Internal Gains

36 object types from idfpy.models.internal_gains · EnergyPlus 26.2

Object Summary
ComfortViewFactorAngles Used to specify radiant view factors for thermal comfort calculations.
ElectricEquipment Sets internal gains for electric equipment in the zone.
ElectricEquipment:Definition Defines the physical characteristics (design level and heat gain fractions) for electric equipment.
ElectricEquipment:ITE:AirCooled This object describes air-cooled electric information technology equipment (ITE) which has variable power …
ElectricEquipment:ITE:AirCooled:Definition Performance characteristics for ElectricEquipment:ITE:AirCooled:Instance.
ElectricEquipment:ITE:AirCooled:Instance This object describes air-cooled electric information technology equipment (ITE) which has variable power …
ElectricEquipment:Instance Sets internal gains for electric equipment in the zone.
GasEquipment Sets internal gains and contaminant rates for gas equipment in the zone.
GasEquipment:Definition Defines the physical characteristics (design level and heat gain fractions) for gas equipment.
GasEquipment:Instance Sets internal gains and contaminant rates for gas equipment in the zone.
HotWaterEquipment Sets internal gains for hot water equipment in the zone.
HotWaterEquipment:Definition Defines the physical characteristics (design level and heat gain fractions) for hot water equipment.
HotWaterEquipment:Instance Sets internal gains for hot water equipment in the zone.
IndoorLivingWall Indoor greenery systems such as indoor living walls are panels of plants, which grow hydroponically or from …
Lights Sets internal gains for lights in the zone.
Lights:Definition Defines the physical characteristics (design level and heat gain fractions) for lights.
Lights:Instance Sets internal gains for lights in the zone.
OtherEquipment Sets internal gains or losses for "other" equipment in the zone.
OtherEquipment:Definition Defines the physical characteristics (design level and heat gain fractions) for "other" equipment.
OtherEquipment:Instance Sets internal gains or losses for "other" equipment in the zone.
People Sets internal gains and contaminant rates for occupants in the zone.
People:Definition Defines the physical characteristics (number of people, heat gain fractions, CO2 generation rate and thermal …
People:Instance Sets internal gains and contaminant rates for occupants in the zone.
SteamEquipment Sets internal gains for steam equipment in the zone.
SteamEquipment:Definition Defines the physical characteristics (design level and heat gain fractions) for steam equipment.
SteamEquipment:Instance Sets internal gains for steam equipment in the zone.
SurfaceContaminantSourceAndSink:Generic:BoundaryLayerDiffusion Simulate generic contaminant source driven by the boundary layer diffusion controlled model.
SurfaceContaminantSourceAndSink:Generic:DepositionVelocitySink Simulate generic contaminant source driven by the boundary layer diffusion controlled model.
SurfaceContaminantSourceAndSink:Generic:PressureDriven Simulate generic contaminant source driven by the pressure difference across a surface.
SwimmingPool:Indoor Specifies an indoor swimming pools linked to a floor surface.
ZoneBaseboard:OutdoorTemperatureControlled Specifies outside temperature-controlled electric baseboard heating.
ZoneContaminantSourceAndSink:CarbonDioxide Represents internal CO2 gains and sinks in the zone.
ZoneContaminantSourceAndSink:Generic:Constant Sets internal generic contaminant gains and sinks in a zone with constant values.
ZoneContaminantSourceAndSink:Generic:CutoffModel Simulate generic contaminant source driven by the cutoff concentration model.
ZoneContaminantSourceAndSink:Generic:DecaySource Simulate generic contaminant source driven by the cutoff concentration model.
ZoneContaminantSourceAndSink:Generic:DepositionRateSink Simulate generic contaminant source driven by the boundary layer diffusion controlled model.

ComfortViewFactorAngles

from idfpy.models import ComfortViewFactorAngles extensible

Used to specify radiant view factors for thermal comfort calculations. Note that the following angle factor fractions must sum up to 1.0 All surfaces must be in the same enclosure.

Field Type Default Details
name
Name
string
angles list Each item: surface_name, angle_factor
Referenced by 2 object types

People, People:Instance

ElectricEquipment

from idfpy.models import ElectricEquipment

Sets internal gains for electric equipment in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to design level of electric equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of electric equipment for this set of attributes Choices: EquipmentLevel => Equipment Level -- simply enter watts of equipment Watts/Area => Watts per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person => Watts per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
watts_per_person
Watts per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 1 object types

DemandManager:ElectricEquipment

ElectricEquipment:Definition

from idfpy.models import ElectricEquipmentDefinition

Defines the physical characteristics (design level and heat gain fractions) for electric equipment. Referenced by one or more ElectricEquipment:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of electric equipment for this set of attributes Choices: EquipmentLevel => Equipment Level -- simply enter watts of equipment Watts/Area => Watts per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person => Watts per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
watts_per_person
Watts per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
Referenced by 1 object types

ElectricEquipment:Instance

ElectricEquipment:ITE:AirCooled

from idfpy.models import ElectricEquipmentITEAirCooled

This object describes air-cooled electric information technology equipment (ITE) which has variable power consumption as a function of loading and temperature. If a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_space_name
Zone or Space Name required
reference ZoneList and SpaceList names are not allowed.
Names a Space, Zone
air_flow_calculation_method
Air Flow Calculation Method
choice FlowFromSystem The specified method is used to calculate the IT inlet temperature and zone return air temperature. If FlowFromSystem is chosen, the zone is assumed to be well-mixed. If FlowControlWithApproachTemperatures is chosen, Supply and Return approach temperature should be defined to indicate the temperature difference due to the air distribution. When FlowControlWithApproachTemperatures is chosen, the inputs of Air Inlet Connection Type, Design Recirculation Fraction and Recirculation Function of Loading and Supply Temperature Curve Name are ignored. For multiple ITE objects defined for one zone, the same calculation method should apply. The FlowControlWithApproachTemperatures only applies to ITE zones with single duct VAV terminal unit. Other return air heat gains from window or lights are not allowed when FlowControlWithApproachTemperatures is chosen. When FlowControlWithApproachTemperatures is chosen, the controlled variable is the supply air temperature, not the well-mixed zone air temperature. The zone cooling setpoint from ZoneControl:Thermostat is ignored for this zone and cooling unmet hours do not apply.
One of FlowControlWithApproachTemperatures, FlowFromSystem
design_power_input_calculation_method
Design Power Input Calculation Method
choice Watts/Unit The entered calculation method is used to specify the design power input Watts/Unit => Watts per Unit -- Design Power = Watts per Unit * Number of Units Watts/Area => Watts per Floor Area -- Design Power = Watts per Floor Area * Floor Area
One of Watts/Area, Watts/Unit
watts_per_unit
Watts per Unit
number
W
Range: ≥ 0
number_of_units
Number of Units
number 1.0 Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
design_power_input_schedule_name
Design Power Input Schedule Name
reference Operating schedule for this equipment, fraction applied to the design power input, generally (0.0 - 1.0) If this field is blank, the schedule is assumed to always be 1.0.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cpu_loading_schedule_name
CPU Loading Schedule Name
reference CPU loading schedule for this equipment as a fraction from 0.0 (idle) to 1.0 (full load). If this field is blank, the schedule is assumed to always be 1.0.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cpu_power_input_function_of_loading_and_air_temperature_curve_name
CPU Power Input Function of Loading and Air Temperature Curve Name required
reference The name of a two-variable curve or table lookup object which modifies the CPU power input as a function of CPU loading (x) and air inlet node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
design_fan_power_input_fraction
Design Fan Power Input Fraction
number 0.0 The fraction of the total power input at design conditions which is for the cooling fan(s)
Range: ≥ 0, ≤ 1
design_fan_air_flow_rate_per_power_input
Design Fan Air Flow Rate per Power Input required
number
m3/s-W
The cooling fan air flow rate per total electric power input at design conditions
Range: ≥ 0
air_flow_function_of_loading_and_air_temperature_curve_name
Air Flow Function of Loading and Air Temperature Curve Name required
reference The name of a two-variable curve or table lookup object which modifies the cooling air flow rate as a function of CPU loading (x) and air inlet node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fan_power_input_function_of_flow_curve_name
Fan Power Input Function of Flow Curve Name required
reference The name of a single-variable curve or table lookup object which modifies the cooling fan power as a function of flow fraction (x). This curve (table) should equal 1.0 at a flow fraction of 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
design_entering_air_temperature
Design Entering Air Temperature
number
C
15.0 The entering air temperature at design conditions.
environmental_class
Environmental Class
choice None Specifies the allowable operating conditions for the air inlet conditions. Used for reporting time outside allowable conditions.
One of A1, A2, A3, A4, B, C, H1, None
air_inlet_connection_type
Air Inlet Connection Type
choice AdjustedSupply Specifies the type of connection between the zone and the ITE air inlet node. AdjustedSupply = ITE inlet temperature will be the current Supply Air Node temperature adjusted by the current recirculation fraction. All heat output is added to the zone air heat balance as a convective gain. ZoneAirNode = ITE air inlet condition is the average zone condition. All heat output is added to the zone air heat balance as a convective gain. RoomAirModel = ITE air inlet and outlet are connected to room air model nodes. This field is only used when Air Flow Calculation Method is FlowFromSystem.
One of AdjustedSupply, RoomAirModel, ZoneAirNode
air_inlet_room_air_model_node_name
Air Inlet Room Air Model Node Name
reference Name of a RoomAir:Node object which is connected to the ITE air inlet.
Names a RoomAir:Node
air_outlet_room_air_model_node_name
Air Outlet Room Air Model Node Name
reference Name of a RoomAir:Node object which is connected to the ITE air outlet.
Names a RoomAir:Node
supply_air_node_name
Supply Air Node Name
string Name of the supply air inlet node serving this ITE. Required if the Air Node Connection Type = AdjustedSupply. Also required if Calculation Method = FlowControlWithApproachTemperatures. Also required if reporting of Supply Heat Index is desired.
design_recirculation_fraction
Design Recirculation Fraction
number 0.0 The recirculation fraction for this equipment at design conditions. This field is used only if the Air Node Connection Type = AdjustedSupply. The default is 0.0 (no recirculation). This field is only used when Air Flow Calculation Method is FlowFromSystem.
Range: ≥ 0, ≤ 0.5
recirculation_function_of_loading_and_supply_temperature_curve_name
Recirculation Function of Loading and Supply Temperature Curve Name
reference The name of a two-variable curve or table lookup object which modifies the recirculation fraction as a function of CPU loading (x) and supply air node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature).This field is used only if the Air Node Connection Type = AdjustedSupply. If this curve is left blank, then the curve is assumed to always equal 1.0. This field is only used when Air Flow Calculation Method is FlowFromSystem.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
design_electric_power_supply_efficiency
Design Electric Power Supply Efficiency
number 1.0 The efficiency of the power supply system serving this ITE
Range: > 0, ≤ 1
electric_power_supply_efficiency_function_of_part_load_ratio_curve_name
Electric Power Supply Efficiency Function of Part Load Ratio Curve Name
reference The name of a single-variable curve or table lookup object which modifies the electric power supply efficiency as a function of part-load ratio (x). This curve (table) should equal 1.0 at full load (PLR = 1.0). If this curve is left blank, then the curve is assumed to always equal 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
fraction_of_electric_power_supply_losses_to_zone
Fraction of Electric Power Supply Losses to Zone
number 1.0 Fraction of the electric power supply losses which are a heat gain to the zone If this field is <1.0, the remainder of the losses are assumed to be lost to the outdoors.
Range: ≥ 0, ≤ 1
cpu_end_use_subcategory
CPU End-Use Subcategory
string ITE-CPU Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
fan_end_use_subcategory
Fan End-Use Subcategory
string ITE-Fans Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
electric_power_supply_end_use_subcategory
Electric Power Supply End-Use Subcategory
string ITE-UPS Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
supply_temperature_difference
Supply Temperature Difference
number
deltaC
The difference of the IT inlet temperature from the AHU supply air temperature. Either Supply Temperature Difference or Supply Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
supply_temperature_difference_schedule
Supply Temperature Difference Schedule
reference The difference schedule of the IT inlet temperature from the AHU supply air temperature. Either Supply Temperature Difference or Supply Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
return_temperature_difference
Return Temperature Difference
number
deltaC
The difference of the the actual AHU return air temperature to the IT equipment outlet temperature. Either Return Temperature Difference or Return Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
return_temperature_difference_schedule
Return Temperature Difference Schedule
reference The difference schedule of the actual AHU return air temperature to the IT equipment outlet temperature. Either Return Temperature Difference or Return Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

ElectricEquipment:ITE:AirCooled:Definition

from idfpy.models import ElectricEquipmentITEAirCooledDefinition

Performance characteristics for ElectricEquipment:ITE:AirCooled:Instance. Defines power, airflow, and efficiency as functions of loading and temperature.

Field Type Default Details
name
Name required
string
air_flow_calculation_method
Air Flow Calculation Method
choice FlowFromSystem The specified method is used to calculate the IT inlet temperature and zone return air temperature. If FlowFromSystem is chosen, the zone is assumed to be well-mixed. If FlowControlWithApproachTemperatures is chosen, Supply and Return approach temperature should be defined to indicate the temperature difference due to the air distribution. When FlowControlWithApproachTemperatures is chosen, the inputs of Air Inlet Connection Type, Design Recirculation Fraction and Recirculation Function of Loading and Supply Temperature Curve Name are ignored. For multiple ITE objects defined for one zone, the same calculation method should apply. The FlowControlWithApproachTemperatures only applies to ITE zones with single duct VAV terminal unit. Other return air heat gains from window or lights are not allowed when FlowControlWithApproachTemperatures is chosen.
One of FlowControlWithApproachTemperatures, FlowFromSystem
design_power_input_calculation_method
Design Power Input Calculation Method
choice EquipmentLevel The entered calculation method is used to specify the design power input Choices: EquipmentLevel => Equipment Level -- simply enter watts of equipment Watts/Area => Watts per Floor Area -- Design Power = Watts per Floor Area * Floor Area
One of EquipmentLevel, Watts/Area
watts_per_unit
Watts per Unit
number
W
Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
cpu_power_input_function_of_loading_and_air_temperature_curve_name
CPU Power Input Function of Loading and Air Temperature Curve Name required
reference The name of a two-variable curve or table lookup object which modifies the CPU power input as a function of CPU loading (x) and air inlet node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
design_fan_power_input_fraction
Design Fan Power Input Fraction
number 0.0 The fraction of the total power input at design conditions which is for the cooling fan(s)
Range: ≥ 0, ≤ 1
design_fan_air_flow_rate_per_power_input
Design Fan Air Flow Rate per Power Input required
number
m3/s-W
The cooling fan air flow rate per total electric power input at design conditions
Range: ≥ 0
air_flow_function_of_loading_and_air_temperature_curve_name
Air Flow Function of Loading and Air Temperature Curve Name required
reference The name of a two-variable curve or table lookup object which modifies the cooling air flow rate as a function of CPU loading (x) and air inlet node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature).
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
fan_power_input_function_of_flow_curve_name
Fan Power Input Function of Flow Curve Name required
reference The name of a single-variable curve or table lookup object which modifies the cooling fan power as a function of flow fraction (x). This curve (table) should equal 1.0 at a flow fraction of 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
design_entering_air_temperature
Design Entering Air Temperature
number
C
15.0 The entering air temperature at design conditions.
environmental_class
Environmental Class
choice None Specifies the allowable operating conditions for the air inlet conditions. Used for reporting time outside allowable conditions.
One of A1, A2, A3, A4, B, C, H1, None
air_inlet_connection_type
Air Inlet Connection Type
choice AdjustedSupply Specifies the type of connection between the zone and the ITE air inlet node. AdjustedSupply = ITE inlet temperature will be the current Supply Air Node temperature adjusted by the current recirculation fraction. All heat output is added to the zone air heat balance as a convective gain. ZoneAirNode = ITE air inlet condition is the average zone condition. All heat output is added to the zone air heat balance as a convective gain. RoomAirModel = ITE air inlet and outlet are connected to room air model nodes. This field is only used when Air Flow Calculation Method is FlowFromSystem.
One of AdjustedSupply, RoomAirModel, ZoneAirNode
design_recirculation_fraction
Design Recirculation Fraction
number 0.0 The recirculation fraction for this equipment at design conditions. This field is used only if the Air Node Connection Type = AdjustedSupply. The default is 0.0 (no recirculation). This field is only used when Air Flow Calculation Method is FlowFromSystem.
Range: ≥ 0, ≤ 0.5
recirculation_function_of_loading_and_supply_temperature_curve_name
Recirculation Function of Loading and Supply Temperature Curve Name
reference The name of a two-variable curve or table lookup object which modifies the recirculation fraction as a function of CPU loading (x) and supply air node temperature (y). This curve (table) should equal 1.0 at design conditions (CPU loading = 1.0 and Design Entering Air Temperature). This field is used only if the Air Node Connection Type = AdjustedSupply. If this curve is left blank, then the curve is assumed to always equal 1.0. This field is only used when Air Flow Calculation Method is FlowFromSystem.
Names a Curve:Bicubic, Curve:Biquadratic, Curve:CubicLinear, Curve:FanPressureRise, Curve:QuadraticLinear, Table:Lookup
design_electric_power_supply_efficiency
Design Electric Power Supply Efficiency
number 1.0 The efficiency of the power supply system serving this ITE
Range: > 0, ≤ 1
electric_power_supply_efficiency_function_of_part_load_ratio_curve_name
Electric Power Supply Efficiency Function of Part Load Ratio Curve Name
reference The name of a single-variable curve or table lookup object which modifies the electric power supply efficiency as a function of part-load ratio (x). This curve (table) should equal 1.0 at full load (PLR = 1.0). If this curve is left blank, then the curve is assumed to always equal 1.0.
Names a Curve:Cubic, Curve:DoubleExponentialDecay, Curve:Exponent, Curve:ExponentialDecay, Curve:ExponentialSkewNormal, Curve:Functional:PressureDrop, Curve:Linear, Curve:Quadratic, Curve:Quartic, Curve:RectangularHyperbola1, Curve:RectangularHyperbola2, Curve:Sigmoid and 1 more
fraction_of_electric_power_supply_losses_to_zone
Fraction of Electric Power Supply Losses to Zone
number 1.0 Fraction of the electric power supply losses which are a heat gain to the zone If this field is <1.0, the remainder of the losses are assumed to be lost to the outdoors.
Range: ≥ 0, ≤ 1
supply_temperature_difference
Supply Temperature Difference
number
deltaC
The difference of the IT inlet temperature from the AHU supply air temperature. Either Supply Temperature Difference or Supply Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
supply_temperature_difference_schedule
Supply Temperature Difference Schedule
reference The difference schedule of the IT inlet temperature from the AHU supply air temperature. Either Supply Temperature Difference or Supply Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
return_temperature_difference
Return Temperature Difference
number
deltaC
The difference of the actual AHU return air temperature to the IT equipment outlet temperature. Either Return Temperature Difference or Return Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
return_temperature_difference_schedule
Return Temperature Difference Schedule
reference The difference schedule of the actual AHU return air temperature to the IT equipment outlet temperature. Either Return Temperature Difference or Return Temperature Difference Schedule is required if Air Flow Calculation Method is set to FlowControlWithApproachTemperatures. This field is ignored when Air Flow Calculation Method is FlowFromSystem.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 1 object types

ElectricEquipment:ITE:AirCooled:Instance

ElectricEquipment:ITE:AirCooled:Instance

from idfpy.models import ElectricEquipmentITEAirCooledInstance

This object describes air-cooled electric information technology equipment (ITE) which has variable power consumption as a function of loading and temperature. The performance characteristics are given by the referenced ElectricEquipment:ITE:AirCooled:Definition object. If a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
electricequipment_ite_aircooled_definition_name
ElectricEquipment ITE AirCooled Definition Name required
reference Names a ElectricEquipment:ITE:AirCooled:Definition
zone_or_space_name
Zone or Space Name required
reference ZoneList and SpaceList names are not allowed.
Names a Space, Zone
multiplier
Multiplier
number 1.0 Multiplies the design power input from the referenced definition.
Range: ≥ 0
design_power_input_schedule_name
Design Power Input Schedule Name
reference Operating schedule for this equipment, fraction applied to the design power input, generally (0.0 - 1.0) If this field is blank, the schedule is assumed to always be 1.0.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cpu_loading_schedule_name
CPU Loading Schedule Name
reference CPU loading schedule for this equipment as a fraction from 0.0 (idle) to 1.0 (full load). If this field is blank, the schedule is assumed to always be 1.0.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_inlet_room_air_model_node_name
Air Inlet Room Air Model Node Name
reference Name of a RoomAir:Node object which is connected to the ITE air inlet.
Names a RoomAir:Node
air_outlet_room_air_model_node_name
Air Outlet Room Air Model Node Name
reference Name of a RoomAir:Node object which is connected to the ITE air outlet.
Names a RoomAir:Node
supply_air_node_name
Supply Air Node Name
string Name of the supply air inlet node serving this ITE. Required if the Air Node Connection Type = AdjustedSupply (set in the Definition). Also required if Air Flow Calculation Method = FlowControlWithApproachTemperatures (set in the Definition). Also required if reporting of Supply Heat Index is desired.
cpu_end_use_subcategory
CPU End-Use Subcategory
string ITE-CPU Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
fan_end_use_subcategory
Fan End-Use Subcategory
string ITE-Fans Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
electric_power_supply_end_use_subcategory
Electric Power Supply End-Use Subcategory
string ITE-UPS Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

ElectricEquipment:Instance

from idfpy.models import ElectricEquipmentInstance

Sets internal gains for electric equipment in the zone. The physical characteristics are given by the referenced ElectricEquipment:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
electric_equipment_definition_name
Electric Equipment Definition Name required
reference Names a ElectricEquipment:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to design level of electric equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
Referenced by 1 object types

DemandManager:ElectricEquipment

GasEquipment

from idfpy.models import GasEquipment

Sets internal gains and contaminant rates for gas equipment in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of gas equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of gas equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
0.0 CO2 generation rate per unit of power input The default value assumes the equipment is fully vented. For unvented equipment, a suggested value is 3.45E-8 m3/s-W. This value is converted from a natural gas CO2 emission rate of 117 lbs CO2 per million Btu. The maximum value assumes to be 10 times of the recommended value.
Range: ≥ 0, ≤ 4e-07
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

GasEquipment:Definition

from idfpy.models import GasEquipmentDefinition

Defines the physical characteristics (design level and heat gain fractions) for gas equipment. Referenced by one or more GasEquipment:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of gas equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
0.0 CO2 generation rate per unit of power input The default value assumes the equipment is fully vented. For unvented equipment, a suggested value is 3.45E-8 m3/s-W. This value is converted from a natural gas CO2 emission rate of 117 lbs CO2 per million Btu. The maximum value assumes to be 10 times of the recommended value.
Range: ≥ 0, ≤ 4e-07
Referenced by 1 object types

GasEquipment:Instance

GasEquipment:Instance

from idfpy.models import GasEquipmentInstance

Sets internal gains and contaminant rates for gas equipment in the zone. The physical characteristics are given by the referenced GasEquipment:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
gas_equipment_definition_name
Gas Equipment Definition Name required
reference Names a GasEquipment:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of gas equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

HotWaterEquipment

from idfpy.models import HotWaterEquipment

Sets internal gains for hot water equipment in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of hot water equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of hot water equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

HotWaterEquipment:Definition

from idfpy.models import HotWaterEquipmentDefinition

Defines the physical characteristics (design level and heat gain fractions) for hot water equipment. Referenced by one or more HotWaterEquipment:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of hot water equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
Referenced by 1 object types

HotWaterEquipment:Instance

HotWaterEquipment:Instance

from idfpy.models import HotWaterEquipmentInstance

Sets internal gains for hot water equipment in the zone. The physical characteristics are given by the referenced HotWaterEquipment:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
hot_water_equipment_definition_name
Hot Water Equipment Definition Name required
reference Names a HotWaterEquipment:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of hot water equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

IndoorLivingWall

from idfpy.models import IndoorLivingWall

Indoor greenery systems such as indoor living walls are panels of plants, which grow hydroponically or from substrates. The living wall structures can be either free-standing or attached to walls. The IndoorLivingWall module directly connects with inside surface heat balance, zone air heat balance, and zone air moisture balance.

Field Type Default Details
name
Name required
string
surface_name
Surface Name required
reference Name of the wall partition where indoor green is located.
Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, Roof, RoofCeiling:Detailed, Wall:Adiabatic, Wall:Detailed, Wall:Exterior and 2 more
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of other equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
evapotranspiration_calculation_method
Evapotranspiration Calculation Method
choice Penman-Monteith Model selection for calculating evapotranspiration of indoor greenery system. This rate can also be actuated with user-defined calculations, see EMS application guide for actuator details.
One of Penman-Monteith, Stanghellini
lighting_method
Lighting Method
choice Three different methods are provided here (LED; Daylight; LED-Daylight)
One of Daylight, LED, LED-Daylight
led_intensity_schedule_name
LED Intensity Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
daylighting_control_name
Daylighting Control Name
string If daylighting is used in the selected lighting methods (Daylight or LED-Daylight), users should define an object of Daylighting:Control to obtain the daylighting illuminance level and an object for Daylighting:ReferencePoint for the daylighting sensor location in the thermal zone. The name of the object of Daylighting:Controls should be specified in this field.
led_daylight_targeted_lighting_intensity_schedule_name
LED-Daylight Targeted Lighting Intensity Schedule Name
reference This field defines targeted LED intensity level for indoor living wall systems. The schedule values can be any positive number representing targeted photosynthetic photon flux density (PPFD). Based on the available daylighting, the required LED lighting level and power will be automatically adjusted to meet the targeted LED intensity level.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
total_leaf_area
Total Leaf Area
number
m2
The value is the one-sided leaf area of an indoor living wall. Based on the users’ input, LAI is calculated as the ratio of the total leaf area and the partition wall area. Typical LAIs are 1.0 for grass and 3.0 for bushes and shrubs. The maximum LAI is 2.0 for the IndoorLivingWall module in EnergyPlus. If the calculated LAI is greater than 2.0, the maximum value of 2.0 is used for LAI in the simulation.
led_nominal_intensity
LED Nominal Intensity
number
umol/m2-s
The value represents photosynthetic photon flux density (PPFD) of LED grow light. PPFD is measured in micro-mole per m2 per second (umol/m2-s) which establishes exactly how many photosynthetically active radiation (PAR) photons are landing on a specific area.
led_nominal_power
LED Nominal Power
number
W
This field defines nominal total LED power for an indoor living wall system.
radiant_fraction_of_led_lights
Radiant Fraction of LED Lights
number 0.6 This field defines the fraction of radiation from LED lights
Range: ≥ 0, ≤ 1

Lights

from idfpy.models import Lights

Sets internal gains for lights in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to design level of lights, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice LightingLevel The entered calculation method is used to create the maximum amount of lights for this set of attributes Choices: LightingLevel => Lighting Level -- simply enter watts of lights Watts/Area => Watts per Floor Area -- enter the number to apply. Value * Floor Area = Lights Watts/Person => Watts per Person -- enter the number to apply. Value * Occupants = Lights
One of LightingLevel, Watts/Area, Watts/Person
lighting_level
Lighting Level
number
W
Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
watts_per_person
Watts per Person
number
W/person
Range: ≥ 0
return_air_fraction
Return Air Fraction
number 0.0 Used only for sizing calculation if return-air-fraction coefficients are specified.
Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_visible
Fraction Visible
number 0.0 Range: ≥ 0, ≤ 1
fraction_replaceable
Fraction Replaceable
number 1.0 For Daylighting:Controls must be 0 or 1: 0 = no dimming control, 1 = full dimming control
Range: ≥ 0, ≤ 1
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
return_air_fraction_calculated_from_plenum_temperature
Return Air Fraction Calculated from Plenum Temperature
choice No One of No, Yes
return_air_fraction_function_of_plenum_temperature_coefficient_1
Return Air Fraction Function of Plenum Temperature Coefficient 1
number 0.0 Used only if Return Air Fraction Is Calculated from Plenum Temperature = Yes Equation is Return Air Fraction = Coefficient#1 - Coefficient#2 X PlenumTemp(degC)
Range: ≥ 0
return_air_fraction_function_of_plenum_temperature_coefficient_2
Return Air Fraction Function of Plenum Temperature Coefficient 2
number
1/K
0.0 Used only if Return Air Fraction Is Calculated from Plenum Temperature = Yes Equation is Return Air Fraction = Coefficient#1 - Coefficient#2 X PlenumTemp(degC)
Range: ≥ 0
return_air_heat_gain_node_name
Return Air Heat Gain Node Name
string Name of the return air node for this heat gain. If left blank, defaults to the first return air node for the zone. Leave this field blank when using a ZoneList name.
exhaust_air_heat_gain_node_name
Exhaust Air Heat Gain Node Name
string Name of the exhaust air node for this heat gain. If the node name is entered, return heat gain will be shared by both return and exhaust air nodes. The air properties of both nodes are weighted by both node mass flow rates.
Referenced by 1 object types

DemandManager:Lights

Lights:Definition

from idfpy.models import LightsDefinition

Defines the physical characteristics (design level and heat gain fractions) for lights. Referenced by one or more Lights:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice LightingLevel The entered calculation method is used to create the maximum amount of lights for this set of attributes Choices: LightingLevel => Lighting Level -- simply enter watts of lights Watts/Area => Watts per Floor Area -- enter the number to apply. Value * Floor Area = Lights Watts/Person => Watts per Person -- enter the number to apply. Value * Occupants = Lights
One of LightingLevel, Watts/Area, Watts/Person
lighting_level
Lighting Level
number
W
Range: ≥ 0
watts_per_floor_area
Watts per Floor Area
number
W/m2
Range: ≥ 0
watts_per_person
Watts per Person
number
W/person
Range: ≥ 0
return_air_fraction
Return Air Fraction
number 0.0 Used only for sizing calculation if return-air-fraction coefficients are specified.
Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_visible
Fraction Visible
number 0.0 Range: ≥ 0, ≤ 1
return_air_fraction_calculated_from_plenum_temperature
Return Air Fraction Calculated from Plenum Temperature
choice No One of No, Yes
return_air_fraction_function_of_plenum_temperature_coefficient_1
Return Air Fraction Function of Plenum Temperature Coefficient 1
number 0.0 Used only if Return Air Fraction Is Calculated from Plenum Temperature = Yes Equation is Return Air Fraction = Coefficient#1 - Coefficient#2 X PlenumTemp(degC)
Range: ≥ 0
return_air_fraction_function_of_plenum_temperature_coefficient_2
Return Air Fraction Function of Plenum Temperature Coefficient 2
number
1/K
0.0 Used only if Return Air Fraction Is Calculated from Plenum Temperature = Yes Equation is Return Air Fraction = Coefficient#1 - Coefficient#2 X PlenumTemp(degC)
Range: ≥ 0
Referenced by 1 object types

Lights:Instance

Lights:Instance

from idfpy.models import LightsInstance

Sets internal gains for lights in the zone. The physical characteristics are given by the referenced Lights:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
lights_definition_name
Lights Definition Name required
reference Names a Lights:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in schedule should be fraction applied to design level of lights, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
fraction_replaceable
Fraction Replaceable
number 1.0 For Daylighting:Controls must be 0 or 1: 0 = no dimming control, 1 = full dimming control
Range: ≥ 0, ≤ 1
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
return_air_heat_gain_node_name
Return Air Heat Gain Node Name
string Name of the return air node for this heat gain. If left blank, defaults to the first return air node for the zone. Leave this field blank when using a ZoneList name.
exhaust_air_heat_gain_node_name
Exhaust Air Heat Gain Node Name
string Name of the exhaust air node for this heat gain. If the node name is entered, return heat gain will be shared by both return and exhaust air nodes. The air properties of both nodes are weighted by both node mass flow rates.
Referenced by 1 object types

DemandManager:Lights

OtherEquipment

from idfpy.models import OtherEquipment

Sets internal gains or losses for "other" equipment in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
fuel_type
Fuel Type
choice None One of Coal, Diesel, DistrictCooling, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, None, OtherFuel1, OtherFuel2, Propane
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of other equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of other equipment. to set a loss, use a negative value in the following fields. for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
power_per_floor_area
Power per Floor Area
number
W/m2
power_per_person
Power per Person
number
W/person
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
0.0 CO2 generation rate per unit of power input The default value assumes the equipment is fully vented.
Range: ≥ 0, ≤ 4e-07
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

OtherEquipment:Definition

from idfpy.models import OtherEquipmentDefinition

Defines the physical characteristics (design level and heat gain fractions) for "other" equipment. Referenced by one or more OtherEquipment:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of other equipment. to set a loss, use a negative value in the following fields. for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
power_per_floor_area
Power per Floor Area
number
W/m2
power_per_person
Power per Person
number
W/person
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
0.0 CO2 generation rate per unit of power input The default value assumes the equipment is fully vented.
Range: ≥ 0, ≤ 4e-07
Referenced by 1 object types

OtherEquipment:Instance

OtherEquipment:Instance

from idfpy.models import OtherEquipmentInstance

Sets internal gains or losses for "other" equipment in the zone. The physical characteristics are given by the referenced OtherEquipment:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
other_equipment_definition_name
Other Equipment Definition Name required
reference Names a OtherEquipment:Definition
fuel_type
Fuel Type
choice None One of Coal, Diesel, DistrictCooling, DistrictHeatingSteam, DistrictHeatingWater, Electricity, FuelOilNo1, FuelOilNo2, Gasoline, NaturalGas, None, OtherFuel1, OtherFuel2, Propane
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of other equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

People

from idfpy.models import People

Sets internal gains and contaminant rates for occupants in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
number_of_people_schedule_name
Number of People Schedule Name required
reference units in schedule should be fraction applied to number of people (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
number_of_people_calculation_method
Number of People Calculation Method
choice People The entered calculation method is used to create the maximum number of people for this set of attributes (i.e. sensible fraction, schedule, etc) Choices: People -- simply enter number of occupants. People per Floor Area -- enter the number to apply. Value * Floor Area = Number of people Floor Area per Person -- enter the number to apply. Floor Area / Value = Number of people
One of Area/Person, People, People/Area
number_of_people
Number of People
number Range: ≥ 0
people_per_floor_area
People per Floor Area
number
person/m2
Range: ≥ 0
floor_area_per_person
Floor Area per Person
number
m2/person
Range: ≥ 0
fraction_radiant
Fraction Radiant
number 0.3 This is radiant fraction of the sensible heat released by people in a zone. This value will be multiplied by the total sensible heat released by people yields the amount of long wavelength radiation gain from people in a zone. Default value is 0.30.
Range: ≥ 0, ≤ 1
sensible_heat_fraction
Sensible Heat Fraction
number or Autocalculate Autocalculate if input, overrides program calculated sensible/latent split
activity_level_schedule_name
Activity Level Schedule Name required
reference Note that W has to be converted to mets in TC routine units in schedule are W/person
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
3.82e-08 CO2 generation rate per unit of activity level. The default value is obtained from ASHRAE Std 62.1 at 0.0084 cfm/met/person over the general adult population.
Range: ≥ 0, ≤ 3.82e-07
enable_ashrae_55_comfort_warnings
Enable ASHRAE 55 Comfort Warnings
choice No One of No, Yes
mean_radiant_temperature_calculation_type
Mean Radiant Temperature Calculation Type
choice EnclosureAveraged optional (only required for thermal comfort runs)
One of AngleFactor, EnclosureAveraged, SurfaceWeighted
surface_name_angle_factor_list_name
Surface Name/Angle Factor List Name
reference optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, ComfortViewFactorAngles, Door, Door:Interzone, FenestrationSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, GlazedDoor and 11 more
work_efficiency_schedule_name
Work Efficiency Schedule Name
reference units in schedule are 0.0 to 1.0 optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
clothing_insulation_calculation_method
Clothing Insulation Calculation Method
choice ClothingInsulationSchedule One of CalculationMethodSchedule, ClothingInsulationSchedule, DynamicClothingModelASHRAE55
clothing_insulation_calculation_method_schedule_name
Clothing Insulation Calculation Method Schedule Name
reference a schedule value of 1 for the Scheduled method, and 2 for the DynamicClothingModelASHRAE55 method
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
clothing_insulation_schedule_name
Clothing Insulation Schedule Name
reference use "Clo" from ASHRAE or Thermal Comfort guides optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_velocity_schedule_name
Air Velocity Schedule Name
reference units in the schedule are m/s optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
thermal_comfort_model_1_type
Thermal Comfort Model 1 Type
choice optional (only needed for people thermal comfort results reporting)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_2_type
Thermal Comfort Model 2 Type
choice optional (second type of thermal comfort model and results reporting)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_3_type
Thermal Comfort Model 3 Type
choice optional (third thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_4_type
Thermal Comfort Model 4 Type
choice optional (fourth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_5_type
Thermal Comfort Model 5 Type
choice optional (fifth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_6_type
Thermal Comfort Model 6 Type
choice optional (sixth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_7_type
Thermal Comfort Model 7 Type
choice optional (seventh thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
ankle_level_air_velocity_schedule_name
Ankle Level Air Velocity Schedule Name
reference units in the schedule are m/s this is the schedule of the air speed at the 0.1 m above the floor optional (only required for runs of thermal comfort models AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cold_stress_temperature_threshold
Cold Stress Temperature Threshold
number
C
15.56 this is the indoor safe temperature threshold for cold stress
heat_stress_temperature_threshold
Heat Stress Temperature Threshold
number
C
30.0 this is the indoor safe temperature threshold for heat stress
Referenced by 2 object types

ZoneControl:Thermostat:ThermalComfort, ZoneMRTCalculation

People:Definition

from idfpy.models import PeopleDefinition

Defines the physical characteristics (number of people, heat gain fractions, CO2 generation rate and thermal comfort model selections) for occupants. Referenced by one or more People:Instance objects.

Field Type Default Details
name
Name required
string
number_of_people_calculation_method
Number of People Calculation Method
choice People The entered calculation method is used to create the maximum number of people for this set of attributes (i.e. sensible fraction, schedule, etc) Choices: People -- simply enter number of occupants. People per Floor Area -- enter the number to apply. Value * Floor Area = Number of people Floor Area per Person -- enter the number to apply. Floor Area / Value = Number of people
One of Area/Person, People, People/Area
number_of_people
Number of People
number Range: ≥ 0
people_per_floor_area
People per Floor Area
number
person/m2
Range: ≥ 0
floor_area_per_person
Floor Area per Person
number
m2/person
Range: ≥ 0
fraction_radiant
Fraction Radiant
number 0.3 This is radiant fraction of the sensible heat released by people in a zone. This value will be multiplied by the total sensible heat released by people yields the amount of long wavelength radiation gain from people in a zone. Default value is 0.30.
Range: ≥ 0, ≤ 1
sensible_heat_fraction
Sensible Heat Fraction
number or Autocalculate Autocalculate if input, overrides program calculated sensible/latent split
carbon_dioxide_generation_rate
Carbon Dioxide Generation Rate
number
m3/s-W
3.82e-08 CO2 generation rate per unit of activity level. The default value is obtained from ASHRAE Std 62.1 at 0.0084 cfm/met/person over the general adult population.
Range: ≥ 0, ≤ 3.82e-07
enable_ashrae_55_comfort_warnings
Enable ASHRAE 55 Comfort Warnings
choice No One of No, Yes
mean_radiant_temperature_calculation_type
Mean Radiant Temperature Calculation Type
choice EnclosureAveraged optional (only required for thermal comfort runs)
One of AngleFactor, EnclosureAveraged, SurfaceWeighted
thermal_comfort_model_1_type
Thermal Comfort Model 1 Type
choice optional (only needed for people thermal comfort results reporting)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_2_type
Thermal Comfort Model 2 Type
choice optional (second type of thermal comfort model and results reporting)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_3_type
Thermal Comfort Model 3 Type
choice optional (third thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_4_type
Thermal Comfort Model 4 Type
choice optional (fourth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_5_type
Thermal Comfort Model 5 Type
choice optional (fifth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_6_type
Thermal Comfort Model 6 Type
choice optional (sixth thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
thermal_comfort_model_7_type
Thermal Comfort Model 7 Type
choice optional (seventh thermal comfort model and report type)
One of AdaptiveASH55, AdaptiveCEN15251, AnkleDraftASH55, CoolingEffectASH55, Fanger, KSU, Pierce
Referenced by 1 object types

People:Instance

People:Instance

from idfpy.models import PeopleInstance

Sets internal gains and contaminant rates for occupants in the zone. The physical characteristics are given by the referenced People:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
people_definition_name
People Definition Name required
reference Names a People:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
number_of_people_schedule_name
Number of People Schedule Name required
reference units in schedule should be fraction applied to number of people (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
activity_level_schedule_name
Activity Level Schedule Name required
reference Note that W has to be converted to mets in TC routine units in schedule are W/person
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
surface_name_angle_factor_list_name
Surface Name/Angle Factor List Name
reference optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, ComfortViewFactorAngles, Door, Door:Interzone, FenestrationSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, GlazedDoor and 11 more
work_efficiency_schedule_name
Work Efficiency Schedule Name
reference units in schedule are 0.0 to 1.0 optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
clothing_insulation_calculation_method
Clothing Insulation Calculation Method
choice ClothingInsulationSchedule One of CalculationMethodSchedule, ClothingInsulationSchedule, DynamicClothingModelASHRAE55
clothing_insulation_calculation_method_schedule_name
Clothing Insulation Calculation Method Schedule Name
reference a schedule value of 1 for the Scheduled method, and 2 for the DynamicClothingModelASHRAE55 method
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
clothing_insulation_schedule_name
Clothing Insulation Schedule Name
reference use "Clo" from ASHRAE or Thermal Comfort guides optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
air_velocity_schedule_name
Air Velocity Schedule Name
reference units in the schedule are m/s optional (only required for runs of thermal comfort models: Fanger, Pierce, KSU, CoolingEffectASH55 and AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the number of people from the referenced definition.
Range: ≥ 0
ankle_level_air_velocity_schedule_name
Ankle Level Air Velocity Schedule Name
reference units in the schedule are m/s this is the schedule of the air speed at the 0.1 m above the floor optional (only required for runs of thermal comfort models AnkleDraftASH55)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cold_stress_temperature_threshold
Cold Stress Temperature Threshold
number
C
15.56 this is the indoor safe temperature threshold for cold stress
heat_stress_temperature_threshold
Heat Stress Temperature Threshold
number
C
30.0 this is the indoor safe temperature threshold for heat stress
Referenced by 2 object types

ZoneControl:Thermostat:ThermalComfort, ZoneMRTCalculation

SteamEquipment

from idfpy.models import SteamEquipment

Sets internal gains for steam equipment in the zone. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of steam equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of steam equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

SteamEquipment:Definition

from idfpy.models import SteamEquipmentDefinition

Defines the physical characteristics (design level and heat gain fractions) for steam equipment. Referenced by one or more SteamEquipment:Instance objects.

Field Type Default Details
name
Name required
string
design_level_calculation_method
Design Level Calculation Method
choice EquipmentLevel The entered calculation method is used to create the maximum amount of steam equipment for this set of attributes Choices: EquipmentLevel => Design Level -- simply enter power input of equipment Watts/Area or Power/Area => Power per Floor Area -- enter the number to apply. Value * Floor Area = Equipment Level Watts/Person or Power/Person => Power per Person -- enter the number to apply. Value * Occupants = Equipment Level
One of EquipmentLevel, Power/Area, Power/Person, Watts/Area, Watts/Person
design_level
Design Level
number
W
Range: ≥ 0
power_per_floor_area
Power per Floor Area
number
W/m2
Range: ≥ 0
power_per_person
Power per Person
number
W/person
Range: ≥ 0
fraction_latent
Fraction Latent
number 0.0 Range: ≥ 0, ≤ 1
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
fraction_lost
Fraction Lost
number 0.0 Range: ≥ 0, ≤ 1
Referenced by 1 object types

SteamEquipment:Instance

SteamEquipment:Instance

from idfpy.models import SteamEquipmentInstance

Sets internal gains for steam equipment in the zone. The physical characteristics are given by the referenced SteamEquipment:Definition object. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
steam_equipment_definition_name
Steam Equipment Definition Name required
reference Names a SteamEquipment:Definition
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to design level of steam equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
multiplier
Multiplier
number 1.0 Multiplies the design level from the referenced definition.
Range: ≥ 0
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.

SurfaceContaminantSourceAndSink:Generic:BoundaryLayerDiffusion

from idfpy.models import SurfaceContaminantSourceAndSinkGenericBoundaryLayerDiffusion

Simulate generic contaminant source driven by the boundary layer diffusion controlled model.

Field Type Default Details
name
Name required
string
surface_name
Surface Name required
reference Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, Roof, RoofCeiling:Detailed, Wall:Adiabatic, Wall:Detailed, Wall:Exterior and 2 more
mass_transfer_coefficient
Mass Transfer Coefficient
number
m/s
Range: ≥ 0
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Initial Emission Rate. When the value is equal to 1.0, the time will be reset to zero.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
henry_adsorption_constant_or_partition_coefficient
Henry Adsorption Constant or Partition Coefficient
number
dimensionless
Range: > 0

SurfaceContaminantSourceAndSink:Generic:DepositionVelocitySink

from idfpy.models import SurfaceContaminantSourceAndSinkGenericDepositionVelocitySink

Simulate generic contaminant source driven by the boundary layer diffusion controlled model.

Field Type Default Details
name
Name required
string
surface_name
Surface Name required
reference Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, Roof, RoofCeiling:Detailed, Wall:Adiabatic, Wall:Detailed, Wall:Exterior and 2 more
deposition_velocity
Deposition Velocity
number
m/s
Range: ≥ 0
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Initial Emission Rate. When the value is equal to 1.0, the time will be reset to zero.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

SurfaceContaminantSourceAndSink:Generic:PressureDriven

from idfpy.models import SurfaceContaminantSourceAndSinkGenericPressureDriven

Simulate generic contaminant source driven by the pressure difference across a surface.

Field Type Default Details
name
Name required
string
surface_name
Surface Name required
reference Names a BuildingSurface:Detailed, Ceiling:Adiabatic, Ceiling:Interzone, Door, Door:Interzone, FenestrationSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone, GlazedDoor, GlazedDoor:Interzone and 9 more
design_generation_rate_coefficient
Design Generation Rate Coefficient
number
m3/s
Range: ≥ 0
generation_schedule_name
Generation Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Design Generation Rate Coefficient
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
generation_exponent
Generation Exponent
number
dimensionless
Range: > 0, ≤ 1

SwimmingPool:Indoor

from idfpy.models import SwimmingPoolIndoor

Specifies an indoor swimming pools linked to a floor surface. The pool is assumed to cover the entire floor to which it is linked.

Field Type Default Details
name
Name required
string
surface_name
Surface Name required
reference Name of the floor surface where the pool is located.
Names a BuildingSurface:Detailed, Floor:Adiabatic, Floor:Detailed, Floor:GroundContact, Floor:Interzone
average_depth
Average Depth required
number
m
activity_factor_schedule_name
Activity Factor Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
make_up_water_supply_schedule_name
Make-up Water Supply Schedule Name
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cover_schedule_name
Cover Schedule Name required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cover_evaporation_factor
Cover Evaporation Factor
number 0.0 Range: ≥ 0, ≤ 1
cover_convection_factor
Cover Convection Factor
number 0.0 Range: ≥ 0, ≤ 1
cover_short_wavelength_radiation_factor
Cover Short-Wavelength Radiation Factor
number 0.0 Range: ≥ 0, ≤ 1
cover_long_wavelength_radiation_factor
Cover Long-Wavelength Radiation Factor
number 0.0 Range: ≥ 0, ≤ 1
pool_water_inlet_node
Pool Water Inlet Node required
string
pool_water_outlet_node
Pool Water Outlet Node required
string
pool_heating_system_maximum_water_flow_rate
Pool Heating System Maximum Water Flow Rate
number
m3/s
Range: ≥ 0
pool_miscellaneous_equipment_power
Pool Miscellaneous Equipment Power
number
W/(m3/s)
Power input per pool water flow rate
Range: ≥ 0
setpoint_temperature_schedule
Setpoint Temperature Schedule required
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
maximum_number_of_people
Maximum Number of People required
number Range: ≥ 0
people_schedule
People Schedule
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
people_heat_gain_schedule
People Heat Gain Schedule
reference Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
Referenced by 2 object types

AirLoopHVAC:DedicatedOutdoorAirSystem, Branch

ZoneBaseboard:OutdoorTemperatureControlled

from idfpy.models import ZoneBaseboardOutdoorTemperatureControlled

Specifies outside temperature-controlled electric baseboard heating. If a ZoneList, SpaceList, or a Zone comprised of more than one Space is specified then this definition applies to all applicable spaces, and each instance will be named with the Space Name plus this Object Name.

Field Type Default Details
name
Name required
string
zone_or_zonelist_or_space_or_spacelist_name
Zone or ZoneList or Space or SpaceList Name required
reference Names a Space, SpaceList, Zone, ZoneList
schedule_name
Schedule Name required
reference units in Schedule should be fraction applied to capacity of the baseboard heat equipment, generally (0.0 - 1.0)
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
capacity_at_low_temperature
Capacity at Low Temperature
number or Autosize
W
Autosize
low_temperature
Low Temperature
number or Autosize
C
Autosize
capacity_at_high_temperature
Capacity at High Temperature
number or Autosize
W
Autosize
high_temperature
High Temperature
number or Autosize
C
Autosize
fraction_radiant
Fraction Radiant
number 0.0 Range: ≥ 0, ≤ 1
end_use_subcategory
End-Use Subcategory
string General Any text may be used here to categorize the end-uses in the ABUPS End Uses by Subcategory table.
design_zone_heating_setpoint
Design Zone Heating Setpoint
number
C
20.0

ZoneContaminantSourceAndSink:CarbonDioxide

from idfpy.models import ZoneContaminantSourceAndSinkCarbonDioxide

Represents internal CO2 gains and sinks in the zone.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
design_generation_rate
Design Generation Rate
number
m3/s
Positive values represent sources and negative values represent sinks.
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Design Generation Rate
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

ZoneContaminantSourceAndSink:Generic:Constant

from idfpy.models import ZoneContaminantSourceAndSinkGenericConstant

Sets internal generic contaminant gains and sinks in a zone with constant values.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
design_generation_rate
Design Generation Rate
number
m3/s
The values represent source.
Range: ≥ 0
generation_schedule_name
Generation Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Design Generation Rate
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
design_removal_coefficient
Design Removal Coefficient
number
m3/s
The value represent sink.
Range: ≥ 0
removal_schedule_name
Removal Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Design removal Coefficient
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules

ZoneContaminantSourceAndSink:Generic:CutoffModel

from idfpy.models import ZoneContaminantSourceAndSinkGenericCutoffModel

Simulate generic contaminant source driven by the cutoff concentration model.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
design_generation_rate_coefficient
Design Generation Rate Coefficient
number
m3/s
Range: ≥ 0
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Design Generation Rate Coefficient
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
cutoff_generic_contaminant_at_which_emission_ceases
Cutoff Generic Contaminant at which Emission Ceases
number
ppm
When the zone concentration level is greater than the cutoff level, emission stops, and the source level is zero.
Range: > 0

ZoneContaminantSourceAndSink:Generic:DecaySource

from idfpy.models import ZoneContaminantSourceAndSinkGenericDecaySource

Simulate generic contaminant source driven by the cutoff concentration model.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
initial_emission_rate
Initial Emission Rate
number
m3/s
Range: ≥ 0
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Initial Emission Rate. When the value is equal to 1.0, the time will be reset to zero.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules
delay_time_constant
Delay Time Constant
number
s
Range: > 0

ZoneContaminantSourceAndSink:Generic:DepositionRateSink

from idfpy.models import ZoneContaminantSourceAndSinkGenericDepositionRateSink

Simulate generic contaminant source driven by the boundary layer diffusion controlled model.

Field Type Default Details
name
Name required
string
zone_name
Zone Name required
reference Names a Zone
deposition_rate
Deposition Rate
number
m/s
Range: ≥ 0
schedule_name
Schedule Name required
reference Value in this schedule should be a fraction (generally 0.0 - 1.0) applied to the Initial Emission Rate. When the value is equal to 1.0, the time will be reset to zero.
Names a ExternalInterface:FunctionalMockupUnitExport:To:Schedule, ExternalInterface:FunctionalMockupUnitImport:To:Schedule, ExternalInterface:Schedule, Schedule:Compact, Schedule:Constant, Schedule:File, Schedule:Year, Schedule:Year:Rules