
reference When this field is provided and valid, the default people CO2 generation rate (used to calculate people count) will be overwritten. from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_supply_air_temperature_schedule_name
Zone Input Supply Air Temperature Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_supply_air_mass_flow_rate_schedule_name
Zone Input Supply Air Mass Flow Rate Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_supply_air_humidity_ratio_schedule_name
Zone Input Supply Air Humidity Ratio Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
zone_input_supply_air_co2_concentration_schedule_name
Zone Input Supply Air CO2 Concentration Schedule Name
reference from Schedule:File
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
begin_month
Begin Month required
integer Range: ≥ 1, ≤ 12
begin_day_of_month
Begin Day of Month required
integer Range: ≥ 1, ≤ 31
end_month
End Month required
integer Range: ≥ 1, ≤ 12
end_day_of_month
End Day of Month required
integer Range: ≥ 1, ≤ 31

LoadProfile:Plant

from idfpy.models import LoadProfilePlant

Used to simulate a scheduled plant loop demand profile. Load and flow rate are specified using schedules. Positive values are heating loads, and negative values are cooling loads. The actual load met is dependent on the performance of the supply loop components. Optional inputs for steam loop.

Field Type Default Details
name
Name required
string
inlet_node_name
Inlet Node Name required
string
outlet_node_name
Outlet Node Name required
string
load_schedule_name
Load Schedule Name required
reference Schedule values are load in [W]
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
peak_flow_rate
Peak Flow Rate required
number
m3/s
flow_rate_fraction_schedule_name
Flow Rate Fraction Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
plant_loop_fluid_type
Plant Loop Fluid Type
choice Water One of Steam, Water
degree_of_subcooling
Degree of SubCooling
number
C
5.0 This field is used only when Plant Loop Fluid Type=Steam.
Range: ≥ 1
degree_of_loop_subcooling
Degree of Loop SubCooling
number
C
20.0 This field is used only when Plant Loop Fluid Type=Steam.
Range: ≥ 10
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

Matrix:TwoDimension

from idfpy.models import MatrixTwoDimension extensible

matrix data in row-major order list each row keeping the columns in order number of values must equal N1 x N2

Field Type Default Details
name
Name required
string
number_of_rows
Number of Rows required
integer
number_of_columns
Number of Columns required
integer
values list Each item: value
Referenced by 1 object types

Construction:ComplexFenestrationState

Parametric:FileNameSuffix

from idfpy.models import ParametricFileNameSuffix unique extensible

Defines the suffixes to be appended to the idf and output file names for each parametric run. If this object is omitted, the suffix will default to the run number.

Field Type Default Details
name
Name
string
suffixes list Each item: suffix_for_file_name_in_run

Parametric:Logic

from idfpy.models import ParametricLogic unique extensible

This object allows some types of objects to be included for some parametric cases and not for others. For example, you might want an overhang on a window in some parametric runs and not others. A single Parametric:Logic object is allowed per file. Consult the Input Output Reference for available commands and syntax.

Field Type Default Details
name
Name required
string
lines list Each item: parametric_logic_line

Parametric:RunControl

from idfpy.models import ParametricRunControl unique extensible

Controls which parametric runs are simulated. This object is optional. If it is not included, then all parametric runs are performed.

Field Type Default Details
name
Name
string
runs list Each item: perform_run

Parametric:SetValueForRun

from idfpy.models import ParametricSetValueForRun extensible

Parametric objects allow a set of multiple simulations to be defined in a single idf file. The parametric preprocessor scans the idf for Parametric:* objects then creates and runs multiple idf files, one for each defined simulation. The core parametric object is Parametric:SetValueForRun which defines the name of a parameter and sets the parameter to different values depending on which run is being simulated.

Field Type Default Details
name
Name required
string Parameter Name Must begin with the dollar sign character. The second character must be a letter. Remaining characters may only be letters or numbers. No spaces allowed.
values list Each item: value_for_run

PlantLoop

from idfpy.models import PlantLoop

Defines a central plant loop.

Field Type Default Details
name
Name required
string
fluid_type
Fluid Type
choice Water One of Steam, UserDefinedFluidType, Water
user_defined_fluid_type
User Defined Fluid Type
reference This field is only required when Fluid Type is UserDefinedFluidType
Names a FluidProperties:GlycolConcentration, FluidProperties:Name
plant_equipment_operation_scheme_name
Plant Equipment Operation Scheme Name required
reference Names a PlantEquipmentOperationSchemes
loop_temperature_setpoint_node_name
Loop Temperature Setpoint Node Name required
string
maximum_loop_temperature
Maximum Loop Temperature required
number
C
minimum_loop_temperature
Minimum Loop Temperature required
number
C
maximum_loop_flow_rate
Maximum Loop Flow Rate required
number or Autosize
m3/s
minimum_loop_flow_rate
Minimum Loop Flow Rate
number
m3/s
0.0
plant_loop_volume
Plant Loop Volume
number or Autocalculate
m3
Autocalculate
plant_side_inlet_node_name
Plant Side Inlet Node Name required
string
plant_side_outlet_node_name
Plant Side Outlet Node Name required
string
plant_side_branch_list_name
Plant Side Branch List Name required
reference Names a BranchList
plant_side_connector_list_name
Plant Side Connector List Name
reference Names a ConnectorList
demand_side_inlet_node_name
Demand Side Inlet Node Name required
string
demand_side_outlet_node_name
Demand Side Outlet Node Name required
string
demand_side_branch_list_name
Demand Side Branch List Name required
reference Names a BranchList
demand_side_connector_list_name
Demand Side Connector List Name
reference Names a ConnectorList
load_distribution_scheme
Load Distribution Scheme
choice SequentialLoad One of Optimal, SequentialLoad, SequentialUniformPLR, UniformLoad, UniformPLR
availability_manager_list_name
Availability Manager List Name
reference Names a AvailabilityManagerAssignmentList
plant_loop_demand_calculation_scheme
Plant Loop Demand Calculation Scheme
choice SingleSetpoint One of DualSetpointDeadband, SingleSetpoint
common_pipe_simulation
Common Pipe Simulation
choice None Specifies a primary-secondary loop configuration. The plant side is the primary loop, and the demand side is the secondary loop. A secondary supply pump is required on the demand side. None = Primary-only, no secondary simulation CommonPipe = Primary-secondary with no temperature control at primary-secondary interface TwoWayCommonPipe = Primary-secondary with control of secondary supply temperature or primary return temperature (requires a setpoint be placed on the plant side or demand side inlet node).
One of CommonPipe, None, TwoWayCommonPipe
pressure_simulation_type
Pressure Simulation Type
choice None One of LoopFlowCorrection, None, PumpPowerCorrection
loop_circulation_time
Loop Circulation Time
number
minutes
2.0 This field is only used to autocalculate the Plant Loop Volume. Loop Volume = Loop Circulation Time * Maximum Loop Flow Rate
Range: ≥ 0
Referenced by 1 object types

Sizing:Plant

Table:IndependentVariable

from idfpy.models import TableIndependentVariable extensible

An independent variable representing a single dimension of a Table:Lookup object.

Field Type Default Details
name
Name required
string
interpolation_method
Interpolation Method
choice Linear One of Cubic, Linear
extrapolation_method
Extrapolation Method
choice Constant One of Constant, Linear
minimum_value
Minimum Value
number
maximum_value
Maximum Value
number
normalization_reference_value
Normalization Reference Value
number
unit_type
Unit Type
choice Dimensionless One of Angle, Dimensionless, Distance, MassFlow, Power, Temperature, VolumetricFlow
external_file_name
External File Name
string
external_file_column_number
External File Column Number
integer Range: ≥ 1
external_file_starting_row_number
External File Starting Row Number
integer Range: ≥ 1
values list Each item: value
Referenced by 1 object types

Table:IndependentVariableList

Table:IndependentVariableList

from idfpy.models import TableIndependentVariableList extensible

A sorted list of independent variables used by one or more Table:Lookup objects.

Field Type Default Details
name
Name required
string
independent_variables list Each item: independent_variable_name
Referenced by 1 object types

Table:Lookup

Table:Lookup

from idfpy.models import TableLookup extensible

Lookup tables are used in place of curves and can represent any number of independent variables (defined as Table:IndependentVariable objects in a Table:IndependentVariableList). Output values are interpolated within the bounds defined by each independent variable and extrapolated beyond the bounds according to the interpolation/extrapolation methods defined by each independent variable.

Field Type Default Details
name
Name required
string
independent_variable_list_name
Independent Variable List Name required
reference Names a Table:IndependentVariableList
normalization_method
Normalization Method
choice None One of AutomaticWithDivisor, DivisorOnly, None
normalization_divisor
Normalization Divisor
number 1.0
minimum_output
Minimum Output
number
maximum_output
Maximum Output
number
output_unit_type
Output Unit Type
choice Dimensionless One of Capacity, Dimensionless, Power, Pressure, Temperature
external_file_name
External File Name
string
external_file_column_number
External File Column Number
integer Range: ≥ 1
external_file_starting_row_number
External File Starting Row Number
integer Range: ≥ 1
values list Each item: output_value
Referenced by 101 object types

AirConditioner:VariableRefrigerantFlow, AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl, AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR, AirTerminal:SingleDuct:ConstantVolume:FourPipeBeam, AirTerminal:SingleDuct:ParallelPIU:Reheat, AirflowNetwork:MultiZone:ExternalNode, AirflowNetwork:OccupantVentilationControl, AvailabilityManager:HybridVentilation, Boiler:HotWater, Branch, Chiller:Absorption:Indirect, Chiller:ConstantCOP, Chiller:Electric, Chiller:Electric:EIR, Chiller:Electric:ReformulatedEIR, Chiller:EngineDriven, ChillerHeater:Absorption:DirectFired, ChillerHeater:Absorption:DoubleEffect, ChillerHeaterPerformance:Electric:EIR, Coil:Cooling:DX:CurveFit:Performance, Coil:Cooling:DX:CurveFit:Speed, Coil:Cooling:DX:MultiSpeed, Coil:Cooling:DX:SingleSpeed, Coil:Cooling:DX:SingleSpeed:ThermalStorage, Coil:Cooling:DX:TwoSpeed, Coil:Cooling:DX:TwoStageWithHumidityControlMode, Coil:Cooling:DX:VariableRefrigerantFlow, Coil:Cooling:DX:VariableRefrigerantFlow:FluidTemperatureControl, Coil:Cooling:DX:VariableSpeed, Coil:Cooling:WaterToAirHeatPump:EquationFit, Coil:Cooling:WaterToAirHeatPump:ParameterEstimation, Coil:Cooling:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:Heating:DX:MultiSpeed, Coil:Heating:DX:SingleSpeed, Coil:Heating:DX:VariableRefrigerantFlow, Coil:Heating:DX:VariableRefrigerantFlow:FluidTemperatureControl, Coil:Heating:DX:VariableSpeed, Coil:Heating:Fuel, Coil:Heating:Gas:MultiStage, Coil:Heating:WaterToAirHeatPump:EquationFit, Coil:Heating:WaterToAirHeatPump:ParameterEstimation, Coil:Heating:WaterToAirHeatPump:VariableSpeedEquationFit, Coil:WaterHeating:AirToWaterHeatPump:Pumped, Coil:WaterHeating:AirToWaterHeatPump:VariableSpeed, Coil:WaterHeating:AirToWaterHeatPump:Wrapped, Coil:WaterHeating:Desuperheater, CoilPerformance:DX:Cooling, Controller:OutdoorAir, CoolingTower:VariableSpeed, CoolingTower:VariableSpeed:Merkel, Dehumidifier:Desiccant:NoFans, Dehumidifier:Desiccant:System, ElectricEquipment:ITE:AirCooled, ElectricEquipment:ITE:AirCooled:Definition, ElectricLoadCenter:Inverter:FunctionOfPower, ElectricLoadCenter:Storage:Battery, ElectricLoadCenter:Storage:Converter, EnergyManagementSystem:CurveOrTableIndexVariable, EvaporativeCooler:Direct:ResearchSpecial, EvaporativeCooler:Indirect:ResearchSpecial, Fan:ComponentModel, Fan:OnOff, Fan:SystemModel, FaultModel:Fouling:AirFilter, Generator:CombustionTurbine, Generator:FuelCell:AirSupply, Generator:FuelCell:Inverter, Generator:FuelCell:PowerModule, Generator:FuelCell:WaterSupply, Generator:FuelSupply, Generator:InternalCombustionEngine, Generator:MicroCHP:NonNormalizedParameters, Generator:MicroTurbine, HeatExchanger:AirToAir:SensibleAndLatent, HeatPump:AirToWater, HeatPump:AirToWater:FuelFired:Cooling, HeatPump:AirToWater:FuelFired:Heating, HeatPump:PlantLoop:EIR:Cooling, HeatPump:PlantLoop:EIR:Heating, HeatPump:WaterToWater:EquationFit:Cooling, HeatPump:WaterToWater:EquationFit:Heating, Humidifier:Steam:Gas, OutdoorAir:Node, Pump:ConstantSpeed, Pump:VariableSpeed, Refrigeration:AirChiller, Refrigeration:Case, Refrigeration:Compressor, Refrigeration:CompressorRack, Refrigeration:Condenser:AirCooled, Refrigeration:GasCooler:AirCooled, Refrigeration:SecondarySystem, SetpointManager:CondenserEnteringReset, SurfaceConvectionAlgorithm:Inside:UserCurve, SurfaceConvectionAlgorithm:Outside:UserCurve, ThermalStorage:Ice:Detailed, WaterHeater:Mixed, WindowMaterial:Glazing, ZoneHVAC:Dehumidifier:DX, ZoneHVAC:EnergyRecoveryVentilator:Controller, ZoneHVAC:HybridUnitaryHVAC

TemperingValve

from idfpy.models import TemperingValve

Temperature-controlled diversion valve used to divert flow around one or more plant components such as a hot water heater. It can only be used on one of two branches between a Splitter and a Mixer.

Field Type Default Details
name
Name required
string
inlet_node_name
Inlet Node Name required
string Name of a Node
outlet_node_name
Outlet Node Name required
string Name of a Node
stream_2_source_node_name
Stream 2 Source Node Name required
string Name of a Node
temperature_setpoint_node_name
Temperature Setpoint Node Name required
string Name of a Node
pump_outlet_node_name
Pump Outlet Node Name required
string
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

ZoneTerminalUnitList

from idfpy.models import ZoneTerminalUnitList extensible

List of variable refrigerant flow (VRF) terminal units served by a given VRF condensing unit. See ZoneHVAC:TerminalUnit:VariableRefrigerantFlow and AirConditioner:VariableRefrigerantFlow.

Field Type Default Details
zone_terminal_unit_list_name
Zone Terminal Unit List Name required
string
terminal_units list Each item: zone_terminal_unit_name
Referenced by 3 object types

AirConditioner:VariableRefrigerantFlow, AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl, AirConditioner:VariableRefrigerantFlow:FluidTemperatureControl:HR