Plant Heating and Cooling Equipment

28 object types from idfpy.models.plant_equipment · EnergyPlus 26.2

Object Summary
Boiler:HotWater This boiler model is an adaptation of the empirical model from the Building Loads and System Thermodynamics …
Boiler:Steam This boiler model is an adaptation of the empirical model from the Building Loads and System Thermodynamics …
CentralHeatPumpSystem This chiller bank can contain multiple chiller heaters and heat pump performance objects.
Chiller:Absorption This indirect absorption chiller model is the empirical model from the Building Loads and System …
Chiller:Absorption:Indirect This indirect absorption chiller model is an enhanced model from the Building Loads and System Thermodynamics …
Chiller:CombustionTurbine This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program.
Chiller:ConstantCOP This constant COP chiller model provides a means of quickly specifying a Chiller where performance data is …
Chiller:Electric This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program.
Chiller:Electric:ASHRAE205 This chiller model utilizes ASHRAE Standard 205 compliant representations for chillers (Representation …
Chiller:Electric:EIR This chiller model is the empirical model from the DOE-2 building Energy simulation program.
Chiller:Electric:ReformulatedEIR This chiller model is an empirical model, a reformulated version of Chiller:Electric:EIR where the …
Chiller:EngineDriven This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program.
ChillerHeater:Absorption:DirectFired Direct fired gas absorption chiller-heater using performance curves similar to DOE-2
ChillerHeater:Absorption:DoubleEffect Exhaust fired absorption chiller-heater using performance curves similar to DOE-2
ChillerHeaterPerformance:Electric:EIR This chiller model is a generic chiller-heater where the cooling mode performance is a function of condenser …
DistrictCooling Centralized source of chilled water, such as a district cooling system.
DistrictHeating:Steam Centralized source of Steam, such as a district heating system.
DistrictHeating:Water Centralized source of hot water, such as a district heating system.
HeatPump:AirToWater air-to-water heat pump system which provides either chilled or hot water with single- or variable speed …
HeatPump:AirToWater:FuelFired:Cooling The object defines a fuel-fired absorption heat pump based on equation-fit models.
HeatPump:AirToWater:FuelFired:Heating The object defines a fuel-fired absorption heat pump based on equation-fit models.
HeatPump:PlantLoop:EIR:Cooling An EIR formulated water to water heat pump model, cooling operation.
HeatPump:PlantLoop:EIR:Heating An EIR formulated water to water heat pump model, heating operation
HeatPump:WaterToWater:EquationFit:Cooling simple water-water heat pump curve-fit model
HeatPump:WaterToWater:EquationFit:Heating simple water-water hp curve-fit model
HeatPump:WaterToWater:ParameterEstimation:Cooling OSU parameter estimation model
HeatPump:WaterToWater:ParameterEstimation:Heating OSU parameter estimation model
PlantComponent:TemperatureSource Simulates an object of pre-determined (constant or scheduled) source temperature The object introduces fluid …

Boiler:HotWater

from idfpy.models import BoilerHotWater

This boiler model is an adaptation of the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Boiler performance curves are generated by fitting catalog data to polynomial equations. A constant efficiency boiler may be modeled by leaving the normalized boiler efficiency curve name input blank.

Field Type Default Details
name
Name required
string
fuel_type
Fuel Type required
choice One of Coal, Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
nominal_capacity
Nominal Capacity
number or Autosize
W
nominal_thermal_efficiency
Nominal Thermal Efficiency required
number Based on the higher heating value of fuel.
Range: > 0
efficiency_curve_temperature_evaluation_variable
Efficiency Curve Temperature Evaluation Variable
choice One of EnteringBoiler, LeavingBoiler
normalized_boiler_efficiency_curve_name
Normalized Boiler Efficiency Curve Name
reference Linear, Quadratic and Cubic efficiency curves are solely a function of PLR. All other efficiency curve types are a function of PLR and boiler water temperature. Linear = C1 + C2*PLR Quadratic = C1 + C2*PLR + C3*PLR^2 Cubic = C1 + C2*PLR + C3*PLR^2 + C4*PLR^3 Biquadratic = C1 + C2*PLR + C3*PLR^2 + C4*T + C5*T^2 + C6*PLR*T QuadraticLinear = C1 + C2*PLR + C3*PLR^2 + (C4 + C5*PLR + C6*PLR^2)*T BiCubic = C1+C2*PLR+C3*PLR2+C4*T+C5*T2+C6*PLR*T+C7*PLR3+C8*T3+C9*PLR2*T+C10*PLR*T2 TriQuadratic curves are not allowed. PLR = part-load ratio T = boiler water temperature (either entering or leaving).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
design_water_flow_rate
Design Water Flow Rate
number or Autosize
m3/s
Autosize
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 Range: ≥ 0
boiler_water_inlet_node_name
Boiler Water Inlet Node Name required
string
boiler_water_outlet_node_name
Boiler Water Outlet Node Name required
string
water_outlet_upper_temperature_limit
Water Outlet Upper Temperature Limit
number
C
99.9
boiler_flow_mode
Boiler Flow Mode
choice NotModulated Select operating mode for fluid flow through the boiler. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by boiler to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by boiler to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
on_cycle_parasitic_electric_load
On Cycle Parasitic Electric Load
number
W
0.0 Range: ≥ 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
off_cycle_parasitic_fuel_load
Off Cycle Parasitic Fuel Load
number
W
parasitic fuel load when the boiler is not operating (i.e., standing pilot)
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Boiler, HVACTemplate:Plant:Boiler:ObjectReference, PlantEquipmentList

Boiler:Steam

from idfpy.models import BoilerSteam

This boiler model is an adaptation of the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Boiler performance curves are generated by fitting catalog data to third order polynomial equations. A constant efficiency boiler is modeled by setting the fuel use coefficients as follows: N9=1, N10=0, N11=0

Field Type Default Details
name
Name required
string
fuel_type
Fuel Type required
choice One of Coal, Diesel, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
maximum_operating_pressure
Maximum Operating Pressure
number
Pa
160000.0
theoretical_efficiency
Theoretical Efficiency
number 0.8 Range: > 0, ≤ 1
design_outlet_steam_temperature
Design Outlet Steam Temperature
number
C
100.0
nominal_capacity
Nominal Capacity
number or Autosize
W
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
coefficient_1_of_fuel_use_function_of_part_load_ratio_curve
Coefficient 1 of Fuel Use Function of Part Load Ratio Curve
number
coefficient_2_of_fuel_use_function_of_part_load_ratio_curve
Coefficient 2 of Fuel Use Function of Part Load Ratio Curve
number
coefficient_3_of_fuel_use_function_of_part_load_ratio_curve
Coefficient 3 of Fuel Use Function of Part Load Ratio Curve
number
water_inlet_node_name
Water Inlet Node Name
string
steam_outlet_node_name
Steam Outlet Node Name
string
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

CentralHeatPumpSystem

from idfpy.models import CentralHeatPumpSystem

This chiller bank can contain multiple chiller heaters and heat pump performance objects. Its function is to encapsulate the extra controls needed to turn individual modules on/off and whether they are to operate in cooling-only, heating-only or simultaneous cooling/heating mode and whether to connect the source water to the evaporator or condenser side.

Field Type Default Details
name
Name required
string
cooling_loop_inlet_node_name
Cooling Loop Inlet Node Name required
string
cooling_loop_outlet_node_name
Cooling Loop Outlet Node Name required
string
source_loop_inlet_node_name
Source Loop Inlet Node Name required
string
source_loop_outlet_node_name
Source Loop Outlet Node Name required
string
heating_loop_inlet_node_name
Heating Loop Inlet Node Name required
string
heating_loop_outlet_node_name
Heating Loop Outlet Node Name required
string
ancillary_power
Ancillary Power
number
W
0.0 Power as demanded from any auxiliary controls
Range: ≥ 0
ancillary_operation_schedule_name
Ancillary Operation Schedule Name
reference This value from this schedule is multiplied times the Ancillary Power
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
chiller_heater_modules_performance_component_object_type_1
Chiller Heater Modules Performance Component Object Type 1 required
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_1
Chiller Heater Modules Performance Component Name 1 required
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_1
Chiller Heater Modules Control Schedule Name 1 required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_1
Number of Chiller Heater Modules 1
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_2
Chiller Heater Modules Performance Component Object Type 2
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_2
Chiller Heater Modules Performance Component Name 2
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_2
Chiller Heater Modules Control Schedule Name 2
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_2
Number of Chiller Heater Modules 2
integer 1 Range: ≥ 1
chiller_heater_performance_component_object_type_3
Chiller Heater Performance Component Object Type 3
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_performance_component_name_3
Chiller Heater Performance Component Name 3
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_3
Chiller Heater Modules Control Schedule Name 3
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_3
Number of Chiller Heater Modules 3
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_4
Chiller Heater Modules Performance Component Object Type 4
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_4
Chiller Heater Modules Performance Component Name 4
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_4
Chiller Heater Modules Control Schedule Name 4
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_4
Number of Chiller Heater Modules 4
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_5
Chiller Heater Modules Performance Component Object Type 5
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_models_performance_component_name_5
Chiller Heater Models Performance Component Name 5
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_5
Chiller Heater Modules Control Schedule Name 5
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_5
Number of Chiller Heater Modules 5
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_6
Chiller Heater Modules Performance Component Object Type 6
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_6
Chiller Heater Modules Performance Component Name 6
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_6
Chiller Heater Modules Control Schedule Name 6
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_6
Number of Chiller Heater Modules 6
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_7
Chiller Heater Modules Performance Component Object Type 7
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_7
Chiller Heater Modules Performance Component Name 7
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_7
Chiller Heater Modules Control Schedule Name 7
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_7
Number of Chiller Heater Modules 7
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_8
Chiller Heater Modules Performance Component Object Type 8
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_8
Chiller Heater Modules Performance Component Name 8
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_8
Chiller Heater Modules Control Schedule Name 8
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_8
Number of Chiller Heater Modules 8
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_9
Chiller Heater Modules Performance Component Object Type 9
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_9
Chiller Heater Modules Performance Component Name 9
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_9
Chiller Heater Modules Control Schedule Name 9
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_9
Number of Chiller Heater Modules 9
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_10
Chiller Heater Modules Performance Component Object Type 10
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_10
Chiller Heater Modules Performance Component Name 10
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_10
Chiller Heater Modules Control Schedule Name 10
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_10
Number of Chiller Heater Modules 10
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_11
Chiller Heater Modules Performance Component Object Type 11
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_11
Chiller Heater Modules Performance Component Name 11
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_module_control_schedule_name_11
Chiller Heater Module Control Schedule Name 11
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_11
Number of Chiller Heater Modules 11
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_12
Chiller Heater Modules Performance Component Object Type 12
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_12
Chiller Heater Modules Performance Component Name 12
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_12
Chiller Heater Modules Control Schedule Name 12
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_12
Number of Chiller Heater Modules 12
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_13
Chiller Heater Modules Performance Component Object Type 13
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_13
Chiller Heater Modules Performance Component Name 13
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_13
Chiller Heater Modules Control Schedule Name 13
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_13
Number of Chiller Heater Modules 13
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_14
Chiller Heater Modules Performance Component Object Type 14
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_14
Chiller Heater Modules Performance Component Name 14
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_14
Chiller Heater Modules Control Schedule Name 14
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_14
Number of Chiller Heater Modules 14
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_15
Chiller Heater Modules Performance Component Object Type 15
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_15
Chiller Heater Modules Performance Component Name 15
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_15
Chiller Heater Modules Control Schedule Name 15
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_15
Number of Chiller Heater Modules 15
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_16
Chiller Heater Modules Performance Component Object Type 16
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_16
Chiller Heater Modules Performance Component Name 16
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_16
Chiller Heater Modules Control Schedule Name 16
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_16
Number of Chiller Heater Modules 16
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_17
Chiller Heater Modules Performance Component Object Type 17
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_17
Chiller Heater Modules Performance Component Name 17
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_17
Chiller Heater Modules Control Schedule Name 17
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_17
Number of Chiller Heater Modules 17
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_18
Chiller Heater Modules Performance Component Object Type 18
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_18
Chiller Heater Modules Performance Component Name 18
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_control_schedule_name_18
Chiller Heater Modules Control Control Schedule Name 18
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_18
Number of Chiller Heater Modules 18
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_19
Chiller Heater Modules Performance Component Object Type 19
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_19
Chiller Heater Modules Performance Component Name 19
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_19
Chiller Heater Modules Control Schedule Name 19
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_19
Number of Chiller Heater Modules 19
integer 1 Range: ≥ 1
chiller_heater_modules_performance_component_object_type_20
Chiller Heater Modules Performance Component Object Type 20
choice One of ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_performance_component_name_20
Chiller Heater Modules Performance Component Name 20
reference Names a ChillerHeaterPerformance:Electric:EIR
chiller_heater_modules_control_schedule_name_20
Chiller Heater Modules Control Schedule Name 20
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_chiller_heater_modules_20
Number of Chiller Heater Modules 20
integer 1 Range: ≥ 1
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

Chiller:Absorption

from idfpy.models import ChillerAbsorption

This indirect absorption chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Chiller performance curves are generated by fitting catalog data to third order polynomial equations. Two sets of coefficients are required.

Field Type Default Details
name
Name required
string
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_pumping_power
Nominal Pumping Power required
number or Autosize
W
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name required
string
condenser_outlet_node_name
Condenser Outlet Node Name required
string
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
design_condenser_inlet_temperature
Design Condenser Inlet Temperature
number
C
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
For variable volume this is the max flow & for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
The steam use coefficients below specify the steam use as a fraction of chiller operating capacity
coefficient_1_of_the_hot_water_or_steam_use_part_load_ratio_curve
Coefficient 1 of the Hot Water or Steam Use Part Load Ratio Curve
number
coefficient_2_of_the_hot_water_or_steam_use_part_load_ratio_curve
Coefficient 2 of the Hot Water or Steam Use Part Load Ratio Curve
number
coefficient_3_of_the_hot_water_or_steam_use_part_load_ratio_curve
Coefficient 3 of the Hot Water or Steam Use Part Load Ratio Curve
number
coefficient_1_of_the_pump_electric_use_part_load_ratio_curve
Coefficient 1 of the Pump Electric Use Part Load Ratio Curve
number The pump electric use coefficients specify the pumping power as a Fraction of Nominal pumping power
coefficient_2_of_the_pump_electric_use_part_load_ratio_curve
Coefficient 2 of the Pump Electric Use Part Load Ratio Curve
number
coefficient_3_of_the_pump_electric_use_part_load_ratio_curve
Coefficient 3 of the Pump Electric Use Part Load Ratio Curve
number
chilled_water_outlet_temperature_lower_limit
Chilled Water Outlet Temperature Lower Limit
number
C
generator_inlet_node_name
Generator Inlet Node Name
string
generator_outlet_node_name
Generator Outlet Node Name
string
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
generator_heat_source_type
Generator Heat Source Type
choice Steam The Generator side of the chiller can be connected to a hot water or steam plant where the generator inlet and outlet nodes are connected to a plant loop. If the generator is not connected to a plant loop, and the generator inlet/outlet nodes are not used, this field should be specified as steam or left blank. When a plant is not used, the model assumes steam as the heat source.
One of HotWater, Steam
design_generator_fluid_flow_rate
Design Generator Fluid Flow Rate
number or Autosize
m3/s
degree_of_subcooling_in_steam_generator
Degree of Subcooling in Steam Generator
number
C
1.0 This field is not used when the generator inlet/outlet nodes are not specified or the generator is connected to a hot water loop.
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:Absorption:Indirect

from idfpy.models import ChillerAbsorptionIndirect

This indirect absorption chiller model is an enhanced model from the Building Loads and System Thermodynamics (BLAST) program. Chiller performance curves are generated by fitting catalog data to third order polynomial equations. The chiller capacity is a function of condenser, chilled water, and generator temperatures. The heat input is a function of part-load ratio, condenser temperature, and chilled water temperature.

Field Type Default Details
name
Name required
string
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_pumping_power
Nominal Pumping Power required
number or Autosize
W
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name required
string
condenser_outlet_node_name
Condenser Outlet Node Name required
string
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
design_condenser_inlet_temperature
Design Condenser Inlet Temperature
number
C
30.0 Used only when condenser flow rate is autosized.
condenser_inlet_temperature_lower_limit
Condenser Inlet Temperature Lower Limit
number
C
15.0 Provides warnings when entering condenser temperature is below minimum. Capacity is not adjusted when entering condenser temperature is below minimum.
chilled_water_outlet_temperature_lower_limit
Chilled Water Outlet Temperature Lower Limit
number
C
5.0 Capacity is adjusted when leaving chilled water temperature is below minimum.
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
Autosize For variable flow this is the max flow & for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
Autosize
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
generator_heat_input_function_of_part_load_ratio_curve_name
Generator Heat Input Function of Part Load Ratio Curve Name required
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
pump_electric_input_function_of_part_load_ratio_curve_name
Pump Electric Input Function of Part Load Ratio Curve Name
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
generator_inlet_node_name
Generator Inlet Node Name
string Enter the generator inlet node name which connects this chiller to a steam or hot water plant, otherwise leave this field blank. Generator nodes are used to model heat input to the chiller.
generator_outlet_node_name
Generator Outlet Node Name
string Enter the generator outlet node name which connects this chiller to a steam or hot water plant, otherwise leave this field blank. Generator nodes are used to model heat input to the chiller.
capacity_correction_function_of_condenser_temperature_curve_name
Capacity Correction Function of Condenser Temperature Curve Name
reference Curve which shows the change in normalized capacity to changes in condenser temperature.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
capacity_correction_function_of_chilled_water_temperature_curve_name
Capacity Correction Function of Chilled Water Temperature Curve Name
reference Curve which shows the change in normalized capacity to changes in leaving chilled water temperature.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
capacity_correction_function_of_generator_temperature_curve_name
Capacity Correction Function of Generator Temperature Curve Name
reference Used when generator fluid type is hot water Curve which shows the change in normalized capacity to changes in generator temperature.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
generator_heat_input_correction_function_of_condenser_temperature_curve_name
Generator Heat Input Correction Function of Condenser Temperature Curve Name
reference Curve which shows the change in normalized heat input to changes in condenser temperature.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
generator_heat_input_correction_function_of_chilled_water_temperature_curve_name
Generator Heat Input Correction Function of Chilled Water Temperature Curve Name
reference Curve which shows the change in normalized heat input to changes in leaving chilled water temperature.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
generator_heat_source_type
Generator Heat Source Type
choice Steam The Generator side of the chiller can be connected to a hot water or steam plant where the generator inlet and outlet nodes are connected to a plant loop. If the generator is not connected to a plant loop, and the generator inlet/outlet nodes are not used, this field should be specified as steam or left blank. When a plant is not used, the model assumes steam as the heat source.
One of HotWater, Steam
design_generator_fluid_flow_rate
Design Generator Fluid Flow Rate
number or Autosize
m3/s
For variable flow this is the max flow and for constant flow this is the flow.
temperature_lower_limit_generator_inlet
Temperature Lower Limit Generator Inlet
number
C
0.0 Provides warnings when entering generator temperature is below minimum. Capacity is not adjusted when entering generator temperature is below minimum.
degree_of_subcooling_in_steam_generator
Degree of Subcooling in Steam Generator
number
C
1.0 This field is not used when the generator inlet/outlet nodes are not specified or the generator is connected to a hot water loop.
Range: ≥ 0, ≤ 20
degree_of_subcooling_in_steam_condensate_loop
Degree of Subcooling in Steam Condensate Loop
number
C
0.0 This field is not used when the generator inlet/outlet nodes are not specified or the generator is connected to a hot water loop.
Range: ≥ 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:CombustionTurbine

from idfpy.models import ChillerCombustionTurbine

This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Chiller performance curves are generated by fitting catalog data to third order polynomial equations. Three sets of coefficients are required.

Field Type Default Details
name
Name required
string
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled, WaterCooled
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_cop
Nominal COP required
number
W/W
Range: > 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name
string
condenser_outlet_node_name
Condenser Outlet Node Name
string
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
design_condenser_inlet_temperature
Design Condenser Inlet Temperature
number
C
temperature_rise_coefficient
Temperature Rise Coefficient required
number Range: > 0
design_chilled_water_outlet_temperature
Design Chilled Water Outlet Temperature
number
C
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
For variable volume this is the max flow & for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
This field is not used for Condenser Type = AirCooled or EvaporativelyCooled
coefficient_1_of_capacity_ratio_curve
Coefficient 1 of Capacity Ratio Curve
number
coefficient_2_of_capacity_ratio_curve
Coefficient 2 of Capacity Ratio Curve
number
coefficient_3_of_capacity_ratio_curve
Coefficient 3 of Capacity Ratio Curve
number
coefficient_1_of_power_ratio_curve
Coefficient 1 of Power Ratio Curve
number
coefficient_2_of_power_ratio_curve
Coefficient 2 of Power Ratio Curve
number
coefficient_3_of_power_ratio_curve
Coefficient 3 of Power Ratio Curve
number
coefficient_1_of_full_load_ratio_curve
Coefficient 1 of Full Load Ratio Curve
number
coefficient_2_of_full_load_ratio_curve
Coefficient 2 of Full Load Ratio Curve
number
coefficient_3_of_full_load_ratio_curve
Coefficient 3 of Full Load Ratio Curve
number
chilled_water_outlet_temperature_lower_limit
Chilled Water Outlet Temperature Lower Limit
number
C
Special Gas Turbine Chiller Parameters Below
coefficient_1_of_fuel_input_curve
Coefficient 1 of Fuel Input Curve
number
coefficient_2_of_fuel_input_curve
Coefficient 2 of Fuel Input Curve
number
coefficient_3_of_fuel_input_curve
Coefficient 3 of Fuel Input Curve
number
coefficient_1_of_temperature_based_fuel_input_curve
Coefficient 1 of Temperature Based Fuel Input Curve
number
coefficient_2_of_temperature_based_fuel_input_curve
Coefficient 2 of Temperature Based Fuel Input Curve
number
coefficient_3_of_temperature_based_fuel_input_curve
Coefficient 3 of Temperature Based Fuel Input Curve
number
coefficient_1_of_exhaust_flow_curve
Coefficient 1 of Exhaust Flow Curve
number
coefficient_2_of_exhaust_flow_curve
Coefficient 2 of Exhaust Flow Curve
number
coefficient_3_of_exhaust_flow_curve
Coefficient 3 of Exhaust Flow Curve
number
coefficient_1_of_exhaust_gas_temperature_curve
Coefficient 1 of Exhaust Gas Temperature Curve
number
coefficient_2_of_exhaust_gas_temperature_curve
Coefficient 2 of Exhaust Gas Temperature Curve
number
coefficient_3_of_exhaust_gas_temperature_curve
Coefficient 3 of Exhaust Gas Temperature Curve
number
coefficient_1_of_temperature_based_exhaust_gas_temperature_curve
Coefficient 1 of Temperature Based Exhaust Gas Temperature Curve
number
coefficient_2_of_temperature_based_exhaust_gas_temperature_curve
Coefficient 2 of Temperature Based Exhaust Gas Temperature Curve
number
coefficient_3_of_temperature_based_exhaust_gas_temperature_curve
Coefficient 3 of Temperature Based Exhaust Gas Temperature Curve
number
coefficient_1_of_recovery_lube_heat_curve
Coefficient 1 of Recovery Lube Heat Curve
number
coefficient_2_of_recovery_lube_heat_curve
Coefficient 2 of Recovery Lube Heat Curve
number
coefficient_3_of_recovery_lube_heat_curve
Coefficient 3 of Recovery Lube Heat Curve
number
coefficient_1_of_u_factor_times_area_curve
Coefficient 1 of U-Factor Times Area Curve
number
coefficient_2_of_u_factor_times_area_curve
Coefficient 2 of U-Factor Times Area Curve
number typical value .9
Range: ≤ 2
gas_turbine_engine_capacity
Gas Turbine Engine Capacity
number or Autosize
W
maximum_exhaust_flow_per_unit_of_power_output
Maximum Exhaust Flow per Unit of Power Output
number
(kg/s)/W
design_steam_saturation_temperature
Design Steam Saturation Temperature
number
C
fuel_higher_heating_value
Fuel Higher Heating Value
number
kJ/kg
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number or Autosize
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered.
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
fuel_type
Fuel Type
choice NaturalGas One of Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
heat_recovery_maximum_temperature
Heat Recovery Maximum Temperature
number
C
80.0 Range: ≥ 0, ≤ 100
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, The heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the chiller is not operating.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_heat_recovery_relative_capacity_fraction
Condenser Heat Recovery Relative Capacity Fraction
number This optional field is the fraction of total rejected heat that can be recovered at full load. Also used to autosize Design Heat Recovery Water Flow Rate as a fraction of Design Condenser Water Flow Rate.
Range: ≥ 0, ≤ 1
turbine_engine_efficiency
Turbine Engine Efficiency
number 0.35 This optional field is the nominal turbine engine efficiency and is used when Gas Turbine Engine Capacity is set to Autosize
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:ConstantCOP

from idfpy.models import ChillerConstantCOP

This constant COP chiller model provides a means of quickly specifying a Chiller where performance data is not available.

Field Type Default Details
name
Name required
string
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_cop
Nominal COP required
number
W/W
Range: > 0
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
For variable volume this is the maximum flow and for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
This field is not used for Condenser Type = AirCooled or EvaporativelyCooled
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name
string
condenser_outlet_node_name
Condenser Outlet Node Name
string
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled, WaterCooled
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the chiller is not operating.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
thermosiphon_capacity_fraction_curve_name
Thermosiphon Capacity Fraction Curve Name
reference quadratic curve = a + b * (Tevap, out - Tcond, in) is typical, other univariate curves may be used Tevap, out = evaporator outlet temperature Tcond, in = condenser inlet temperature If this field is blank the thermosiphon model is disabled.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermosiphon_minimum_temperature_difference
Thermosiphon Minimum Temperature Difference
number 0.0 Thermosiphon model is disabled below this minimum limit and when the load is greater than calculated using the previous field.
Range: ≥ 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:Electric

from idfpy.models import ChillerElectric

This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Chiller performance curves are generated by fitting catalog data to third order polynomial equations. Three sets of coefficients are required.

Field Type Default Details
name
Name required
string
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled, WaterCooled
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_cop
Nominal COP required
number
W/W
Range: > 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name
string
condenser_outlet_node_name
Condenser Outlet Node Name
string
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
design_condenser_inlet_temperature
Design Condenser Inlet Temperature
number
C
temperature_rise_coefficient
Temperature Rise Coefficient required
number Range: > 0
design_chilled_water_outlet_temperature
Design Chilled Water Outlet Temperature
number
C
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
For variable volume this is the maximum flow & for constant flow this is the flow.
design_condenser_fluid_flow_rate
Design Condenser Fluid Flow Rate
number or Autosize
m3/s
For Condenser Type = AirCooled or EvaporativelyCooled, this flow rate is used to calculate the condenser outlet node conditions. If this field is blank or Autosize, the flow rate is estimated using 850 cfm/ton of nominal capacity.
coefficient_1_of_capacity_ratio_curve
Coefficient 1 of Capacity Ratio Curve
number
coefficient_2_of_capacity_ratio_curve
Coefficient 2 of Capacity Ratio Curve
number
coefficient_3_of_capacity_ratio_curve
Coefficient 3 of Capacity Ratio Curve
number
coefficient_1_of_power_ratio_curve
Coefficient 1 of Power Ratio Curve
number
coefficient_2_of_power_ratio_curve
Coefficient 2 of Power Ratio Curve
number
coefficient_3_of_power_ratio_curve
Coefficient 3 of Power Ratio Curve
number
coefficient_1_of_full_load_ratio_curve
Coefficient 1 of Full Load Ratio Curve
number
coefficient_2_of_full_load_ratio_curve
Coefficient 2 of Full Load Ratio Curve
number
coefficient_3_of_full_load_ratio_curve
Coefficient 3 of Full Load Ratio Curve
number
chilled_water_outlet_temperature_lower_limit
Chilled Water Outlet Temperature Lower Limit
number
C
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number or Autosize
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered. Heat recovery is only available with Condenser Type = WaterCooled.
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the chiller is not operating.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_heat_recovery_relative_capacity_fraction
Condenser Heat Recovery Relative Capacity Fraction
number This optional field is the fraction of total rejected heat that can be recovered at full load
Range: ≥ 0, ≤ 1
heat_recovery_inlet_high_temperature_limit_schedule_name
Heat Recovery Inlet High Temperature Limit Schedule Name
reference This optional schedule of temperatures will turn off heat recovery if inlet exceeds the value
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_recovery_leaving_temperature_setpoint_node_name
Heat Recovery Leaving Temperature Setpoint Node Name
string This optional field provides control over the heat recovery Using this triggers a model more suited to series bundle and chillers with higher temperature heat recovery If this field is not used, the bundles are modeled as being in parallel
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
thermosiphon_capacity_fraction_curve_name
Thermosiphon Capacity Fraction Curve Name
reference quadratic curve = a + b * (Tevap, out - Tcond, in) is typical, other univariate curves may be used Tevap, out = evaporator outlet temperature Tcond, in = condenser inlet temperature If this field is blank the thermosiphon model is disabled.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermosiphon_minimum_temperature_difference
Thermosiphon Minimum Temperature Difference
number 0.0 Thermosiphon model is disabled below this minimum limit and when the load is greater than calculated using the previous field.
Range: ≥ 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:Electric:ASHRAE205

from idfpy.models import ChillerElectricASHRAE205

This chiller model utilizes ASHRAE Standard 205 compliant representations for chillers (Representation Specification RS0001).

Field Type Default Details
name
Name required
string
representation_file_name
Representation File Name required
string The name of the ASHRAE205 RS0001 (chiller) representation file
performance_interpolation_method
Performance Interpolation Method
choice Linear One of Cubic, Linear
rated_capacity
Rated Capacity
number or Autosize
W
Autosize Not yet implemented / reserved for future use. Full load capacity at AHRI 550/590 test conditions. Used to scale representation data.
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized flow rates.
Range: > 0
ambient_temperature_indicator
Ambient Temperature Indicator required
choice Used to determine standby losses
One of Outdoors, Schedule, Zone
ambient_temperature_schedule_name
Ambient Temperature Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
ambient_temperature_zone_name
Ambient Temperature Zone Name
reference Any energy imbalance on the chiller results in heat added to this zone.
Names a Zone
ambient_temperature_outdoor_air_node_name
Ambient Temperature Outdoor Air Node Name
string required for Ambient Temperature Indicator=Outdoors
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
chilled_water_maximum_requested_flow_rate
Chilled Water Maximum Requested Flow Rate
number or Autosize
m3/s
Autosize
condenser_inlet_node_name
Condenser Inlet Node Name
string
condenser_outlet_node_name
Condenser Outlet Node Name
string
condenser_maximum_requested_flow_rate
Condenser Maximum Requested Flow Rate
number or Autosize
m3/s
Autosize
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
oil_cooler_inlet_node_name
Oil Cooler Inlet Node Name
string Use if the oil cooler uses an external cooling loop, otherwise the oil cooler will add heat to the ambient conditions (i.e., it is air cooled).
oil_cooler_outlet_node_name
Oil Cooler Outlet Node Name
string
oil_cooler_design_flow_rate
Oil Cooler Design Flow Rate
number
m3/s
Range: > 0
auxiliary_inlet_node_name
Auxiliary Inlet Node Name
string Use if the auxiliary components of the chiller use an external cooling loop, otherwise the auxiliary components will add heat to the ambient conditions (i.e., they are air cooled).
auxiliary_outlet_node_name
Auxiliary Outlet Node Name
string
auxiliary_cooling_design_flow_rate
Auxiliary Cooling Design Flow Rate
number
m3/s
Range: > 0
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string Not yet implemented / reserved for future use. Heat recovery is not yet within scope of ASHRAE Standard 205.
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string Not yet implemented / reserved for future use. Heat recovery is not yet within scope of ASHRAE Standard 205.
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:Electric:EIR

from idfpy.models import ChillerElectricEIR

This chiller model is the empirical model from the DOE-2 building Energy simulation program. Chiller performance at off-reference conditions is modeled using three polynomial equations. Three curves objects are required.

Field Type Default Details
name
Name required
string
reference_capacity
Reference Capacity required
number or Autosize
W
reference_cop
Reference COP required
number
W/W
Efficiency of the chiller compressor (cooling output/compressor energy input). Condenser fan power should not be included here.
Range: > 0
reference_leaving_chilled_water_temperature
Reference Leaving Chilled Water Temperature
number
C
6.67
reference_entering_condenser_fluid_temperature
Reference Entering Condenser Fluid Temperature
number
C
29.4
reference_chilled_water_flow_rate
Reference Chilled Water Flow Rate
number or Autosize
m3/s
reference_condenser_fluid_flow_rate
Reference Condenser Fluid Flow Rate
number or Autosize
m3/s
This field is only used for Condenser Type = AirCooled or EvaporativelyCooled when Heat Recovery is specified
cooling_capacity_function_of_temperature_curve_name
Cooling Capacity Function of Temperature Curve Name required
reference Cooling capacity as a function of CW supply temp and entering condenser temp curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Electric Input to Cooling Output Ratio Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) as a function of temperature EIR = 1/COP curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) as a function of Part Load Ratio (PLR) EIR = 1/COP quadratic curve = a + b*PLR + c*PLR**2 is typical, other univariate curves may be used PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 Part load ratio below which the chiller starts cycling on/off to meet the load. Must be less than or equal to Maximum Part Load Ratio.
Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Maximum allowable part load ratio. Must be greater than or equal to Minimum Part Load Ratio.
Range: > 0
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 Optimum part load ratio where the chiller is most efficient. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: > 0
minimum_unloading_ratio
Minimum Unloading Ratio
number 0.2 Part load ratio where the chiller can no longer unload and false loading begins. Minimum unloading ratio must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: ≥ 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name
string Not required if air-cooled or evaporatively-cooled
condenser_outlet_node_name
Condenser Outlet Node Name
string Not required if air-cooled or evaporatively-cooled
condenser_type
Condenser Type
choice WaterCooled One of AirCooled, EvaporativelyCooled, WaterCooled
condenser_fan_power_ratio
Condenser Fan Power Ratio
number
W/W
0.0 Use for air-cooled or evaporatively-cooled condensers. Ratio of condenser fan power to reference chiller capacity
Range: ≥ 0
fraction_of_compressor_electric_consumption_rejected_by_condenser
Fraction of Compressor Electric Consumption Rejected by Condenser
number 1.0 Fraction of compressor electrical energy that must be rejected by the condenser. Enter a value of 1.0 when modeling hermetic chillers. For open chillers, enter the compressor motor efficiency. This value should be greater than 0.6 for practical applications.
Range: > 0, ≤ 1
leaving_chilled_water_lower_temperature_limit
Leaving Chilled Water Lower Temperature Limit
number
C
2.0
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number or Autosize
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered. Heat recovery is only available with Condenser Type = WaterCooled.
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the chiller is not operating.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_heat_recovery_relative_capacity_fraction
Condenser Heat Recovery Relative Capacity Fraction
number This optional field is the fraction of total rejected heat that can be recovered at full load
Range: ≥ 0, ≤ 1
heat_recovery_inlet_high_temperature_limit_schedule_name
Heat Recovery Inlet High Temperature Limit Schedule Name
reference This optional schedule of temperatures will turn off heat recovery if inlet exceeds the value
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_recovery_leaving_temperature_setpoint_node_name
Heat Recovery Leaving Temperature Setpoint Node Name
string This optional field provides control over the heat recovery Using this triggers a model more suited to series bundle and chillers with higher temperature heat recovery If this field is not used, the bundles are modeled as being in parallel
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
condenser_flow_control
Condenser Flow Control
choice ConstantFlow Select the chiller condenser flow request mode. With "ConstantFlow" a chiller will always request its maximum condenser flow rate. With "ModulatedChillerPLR" the condenser flow request corresponds to the chiller part load ratio multiplied by the chiller maximum condenser flow rate. With "ModulatedLoopPLR" the chiller will request a flow rate that is function of the chilled water loop's part load ratio, see the "Condenser Loop Flow Rate Fraction Function of Loop Part Load Ratio Curve Name" input. With "ModulatedDeltaTemperature" the chiller will request the flow rate required to meet the condenser loop load based on the condenser leaving fluid temperature and a reference temperature, see the "Temperature Difference Across Condenser" and "Temperature Difference Across Condenser Schedule Name" input. Use "ConstantFlow" when modeling a constant flow condenser plant loop, choose one of the other inputs when modeling a variable flow condenser plant loop.
One of ConstantFlow, ModulatedChillerPLR, ModulatedDeltaTemperature, ModulatedLoopPLR
condenser_loop_flow_rate_fraction_function_of_loop_part_load_ratio_curve_name
Condenser Loop Flow Rate Fraction Function of Loop Part Load Ratio Curve Name
reference Condenser loop flow rate fraction as a function of loop part load ratio CWFR = C * PLR + D Where: CWFR is the condenser water flow fraction (actual/design) C and D are coefficients, see "Optimizing Design & Control Of Chilled Water Plants, Part 5", S. Taylor, ASHRAE Journal June 2012 PLR is the chilled water plant loop part load ratio (actual/design)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
temperature_difference_across_condenser_schedule_name
Temperature Difference Across Condenser Schedule Name
reference A schedule that defines the temperature difference across the condenser. This input is used to calculate the condenser flow. This input is only used when "Condenser Flow Control" is set to "ModulatedDeltaTemperature".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_minimum_flow_fraction
Condenser Minimum Flow Fraction
number 0.2 This input corresponds to the minimum flow fraction to be simulated. The minimum condenser flow corresponds to this fraction multiplied by the maximum condenser flow rate. This input is only used when the "Condenser Flow Control" input is set to "ModulatedChillerPLR", "ModulatedLoopPLR" or "ModulatedDeltaTemperature".
Range: ≥ 0, ≤ 1
thermosiphon_capacity_fraction_curve_name
Thermosiphon Capacity Fraction Curve Name
reference quadratic curve = a + b * (Tevap, out - Tcond, in) is typical, other univariate curves may be used Tevap, out = evaporator outlet temperature Tcond, in = condenser inlet temperature If this field is blank the thermosiphon model is disabled.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermosiphon_minimum_temperature_difference
Thermosiphon Minimum Temperature Difference
number 0.0 Thermosiphon model is disabled below this minimum limit and when the load is greater than calculated using the previous field.
Range: ≥ 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:Electric:ReformulatedEIR

from idfpy.models import ChillerElectricReformulatedEIR

This chiller model is an empirical model, a reformulated version of Chiller:Electric:EIR where the performance is a function of condenser leaving fluid Temperature instead of condenser entering fluid Temperature. Chiller performance at off-reference conditions is modeled using three polynomial equations. Three curve objects are required.

Field Type Default Details
name
Name required
string
reference_capacity
Reference Capacity required
number or Autosize
W
reference_cop
Reference COP required
number
W/W
Efficiency of the chiller compressor (cooling output/compressor energy input). Condenser fan power should not be included here.
Range: > 0
reference_leaving_chilled_water_temperature
Reference Leaving Chilled Water Temperature
number
C
6.67
reference_leaving_condenser_water_temperature
Reference Leaving Condenser Water Temperature
number
C
35.0
reference_chilled_water_flow_rate
Reference Chilled Water Flow Rate
number or Autosize
m3/s
reference_condenser_water_flow_rate
Reference Condenser Water Flow Rate
number or Autosize
m3/s
cooling_capacity_function_of_temperature_curve_name
Cooling Capacity Function of Temperature Curve Name required
reference Cooling capacity as a function of supply (leaving) chilled water temperature and leaving condenser fluid temperature curve = a + b*CWS + c*CWS**2 + d*LCT + e*LCT**2 + f*CWS*LCT CWS = supply (leaving) chilled water temperature(C) LCT = leaving condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Electric Input to Cooling Output Ratio Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) as a function of supply (leaving) chilled water temperature and leaving condenser fluid temperature. EIR = 1/COP. curve = a + b*CWS + c*CWS**2 + d*LCT + e*LCT**2 + f*CWS*LCT CWS = supply (leaving) chilled water temperature(C) LCT = leaving condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_type
Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Type
choice LeavingCondenserWaterTemperature Two curve types are available: Type LeavingCondenserWaterTemperature: based on the leaving condenser water temperature. Type Lift: based on the normalized lift, which is the temperature difference between the leaving condenser water temperature and the leaving evaporator water temperature.
One of LeavingCondenserWaterTemperature, Lift
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) as a function of Part Load Ratio (PLR) EIR = 1/COP The form of this curve is based on the input for Electric Input to Cooling Output RatioFunction of Part Load Ratio Curve Type Type=LeavingCondenserWaterTemperature: Calculated based on LCT and PLR Curve object type should be Curve:Bicubic or Table:Lookup Bicubic curve = a + b*LCT + c*LCT**2 + d*PLR + e*PLR**2 + f*LCT*PLR + g*0 + h*PLR**3 + i*0 + j*0 PLR = part load ratio (cooling load/steady state capacity) LCT = leaving condenser fluid temperature(C) Type=Lift: Calculated based on dT*, Tdev* and PLR Curve object type should be Curve:ChillerPartLoadWithLiftCurves or Table:Lookup ChillerPartLoadWithLiftCurves curve = a + b*(dT*) + c*(dT*)**2 + d*PLR + e*PLR**2 + f*(dT*)*PLR + g*(dT*)**3 + h*PLR**3 + i*(dT*)**2*PLR + j*(dT*)*PLR**2 + k*(dT*)**2*PLR**2 + l*(Tdev*)*PLR**3 x = dT* = normalized fractional Lift = dT / dTref y = PLR = part load ratio (cooling load/steady state capacity) z = Tdev* = normalized Tdev = Tdev / dTref Where: dT = Lift = Leaving Condenser Water Temperature - Leaving Chilled Water Temperature dTref = dT at the reference condition Tdev = Leaving Chilled Water Temperature - Reference Chilled Water Temperature
Names a Curve:Bicubic, Curve:Biquadratic, Curve:ChillerPartLoadWithLift, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Curve:Triquadratic, Table:Lookup
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 Part load ratio below which the chiller starts cycling on/off to meet the load. Must be less than or equal to Maximum Part Load Ratio.
Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Maximum allowable part load ratio. Must be greater than or equal to Minimum Part Load Ratio.
Range: > 0
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 Optimum part load ratio where the chiller is most efficient. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: > 0
minimum_unloading_ratio
Minimum Unloading Ratio
number 0.2 Part load ratio where the chiller can no longer unload and false loading begins. Minimum unloading ratio must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio.
Range: ≥ 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name required
string
condenser_outlet_node_name
Condenser Outlet Node Name required
string
fraction_of_compressor_electric_consumption_rejected_by_condenser
Fraction of Compressor Electric Consumption Rejected by Condenser
number 1.0 Fraction of compressor electrical energy that must be rejected by the condenser. Enter a value of 1.0 when modeling hermetic chillers. For open chillers, enter the compressor motor efficiency. This value should be greater than 0.6 for practical applications.
Range: > 0, ≤ 1
leaving_chilled_water_lower_temperature_limit
Leaving Chilled Water Lower Temperature Limit
number
C
2.0
chiller_flow_mode_type
Chiller Flow Mode Type
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number or Autosize
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered.
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
condenser_heat_recovery_relative_capacity_fraction
Condenser Heat Recovery Relative Capacity Fraction
number This optional field is the fraction of total rejected heat that can be recovered at full load
Range: ≥ 0, ≤ 1
heat_recovery_inlet_high_temperature_limit_schedule_name
Heat Recovery Inlet High Temperature Limit Schedule Name
reference This optional schedule of temperatures will turn off heat recovery if inlet exceeds the value
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
heat_recovery_leaving_temperature_setpoint_node_name
Heat Recovery Leaving Temperature Setpoint Node Name
string This optional field provides control over the heat recovery Using this triggers a model more suited to series bundle and chillers with higher temperature heat recovery If this field is not used, the bundles are modeled as being in parallel
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
condenser_flow_control
Condenser Flow Control
choice ConstantFlow Select the chiller condenser flow request mode. With "ConstantFlow" a chiller will always request its maximum condenser flow rate. With "ModulatedChillerPLR" the condenser flow request corresponds to the chiller part load ratio multiplied by the chiller maximum condenser flow rate. With "ModulatedLoopPLR" the chiller will request a flow rate that is function of the chilled water loop's part load ratio, see the "Condenser Loop Flow Rate Fraction Function of Loop Part Load Ratio Curve Name" input. With "ModulatedDeltaTemperature" the chiller will request the flow rate required to meet the condenser loop load based on the condenser leaving fluid temperature and a reference temperature, see the "Temperature Difference Across Condenser" and "Temperature Difference Across Condenser Schedule Name" input. Use "ConstantFlow" when modeling a constant flow condenser plant loop, choose one of the other inputs when modeling a variable flow condenser plant loop.
One of ConstantFlow, ModulatedChillerPLR, ModulatedDeltaTemperature, ModulatedLoopPLR
condenser_loop_flow_rate_fraction_function_of_loop_part_load_ratio_curve_name
Condenser Loop Flow Rate Fraction Function of Loop Part Load Ratio Curve Name
reference Condenser loop flow rate fraction as a function of loop part load ratio CWFR = C * PLR + D Where: CWFR is the condenser water flow fraction (actual/design) C and D are coefficients, see "Optimizing Design & Control Of Chilled Water Plants, Part 5", S. Taylor, ASHRAE Journal June 2012 PLR is the chilled water plant loop part load ratio (actual/design)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
temperature_difference_across_condenser_schedule_name
Temperature Difference Across Condenser Schedule Name
reference A schedule that defines the temperature difference across the condenser. This input is used to calculate the condenser flow. This input is only used when "Condenser Flow Control" is set to "ModulatedDeltaTemperature".
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_minimum_flow_fraction
Condenser Minimum Flow Fraction
number 0.2 This input corresponds to the minimum flow fraction to be simulated. The minimum condenser flow corresponds to this fraction multiplied by the maximum condenser flow rate. This input is only used when the "Condenser Flow Control" input is set to "ModulatedChillerPLR", "ModulatedLoopPLR" or "ModulatedDeltaTemperature".
Range: ≥ 0, ≤ 1
thermosiphon_capacity_fraction_curve_name
Thermosiphon Capacity Fraction Curve Name
reference quadratic curve = a + b * (Tevap, out - Tcond, in) is typical, other univariate curves may be used Tevap, out = evaporator outlet temperature Tcond, in = condenser inlet temperature If this field is blank the thermosiphon model is disabled.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermosiphon_minimum_temperature_difference
Thermosiphon Minimum Temperature Difference
number 0.0 Thermosiphon model is disabled below this minimum limit and when the load is greater than calculated using the previous field.
Range: ≥ 0
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

Chiller:EngineDriven

from idfpy.models import ChillerEngineDriven

This chiller model is the empirical model from the Building Loads and System Thermodynamics (BLAST) program. Chiller performance curves are generated by fitting catalog data to third order polynomial equations. Three sets of coefficients are required.

Field Type Default Details
name
Name required
string
condenser_type
Condenser Type
choice AirCooled One of AirCooled, EvaporativelyCooled, WaterCooled
nominal_capacity
Nominal Capacity required
number or Autosize
W
nominal_cop
Nominal COP required
number
W/W
Nominal Refrigeration Cycle COP
Range: > 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name
string
condenser_outlet_node_name
Condenser Outlet Node Name
string
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
design_condenser_inlet_temperature
Design Condenser Inlet Temperature
number
C
temperature_rise_coefficient
Temperature Rise Coefficient required
number Range: > 0
design_chilled_water_outlet_temperature
Design Chilled Water Outlet Temperature
number
C
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
For variable volume this is the maximum flow and for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
This field is not used for Condenser Type = AirCooled or EvaporativelyCooled
coefficient_1_of_capacity_ratio_curve
Coefficient 1 of Capacity Ratio Curve
number
coefficient_2_of_capacity_ratio_curve
Coefficient 2 of Capacity Ratio Curve
number
coefficient_3_of_capacity_ratio_curve
Coefficient 3 of Capacity Ratio Curve
number
coefficient_1_of_power_ratio_curve
Coefficient 1 of Power Ratio Curve
number
coefficient_2_of_power_ratio_curve
Coefficient 2 of Power Ratio Curve
number
coefficient_3_of_power_ratio_curve
Coefficient 3 of Power Ratio Curve
number
coefficient_1_of_full_load_ratio_curve
Coefficient 1 of Full Load Ratio Curve
number
coefficient_2_of_full_load_ratio_curve
Coefficient 2 of Full Load Ratio Curve
number
coefficient_3_of_full_load_ratio_curve
Coefficient 3 of Full Load Ratio Curve
number
chilled_water_outlet_temperature_lower_limit
Chilled Water Outlet Temperature Lower Limit
number
C
Special EngineDriven Chiller Parameters Below
fuel_use_curve_name
Fuel Use Curve Name
reference Curve is a function of Part Load Ratio (PLR) curve = a + b*PLR + c*PLR**2 PLR = Ratio of evaporator heat transfer rate to nominal capacity
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
jacket_heat_recovery_curve_name
Jacket Heat Recovery Curve Name
reference Curve is a function of Part Load Ratio (PLR) curve = a + b*PLR + c*PLR**2 PLR = Ratio of evaporator heat transfer rate to nominal capacity
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
lube_heat_recovery_curve_name
Lube Heat Recovery Curve Name
reference Curve is a function of Part Load Ratio (PLR) curve = a + b*PLR + c*PLR**2 PLR = Ratio of evaporator heat transfer rate to nominal capacity
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
total_exhaust_energy_curve_name
Total Exhaust Energy Curve Name
reference Curve is a function of Part Load Ratio (PLR) curve = a + b*PLR + c*PLR**2 PLR = Ratio of evaporator heat transfer rate to nominal capacity
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
exhaust_temperature_curve_name
Exhaust Temperature Curve Name
reference Curve is a function of Part Load Ratio (PLR) curve = a + b*PLR + c*PLR**2 PLR = Ratio of evaporator heat transfer rate to nominal capacity
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
coefficient_1_of_u_factor_times_area_curve
Coefficient 1 of U-Factor Times Area Curve
number curve = C1 * (nominal capacity)**C2
coefficient_2_of_u_factor_times_area_curve
Coefficient 2 of U-Factor Times Area Curve
number curve = C1 * (nominal capacity)**C2 typical value .9
Range: ≤ 2
maximum_exhaust_flow_per_unit_of_power_output
Maximum Exhaust Flow per Unit of Power Output
number
(kg/s)/W
Range: ≥ 0
design_minimum_exhaust_temperature
Design Minimum Exhaust Temperature
number
C
fuel_type
Fuel Type required
choice One of Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
fuel_higher_heating_value
Fuel Higher Heating Value
number
kJ/kg
design_heat_recovery_water_flow_rate
Design Heat Recovery Water Flow Rate
number or Autosize
m3/s
0.0 If non-zero, then the heat recovery inlet and outlet node names must be entered.
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string
chiller_flow_mode
Chiller Flow Mode
choice NotModulated Select operating mode for fluid flow through the chiller. "NotModulated" is for either variable or constant pumping with flow controlled by the external plant system. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "LeavingSetpointModulated" is for variable pumping with flow controlled by chiller to vary flow to target a leaving temperature setpoint.
One of ConstantFlow, LeavingSetpointModulated, NotModulated
maximum_temperature_for_heat_recovery_at_heat_recovery_outlet_node
Maximum Temperature for Heat Recovery at Heat Recovery Outlet Node
number
C
60.0 Range: ≥ 0, ≤ 100
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
basin_heater_capacity
Basin Heater Capacity
number
W/K
0.0 This field is only used for Condenser Type = EvaporativelyCooled and for periods when the basin heater is available (field Basin Heater Operating Schedule Name). For this situation, the heater maintains the basin water temperature at the basin heater setpoint temperature when the outdoor air temperature falls below the setpoint temperature. The basin heater only operates when the chiller is not operating.
Range: ≥ 0
basin_heater_setpoint_temperature
Basin Heater Setpoint Temperature
number
C
2.0 This field is only used for Condenser Type = EvaporativelyCooled. Enter the outdoor dry-bulb temperature when the basin heater turns on.
Range: ≥ 2
basin_heater_operating_schedule_name
Basin Heater Operating Schedule Name
reference This field is only used for Condenser Type = EvaporativelyCooled. Schedule values greater than 0 allow the basin heater to operate whenever the outdoor air dry-bulb temperature is below the basin heater setpoint temperature. If a schedule name is not entered, the basin heater is allowed to operate throughout the entire simulation.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
condenser_heat_recovery_relative_capacity_fraction
Condenser Heat Recovery Relative Capacity Fraction
number This optional field is the fraction of total rejected heat that can be recovered at full load. Also used to autosize Design Heat Recovery Water Flow Rate as a fraction of Design Condenser Water Flow Rate.
Range: ≥ 0, ≤ 1
Referenced by 8 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, FaultModel:Fouling:Chiller, FaultModel:Fouling:EvaporativeCooler, FaultModel:TemperatureSensorOffset:ChillerSupplyWater, HVACTemplate:Plant:Chiller:ObjectReference, PlantEquipmentList, PlantEquipmentOperation:ThermalEnergyStorage

ChillerHeater:Absorption:DirectFired

from idfpy.models import ChillerHeaterAbsorptionDirectFired

Direct fired gas absorption chiller-heater using performance curves similar to DOE-2

Field Type Default Details
name
Name required
string
nominal_cooling_capacity
Nominal Cooling Capacity
number or Autosize
W
Autosize
heating_to_cooling_capacity_ratio
Heating to Cooling Capacity Ratio
number 0.8 A positive fraction that represents the ratio of the heating capacity divided by the cooling capacity at rated conditions.
Range: ≥ 0
fuel_input_to_cooling_output_ratio
Fuel Input to Cooling Output Ratio
number 0.97 The positive fraction that represents the ratio of the instantaneous fuel used divided by the cooling capacity at rated conditions.
Range: > 0
fuel_input_to_heating_output_ratio
Fuel Input to Heating Output Ratio
number 1.25 The positive fraction that represents the ratio of the instantaneous fuel used divided by the nominal heating capacity.
Range: ≥ 0
electric_input_to_cooling_output_ratio
Electric Input to Cooling Output Ratio
number 0.01 The positive fraction that represents the ratio of the instantaneous electricity used divided by the cooling capacity at rated conditions. If the chiller is both heating and cooling only the cooling electricity is used.
Range: ≥ 0
electric_input_to_heating_output_ratio
Electric Input to Heating Output Ratio
number 0.0 The positive fraction that represents the ratio of the instantaneous electricity used divided by the nominal heating capacity. If the chiller is both heating and cooling only the cooling electricity is used.
Range: ≥ 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name required
string
condenser_outlet_node_name
Condenser Outlet Node Name
string Not required if air-cooled
hot_water_inlet_node_name
Hot Water Inlet Node Name required
string
hot_water_outlet_node_name
Hot Water Outlet Node Name required
string
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 The positive fraction that represents the minimum cooling output possible when operated continually at rated temperature conditions divided by the nominal cooling capacity at those same conditions. If the load on the chiller is below this fraction the chiller will cycle.
Range: > 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 The positive fraction that represents the maximum cooling output possible at rated temperature conditions divided by the nominal cooling capacity at those same conditions. If greater than 1.0, the chiller is typically thought of as capable of being overloaded.
Range: ≥ 0.5
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 The positive fraction that represents the optimal cooling output at rated temperature conditions divided by the nominal cooling capacity at those same conditions. It represents the most desirable operating point for the chiller.
Range: > 0
design_entering_condenser_water_temperature
Design Entering Condenser Water Temperature
number
C
29.0 The temperature of the water entering the condenser of the chiller when operating at design conditions. This is usually based on the temperature delivered by the cooling tower in a water cooled application.
design_leaving_chilled_water_temperature
Design Leaving Chilled Water Temperature
number
C
7.0 The temperature of the water leaving the evaporator of the chiller when operating at design conditions also called the chilled water supply temperature or leaving chilled water temperature.
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
Autosize For variable volume this is the max flow & for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
Autosize The water flow rate at design conditions through the condenser. This field is not used for Condenser Type = AirCooled
design_hot_water_flow_rate
Design Hot Water Flow Rate
number or Autosize
m3/s
Autosize The water flow rate at design conditions through the heater side.
cooling_capacity_function_of_temperature_curve_name
Cooling Capacity Function of Temperature Curve Name
reference The CoolCapFT curve represents the fraction of the cooling capacity of the chiller as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_input_to_cooling_output_ratio_function_of_temperature_curve_name
Fuel Input to Cooling Output Ratio Function of Temperature Curve Name
reference The curve represents the fraction of the fuel input to the chiller at full load as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Fuel Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
reference The curve represents the fraction of the fuel input to the chiller as the load on the chiller varies but the operating temperatures remain at the design values. The curve is normalized so that at full load the value of the curve should be 1.0. The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Electric Input to Cooling Output Ratio Function of Temperature Curve Name
reference The curve represents the fraction of the electricity to the chiller at full load as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
reference The curve represents the fraction of the electricity to the chiller as the load on the chiller varies but the operating temperatures remain at the design values. The curve is normalized so that at full load the value of the curve should be 1.0. The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_capacity_function_of_cooling_capacity_curve_name
Heating Capacity Function of Cooling Capacity Curve Name
reference The curve represents how the heating capacity of the chiller varies with cooling capacity when the chiller is simultaneous heating and cooling. The curve is normalized so an input of 1.0 represents the nominal cooling capacity and an output of 1.0 represents the full heating capacity (see the Heating to cooling capacity ratio input) The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
fuel_input_to_heat_output_ratio_during_heating_only_operation_curve_name
Fuel Input to Heat Output Ratio During Heating Only Operation Curve Name
reference When the chiller is operating as only a heater, this curve is used to represent the fraction of fuel used as the heating load varies. It is normalized so that a value of 1.0 is the full heating capacity. The curve is usually linear or quadratic and will probably be similar to a boiler curve for most chillers.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
temperature_curve_input_variable
Temperature Curve Input Variable
choice EnteringCondenser Sets the second independent variable in the three temperature dependent performance curves to either the leaving or entering condenser water temperature. Manufacturers express the performance of their chillers using either the leaving condenser water temperature (to the tower) or the entering condenser water temperature (from the tower).
One of EnteringCondenser, LeavingCondenser
condenser_type
Condenser Type
choice WaterCooled The condenser can either be air cooled or connected to a cooling tower.
One of AirCooled, WaterCooled
chilled_water_temperature_lower_limit
Chilled Water Temperature Lower Limit
number
C
2.0 The chilled water supply temperature below which the chiller will shut off.
fuel_higher_heating_value
Fuel Higher Heating Value
number
kJ/kg
0.0 Not currently used.
fuel_type
Fuel Type
choice NaturalGas One of Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

ChillerHeater:Absorption:DoubleEffect

from idfpy.models import ChillerHeaterAbsorptionDoubleEffect

Exhaust fired absorption chiller-heater using performance curves similar to DOE-2

Field Type Default Details
name
Name required
string
nominal_cooling_capacity
Nominal Cooling Capacity
number or Autosize
W
Autosize
heating_to_cooling_capacity_ratio
Heating to Cooling Capacity Ratio
number 0.8 A positive fraction that represents the ratio of the heating capacity divided by the cooling capacity at rated conditions.
Range: ≥ 0
thermal_energy_input_to_cooling_output_ratio
Thermal Energy Input to Cooling Output Ratio
number 0.97 The positive fraction that represents the ratio of the instantaneous fuel used divided by the cooling capacity at rated conditions.
Range: > 0
thermal_energy_input_to_heating_output_ratio
Thermal Energy Input to Heating Output Ratio
number 1.25 The positive fraction that represents the ratio of the instantaneous fuel used divided by the nominal heating capacity.
Range: ≥ 0
electric_input_to_cooling_output_ratio
Electric Input to Cooling Output Ratio
number 0.01 The positive fraction that represents the ratio of the instantaneous electricity used divided by the cooling capacity at rated conditions. If the chiller is both heating and cooling only the cooling electricity is used.
Range: ≥ 0
electric_input_to_heating_output_ratio
Electric Input to Heating Output Ratio
number 0.0 The positive fraction that represents the ratio of the instantaneous electricity used divided by the nominal heating capacity. If the chiller is both heating and cooling only the cooling electricity is used.
Range: ≥ 0
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
condenser_inlet_node_name
Condenser Inlet Node Name required
string
condenser_outlet_node_name
Condenser Outlet Node Name
string Not required if air-cooled
hot_water_inlet_node_name
Hot Water Inlet Node Name required
string
hot_water_outlet_node_name
Hot Water Outlet Node Name required
string
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 The positive fraction that represents the minimum cooling output possible when operated continually at rated temperature conditions divided by the nominal cooling capacity at those same conditions. If the load on the chiller is below this fraction the chiller will cycle.
Range: > 0
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 The positive fraction that represents the maximum cooling output possible at rated temperature conditions divided by the nominal cooling capacity at those same conditions. If greater than 1.0, the chiller is typically thought of as capable of being overloaded.
Range: ≥ 0.5
optimum_part_load_ratio
Optimum Part Load Ratio
number 1.0 The positive fraction that represents the optimal cooling output at rated temperature conditions divided by the nominal cooling capacity at those same conditions. It represents the most desirable operating point for the chiller.
Range: > 0
design_entering_condenser_water_temperature
Design Entering Condenser Water Temperature
number
C
29.0 The temperature of the water entering the condenser of the chiller when operating at design conditions. This is usually based on the temperature delivered by the cooling tower in a water cooled application.
design_leaving_chilled_water_temperature
Design Leaving Chilled Water Temperature
number
C
7.0 The temperature of the water leaving the evaporator of the chiller when operating at design conditions also called the chilled water supply temperature or leaving chilled water temperature.
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
Autosize For variable volume this is the max flow & for constant flow this is the flow.
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
Autosize The water flow rate at design conditions through the condenser. This field is not used for Condenser Type = AirCooled
design_hot_water_flow_rate
Design Hot Water Flow Rate
number or Autosize
m3/s
Autosize The water flow rate at design conditions through the heater side.
cooling_capacity_function_of_temperature_curve_name
Cooling Capacity Function of Temperature Curve Name
reference The CoolCapFT curve represents the fraction of the cooling capacity of the chiller as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_input_to_cooling_output_ratio_function_of_temperature_curve_name
Fuel Input to Cooling Output Ratio Function of Temperature Curve Name
reference The curve represents the fraction of the fuel input to the chiller at full load as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Fuel Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
reference The curve represents the fraction of the fuel input to the chiller as the load on the chiller varies but the operating temperatures remain at the design values. The curve is normalized so that at full load the value of the curve should be 1.0. The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Electric Input to Cooling Output Ratio Function of Temperature Curve Name
reference The curve represents the fraction of the electricity to the chiller at full load as it varies by temperature. The curve is normalized so that at design conditions the value of the curve should be 1.0. This is a biquadratic curve with the input variables being the leaving chilled water temperature and either the entering or leaving condenser water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
reference The curve represents the fraction of the electricity to the chiller as the load on the chiller varies but the operating temperatures remain at the design values. The curve is normalized so that at full load the value of the curve should be 1.0. The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_capacity_function_of_cooling_capacity_curve_name
Heating Capacity Function of Cooling Capacity Curve Name
reference The curve represents how the heating capacity of the chiller varies with cooling capacity when the chiller is simultaneous heating and cooling. The curve is normalized so an input of 1.0 represents the nominal cooling capacity and an output of 1.0 represents the full heating capacity (see the Heating to cooling capacity ratio input) The curve is usually linear or quadratic.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
fuel_input_to_heat_output_ratio_during_heating_only_operation_curve_name
Fuel Input to Heat Output Ratio During Heating Only Operation Curve Name
reference When the chiller is operating as only a heater, this curve is used to represent the fraction of fuel used as the heating load varies. It is normalized so that a value of 1.0 is the full heating capacity. The curve is usually linear or quadratic and will probably be similar to a boiler curve for most chillers.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
temperature_curve_input_variable
Temperature Curve Input Variable
choice EnteringCondenser Sets the second independent variable in the three temperature dependent performance curves to either the leaving or entering condenser water temperature. Manufacturers express the performance of their chillers using either the leaving condenser water temperature (to the tower) or the entering condenser water temperature (from the tower).
One of EnteringCondenser, LeavingCondenser
condenser_type
Condenser Type
choice WaterCooled The condenser can either be air cooled or connected to a cooling tower.
One of AirCooled, WaterCooled
chilled_water_temperature_lower_limit
Chilled Water Temperature Lower Limit
number
C
2.0 The chilled water supply temperature below which the chiller will shut off.
exhaust_source_object_type
Exhaust Source Object Type required
choice One of Generator:MicroTurbine
exhaust_source_object_name
Exhaust Source Object Name
reference Names a Generator:MicroTurbine
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

ChillerHeaterPerformance:Electric:EIR

from idfpy.models import ChillerHeaterPerformanceElectricEIR

This chiller model is a generic chiller-heater where the cooling mode performance is a function of condenser entering or leaving fluid temperature and the heating mode performance is typically a function of condenser leaving fluid temperature. Performance at off-reference conditions is modeled using three polynomial equations per mode. Six curve objects are required.

Field Type Default Details
name
Name required
string
reference_cooling_mode_evaporator_capacity
Reference Cooling Mode Evaporator Capacity required
number or Autosize
W
reference_cooling_mode_cop
Reference Cooling Mode COP required
number
W/W
Efficiency of the chiller compressor (cooling output/compressor energy input).
Range: > 0
reference_cooling_mode_leaving_chilled_water_temperature
Reference Cooling Mode Leaving Chilled Water Temperature
number
C
6.67
reference_cooling_mode_entering_condenser_fluid_temperature
Reference Cooling Mode Entering Condenser Fluid Temperature
number
C
29.44
reference_cooling_mode_leaving_condenser_water_temperature
Reference Cooling Mode Leaving Condenser Water Temperature
number
C
35.0
reference_heating_mode_cooling_capacity_ratio
Reference Heating Mode Cooling Capacity Ratio
number 0.75 During simultaneous cooling-heating mode, this ratio is relative to the Reference Cooling Mode Cooling Capacity (Evaporator capacity at simul clg-htg mode ref condition)/ (Evaporator capacity at cooling mode ref condition)
reference_heating_mode_cooling_power_input_ratio
Reference Heating Mode Cooling Power Input Ratio
number 1.38 During simultaneous cooling-heating mode, this ratio is relative to the Reference Cooling Mode COP (Power at simultaneous clg-htg mode reference condition)/ (Power at cooling mode reference condition)
Range: > 0
reference_heating_mode_leaving_chilled_water_temperature
Reference Heating Mode Leaving Chilled Water Temperature
number
C
6.67 During simultaneous cooling-heating mode
reference_heating_mode_leaving_condenser_water_temperature
Reference Heating Mode Leaving Condenser Water Temperature
number
C
49.0 During simultaneous cooling-heating mode
reference_heating_mode_entering_condenser_fluid_temperature
Reference Heating Mode Entering Condenser Fluid Temperature
number
C
29.44
heating_mode_entering_chilled_water_temperature_low_limit
Heating Mode Entering Chilled Water Temperature Low Limit
number
C
12.22 During simultaneous cooling-heating mode
chilled_water_flow_mode_type
Chilled Water Flow Mode Type
choice ConstantFlow Sets chilled water flow rate to either constant or variable.
One of ConstantFlow, VariableFlow
design_chilled_water_flow_rate
Design Chilled Water Flow Rate
number or Autosize
m3/s
design_condenser_water_flow_rate
Design Condenser Water Flow Rate
number or Autosize
m3/s
design_hot_water_flow_rate
Design Hot Water Flow Rate
number
m3/s
0.0 Range: ≥ 0
compressor_motor_efficiency
Compressor Motor Efficiency
number 1.0 Fraction of compressor electrical energy that must be rejected by the condenser. Enter 1.0 or leave this field blank for a hermetic compressor.
Range: ≥ 0, ≤ 1
cooling_mode_temperature_curve_condenser_water_independent_variable
Cooling Mode Temperature Curve Condenser Water Independent Variable
choice EnteringCondenser Sets the second independent variable in the three temperature dependent performance curves to either the leaving or entering condenser water temperature. Manufacturers express the performance of their chillers using either the leaving condenser water temperature (to the tower) or the entering condenser water temperature (from the tower). Cooling mode is generally a stronger function of Entering Condenser Fluid Temperature
One of EnteringCondenser, LeavingCondenser
cooling_mode_cooling_capacity_function_of_temperature_curve_name
Cooling Mode Cooling Capacity Function of Temperature Curve Name required
reference Cooling capacity as a function of leaving chilled water temperature and either entering or leaving condenser fluid temperature curve = a + b*CWS + c*CWS**2 + d*TCond + e*TCond**2 + f*CWS*TCond If ClgModeCondWaterCurveInputVariable = EnteringCondenser, TCond = ECT If ClgModeCondWaterCurveInputVariable = LeavingCondenser, TCond = LCT CWS = supply (leaving) chilled water temperature(C) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_mode_electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Cooling Mode Electric Input to Cooling Output Ratio Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) as a function of supply (leaving) chilled water temperature and leaving condenser fluid temperature. EIR = 1/COP. curve = a + b*CWS + c*CWS**2 + d*TCond + e*TCond**2 + f*CWS*TCond If ClgModeCondWaterCurveInputVariable = EnteringCondenser, TCond = ECT If ClgModeCondWaterCurveInputVariable = LeavingCondenser, TCond = LCT CWS = supply (leaving) chilled water temperature(C) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_mode_electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Cooling Mode Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) as a function of Part Load Ratio (PLR) EIR = 1/COP Bicubic = a + b*TCond + c*TCond**2 + d*PLR + e*PLR**2 + f*TCond*PLR +g*0 + h*PLR**3+i*0+j*0 If ClgModeCondWaterCurveInputVariable = EnteringCondenser, TCond = ECT If ClgModeCondWaterCurveInputVariable = LeavingCondenser, TCond = LCT Normally, a bicubic curve here should be in terms of LCT rather than ECT Also, a bicubic curve is more applicable for variable-speed compressor motor drives or Quadratic = a + b*PLR + c*PLR**2 PLR = part load ratio (cooling load/steady-state capacity) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
cooling_mode_cooling_capacity_optimum_part_load_ratio
Cooling Mode Cooling Capacity Optimum Part Load Ratio
number 1.0 Optimum part load ratio where the chiller is most efficient. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio. The Min/Max PLR are taken from their associated EIR-FPLR curve references.
Range: > 0
heating_mode_temperature_curve_condenser_water_independent_variable
Heating Mode Temperature Curve Condenser Water Independent Variable
choice LeavingCondenser Sets the second independent variable in the three temperature dependent performance curves to either the leaving or entering condenser water temperature. Manufacturers express the performance of their chillers using either the leaving condenser water temperature (to the tower) or the entering condenser water temperature (from the tower). Heating mode (or Simul Clg/Htg Load) should be a function of Leaving Condenser Fluid Temperature Only use EnteringCondenser as a last resort in case no performance data exists for LeavingCondenser
One of EnteringCondenser, LeavingCondenser
heating_mode_cooling_capacity_function_of_temperature_curve_name
Heating Mode Cooling Capacity Function of Temperature Curve Name required
reference Evaporator (cooling) capacity as a function of leaving chilled water temperature and leaving condenser fluid temperature when in heating or simultaneous cool/heat mode curve = a + b*CWS + c*CWS**2 + d*TCond + e*TCond**2 + f*CWS*TCond If independent variable = EnteringCondenser, TCond = ECT If independent variable = LeavingCondenser, TCond = LCT CWS = supply (leaving) chilled water temperature(C) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_mode_electric_input_to_cooling_output_ratio_function_of_temperature_curve_name
Heating Mode Electric Input to Cooling Output Ratio Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) as a function of leaving chilled water temperature when in heating or simultaneous cool/heat mode and leaving condenser fluid temperature. EIR = 1/COP. curve = a + b*CWS + c*CWS**2 + d*TCond + e*TCond**2 + f*CWS*TCond If independent variable = EnteringCondenser, TCond = ECT If independent variable = LeavingCondenser, TCond = LCT CWS = leaving chilled water temperature(C) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_mode_electric_input_to_cooling_output_ratio_function_of_part_load_ratio_curve_name
Heating Mode Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) as a function of Part Load Ratio (PLR) when in heating or simultaneous cool/heat mode EIR = 1/COP Bicubic = a + b*LCT + c*LCT**2 + d*PLR + e*PLR**2 + f*LCT*PLR + g*0 + h*PLR**3 + i*0 + j*0 Normally, a bicubic curve here should be in terms of LCT rather than ECT Also, a bicubic curve is more applicable for variable-speed compressor motor drives or Quadratic = a + b*PLR + c*PLR**2 PLR = part load ratio (cooling load/steady-state capacity) LCT = leaving condenser fluid temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
heating_mode_cooling_capacity_optimum_part_load_ratio
Heating Mode Cooling Capacity Optimum Part Load Ratio
number 1.0 Optimum part load ratio where the chiller is most efficient when in heating or simultaneous cool/heat mode. Must be greater than or equal to the Minimum Part Load Ratio and less than or equal to the Maximum Part Load Ratio. The Min/Max PLR are taken from their associated EIR-FPLR curve references.
Range: > 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
Referenced by 1 object types

CentralHeatPumpSystem

DistrictCooling

from idfpy.models import DistrictCooling

Centralized source of chilled water, such as a district cooling system.

Field Type Default Details
name
Name required
string
chilled_water_inlet_node_name
Chilled Water Inlet Node Name required
string
chilled_water_outlet_node_name
Chilled Water Outlet Node Name required
string
nominal_capacity
Nominal Capacity
number or Autosize
W
capacity_fraction_schedule_name
Capacity Fraction Schedule Name
reference Schedule values are multiplied by Nominal Capacity for current capacity
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

DistrictHeating:Steam

from idfpy.models import DistrictHeatingSteam

Centralized source of Steam, such as a district heating system.

Field Type Default Details
name
Name required
string
steam_inlet_node_name
Steam Inlet Node Name required
string
steam_outlet_node_name
Steam Outlet Node Name required
string
nominal_capacity
Nominal Capacity
number or Autosize
W
capacity_fraction_schedule_name
Capacity Fraction Schedule Name
reference Schedule values are multiplied by Nominal Capacity for current capacity
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

DistrictHeating:Water

from idfpy.models import DistrictHeatingWater

Centralized source of hot water, such as a district heating system.

Field Type Default Details
name
Name required
string
hot_water_inlet_node_name
Hot Water Inlet Node Name required
string
hot_water_outlet_node_name
Hot Water Outlet Node Name required
string
nominal_capacity
Nominal Capacity
number or Autosize
W
capacity_fraction_schedule_name
Capacity Fraction Schedule Name
reference Schedule values are multiplied by Nominal Capacity for current capacity
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList

HeatPump:AirToWater

from idfpy.models import HeatPumpAirToWater

air-to-water heat pump system which provides either chilled or hot water with single- or variable speed compressors.

Field Type Default Details
name
Name required
string
availability_schedule_name_heating
Availability Schedule Name Heating
reference Enter the name of a schedule that defines the availability of the unit in heating mode Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
availability_schedule_name_cooling
Availability Schedule Name Cooling
reference Enter the name of a schedule that defines the availability of the unit in cooling mode Schedule values of 0 denote the unit is off. All other values denote the unit is available If this field is left blank, the unit is available the entire simulation
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
operating_mode_control_method
Operating Mode Control Method
choice Load One of EMSControlled, Load, ScheduledModes
operating_mode_control_option_for_multiple_unit
Operating Mode Control Option for Multiple Unit
choice SingleMode this determines how the operation mode is assigned when the load is too large to be met by multiple heat pump units SingleMode: all units will operate in the same mode (either all cooling or all heating). If the heating load is larger, then all unit operates in heating mode; otherwise, all operate in cooling mode. CoolingPriority: each unit will be staged one by one based on cooling demand first, after all cooling demand is met, if there are remaining heat pumps, they will be used to fulfill the remaining heating demand. HeatingPriority: similar to the previous cooling priority one, but will prioritize to meet the heating demand first Balanced: balance the percent satisfied heating or cooling load
One of Balanced, CoolingPriority, HeatingPriority, SingleMode
operating_mode_control_schedule_name
Operating Mode Control Schedule Name
reference This field is used if the control method is set to ScheduledModes Schedule values control operating mode: 0=off, 1=cooling, 2=heating
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Below this operating limit compressor cycling will occur
Range: ≥ 0
rated_inlet_air_temperature_in_heating_mode
Rated Inlet Air Temperature in Heating Mode
number
C
8.0 inlet air dry-bulb temperature corresponding to rated heat pump performance (capacity, COP).
rated_air_flow_rate_in_heating_mode
Rated Air Flow Rate in Heating Mode
number or Autosize
m3/s
Autosize air flow rate corresponding to rated heat pump performance (capacity, COP).
rated_leaving_water_temperature_in_heating_mode
Rated Leaving Water Temperature in Heating Mode
number
C
40.0 outlet water temperature corresponding to rated heat pump performance (heating capacity, COP).
rated_water_flow_rate_in_heating_mode
Rated Water Flow Rate in Heating Mode
number or Autosize
m3/s
Autosize Condenser water flow rate corresponding to rated heat pump performance (capacity, COP).
minimum_outdoor_air_temperature_in_heating_mode
Minimum Outdoor Air Temperature in Heating Mode
number
C
-30.0 Enter the minimum outdoor temperature allowed for heating operation Heating is disabled below this temperature
maximum_outdoor_air_temperature_in_heating_mode
Maximum Outdoor Air Temperature in Heating Mode
number
C
100.0 Enter the maximum outdoor temperature allowed for heating operation Heating is disabled above this temperature
minimum_leaving_water_temperature_curve_name_in_heating_mode
Minimum Leaving Water Temperature Curve Name in Heating Mode
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_leaving_water_temperature_curve_name_in_heating_mode
Maximum Leaving Water Temperature Curve Name in Heating Mode
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
sizing_factor_for_heating
Sizing Factor for Heating
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
rated_inlet_air_temperature_in_cooling_mode
Rated Inlet Air Temperature in Cooling Mode
number
C
30.0 inlet air dry-bulb temperature corresponding to rated heat pump performance (capacity, COP).
rated_air_flow_rate_in_cooling_mode
Rated Air Flow Rate in Cooling Mode
number or Autosize
m3/s
Autosize air flow rate corresponding to rated heat pump performance (capacity, COP).
rated_leaving_water_temperature_in_cooling_mode
Rated Leaving Water Temperature in Cooling Mode
number
C
8.0 outlet water temperature corresponding to rated heat pump performance (cooling capacity, COP).
rated_water_flow_rate_in_cooling_mode
Rated Water Flow Rate in Cooling Mode
number or Autosize
m3/s
Autosize Condenser water flow rate corresponding to rated heat pump performance (capacity, COP).
minimum_outdoor_air_temperature_in_cooling_mode
Minimum Outdoor Air Temperature in Cooling Mode
number
C
-30.0 Enter the minimum outdoor temperature allowed for cooling operation Cooling is disabled below this temperature
maximum_outdoor_air_temperature_in_cooling_mode
Maximum Outdoor Air Temperature in Cooling Mode
number
C
100.0 Enter the maximum outdoor temperature allowed for cooling operation Cooling is disabled above this temperature
minimum_leaving_water_temperature_curve_name_in_cooling_mode
Minimum Leaving Water Temperature Curve Name in Cooling Mode
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_leaving_water_temperature_curve_name_in_cooling_mode
Maximum Leaving Water Temperature Curve Name in Cooling Mode
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
sizing_factor_for_cooling
Sizing Factor for Cooling
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
air_inlet_node_name
Air Inlet Node Name required
string The node from which the heat pump draws its inlet air.
air_outlet_node_name
Air Outlet Node Name required
string The node to which the heat pump sends its outlet air.
hot_water_inlet_node_name
Hot Water Inlet Node Name
string The node connects to the hot water loop
hot_water_outlet_node_name
Hot Water Outlet Node Name
string The node connects to the hot water loop
chilled_water_inlet_node_name
Chilled Water Inlet Node Name
string The node connects to the chilled water loop
chilled_water_outlet_node_name
Chilled Water Outlet Node Name
string The node connects to the chilled water loop
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry Bulb Temperature For Defrost Operation
number 10.0 defrost operation will not be active above this outdoor temperature
heat_pump_defrost_control
Heat Pump Defrost Control
choice None One of None, OnDemand, Timed, TimedEmpirical
heat_pump_defrost_time_period_fraction
Heat Pump Defrost Time Period Fraction
number 0.058333 Fraction of time in defrost mode only applicable if timed defrost control is specified
Range: ≥ 0
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number
W
0.0 only applicable if resistive defrost strategy is specified
Range: ≥ 0
defrost_energy_input_ratio_function_of_temperature_curve_name
Defrost Energy Input Ratio Function of Temperature Curve Name
reference univariate curve = a + b*OAT is typical, other univariate curves may be used bivariate curve = a + b*WB + c*WB**2 + d*OAT + e*OAT**2 + f*WB*OAT OAT = outdoor air dry-bulb temperature (C) WB = wet-bulb temperature (C) of air entering the indoor coil only required if Timed or OnDemand defrost strategy is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heat_pump_multiplier
Heat Pump Multiplier
integer 1 intend to model modular heat pumps
control_type
Control Type
choice VariableSpeed One of FixedSpeed, VariableSpeed
crankcase_heater_capacity
Crankcase Heater Capacity
number
W
0.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Ambient Temperature for Crankcase Heater Operation and the heat pump is off. The ambient temperature uses the outdoor air temperature.
Range: ≥ 0
crankcase_heater_capacity_function_of_temperature_curve_name
Crankcase Heater Capacity Function of Temperature Curve Name
reference A Curve:* or Table:Lookup object encoding the relationship between the crankcase heater capacity and the outdoor air temperature. When this field is missing or empty, constant crankcase heater capacity will be assumed.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_ambient_temperature_for_crankcase_heater_operation
Maximum Ambient Temperature for Crankcase Heater Operation
number
C
10.0 The compressor crankcase heater only operates when the dry-bulb temperature of air surrounding the compressor is below the Maximum Outdoor Temperature for Crankcase Heater Operation and the unit is off.
Range: ≥ 0
number_of_speeds_for_heating
Number of Speeds for Heating
integer 1 the number of speed levels in heating mode if there's only cooling component, set this field to 0
Range: ≥ 0, ≤ 5
rated_heating_capacity_at_speed_1
Rated Heating Capacity at Speed 1
number or Autosize
W
Autosize
rated_cop_for_heating_at_speed_1
Rated COP for Heating at Speed 1
number
W/W
3.0 Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_at_speed_1
Normalized Heating Capacity Function of Temperature Curve Name at Speed 1
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_at_speed_1
Heating Energy Input Ratio Function of Temperature Curve Name at Speed 1
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_at_speed_1
Heating Energy Input Ratio Function of PLR Curve Name at Speed 1
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_heating_capacity_at_speed_2
Rated Heating Capacity at Speed 2
number or Autosize
W
Autosize
rated_cop_for_heating_at_speed_2
Rated COP for Heating at Speed 2
number
W/W
Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_at_speed_2
Normalized Heating Capacity Function of Temperature Curve Name at Speed 2
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_at_speed_2
Heating Energy Input Ratio Function of Temperature Curve Name at Speed 2
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_at_speed_2
Heating Energy Input Ratio Function of PLR Curve Name at Speed 2
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_heating_capacity_at_speed_3
Rated Heating Capacity at Speed 3
number or Autosize
W
Autosize
rated_cop_for_heating_at_speed_3
Rated COP for Heating at Speed 3
number
W/W
Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_at_speed_3
Normalized Heating Capacity Function of Temperature Curve Name at Speed 3
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_at_speed_3
Heating Energy Input Ratio Function of Temperature Curve Name at Speed 3
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_at_speed_3
Heating Energy Input Ratio Function of PLR Curve Name at Speed 3
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_heating_capacity_at_speed_4
Rated Heating Capacity at Speed 4
number or Autosize
W
Autosize
rated_cop_for_heating_at_speed_4
Rated COP for Heating at Speed 4
number
W/W
Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_at_speed_4
Normalized Heating Capacity Function of Temperature Curve Name at Speed 4
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_at_speed_4
Heating Energy Input Ratio Function of Temperature Curve Name at Speed 4
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_at_speed_4
Heating Energy Input Ratio Function of PLR Curve Name at Speed 4
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_heating_capacity_at_speed_5
Rated Heating Capacity at Speed 5
number or Autosize
W
Autosize
rated_cop_for_heating_at_speed_5
Rated COP for Heating at Speed 5
number
W/W
Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_at_speed_5
Normalized Heating Capacity Function of Temperature Curve Name at Speed 5
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_at_speed_5
Heating Energy Input Ratio Function of Temperature Curve Name at Speed 5
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_at_speed_5
Heating Energy Input Ratio Function of PLR Curve Name at Speed 5
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
booster_mode_on_heating
Booster Mode On Heating
choice No One of No, Yes
rated_heating_capacity_in_booster_mode
Rated Heating Capacity in Booster Mode
number
W
Range: > 0
rated_heating_cop_in_booster_mode
Rated Heating COP in Booster Mode
number
W/W
3.0 Range: > 0
normalized_heating_capacity_function_of_temperature_curve_name_in_booster_mode
Normalized Heating Capacity Function of Temperature Curve Name in Booster Mode
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_temperature_curve_name_in_booster_mode
Heating Energy Input Ratio Function of Temperature Curve Name in Booster Mode
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heating_energy_input_ratio_function_of_plr_curve_name_in_booster_mode
Heating Energy Input Ratio Function of PLR Curve Name in Booster Mode
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
number_of_speeds_for_cooling
Number of Speeds for Cooling
integer 1 the number of speed levels in cooling mode if there's only heating component, set this field to 0
Range: ≥ 0, ≤ 5
rated_cooling_capacity_at_speed_1
Rated Cooling Capacity at Speed 1
number or Autosize
W
Autosize
rated_cop_for_cooling_at_speed_1
Rated COP for Cooling at Speed 1
number
W/W
3.0 Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_at_speed_1
Normalized Cooling Capacity Function of Temperature Curve Name at Speed 1
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_at_speed_1
Cooling Energy Input Ratio Function of Temperature Curve Name at Speed 1
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_at_speed_1
Cooling Energy Input Ratio Function of PLR Curve Name at Speed 1
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_cooling_capacity_at_speed_2
Rated Cooling Capacity at Speed 2
number or Autosize
W
Autosize
rated_cop_for_cooling_at_speed_2
Rated COP for Cooling at Speed 2
number
W/W
Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_at_speed_2
Normalized Cooling Capacity Function of Temperature Curve Name at Speed 2
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_at_speed_2
Cooling Energy Input Ratio Function of Temperature Curve Name at Speed 2
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_at_speed_2
Cooling Energy Input Ratio Function of PLR Curve Name at Speed 2
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_cooling_capacity_at_speed_3
Rated Cooling Capacity at Speed 3
number or Autosize
W
Autosize
rated_cop_for_cooling_at_speed_3
Rated COP for Cooling at Speed 3
number
W/W
Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_at_speed_3
Normalized Cooling Capacity Function of Temperature Curve Name at Speed 3
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_at_speed_3
Cooling Energy Input Ratio Function of Temperature Curve Name at Speed 3
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_at_speed_3
Cooling Energy Input Ratio Function of PLR Curve Name at Speed 3
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_cooling_capacity_at_speed_4
Rated Cooling Capacity at Speed 4
number or Autosize
W
Autosize
rated_cop_for_cooling_at_speed_4
Rated COP for Cooling at Speed 4
number
W/W
Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_at_speed_4
Normalized Cooling Capacity Function of Temperature Curve Name at Speed 4
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_at_speed_4
Cooling Energy Input Ratio Function of Temperature Curve Name at Speed 4
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_at_speed_4
Cooling Energy Input Ratio Function of PLR Curve Name at Speed 4
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
rated_cooling_capacity_at_speed_5
Rated Cooling Capacity at Speed 5
number or Autosize
W
Autosize
rated_cop_for_cooling_at_speed_5
Rated COP for Cooling at Speed 5
number
W/W
Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_at_speed_5
Normalized Cooling Capacity Function of Temperature Curve Name at Speed 5
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_at_speed_5
Cooling Energy Input Ratio Function of Temperature Curve Name at Speed 5
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_at_speed_5
Cooling Energy Input Ratio Function of PLR Curve Name at Speed 5
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
booster_mode_on_cooling
Booster Mode On Cooling
choice No One of No, Yes
rated_cooling_capacity_in_booster_mode
Rated Cooling Capacity in Booster Mode
number
W
Range: > 0
rated_cooling_cop_in_booster_mode
Rated Cooling COP in Booster Mode
number
W/W
3.0 Range: > 0
normalized_cooling_capacity_function_of_temperature_curve_name_in_booster_mode
Normalized Cooling Capacity Function of Temperature Curve Name in Booster Mode
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_temperature_curve_name_in_booster_mode
Cooling Energy Input Ratio Function of Temperature Curve Name in Booster Mode
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table of air and water temperature.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
cooling_energy_input_ratio_function_of_plr_curve_name_in_booster_mode
Cooling Energy Input Ratio Function of PLR Curve Name in Booster Mode
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

HeatPump:AirToWater:FuelFired:Cooling

from idfpy.models import HeatPumpAirToWaterFuelFiredCooling

The object defines a fuel-fired absorption heat pump based on equation-fit models.

Field Type Default Details
name
Name required
string Name of the fuel fired absorption heat pump system system
water_inlet_node_name
Water Inlet Node Name required
string Inlet node name of the water side connection
water_outlet_node_name
Water Outlet Node Name required
string Outlet node name of the water side connection
air_source_node_name
Air Source Node Name
reference This is the air source node name, which is the condenser side of the heat pump in cooling mode. Enter the name of an OutdoorAir:Node object.
Names a OutdoorAir:Node
companion_heating_heat_pump_name
Companion Heating Heat Pump Name
reference The name of the companion HeatPump:AirToWater:FuelFired:Heating object This field is used for a heat pump with switchable heating and cooling mode.
Names a HeatPump:AirToWater:FuelFired:Heating
fuel_type
Fuel Type
choice NaturalGas Fuel Type (NaturalGas, Propane, Gasoline, Diesel etc.)
One of Coal, Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
nominal_cooling_capacity
Nominal Cooling Capacity
number or Autosize
W
Nominal Cooling Capacity in [W] (autosizable)
nominal_cop
Nominal COP
number
W/W
1.0 Nominal COP (Coefficient of Performance)
Range: > 0
design_flow_rate
Design Flow Rate
number or Autosize
m3/s
Design Flow Rate in m3/s (autosizable)
design_supply_temperature
Design Supply Temperature
number
C
7.0 Design Supply Temperature in [degree C]
design_temperature_lift
Design Temperature Lift
number or Autosize
deltaC
11.1 Design Temperature Lift in [degree C]
sizing_factor
Sizing Factor
number 1.0 Sizing Factor for equipment sizing
Range: ≥ 0
flow_mode
Flow Mode
choice NotModulated Flow Mode for the water side of the fuel-fired absorption heat pump
One of ConstantFlow, LeavingSetpointModulated, NotModulated
outdoor_air_temperature_curve_input_variable
Outdoor Air Temperature Curve Input Variable
choice DryBulb Outdoor air temperature curve input variable; The options are Outdoor Air Dry Bulb or Wet Bulb temperature for curves
One of DryBulb, WetBulb
water_temperature_curve_input_variable
Water Temperature Curve Input Variable
choice EnteringEvaporator Water Temperature curve input variable - Condenser Entering or Leaving Water Temperature for curves
One of EnteringEvaporator, LeavingEvaporator
normalized_capacity_function_of_temperature_curve_name
Normalized Capacity Function of Temperature Curve Name required
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_energy_input_ratio_function_of_temperature_curve_name
Fuel Energy Input Ratio Function of Temperature Curve Name required
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_energy_input_ratio_function_of_plr_curve_name
Fuel Energy Input Ratio Function of PLR Curve Name required
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 Minimum Part Load Ratio (PLR) in between 0 and 1
Range: > 0, ≤ 1
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Maximum Part Load Ratio (PLR) in between 0 and 1
Range: > 0, ≤ 1
cycling_ratio_factor_curve_name
Cycling Ratio Factor Curve Name
reference Cycling Ratio Factor (CRF) Curve Name, which is a cubic curve or a lookup table function of Cycling Ratio (defined as = PLR/PLRmin); if left blank, no adjustment will be made.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
nominal_auxiliary_electric_power
Nominal Auxiliary Electric Power
number
W
Nominal Auxiliary Electric Power in [W]
Range: ≥ 0
auxiliary_electric_energy_input_ratio_function_of_temperature_curve_name
Auxiliary Electric Energy Input Ratio Function of Temperature Curve Name
reference Auxiliary Electric EIRFT - Auxiliary Electric Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table. which accounts for system internal fans, pumps, and electronics
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
auxiliary_electric_energy_input_ratio_function_of_plr_curve_name
Auxiliary Electric Energy Input Ratio Function of PLR Curve Name
reference Auxiliary Electric EIRFPLR - Auxiliary Electric Energy Input Ratio Function of PLR (Part Load Ratio) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
standby_electric_power
Standby Electric Power
number
W
0.0 Standby Electric Power in [W]
Range: ≥ 0
minimum_unloading_ratio
Minimum Unloading Ratio
number 0.25 Minimum modulation level of the gas-fired heat pump. Typically less than 1.0 and slightly higher than the minimum part load ratio.
Range: ≥ 0, ≤ 1
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:AirToWater:FuelFired:Heating

HeatPump:AirToWater:FuelFired:Heating

from idfpy.models import HeatPumpAirToWaterFuelFiredHeating

The object defines a fuel-fired absorption heat pump based on equation-fit models.

Field Type Default Details
name
Name required
string Name of the fuel fired absorption heat pump system system
water_inlet_node_name
Water Inlet Node Name required
string Inlet node name of the water side connection
water_outlet_node_name
Water Outlet Node Name required
string Outlet node name of the water side connection
air_source_node_name
Air Source Node Name
reference This is the air source node name, which is the evaporator side of the heat pump in heating mode. Enter the name of an OutdoorAir:Node object.
Names a OutdoorAir:Node
companion_cooling_heat_pump_name
Companion Cooling Heat Pump Name
reference The name of the companion HeatPump:AirToWater:FuelFired:Cooling object This field is used for a heat pump with switchable heating and cooling mode.
Names a HeatPump:AirToWater:FuelFired:Cooling
fuel_type
Fuel Type
choice NaturalGas Fuel Type (NaturalGas, Propane, Gasoline, Diesel etc.)
One of Coal, Diesel, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, OtherFuel1, OtherFuel2, Propane
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
nominal_heating_capacity
Nominal Heating Capacity
number or Autosize
W
Nominal Heating Capacity in [W] (autosizable)
nominal_cop
Nominal COP
number
W/W
1.0 Nominal COP (Coefficient of Performance)
Range: > 0
design_flow_rate
Design Flow Rate
number or Autosize
m3/s
Design Flow Rate in m3/s (autosizable)
design_supply_temperature
Design Supply Temperature
number
C
60.0 Design Supply Temperature in [degree C]
design_temperature_lift
Design Temperature Lift
number or Autosize
deltaC
11.1 Design Temperature Lift in [degree C]
sizing_factor
Sizing Factor
number 1.0 Sizing Factor for equipment sizing
Range: ≥ 0
flow_mode
Flow Mode
choice NotModulated Flow Mode for the water side of the fuel-fired absorption heat pump
One of ConstantFlow, LeavingSetpointModulated, NotModulated
outdoor_air_temperature_curve_input_variable
Outdoor Air Temperature Curve Input Variable
choice DryBulb Outdoor air temperature curve input variable; The options are Outdoor Air Dry Bulb or Wet Bulb temperature for curves
One of DryBulb, WetBulb
water_temperature_curve_input_variable
Water Temperature Curve Input Variable
choice EnteringCondenser Water Temperature curve input variable - Condenser Entering or Leaving Water Temperature for curves
One of EnteringCondenser, LeavingCondenser
normalized_capacity_function_of_temperature_curve_name
Normalized Capacity Function of Temperature Curve Name required
reference CAPFT - Normalized Capacity Function of Temperature Curve Name, which is a biquadratic curve or a lookup table.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_energy_input_ratio_function_of_temperature_curve_name
Fuel Energy Input Ratio Function of Temperature Curve Name required
reference EIRFT - Fuel Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fuel_energy_input_ratio_function_of_plr_curve_name
Fuel Energy Input Ratio Function of PLR Curve Name required
reference EIRFPLR - Fuel Energy Input Ratio Function of Part Load Ratio(PLR) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.1 Minimum Part Load Ratio (PLR) in between 0 and 1
Range: > 0, ≤ 1
maximum_part_load_ratio
Maximum Part Load Ratio
number 1.0 Maximum Part Load Ratio (PLR) in between 0 and 1
Range: > 0, ≤ 1
defrost_control_type
Defrost Control Type
choice Timed Defrost operation control type: Timed or OnDemand
One of OnDemand, Timed
defrost_operation_time_fraction
Defrost Operation Time Fraction
number 0.0 Defrost operation time fraction, which will be used only for Timed Defrost Control Type.
Range: ≥ 0, ≤ 1
fuel_energy_input_ratio_defrost_adjustment_curve_name
Fuel Energy Input Ratio Defrost Adjustment Curve Name
reference EIRDEFROST - Energy Input Ratio Defrost Adjustment Curve Name, which is a cubic curve or a lookup table function of Outdoor Air Temperature. This field is only used when OnDemand Defrost Control Type is selected.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
resistive_defrost_heater_capacity
Resistive Defrost Heater Capacity
number
W
0.0 The heating power of electric resistive defrost heater. Only used for timed defrost control type.
Range: ≥ 0
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry-bulb Temperature for Defrost Operation
number
C
5.0 There will be no defrost operation when outdoor air is above this temperature.
Range: ≥ 0, ≤ 10
cycling_ratio_factor_curve_name
Cycling Ratio Factor Curve Name
reference Cycling Ratio Factor (CRF) Curve Name, which is a cubic curve or a lookup table function of Cycling Ratio (defined as = PLR/PLRmin); if left blank, no adjustment will be made.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
nominal_auxiliary_electric_power
Nominal Auxiliary Electric Power
number
W
Nominal Auxiliary Electric Power in [W]
Range: ≥ 0
auxiliary_electric_energy_input_ratio_function_of_temperature_curve_name
Auxiliary Electric Energy Input Ratio Function of Temperature Curve Name
reference Auxiliary Electric EIRFT - Auxiliary Electric Energy Input Ratio Function of Temperature Curve Name, which is a biquadratic curve or a lookup table. which accounts for system internal fans, pumps, and electronics
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
auxiliary_electric_energy_input_ratio_function_of_plr_curve_name
Auxiliary Electric Energy Input Ratio Function of PLR Curve Name
reference Auxiliary Electric EIRFPLR - Auxiliary Electric Energy Input Ratio Function of PLR (Part Load Ratio) Curve Name, which is a cubic curve or a lookup table.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
standby_electric_power
Standby Electric Power
number
W
0.0 Standby Electric Power in [W]
Range: ≥ 0
minimum_unloading_ratio
Minimum Unloading Ratio
number 0.25 Minimum modulation level of the gas-fired heat pump. Typically less than 1.0 and slightly higher than the minimum part load ratio.
Range: ≥ 0, ≤ 1
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:AirToWater:FuelFired:Cooling

HeatPump:PlantLoop:EIR:Cooling

from idfpy.models import HeatPumpPlantLoopEIRCooling

An EIR formulated water to water heat pump model, cooling operation.

Field Type Default Details
name
Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
condenser_type
Condenser Type
choice WaterSource One of AirSource, WaterSource
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string Not available with water source condenser type
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string Not available with water source condenser type
companion_heat_pump_name
Companion Heat Pump Name
reference This field allows the user to specify a companion heating object for this cooling object. The companion is used in sizing the heat pump as well as to allow checks for unexpected simultaneous operation of the two objects.
Names a HeatPump:PlantLoop:EIR:Heating
load_side_reference_flow_rate
Load Side Reference Flow Rate
number or Autosize
m3/s
Autosize This component is currently a constant-flow device, meaning it will always try to request the full design flow from the central plant manager.
source_side_reference_flow_rate
Source Side Reference Flow Rate
number or Autosize
m3/s
Autosize
heat_recovery_reference_flow_rate
Heat Recovery Reference Flow Rate
number or Autosize
m3/s
Autosize Not available with water source condenser type
reference_capacity
Reference Capacity
number or Autosize
W
Autosize
reference_coefficient_of_performance
Reference Coefficient of Performance
number
W/W
3.0 Range: > 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized load side reference flow rate which is then used to autosize the capacity
Range: > 0
capacity_modifier_function_of_temperature_curve_name
Capacity Modifier Function of Temperature Curve Name required
reference Cooling capacity modifier as a function of CW supply temp and entering condenser temp curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_output_ratio_modifier_function_of_temperature_curve_name
Electric Input to Output Ratio Modifier Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) modifier as a function of temperature EIR = 1/COP curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_output_ratio_modifier_function_of_part_load_ratio_curve_name
Electric Input to Output Ratio Modifier Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) modifier as a function of Part Load Ratio (PLR) EIR = 1/COP quadratic curve = a + b*PLR + c*PLR**2 is typical, other univariate curves may be used PLR = part load ratio (cooling load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
control_type
Control Type
choice Load Heat pump can be controlled on leaving water temperature set point or plant load
One of Load, Setpoint
flow_mode
Flow Mode
choice ConstantFlow Select operating mode for fluid flow through the chiller. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "VariableSpeedPumping" is for variable pumping with flow proportional to chiller operating part load ratio.
One of ConstantFlow, VariableSpeedPumping
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Below this operating limit compressor cycling will occur
Range: ≥ 0
minimum_source_inlet_temperature
Minimum Source Inlet Temperature
number
C
-100.0 Enter the minimum inlet outdoor air dry-bulb temperature for air-cooled units or minimum inlet water temperature for water-cooled units. The unit is disabled below this temperature.
maximum_source_inlet_temperature
Maximum Source Inlet Temperature
number
C
100.0 Enter the maximum inlet outdoor air dry-bulb temperature for air-cooled units or maximum inlet water temperature for water-cooled units. The unit is disabled above this temperature.
minimum_supply_water_temperature_curve_name
Minimum Supply Water Temperature Curve Name
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_supply_water_temperature_curve_name
Maximum Supply Water Temperature Curve Name
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_heat_recovery_outlet_temperature
Maximum Heat Recovery Outlet Temperature
number
C
60.0 Enter the maximum heat recovery leaving water temperature limit The hot water temperature is not allowed to exceed this value Not available with water source condenser type
heat_recovery_capacity_modifier_function_of_temperature_curve_name
Heat Recovery Capacity Modifier Function of Temperature Curve Name
reference Cooling capacity modifier as a function of CW supply temp and condenser entering fluid temp curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C) If this field is blank, the AWHP curve without heat recovery will be used
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heat_recovery_electric_input_to_output_ratio_modifier_function_of_temperature_curve_name
Heat Recovery Electric Input to Output Ratio Modifier Function of Temperature Curve Name
reference Electric Input Ratio (EIR) modifier as a function of temperature EIR = 1/COP curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) chilled water temperature(C) ECT = entering condenser fluid temperature(C) If this field is blank, the AWHP curve without heat recovery will be used
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
thermosiphon_capacity_fraction_curve_name
Thermosiphon Capacity Fraction Curve Name
reference quadratic curve = a + b * (Tevap, out - Tcond, in) is typical, other univariate curves may be used Tevap, out = evaporator outlet temperature Tcond, in = condenser inlet temperature If this field is blank the thermosiphon model is disabled.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
thermosiphon_minimum_temperature_difference
Thermosiphon Minimum Temperature Difference
number 0.0 Thermosiphon model is disabled below this minimum limit and when the load is greater than calculated using the previous field.
Range: ≥ 0
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:PlantLoop:EIR:Heating, PlantEquipmentList, PlantEquipmentOperation:ChillerHeaterChangeover

HeatPump:PlantLoop:EIR:Heating

from idfpy.models import HeatPumpPlantLoopEIRHeating

An EIR formulated water to water heat pump model, heating operation

Field Type Default Details
name
Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
condenser_type
Condenser Type
choice WaterSource One of AirSource, WaterSource
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
heat_recovery_inlet_node_name
Heat Recovery Inlet Node Name
string Not available with water source condenser type
heat_recovery_outlet_node_name
Heat Recovery Outlet Node Name
string Not available with water source condenser type
companion_heat_pump_name
Companion Heat Pump Name
reference This field allows the user to specify a companion cooling object for this heating object. The companion is used in sizing the heat pump as well as to allow checks for unexpected simultaneous operation of the two objects.
Names a HeatPump:PlantLoop:EIR:Cooling
load_side_reference_flow_rate
Load Side Reference Flow Rate
number or Autosize
m3/s
Autosize This component is currently a constant-flow device, meaning it will always try to request the full design flow from the central plant manager.
source_side_reference_flow_rate
Source Side Reference Flow Rate
number or Autosize
m3/s
Autosize
heat_recovery_reference_flow_rate
Heat Recovery Reference Flow Rate
number or Autosize
m3/s
Autosize Not available with water source condenser type
reference_capacity
Reference Capacity
number or Autosize
W
Autosize
reference_coefficient_of_performance
Reference Coefficient of Performance
number
W/W
3.0 Range: > 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized load side reference flow rate which is then used to autosize the capacity
Range: > 0
capacity_modifier_function_of_temperature_curve_name
Capacity Modifier Function of Temperature Curve Name required
reference Heating capacity modifier as a function of CW supply temp and entering condenser temp curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) hot water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_output_ratio_modifier_function_of_temperature_curve_name
Electric Input to Output Ratio Modifier Function of Temperature Curve Name required
reference Electric Input Ratio (EIR) modifier as a function of temperature EIR = 1/COP curve = a + b*CWS + c*CWS**2 + d*ECT + e*ECT**2 + f*CWS*ECT CWS = supply (leaving) hot water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
electric_input_to_output_ratio_modifier_function_of_part_load_ratio_curve_name
Electric Input to Output Ratio Modifier Function of Part Load Ratio Curve Name required
reference Electric Input Ratio (EIR) modifier as a function of Part Load Ratio (PLR) EIR = 1/COP quadratic curve = a + b*PLR + c*PLR**2 is typical, other univariate curves may be used PLR = part load ratio (hot load/steady state capacity)
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
heating_to_cooling_capacity_sizing_ratio
Heating To Cooling Capacity Sizing Ratio
number 1.0 Multiplies the autosized heating capacity
Range: ≥ 0
heat_pump_sizing_method
Heat Pump Sizing Method
choice CoolingCapacity Specifies sizing method when companion coil exists
One of CoolingCapacity, GreaterOfHeatingOrCooling, HeatingCapacity
control_type
Control Type
choice Load Heat pump can be controlled on leaving water temperature set point or plant load
One of Load, Setpoint
flow_mode
Flow Mode
choice ConstantFlow Select operating mode for fluid flow through the chiller. "ConstantFlow" is for constant pumping with flow controlled by chiller to operate at full design flow rate. "VariableSpeedPumping" is for variable pumping with flow proportional to chiller operating part load ratio.
One of ConstantFlow, VariableSpeedPumping
minimum_part_load_ratio
Minimum Part Load Ratio
number 0.0 Below this operating limit compressor cycling will occur
Range: ≥ 0
minimum_source_inlet_temperature
Minimum Source Inlet Temperature
number
C
-100.0 Enter the minimum inlet outdoor air dry-bulb temperature for air-cooled units or minimum inlet water temperature for water-cooled units. The unit is disabled below this temperature.
maximum_source_inlet_temperature
Maximum Source Inlet Temperature
number
C
100.0 Enter the maximum inlet outdoor air dry-bulb temperature for air-cooled units or maximum inlet water temperature for water-cooled units. The unit is disabled above this temperature.
minimum_supply_water_temperature_curve_name
Minimum Supply Water Temperature Curve Name
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_supply_water_temperature_curve_name
Maximum Supply Water Temperature Curve Name
reference quadratic curve = a + b*OAT is typical, other univariate curves may be used OAT = Outdoor Dry-Bulb Temperature
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
dry_outdoor_correction_factor_curve_name
Dry Outdoor Correction Factor Curve Name
reference Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
maximum_outdoor_dry_bulb_temperature_for_defrost_operation
Maximum Outdoor Dry Bulb Temperature For Defrost Operation
number 10.0 defrost operation will not be active above this outdoor temperature
heat_pump_defrost_control
Heat Pump Defrost Control
choice A blank field is the same as None.
One of None, OnDemand, Timed, TimedEmpirical
heat_pump_defrost_time_period_fraction
Heat Pump Defrost Time Period Fraction
number 0.058333 Nominal fraction of time in defrost mode only applicable if Timed or TimedEmpirical heat pump defrost control is specified
Range: ≥ 0
defrost_energy_input_ratio_function_of_temperature_curve_name
Defrost Energy Input Ratio Function of Temperature Curve Name
reference univariate curve = a + b*OAT is typical, other univariate curves may be used bivariate curve = a + b*WB + c*WB**2 + d*OAT + e*OAT**2 + f*WB*OAT OAT = outdoor air dry-bulb temperature (C) WB = wet-bulb temperature (C) of air entering the indoor coil only required if Timed or OnDemand defrost strategy is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
timed_empirical_defrost_frequency_curve_name
Timed Empirical Defrost Frequency Curve Name
reference univariate curve = a + b*OAT is typical, other univariate curves may be used OAT = outdoor air dry-bulb temperature (C) Timed Empirical Defrost Frequency fraction in hours = curve output only applicable if TimedEmpirical defrost control is specified
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
timed_empirical_defrost_heat_load_penalty_curve_name
Timed Empirical Defrost Heat Load Penalty Curve Name
reference univariate curve = a + b*OAT is typical, other univariate curves may be used bivariate curve = a + b*WB + c*WB**2 + d*OAT + e*OAT**2 + f*WB*OAT OAT = outdoor air dry-bulb temperature (C) WB = wet-bulb temperature (C) of air entering the indoor coil Timed Empirical Defrost Heat Load Penalty in watts = hot load * curve output only applicable if TimedEmpirical defrost control is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
timed_empirical_defrost_heat_input_energy_fraction_curve_name
Timed Empirical Defrost Heat Input Energy Fraction Curve Name
reference univariate curve = a + b*OAT is typical, other univariate curves may be used bivariate curve = a + b*WB + c*WB**2 + d*OAT + e*OAT**2 + f*WB*OAT OAT = outdoor air dry-bulb temperature (C) WB = wet-bulb temperature (C) of air entering the indoor coil Timed Empirical Defrost Heat Input Energy in watts = rated hot load * curve output only applicable if TimedEmpirical defrost control is specified
Names a Curve:Bicubic, Curve:Biquadratic, Curve:Cubic, Curve:CubicLinear, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:FanPressureRise, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic and 6 more
minimum_heat_recovery_outlet_temperature
Minimum Heat Recovery Outlet Temperature
number
C
4.5 Enter the minimum heat recovery leaving water temperature limit The chilled water temperature is not allowed to drop below this value Not available with water source condenser type
heat_recovery_capacity_modifier_function_of_temperature_curve_name
Heat Recovery Capacity Modifier Function of Temperature Curve Name
reference Heating capacity modifier as a function of HW supply temp and entering condenser fluid temp curve = a + b*HWS + c*HWS**2 + d*ECT + e*ECT**2 + f*HWS*ECT HWS = supply (leaving) hot water temperature(C) ECT = entering condenser fluid temperature(C)
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
heat_recovery_electric_input_to_output_ratio_modifier_function_of_temperature_curve_name
Heat Recovery Electric Input to Output Ratio Modifier Function of Temperature Curve Name
reference Electric Input Ratio (EIR) modifier as a function of temperature EIR = 1/COP curve = a + b*HWS + c*HWS**2 + d*ECT + e*ECT**2 + f*HWS*ECT HWS = supply (leaving) hot water temperature(C) ECT = entering condenser fluid temperature(C) If this field is blank, the AWHP curve without heat recovery will be used
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
Referenced by 5 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:PlantLoop:EIR:Cooling, PlantEquipmentList, PlantEquipmentOperation:ChillerHeaterChangeover

HeatPump:WaterToWater:EquationFit:Cooling

from idfpy.models import HeatPumpWaterToWaterEquationFitCooling

simple water-water heat pump curve-fit model

Field Type Default Details
name
Name required
string
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
reference_load_side_flow_rate
Reference Load Side Flow Rate required
number or Autosize
m3/s
reference_source_side_flow_rate
Reference Source Side Flow Rate required
number or Autosize
m3/s
reference_cooling_capacity
Reference Cooling Capacity required
number or Autosize
W
reference_cooling_power_consumption
Reference Cooling Power Consumption required
number or Autosize
W
cooling_capacity_curve_name
Cooling Capacity Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
cooling_compressor_power_curve_name
Cooling Compressor Power Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
reference_coefficient_of_performance
Reference Coefficient of Performance
number
W/W
8.0 This optional field is used to autosize Reference Cooling Power Consumption COP = Rated Cooling Capacity / Rated Cooling Power Consumption
Range: > 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
companion_heating_heat_pump_name
Companion Heating Heat Pump Name
reference This optional field is used to coordinate sizing calculations between heating and cooling modes.
Names a HeatPump:WaterToWater:EquationFit:Heating
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:WaterToWater:EquationFit:Heating, PlantEquipmentList

HeatPump:WaterToWater:EquationFit:Heating

from idfpy.models import HeatPumpWaterToWaterEquationFitHeating

simple water-water hp curve-fit model

Field Type Default Details
name
Name required
string
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
reference_load_side_flow_rate
Reference Load Side Flow Rate required
number or Autosize
m3/s
reference_source_side_flow_rate
Reference Source Side Flow Rate required
number or Autosize
m3/s
reference_heating_capacity
Reference Heating Capacity required
number or Autosize
W
reference_heating_power_consumption
Reference Heating Power Consumption required
number or Autosize
W
heating_capacity_curve_name
Heating Capacity Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
heating_compressor_power_curve_name
Heating Compressor Power Curve Name required
reference Names a Curve:QuadLinear, Table:Lookup
reference_coefficient_of_performance
Reference Coefficient of Performance
number
W/W
7.5 This optional field is used to autosize Reference Heating Power Consumption COP = Reference Heating Capacity / Reference Heating Power Consumption
Range: > 0
sizing_factor
Sizing Factor
number 1.0 Multiplies the autosized capacity and flow rates
Range: > 0
companion_cooling_heat_pump_name
Companion Cooling Heat Pump Name
reference Names a HeatPump:WaterToWater:EquationFit:Cooling
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, HeatPump:WaterToWater:EquationFit:Cooling, PlantEquipmentList

HeatPump:WaterToWater:ParameterEstimation:Cooling

from idfpy.models import HeatPumpWaterToWaterParameterEstimationCooling

OSU parameter estimation model

Field Type Default Details
name
Name required
string
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
nominal_cop
Nominal COP
number
W/W
Range: > 0
nominal_capacity
Nominal Capacity
number
W
Range: > 0
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
load_side_flow_rate
Load Side Flow Rate
number
m3/s
Range: > 0
source_side_flow_rate
Source Side Flow Rate
number
m3/s
Range: > 0
load_side_heat_transfer_coefficient
Load Side Heat Transfer Coefficient
number
W/K
Range: > 0
source_side_heat_transfer_coefficient
Source Side Heat Transfer Coefficient
number
W/K
Range: > 0
piston_displacement
Piston Displacement
number
m3/s
Range: > 0
compressor_clearance_factor
Compressor Clearance Factor
number Range: > 0
compressor_suction_and_discharge_pressure_drop
Compressor Suction and Discharge Pressure Drop
number
Pa
Range: > 0
superheating
Superheating
number
C
Range: > 0
constant_part_of_electromechanical_power_losses
Constant Part of Electromechanical Power Losses
number
W
Range: > 0
loss_factor
Loss Factor
number Used to define electromechanical loss that is proportional to the theoretical power %
Range: > 0
high_pressure_cut_off
High Pressure Cut Off
number
Pa
500000000.0 Range: ≥ 0
low_pressure_cut_off
Low Pressure Cut Off
number
Pa
0.0 Range: ≥ 0
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

HeatPump:WaterToWater:ParameterEstimation:Heating

from idfpy.models import HeatPumpWaterToWaterParameterEstimationHeating

OSU parameter estimation model

Field Type Default Details
name
Name required
string
source_side_inlet_node_name
Source Side Inlet Node Name required
string
source_side_outlet_node_name
Source Side Outlet Node Name required
string
load_side_inlet_node_name
Load Side Inlet Node Name required
string
load_side_outlet_node_name
Load Side Outlet Node Name required
string
nominal_cop
Nominal COP
number
W/W
Range: > 0
nominal_capacity
Nominal Capacity
number
W
Range: > 0
minimum_part_load_ratio
Minimum Part Load Ratio
number Range: ≥ 0
maximum_part_load_ratio
Maximum Part Load Ratio
number Range: ≥ 0
optimum_part_load_ratio
Optimum Part Load Ratio
number Range: ≥ 0
load_side_flow_rate
Load Side Flow Rate
number
m3/s
Range: > 0
source_side_flow_rate
Source Side Flow Rate
number
m3/s
Range: > 0
load_side_heat_transfer_coefficient
Load Side Heat Transfer Coefficient
number
W/K
Range: > 0
source_side_heat_transfer_coefficient
Source Side Heat Transfer Coefficient
number
W/K
Range: > 0
piston_displacement
Piston Displacement
number
m3/s
Range: > 0
compressor_clearance_factor
Compressor Clearance Factor
number Range: > 0
compressor_suction_and_discharge_pressure_drop
Compressor Suction and Discharge Pressure Drop
number
Pa
Range: > 0
superheating
Superheating
number
C
Range: > 0
constant_part_of_electromechanical_power_losses
Constant Part of Electromechanical Power Losses
number
W
Range: > 0
loss_factor
Loss Factor
number Used to define electromechanical loss that is proportional to the theoretical power %
Range: > 0
high_pressure_cut_off
High Pressure Cut Off
number
Pa
500000000.0 Range: ≥ 0
low_pressure_cut_off
Low Pressure Cut Off
number
Pa
0.0 Range: ≥ 0
Referenced by 3 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, PlantEquipmentList

PlantComponent:TemperatureSource

from idfpy.models import PlantComponentTemperatureSource

Simulates an object of pre-determined (constant or scheduled) source temperature The object introduces fluid into the plant loop at the specified temperature and at the same flow rate as the fluid enters the component Fluid entering the component vanishes equivalent to the relief air in an air system

Field Type Default Details
name
Name required
string Component Name
inlet_node
Inlet Node required
string Name of the source inlet node
outlet_node
Outlet Node required
string Name of the source outlet node
design_volume_flow_rate
Design Volume Flow Rate required
number or Autosize
m3/s
The design volumetric flow rate for this source
temperature_specification_type
Temperature Specification Type
choice One of Constant, Scheduled
source_temperature
Source Temperature
number
C
Used if Temperature Specification Type = Constant
source_temperature_schedule_name
Source Temperature Schedule Name
reference
C
Used if Temperature Specification Type = Scheduled
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 4 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch, CondenserEquipmentList, PlantEquipmentList